Watson McDaniel Pressure Reducing Valve.pdf
PDF 171 KB Posted
- Attached to
- Watson McDaniel Pressure Reducing Valve
- Solicitation number
- W912DW23C0014_SPECIAL_NOTICE
About this file
The documents detail Watson McDaniel's Pressure Reducing Valve (PRV) technical specifications for a U.S. Army Corps of Engineers contract (Solicitation W912DW23C0014_SPECIAL_NOTICE) for the Washington State University Plant Biosciences Research Building. The PRV system is designed for steam pressure regulation, featuring parallel valves capable of managing wide flow rate variations, with two valve sizes (2 1/2" Reduced and 2 1/2" Full) that handle flow rates of 3,707 and 7,528 lbs/hr respectively. The valves are globe-type, constructed with hardened stainless steel seats and stems, and operate at 100 psig inlet pressure with a 15 psig outlet pressure.
The solicitation requires manufacturers to submit detailed product specifications demonstrating compliance with Buy American Construction Materials requirements by 1:00 p.m. Pacific Time on 20 March 2025. Responses must include catalog cuts, technical specifications, manufacturing location, and pricing. The valves are intended for the Agricultural Research Services project, with applicable NAICS codes 332919 (Metal Valve Manufacturing) and 423830 (Industrial Machinery Wholesalers). The technical documentation provides comprehensive installation guidelines, operational parameters, and system configuration details for the pilot-operated pressure reducing valves.
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REGULATING VALVE APPLICATIONS
PRESSURE REDUCING STATION • Parallel for High Flow Turndown
PURPOSE: For reducing steam system inlet pressure to a constant outlet pressure when steam flow rates vary widely. This will help improve system rangeability resulting in more accurate control.
OPERATION: Because regulators are simple, self-powered devices which do not rely on an external control signal to determine valve steam position, they may not have the flow rangeability of control valves.
Therefore, if a system has large flow variations (such as summer and winter loads), multiple regulators should be considered. Typically referred to as a 1/3 - 2/3 system, one valve may be sized for approximately 1/3 of the total maximum load demand and a larger valve for the remaining 2/3. When full load is required, both valves will be open and regulating. The small regulator is typically the primary valve and is set at a pressure 2 psi higher than the larger secondary valve. This allows the small regulator to be the only one flowing when demand is low. When flow increases and the small valve cannot keep up with the demand, the downstream pressure will begin to drop which will allow the larger secondary valve to open in order to help satisfy the demand. Although the smaller regulator is commonly selected as the primary valve, either the smaller or larger regulator may be set as the primary valve based on anticipated load demand requirements. The primary valve should always be set a minimum of 2 psi above the secondary valve.
INSTALLATION GUIDELINES: (see Figure 8)
• This example depicts a parallel pilot-operated steam PRV pressure reducing station using HD Regulators with Pressure Pilot. An external sensing line is required to sense downstream pressure from each regulator. The end of each sensing line is placed away from the turbulent flow at the valve outlet. This helps to improve accuracy of the set pressures. Set pressure for each PRV is adjusted by turning a screw on the pilot to increase or decrease compression on a balancing spring.
• Proper setting of the valves is key to proper operation. The chosen primary valve should be set at a pressure approximately 2 PSI higher than that of the secondary valve.
• For optimum operation and service life, maintain recommended minimum piping straight runs before and after the PRV. Inlet pipe diameters could be 1-2 sizes larger and outlet pipe diameters 2-3 sizes larger than the end connections of an appropriately sized PRV. The purpose of increasing the pipe size downstream of the regulator is to keep the steam velocity constant on both sides of the regulator.
• Each pressure sensing line should slope downwards, away from the regulator, to prevent condensate from entering the pilot.
• Eccentric reducers, if required, are used on valve inlets to prevent accumulation of condensate which could become entrained with high-velocity steam, possibly resulting in dangerous waterhammer.
• While the separator shown upstream is appropriate for protection of the PRV, it is not always required, as a properly sized drip leg with steam trap may be sufficient. It is recommended for systems where steam is known to be “wet” and the entrained moisture could affect valve performance and/or result in component damage.
• Consider installing a properly sized bypass line with globe valve to provide continuous operation should regulator maintenance be required.
• Consider low-cracking pressure (1/4 PSI opening pressure) check valves after steam traps when discharging into condensate return lines. Check valves eliminate the possibility of condensate backing up through the steam trap into the system.
• A safety relief valve (SRV) is appropriate where applicable codes dictate their requirement, or anywhere protection of downstream piping and equipment from over-pressurization is desired. The SRV needs to handle the complete volume of steam from the regulator and bypass loop. Consult the factory for appropriate SRV sizing guidelines.
EN
G
IN
EE
R
IN
G www.watsonmcdaniel.com •• Pottstown PA • USA • Tel: 610-495-5131
R E
G U
LA
TIN
G V
A
LV
E A
P P
LIC
A
TIO
N
S
PRESSURE RED
UC
IN
G
STA
TIO
N
Pa ra lle l fo r H ig h Flow
Turnd ow n
Fig ure 8:
PARALLEL Pressure Reducing Station (HD Regulator Applications)
ENGINEERING
Drip Pan
Elbow
Vent
STEAM
INLET
SEPARATOR
Bypass Globe Valve
To Condensate Return
WFT
Trap
HD Regulating Valve with
Pressure Pilot
Y-Strainer
Union
STEAM
OUTLET
10 Pipe Diameters Minimum
FTT
Trap
10 Pipe Diameters Minimum
10 Pipe Diameters Minimum
Gate Valve
TD600L
Trap
10 Pipe Diameters Minimum
HD Regulating Valve with
Pressure Pilot
Y-Strainer
Check Valve
Test Valve
Pressure Sensing Line
Pressure Sensing Line
Safety Relief Valve
Re duced Ou tlet Pressure
Te l: 6
-4
-5
Po ttsto w n
PA
U
SA
w w w
.w a tso nm c d a nie l.c o m
Secondary
Primary
Watson McDaniel Pilot Operated PRV Datasheet
Part Number: HDR-18-F150
Service conditions
Line
Valve Body/Bonnet
Trim
Report generated by: Mike, Mon Dec 02 14:25:10 MST 2024 Version 1.1
Fluid Steam
Flow Rate 3707.00 lbs/hr
Inlet Pressure 100.00 psig
Intermediate Pressure 0.00 psig
Outlet Pressure 15.00 psig
Inlet Temperature 338°F
Required Cv 20.10
Rated Cv 25.90
Travel 77.59%
Predicted SPL 82.10 dBA
Inlet Pipe Size 2.50" sch 40
Inlet Velocity 7223.24 ft/min
Outlet Pipe Size 6.00" sch 40
Outlet Velocity 4280.41 ft/min
Type Globe
Size 2 1/2" Red.
Mfr & Model Watson McDaniel HD Series
Valve Connection 150# FLG
Option None
SS Diapragm No
SS Ext. Tube No
Balanced/Unbalanced Unbalanced
Seat Material Hardened SS
Stem Material Hardened SS
Watson McDaniel Pilot Operated PRV Datasheet
Part Number: HD-18-F150
Service conditions
Line
Valve Body/Bonnet
Trim
Report generated by: Mike, Mon Dec 02 14:23:02 MST 2024 Version 1.1
Fluid Steam
Flow Rate 7528.00 lbs/hr
Inlet Pressure 100.00 psig
Intermediate Pressure 0.00 psig
Outlet Pressure 15.00 psig
Inlet Temperature 338°F
Required Cv 41.50
Rated Cv 55.00
Travel 75.45%
Predicted SPL 85.92 dBA
Inlet Pipe Size 4.00" sch 40
Inlet Velocity 5516.76 ft/min
Outlet Pipe Size 8.00" sch 40
Outlet Velocity 5019.83 ft/min
Type Globe
Size 2 1/2" Full
Mfr & Model Watson McDaniel HD Series
Valve Connection 150# FLG
Option None
SS Diapragm No
SS Ext. Tube No
Balanced/Unbalanced Unbalanced
Seat Material Hardened SS
Stem Material Hardened SS