This document is a 100 percent consolidated bid set for the Wolfskill Irrigation Well Phase 2 project in Winters, CA. The United States Department of Agriculture (USDA), Agricultural Research Service (ARS), Pacific West Area Office has a construction requirement to provide labor, materials, equipment, supplies, supervision, and transportation to complete this project at the USDA-ARS-PWA National Clonal Germplasm Repository in Winters, CA. The project is estimated to be between $250,000 and $500,000 in value and will be issued as a firm-fixed price construction contract. The requirement will be 100% set-aside for small businesses under NAICS Code 237110 with a $45M size standard. The Request for Proposal (RFP), Solicitation Number 12905B24R0012, may be issued on or around May 29, 2024, and will be accessible via SAM.gov. Potential offerors must be registered in the System for Award Management.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Wolfskill Irrigation Well Phase 2 Technical Specifications_Redacted.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1. THE CONTRACTOR SHALL CONDUCT ALL OPERATIONS IN STRICT ACCORDANCE WITH THE
SAFETY REQUIREMENTS IMPOSED BY THE OWNER AND OSHA. IT IS SOLELY THE
CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND
REGULATIONS GOVERNING THIS WORK. THE CONTRACTOR SHALL REMOVE ALL DEBRIS
FROM THE OWNER'S PROPERTY AND DISCARD ACCORDING TO LOCAL REGULATIONS.
2. THIS STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER IT IS FULLY
COMPLETED. HOWEVER, THE CONTRACTOR IS SOLELY RESPONSIBLE TO DETERMINE THE
ERECTION PROCEDURES AND SEQUENCES REQUIRED TO ENSURE STABILITY OF THE
STRUCTURE AND ITS COMPONENT PARTS DURING CONSTRUCTION. ANY TEMPORARY
BRACING, CONNECTIONS, GUYS, OR TIE-DOWNS THAT MAY BE NECESSARY DURING
ERECTION ARE NOT SHOWN ON STRUCTURAL DRAWINGS. IF APPLIED, THEY SHALL BE
REMOVED AS CONDITIONS PERMIT, AND SHALL REMAIN THE PROPERTY OF THE
CONTRACTOR. THIS CONSTRUCTION STABILITY REQUIREMENT APPLIES CONTINUOUSLY
AND IS NOT LIMITED TO NORMAL WORKING HOURS.
3. ALL TEMPORARY SHORING DRAWINGS SHALL BE PREPARED AND STAMPED BY A LICENSED
ENGINEER.
4. EXISTING UTILITIES AND ALL OTHER OBSTRUCTIONS TO WORK SHALL BE TEMPORARILY
REMOVED AND RE-INSTALLED (INCLUDING NECESSARY MODIFICATIONS) BY THE
CONTRACTOR AFTER COMPLETION OF NEW WORK.
5. DIMENSIONS PERTAINING TO EXISTING CONDITIONS SHALL BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO ANY FABRICATION, CONSTRUCTION, OR ERECTION.
6. ALL DETAILS, SECTIONS, AND NOTES PROVIDED ON STRUCTURAL DRAWINGS ARE
INTENDED TO BE TYPICAL FOR SIMILAR SITUATIONS ELSEWHERE, UNLESS SPECIFICALLY
NOTED OTHERWISE. FOR ANY DETAILS AND DIMENSIONS NOT PROVIDED, REFER TO
ARCHITECTURAL DRAWINGS. ALL DIMENSIONS AND ELEVATIONS SHOWN ON STRUCTURAL
DRAWINGS WERE INTENDED TO CONFORM WITH THE INFORMATION PROVIDED ON
ARCHITECTURAL DRAWINGS. THE CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO
THE ARCHITECT OR STRUCTURAL ENGINEER FOR RESOLUTION BEFORE PROCEEDING WITH
ANY ADDITIONAL WORK.
7. OPENING SIZES AND LOCATIONS SHOWN FOR PIPES, ETC. ARE SHOWN FOR GENERAL
INFORMATION ONLY. REFER TO RELATED DRAWINGS (ARCH., MECH., ELECT, ETC.) FOR
OTHER POSSIBLE EQUIPMENT SUPPORTS; SLEEVES; AND OTHER EMBEDDED ITEMS NOT
SPECIFICALLY INDICATED ON STRUCTURAL DRAWINGS. COORDINATE ALL REQUIRED
DIMENSIONS WITH APPLICABLE TRADE CONTRACTORS PRIOR TO ANY CONCRETE
PLACEMENT. ANY OPENINGS REQUIRED TO BE LARGER THAN OPENINGS SHOWN SHALL BE
VERIFIED PRIOR TO CONSTRUCTION.
8. ALL SPECIAL INSPECTIONS REQUIRED BY THE BUILDING OFFICIAL SHALL BE CONDUCTED IN
ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE GOVERNING BUILDING CODE.
REFER TO THE SPECIAL INSPECTION REQUIREMENTS ON SHEET S-002.
9. REFER TO SHEET S-001 FOR SHOP DRAWINGS AND SUBMITTAL REQUIREMENTS.
10. SHOP DRAWINGS AND SUBMITTALS PREPARED BY SUPPLIERS AND/OR SUBCONTRACTORS
SHALL BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR PRIOR TO
SUBMISSION TO THE STRUCTURAL ENGINEER. ALL DEVIATIONS FROM THE CONTRACT
DOCUMENTS SHALL BE CIRCLED AND NOTED ON THE SHOP DRAWINGS BY THE
CONTRACTOR. THE SCOPE OF THE STRUCTURAL ENGINEER'S REVIEW WILL BE LIMITED TO
CHECKING CONTRACTOR'S GENERAL CONFORMANCE WITH THE CONTRACT DOCUMENTS
AND DESIGN CONCEPT. NO SHOP WORK IS PERMITTED TO COMMENCE UNTIL THE RETURN
OF THE SHOP DRAWINGS BY THE GENERAL CONTRACTOR. DO NOT BEGIN SHOP WORK
UNTIL SHOP DRAWINGS ARE RETURNED WITH ENGINEER’S COMMENTS.
11. USE THE PROJECT SPECIFICATIONS IN CONJUNCTION WITH THE STRUCTURAL DRAWINGS
TO DETERMINE THE COMPLETE PROJECT REQUIREMENTS. ANY DISCREPANCIES OR
CONFLICTS FOUND BETWEEN THE PROJECT SPECIFICATIONS AND THE STRUCTURAL
DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT OR STRUCTURAL
ENGINEER IMMEDIATELY. THE STRICTEST PROVISION SHALL GOVERN UNLESS THE A/E
DETERMINES OTHERWISE.
CAST-IN-PLACE CONCRETE
ALL CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT ACI 301,
"SPECIFICATIONS FOR STRUCTURAL CONCRETE" AND ACI 117 "STANDARD SPECIFICATIONS
FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS" WITH THE
FOLLOWING SUPPLEMENTAL REQUIREMENTS:
1. ALL CONCRETE SHALL BE NORMAL WEIGHT WITH TYPE I OR TYPE II PORTLAND CEMENT
CONFORMING TO ASTM C150 AND AGGREGATES CONFORMING TO ASTM C33.
2. GROUT UNDER STEEL COLUMN AND BEAM BEARINGS SHALL BE NON-METALLIC,
NON-SHRINK, NON-GAS FORMING, EXPANSIVE TYPE "SONOGROUT" BY
SONNEBORN/CONTECH, "SEALTIGHT 588" BY W.R. MEADOWS, "EUCO NS" BY THE EUCLID
CHEMICAL COMPANY, OR "MASTERFLOW 928" BY MASTERBUILDERS. GROUT UNDER STEEL
BEARINGS SUPPORTING EQUIPMENT SHALL BE "SIKADUR-42" HIGH STRENGTH POURABLE
EPOXY RESIN GROUT BY THE SIKA CORPORATION. TYPICAL, UNLESS NOTED OTHERWISE.
3. CONCRETE SHALL BE PLACED AT THE SITE WITHIN 90 MINUTES AFTER WATER HAS BEEN
ADDED TO THE CEMENT AND AGGREGATE. ADDITION OF WATER TO THE MIX AT THE
PROJECT SITE WILL NOT BE ALLOWED. ALL WATER MUST BE ADDED AT THE BATCH PLANT.
4.. CHLORIDE BASED ADMIXTURES ARE PROHIBITED IN ALL REINFORCED CONCRETE. OTHER
ADMIXTURES SHALL CONFORM TO ASTM C494.
5. MAXIMUM SLUMP SHALL BE PER TABLE BELOW, AS DETERMINED IN ACCORDANCE WITH
ASTM C143.
8 INCHES, PLUS OR MINUS 1 INCH FOR CONCRETE WITH VERIFIED SLUMP OF 3 INCHES
PLUS OR MINUS 1 INCH BEFORE ADDING HIGH-RANGE WATER-REDUCING ADMIXTURE OR
PLASTICIZING ADMIXTURE AT PROJECT SITE.
6. AIR ENTRAIN ALL CONCRETE EXPOSED TO WEATHER 6% +/- 1 1/2%.
7. CONCRETE FINISH:
A. EXTERIOR SLABS - FLOAT/BROOM
8. CJ SHOWN ON PLAN INDICATES EITHER SLAB CONTRACTION JOINT OR CONSTRUCTION
JOINT AT CONTRACTOR'S OPTION, REFER TO DETAIL 01/S-501.
9.. ALL REINFORCING STEEL SHALL BE DEFORMED AND CONFORM TO ASTM A615 GRADE 60,
EXCEPT AS NOTED. WELDED REINFORCING STEEL SHALL BE DEFORMED AND CONFORM
TO ASTM A706 GRADE 60.
10. CONCRETE COVER ON REINFORCING STEEL SHALL BE PER CURRENT ACI 318 UNLESS
NOTED OTHERWISE.
11. REINFORCING BARS REQUIRED FOR PROPER SUPPORT OF THE PRINCIPAL REINFORCING
SHALL BE DETAILED AND SUPPLIED BY THE CONTRACTOR WHETHER OR NOT THEY ARE
INDICATED ON THE DRAWINGS.
12. ALL HOOK BARS SHALL HAVE 90 DEGREE ACI STANDARD HOOKS, UNLESS NOTED
OTHERWISE. HOOKS MAY BE ROTATED TO MAINTAIN CLEARANCES. ALL BAR SPLICES AND
LAPS, WHEN NOT SPECIFICALLY DIMENSIONED ON DRAWINGS, SHALL BE PER ACI
STANDARD REQUIREMENTS. CLASS B LAPS SHALL BE USED, UNLESS NOTED OTHERWISE.
13. TOP AND BOTTOM BARS DESIGNATED AS CONTINUOUS IN STRUCTURAL DRAWINGS SHALL
BE LAPPED AS FOLLOWS:
A. TOP BARS NEAR MIDSPAN
B. BOTTOM BARS DIRECTLY OVER SUPPORTS
14. ALL LAP SPLICES, WHEN NOT SPECIFICALLY DIMENSIONED ON DRAWINGS, SHALL BE PER
ACI 318-19 SECTION 25.5.2.1. LAPPING BARS OF TWO DIFFERENT SIZES SHALL BE PER ACI
318-19 SECTION 25.5.2.2.
15. PROVIDE HORIZONTAL EXTERIOR CORNER BARS WITH SAME SIZE AND SPACING AS WALL
REINFORCING BARS, UNLESS NOTED OTHERWISE.
16. THE PLACEMENT OF CONDUITS IN CONCRETE SHALL ONLY BE ACCEPTED IN ISOLATED
CASES AND SHALL ADHERE TO THE FOLLOWING:
A. CONDUITS PLACED IN SLAB ON GRADE SHALL BE PLACED DIRECTLY ON THE SUBGRADE
OR VAPOR RETARDER. OUTSIDE DIAMETER OF CONDUIT SHALL NOT EXCEED 1/4 OF SLAB
THICKNESS.
B. ALUMINUM CONDUITS, PIPES, OR SLEEVES ARE NOT PERMITTED.
C. OUTSIDE DIAMETER OF CONDUITS SHALL BE 1" OR LESS WHERE EMBEDDED IN
STRUCTURAL SLABS, AND 1 1/2" OR LESS WHERE EMBEDDED IN BEAMS, WALLS OR
COLUMNS.
D. BUNCHING OF CONDUITS IS NOT PERMITTED. CONDUITS SHALL BE SPACED 3
DIAMETERS OR GREATER ON CENTER. NO CROSSOVERS ARE PERMITTED IN SLABS.
E. MINIMUM CONCRETE COVER ON CONDUITS SHALL BE 1 1/2".
FOUNDATIONS
1. ALL EXCAVATION WORK SHALL PROCEED WITH CAUTION TO AVOID DAMAGE TO UNKNOWN
UNDERGROUND UTILITIES.
2. THE FOUNDATION DESIGN IS BASED UPON THE RECOMMENDATIONS OUTLINED IN THE
GEOTECHNICAL STUDY BY GEO ENGINEERS, INC. (FILE NO. 10883-028-00 DATED JANUARY
19,2024). CONTRACTOR SHALL REVIEW ENTIRE GEOTECHNICAL INVESTIGATION REPORT
PRIOR TO EXCAVATION WORK.
3. ALL EXCAVATION AND FILL SHALL BE PERFORMED ACCORDING TO THE ABOVE
REFERENCED GEOTECHNICAL REPORT.
4. ALL EXCAVATIONS SHALL BE INSPECTED BY A REPRESENTATIVE OF THE GEOTECHNICAL
ENGINEER, OR AN APPROVED GEOTECHNICAL TESTING AGENCY TO VERIFY THE PROPER
BEARING MATERIAL EXISTS PRIOR TO PLACING ENGINEERED FILL, FOUNDATION CONCRETE
AND/OR SLAB ON GRADE. FOUNDATION ELEVATIONS SHOWN ARE FOR BIDDING PURPOSES
ONLY, AND MAY VARY TO SUIT ACTUAL SUBSURFACE SOIL CONDITIONS.
5. SHALLOW SPREAD FOOTINGS BEARING ON NATURAL SOIL OR NEW GRANULAR
ENGINEERED FILL ARE DESIGNED FOR A MAXIMUM SOIL BEARING PRESSURE OF 2,000 PSF.
SOILS UNSUITABLE FOR SUPPORTING FOUNDATIONS SHALL BE REMOVED AND BACKFILLED
TO THE DESIGN BEARING ELEVATION, AS DIRECTED BY THE GEOTECHNICAL ENGINEER.
6. ALL FOUNDATION BEARING SURFACES SHALL BE UNDISTURBED, LEVEL (WITHIN 1 IN 12),
AND UNLESS NOTED OTHERWISE, ALL FOOTINGS MAY BE POURED NEAT (WITHOUT SIDE
FORMS) WHERE SOIL CONDITIONS PERMIT.
7. ALL COLUMN DOWELS AND ANCHOR BOLTS SHALL BE SET BY A TEMPLATE METHOD PRIOR
TO CONCRETE PLACEMENT.
STRUCTURAL STEEL
THE FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO ALL
REQUIREMENTS OF THE CURRENT AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS" AND AISC 303 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND
BRIDGES" WITH THE FOLLOWING SUPPLEMENTAL REQUIREMENTS:
1. ALL PLATES, BARS, CHANNELS, AND ANGLES SHALL CONFORM TO ASTM A36, Fy=36 KSI.
HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500, GRADE C, WITH A
MINIMUM YIELD STRESS (Fy) OF 50 KSI FOR SQUARE AND RECTANGULAR SHAPES.
2. SPLICING OF STRUCTURAL STEEL IS PROHIBITED EXCEPT AS DETAILED.
3. ALL STRUCTURAL STEEL SHALL BE NEW UNLESS NOTED OTHERWISE, AND SHALL BE MADE
FREE OF RUST, SCALE, ETC., AND ALL STEEL EXPOSED TO WEATHER OR BELOW GRADE
SHALL BE HOT-DIP GALVANIZED, EXCEPT AS NOTED.
4. WELDING SHALL CONFORM TO THE CURRENT AWS D1.1 "STRUCTURAL WELDING
CODE-STEEL", AND WELDING ELECTRODES SHALL BE E70. ALL FIELD WELDS ON
GALVANIZED STEEL SHALL BE TOUCHED UP WITH COLD GALVANIZING COMPOUND.
5. WELDS SHALL BE MADE ONLY BY CERTIFIED WELDERS AND WELDING OPERATORS WHO
HAVE BEEN PREVIOUSLY QUALIFIED BY TESTS AS PRESCRIBED IN THE CURRENT AWS D1.1
"STRUCTURAL WELDING CODE-STEEL". PROOF OF CERTIFICATION SHALL BE SUBMITTED TO
THE OWNER FOR APPROVAL BEFORE ANY WELDING IS PERMITTED TO BEGIN.
6. ANCHOR BOLTS FOR COLUMNS SHALL CONFORM TO ASTM F1554, GRADE AS NOTED ON
DRAWINGS, AND SHALL BE SET BY A TEMPLATE METHOD, OR AN APPROVED EQUIVALENT
METHOD.
7. DESIGN CONNECTIONS FOR THE FULL UNIFORM LOAD CAPACITY OF THE CONTINUOUSLY
BRACED MEMBER, UNLESS NOTED OTHERWISE.
STEEL ROOF DECK
1. METAL DECK FOR ROOFS SHALL CONFORM TO THE STEEL DECK INSTITUTE DESIGN
MANUAL FOR ROOF DECKS.
2. STEEL ROOF DECK SHALL BE GALVANIZED G60, UNLESS NOTED OTHERWISE.
3. ROOF DECK SHALL BE FASTENED TO ALL SUPPORTS WITH 5/8" DIAMETER PUDDLE WELDS
WITH A 36/5 PATTERN AND AT 6" OC AT ALL EDGES. DECK SIDELAPS SHALL BE FASTENED
WITH #10 TEK SCREWS AT 1/4 POINTS. UNLESS NOTED OTHERWISE, ALL DECK SHALL HAVE
A MINIMUM END LAP OF 3".
4. THE STEEL ROOF DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES: 1 1/2" x 22 GA DECK - Ip=0.155 IN4, Sp=0.186 IN3, In=0.183 IN4, Sn=0.192 IN3, Fy=33KSI MINIMUM.
f'c MAX WATER
CEMENT RATIO
SLUMP
EXTERIOR SLABS AND FOOTINGS 4,500 PSI 0.45 5 inches
SHOP DRAWINGS AND SUBMITTALS
SHOP DRAWINGS AND SUBMITTALS REQUIRED BY THE PROJECT AND PREPARED BY
SUPPLIERS AND/OR SUBCONTRACTORS SHALL BE REVIEWED AND STAMPED BY THE
CONTRACTOR PRIOR TO SUBMISSION TO THE STRUCTURAL ENGINEER. ALL DEVIATIONS FROM
THE ENGINEERING DRAWINGS SHALL BE CIRCLED AND NOTED ON THE SHOP DRAWINGS BY
THE CONTRACTOR. THE SCOPE OF THE STRUCTURAL ENGINEER'S REVIEW WILL BE LIMITED TO
CHECKING CONTRACTOR'S GENERAL CONFORMANCE WITH THE CONTRACT DOCUMENTS AND
DESIGN CONCEPT. NO SHOP WORK IS PERMITTED TO COMMENCE UNTIL THE STRUCTURAL
ENGINEER RETURNS A STAMPED, REVIEWED COPY OF THE SHOP DRAWINGS AND SUBMITTALS
TO THE CONTRACTOR.
THE FOLLOWING ITEMS ARE REQUIRED TO BE SUBMITTED TO THE STRUCTURAL ENGINEER
FOR REVIEW:
A. CAST-IN-PLACE CONCRETE
i. MIX DESIGNS: SUBMIT MIX DESIGNS AND TEST REPORTS ON MIXES FOR EACH CLASS OF
CONCRETE IN ACCORDANCE WITH CHAPTER 26 OF ACI 318.
ii. SHOP DRAWINGS: FABRICATION, BENDING AND PLACEMENT OF REINFORCING STEEL, BAR
CHAIRS, SPACERS, ACCESSORIES AND RELATED WORK, COMPLYING WITH ACI 315, SHOWING
BAR SCHEDULES, STIRRUP SPACING, DIAGRAMS OF BENT BARS AND ARRANGEMENT OF
REINFORCING. INCLUDE SPECIAL REINFORCING AT OPENINGS IN CONCRETE.
iii. CONCRETE SPECIMEN TEST REPORTS: TESTING AGENCY SHALL PROVIDE LABORATORY
CONCRETE SPECIMEN TEST REPORTS THAT SHALL INCLUDE THE 28-DAY COMPRESSIVE
STRENGTH SLUMP, AIR CONTENT AND TEMPERATURE OF THE CONCRETE WHEN THE SAMPLE
WAS TAKEN.
B. STRUCTURAL STEEL
SHOP DRAWINGS: SHOW FABRICATION OF STRUCTURAL-STEEL COMPONENTS:
i. INCLUDE DETAILS OF CUTS, CONNECTIONS, SPLICES, CAMBER, HOLES, AND OTHER
PERTINENT DATA.
ii. INCLUDE EMBEDMENT DRAWINGS.
iii. INDICATE WELDS BY STANDARD AWS SYMBOLS, DISTINGUISHING BETWEEN SHOP AND
FIELD WELDS, AND SHOW SIZE, LENGTH, AND TYPE OF EACH WELD. SHOW BACKING BARS
THAT ARE TO BE REMOVED AND SUPPLEMENTAL FILLET WELDS WHERE BACKING BARS ARE
TO REMAIN.
iv. INDICATE TYPE, SIZE, AND LENGTH OF BOLTS, DISTINGUISHING BETWEEN SHOP AND FIELD
BOLTS. IDENTIFY PRETENSIONED AND SLIP-CRITICAL, HIGH-STRENGTH BOLTED
CONNECTIONS.
C. STEEL DECKING
SHOP DRAWINGS:
i. INCLUDE LAYOUT AND TYPES OF DECK PANELS, ANCHORAGE DETAILS, REINFORCING
CHANNELS, PANS, CUT DECK OPENINGS, SPECIAL JOINTING, ACCESSORIES, AND
ATTACHMENTS TO OTHER CONSTRUCTION.
D
C
B
A
1 2 3 4 5
54321
A
B
C
D
Designing Better Futures
DATE
CHECKED
DRAWN
PROJ. NO.
COFFMAN ENGINEERS INC.C
SHEET NO:
SHEET TITLE:
REV DATE DESCRIPTION
KZF DESIGN INC.
700 Broadway Street Cincinnati, OH 45202 main 513.621.6211 kzf.com
700 Broadway Street Cincinnati, OH 45202 main 513.621.6211 kzf.com
WOLFSKILL
IRRIGATION WELL
PHASE 2
USDA
AGRICULTURAL
RESEARCH SERVICE
100% BID SET
NATIONAL CLONAL
GERMPLASM
REPOSITORY
2024-04-01
CAIN
OVERWEIN
230525
S-001
GENERAL NOTES