Smoke_Density_Toxicity_Chamber_SOW_and_Salient_Characteristics.docx
DOCX document 14 KB Posted
- Attached to
- Smoke Density/Toxicity Chamber
- Solicitation number
- W91ZLK-16-T-0205
About this file
Statement of Work/Salient Characteristics for Required Smoke Density/Toxicity Chamber
View the file
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work – Salient Characteristics Smoke Density/Toxicity Chamber - This equipment will be used to measure the smoke and toxic gases emitted by burning materials under flaming and non-flaming conditions. The chamber will be used to evaluate materials used by Army to determine potential exposure hazards. The apparatus must be constructed to meet the specifications for the measurement of smoke given off by burning materials as cited by International, National, Industrial and Regional codes and regulations. Measures Specific Optical Density (E662), Mass Optical Density (ISO5659-2), and Smoke Toxicity under flaming and non-flaming conditions.
Test Chamber Shall Include:
| • | Compatibility with 208 Volt Single Phase Facility Power. |
| • | Stainless steel Test Chamber coated with corrosion resistant lining. |
| • | Full front door opening for easy cleaning. |
| • | Specimen access door for use during testing. |
| • | Two Interchangeable Furnace assemblies; one ASTM Method E662 horizontal furnace and one ISO 5659-2 cone furnace. |
| • | The ASTM E662 Furnace shall include: |
a) Vertical furnace assembly.
b) Stainless steel specimen guide bars.
c) Pneumatic specimen positioning system.
d) 2 Stainless steel specimen holders.
e) Calibrated Heat Flux Transducer; 0 to 5 BTU/ft²/second (0 to 5.58 W/cm²).
f) Heat flux transducer is mounted in Modified Specimen Holder for ease of use.
• The ISO5659-2 Furnace includes:
a) Horizontal furnace assembly manufactured from Hi-quality Stainless Steel.
b) Cone type heater element.
c) PID temperature control of heater element.
d) Shutter to screen test specimen from heat before starting test.
e) Pneumatically controlled shutter position.
f) Specimen holder support assembly.
g) 2 Stainless Steel specimen holders.
h) Hi-precision Weigh cell to measure mass loss during test.
i) Calibrated Heat Flux transducer 0 to 100 kW/m².
h) Heat flux transducer positioning system for ease of use.
| • | Easy change over from ASTM Method E662 horizontal furnace to ISO 5659-2 cone furnace. |
| • | Photo Detector & Radiometer (light sensing instrumentation). |
| • | Chamber pressure continuously monitored and digitally displayed on control panel. |
| • | Automatic over-pressure relief system. |
| • | Safety Pressure relief blow out panel. |
| • | Powered positive venting of smoke effluents after test. |
| • | Intuitive/Easy to use Instrument Control Panel. |
| • | Data acquisition system to record data during test |
| • | The Data acquisition system shall include: |
a) Easy to use Windows Menus.
b) Guides operator through calibration and specimen testing.
c) Test data calculation and reporting.
d) Windows 7 compatible software.
| • | Smoke Gas Toxicity Package: |
| • | The Smoke Gas Toxicity Package shall include: |
a) Gas Extraction Pump.
b) 20 Detector Tubes per gas (To measure HCN, NOx, CO, HF, HCl, SO2 as per BSS 7239 and AITM 3.0005).
| • | Accessories and Spare Parts to include: |
| a) Spare Furnace (Heater Assembly) for ASTM E662. | |
| b) Spare Standard Burner, Multi-Tip, Multi-Angle ASTM E662 | |
| c) Spare Burner, Multi-Tip, Single Angle ASTM E662 | |
| d) Flux Transducer (use with ASTM Furnace Assembly) E662 | |
| e) Specimen Holder, ASTM E662 | |
| f) Specimen Holder A - Wire 0.25” maximum diameter ASTM E662 | |
| g) Specimen Holder B- Insulated Wire 0.125” maximum diameter ASTM E662 | |
| h) ISO/Cone Heater Assembly ISO 5659-2 | |
| i) Flux Transducer (use with ISO Furnace Assembly) ISO 5659-2 | |
| j) Specimen Holder, ISO 5659-2 |
File details come from the government source that posted it. Updated .