WRA-3328TechnicalSpecs.pdf
PDF 33 KB Posted
- Solicitation number
- S125211-vCurrent
- Issued by
- Suffolk County, Woburn City, Massachusetts
About this file
This document is a technical specifications sheet for a sodium hypochlorite and sodium bisulfite tank venting system as part of a state or local government contract opportunity. The specifications outline the construction, service conditions, and instrumentation data for 12 conservation vent units required for 6 tanks, including details on the tank capacity, pressure/vacuum settings, materials, and manufacturer. The document provides the job number, specification number, and date, as well as notes on the vendor's requirements to provide a permanent nameplate and certified calibration sheet for each vent unit.
The pricing, set-asides, incumbents, or funding details are not included in this technical specifications document. The information provided focuses solely on the detailed technical requirements and vendor deliverables for the tank venting system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| WRA-3328.pdf | ||
| WRA3328QandA070111.pdf | ||
| S125211-vCurrent_OD.xlsx | XLSX spreadsheet |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet 1 of 1
Spec No. CSV-1 Rev. 1
Job No. Date 6/14/2011
Req. BY PDS
CHK'D APPR.
1 Tag No.
2 Description of Service SODIUM HYPOCHLORITE AND SODIUM BISULFITE TANK VENTING
GENERAL 3 Quantity
4 PID No.
5 Fluid
Inbreathing (Vacuum)
6 Pressure/Vacuum 0.5
7 Temperature 0 TO 100
8 Ambient Temperature
10 Capacity of Tank 27,000 GALLONS
11 Tank Design Pressure ATMOSPHERIC
12 Tank Design Vacuum ATMOSPHERIC
13 Flame Arrester NO
14 Body Material DEKARANE 470
15 Internal Stem and Guides SAME AS BODY
16 Weights ENCAPSULATED 316 SS OR HASTELLOY
18 Pressure Setting SEE ABOVE
19 Filling Rate (GPM) N/A
20 Total Outbreathing (SCFH) N/A
21 Vacuum Setting SEE ABOVE
22 Emptying Rate (GPM) N/A
23 Total Inbreathing (SCFH) N/A
24 End-of-Line Unit YES
25 In-Line Unit NO
26 Size INLET: 8 INCH OUTLET: N/A 27 Flange 150 LB ANSI
28 Housing SELF DRAINING
29 Body Material DEKARANE 470
30 Internal Stem and Guides SAME AS BODY
31 Weights ENCAPSULATED 316 SS OR HASTELLOY
32 Outlet Cover REQUIRED
33 Leakage 34 Manufacturer PROTECTOSEAL SHAND & JURS OR EQUAL
35 Model No. PVC8540B 94060
NOTES 40
Printed On: 6/17/2011 14:54
CONSTRUCTION
PROCESS DATA
SERVICE
CONDITIONS
0 TO 100
SODIUM HYPOCHLORITE OR SODIUM BISULFITE TANK VAPORS
VENTING
REQ.
VALVE CONCEPTS, INC
1 SCFH@ 90% SETPOINT
-10 TO 100
SEE ATTACHED TABLE
N/A
Deg F
WRA-3328
12 TOTAL (2 PER TANK-6 TANKS)
Units
OZ/IN2
Conservation Vent
Instrumentation Data Sheet
Deg F
Outbreathing (Pressure)
0.3*
* 0.3 OZ IS PREFERRED SETTING. 0.5 OZ IS ACCEPATABLE.
1. Vendor to provide peranent 316 SS nameplate stamped with item Tag No. (Tags names will be povided to vendor during manufature)
2. Vendor to provide certified calibration sheet for each vent.
CONSERVATION