Waste Oil Furnace Specs[1]..doc

DOC document 25 KB Posted

Attached to
The purchase of 1 waste oil furnace
Solicitation number
RFQ - 17D - 07080700000000000078
Issued by
Maine

About this file

This document contains the specifications for a waste oil furnace that is the subject of a state and local contract opportunity in Maine. The furnace must have a fuel consumption of no more than 1.2 gallons per hour, a minimum BTU rating of 175,000 per hour, and be able to accept various waste oils and fuel oils as fuel. The furnace must come with a self-metering oil pump, have a minimum air flow of 1650 CFM, and include a new burner assembly. Electrical requirements are 115 VAC, 60 Hz, single phase with a 20 amp circuit breaker, and the unit must have a one-year warranty on all parts and labor. The contract opportunity is for the purchase of 1 waste oil furnace.

The pricing terms, set-asides, or funding sources are not specified in the document. The document also does not provide information on any incumbent vendors, the current environment, or any other salient details beyond the technical specifications of the required furnace.

View the file

Other files

File Type Posted
Conditions and Instructions to Bidders.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specifications for

Waste Oil Furnace

The intent of these specifications is to describe a waste oil furnace that shall provide a heating appliance tested to current standards for burning waste oils.

1. Fuel consumption shall not be more than 1.2 gallons per-hour.

2. BTU’s shall have a minimum rating of 175,000 per-hour

3. Waste oil furnace shall be able to accept Crankcase, ATF, Hydraulic oils, and #2, #4, and #5 fuel oils as fuel.

4. Furnace shall come with a self metering oil pump.

5. Air flow shall be a minimum of 1650 CFM (Cubic Feet Per-Minute).

6. Furnace shall come complete with new Burner assembly.

7. Stack size shall be 8 inches in diameter.

8. Electrical requirements shall be 115 VAC, 60 H Single phase, 20 amp circuit breaker.

9. Unit shall be warranted for one full year on all parts and labor.

10. Trade-in of existing unit is desirable.