AIII 19-15 UMCS Technical Exhibit03_02220 Main library.pdf
PDF 582 KB Posted
- Solicitation number
- W91QVN20R0045
About this file
This is a solicitation for Utility Monitoring Control Systems (UMCS) services at USAG Humphreys. The contractor shall provide all labor, materials, equipment, tools, transportation, supervision, technical guidance and field experience necessary for the preventive and corrective maintenance of the UMCS, DDC systems, HVAC systems, SCADA systems, electrical distribution systems, power generation systems, communication infrastructure, and other associated systems. The contractor shall have appropriate licenses, certifications, proprietary tools, and expertise to perform required duties. The contractor shall use open-source and open-protocol procedures and not install proprietary software that could create future transitional issues. The agency is the Department of the Army Materiel Command Army Contracting Command.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
HC
DX
C
CLOSED WHEN PRESSURE IS BELOW SETPOINT
OPEN WHEN PRESSURE IS BELOW SETPOINT
CLOSED WHEN PRESSURE IS ABOVE SETPOINT
CONTACT, PRESSURE, LOW LIMIT (LL)
OPEN WHEN PRESSURE IS BELOW SETPOINT
CLOSED WHEN PRESSURE IS ABOVE SETPOINT
CONTACT, PRESSURE, LOW LIMIT (LL)
SHOWN IN UNACTIVATED POSITION
SHOWN IN ACTIVATED POSITION
PRESSURE GAUGEP
FILTER
XX-C
COIL, HEATING
CONTACT, PRESSURE, HIGH LIMIT (HL)
OPEN WHEN PRESSURE IS ABOVE SETPOINT
CLOSED WHEN PRESSURE IS BELOW SETPOINT
OPEN WHEN PRESSURE IS ABOVE SETPOINT
CONTACT, PRESSURE, HIGH LIMIT (HL)
SHOWN IN ACTIVATED POSITION
SHOWN IN UNACTIVATED POSITION
COIL, COOLING, DIRECT-EXPANSION
COIL, HEAT/COOL
COIL, COOLING
FAN
YY = CONTACT NUMBER
xx = RELAY COIL NUMBER
YY = CONTACT NUMBER
xx = RELAY COIL NUMBER
RELAY COIL CONTACT
NORMALLY CLOSED
Rxx-YY
RELAY COIL CONTACT
NORMALLY OPEN
Rxx-YY
AFMA
W-X-Y-Z
REV
DIR
DDC
W-X-Y-Z
SEE "DEVICE SYMBOL, GENERIC"
VALVE, BALANCING
AIR FLOW MEASUREMENT ARRAY,
WITH FLOW TRANSMITTER
ACTUATOR, ELECTRIC
IN DAMPER SCHEDULE
RELAY COIL
MOTOR STARTER
Rxx
MS-#
MOTORM#
DAMPER, PARALLEL BLADE
DAMPER, OPPOSED BLADE
IN DAMPER SCHEDULE
## = DAMPER NUMBER AS SHOWN
## = DAMPER NUMBER AS SHOWN
NORMALLY OPEN OR CLOSED
NORMALLY OPEN OR CLOSED
D-##
D-##
DAMPER, BALANCING
## : DEVICE NUMBER
DEVICE SYMBOL, GENERIC
REV : REVERSE CONTROL ACTION
DIR : DIRECT CONTROL ACTION, OR
MULTIPLE OUTPUT DEVICE WHERE AT LEAST 1
OUTPUT IS ALWAYS SAFETY INTERLOCK
DDC : DIRECT DIGITAL CONTROL
DEVICE SYMBOL, CONTROLLER
GENERIC USAGE TO SHOW LOCATION OF DEVICE;
PROCESS OR DEVICE BEING MEASURED OR
CONTROLLED; SIGNAL TYPE; MODIFIERS AND
OTHER APPLICATION INFORMATION
USED TO REPRESENT SENSORS, INSTRUMENTS
W-X-Y-Z : (SEE ABBREVIATIONS AND ACRONYMS)
SAFETIES, AND OTHER CONTROL DEVICES
DEVICE SYMBOL, GENERIC
CONTACT, TEMPERATURE, LOW LIMIT (LL)
SHOWN IN ACTIVATED POSITION
CONTACT, TEMPERATURE, LOW LIMIT (LL)
CLOSED WHEN TEMPERATURE IS ABOVE SETPOINT
CLOSED WHEN TEMPERATURE IS ABOVE SETPOINT
OPEN WHEN TEMPERATURE IS BELOW SETPOINT
OPEN WHEN TEMPERATURE IS BELOW SETPOINT
SHOWN IN UNACTIVATED POSITION
CURRENT TRANSFORMER/SWITCH
OPEN WHEN TEMPERATURE IS ABOVE SETPOINT
CLOSED WHEN TEMPERATURE IS BELOW SETPOINT
SHOWN IN ACTIVATED POSITION
CONTACT, TEMPERATURE, HIGH LIMIT (HL)
OPEN WHEN TEMPERATURE IS ABOVE SETPOINT
CLOSED WHEN TEMPERATURE IS BELOW SETPOINT
CONTACT, TEMPERATURE, HIGH LIMIT (HL)
SHOWN IN UNACTIVATED POSITION
COM = COMMON PORT
VARIABLE FREQUENCY DRIVE
XX = PROCESS/DEVICE BEING
C = 4-20 mA, VDC, or SNVT
SS = START/STOP COMMAND
S = STATUS FEEDBACK (ON/OFF)
IN VALVE SCHEDULE
## = VALVE NUMBER AS SHOWN
XX-S
VFD
XX-SS
WITH SPRING RETURN FAILSAFE
NO = NORMALLY OPEN
NC = NORMALLY CLOSED
COM = COMMON PORT
NC = NORMALLY CLOSED
NO = NORMALLY OPEN
WITH SPRING RETURN FAILSAFE
VALVE, 3-WAY MIXING
IN VALVE SCHEDULE
## = VALVE NUMBER AS SHOWN
NC
V-##
NO COM
NC
IN VALVE SCHEDULE
VALVE, NORMALLY CLOSED
IN VALVE SCHEDULE
VALVE, NORMALLY OPEN
VALVE, 3-WAY DIVERTING
WITH SPRING RETURN FAILSAFE
WITH SPRING RETURN FAILSAFE
## = VALVE NUMBER AS SHOWN
## = VALVE NUMBER AS SHOWN
V-##
COM NO
V-##
NO
NC
V-##
THERMOWELL IN PIPE
THERMOSTAT WITH SPECIFIED
TEMPERATURE SENSOR, POINT
SEE "DEVICE SYMBOL, GENERIC"
STAT
TEMPERATURE SENSOR, AVERAGING
or TEMPERATURE LOW LIMIT / FREEZESTAT
SEE "DEVICE SYMBOL, GENERIC"
TEMPERATURE GAUGET
SWITCH, MANUAL
RADIATOR
PRESSURE SWITCH, DIFFERENTIAL,
H = HIGH PRESSURE TAP
L = LOW PRESSURE TAP
SEE "DEVICE SYMBOL, GENERIC"
P H L
PUMP
LOCAL DISPLAY PANEL
## = SEQUENTIAL NUMBER
(WHEN MORE THAN 3~15 LDP)##
LDP
W-X-Y-Z
W-X-Y-Z : (SEE ABBREVIATIONS AND ACRONYMS)
GENERIC USAGE TO SHOW LOCATION OF DEVICE;
PROCESS OR DEVICE BEING MEASURED OR
CONTROLLED; SIGNAL TYPE; MODIFIERS AND
OTHER APPLICATION INFORMATION
CONTROL SIGNAL LINE, LOW VOLTAGE
xx = SEQUENTIAL RELAY
(SOLENOID) NUMBER
CONTROL SCHEMATIC SYMBOLS
CONTROLLED
CONTROL SIGNAL
I/O FUNCTIONS
WITH GAUGE
AS SHOWN
AS SHOWN
BOILER
RESET BUTTON FOR SAFETY RESETRST-BUT
SMOKE DETECTOR, DUCT-MOUNTED
SEE "DEVICE SYMBOL, GENERIC"
SD
TWO-POSITION
ADJUSTABLE
AIRFLOW MEASUREMENT ARRAY
ALARM
BYPASS AIR
BUILDING
BUTTON
COMMAND
COLD DECK
CHILLER
COOLING
CARBON DIOXIDE
COMMON
COMPARATOR
CONFIGURATION PROPERTY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
CURRENT TRANSFORMER/SWITCH
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER
DAMPER
DISCHARGE AIR
DEADBAND
DIRECT DIGITAL CONTROL(LER)
DIFFERENCE
DIRECT (CONTROL ACTION)
DISABLE
DISPLAY
DIRECT EXPANSION
EXHAUST AIR
ECONOMIZER
EXHAUST FAN
ENABLE
FLOW
FIRE ALARM PANEL
FILTER
HOT DECK
HIGH LIMIT
HEATING
HUMIDIFIER
HOT WATER
HOT WATER RETURN
HOT WATER SUPPLY
HEAT EXCHANGER
2P
ADJ
AFMA
ALM
BA
BLDG
BUT
C
CD
CHLR
CLG
CO2
COM
COMP
CP
CR
CS
CT
CHR
CHS
CW
D
DA
DB
DDC
DIFF
DIR
DIS
DISP
DX
EA
ECO
EF
ENA
FAP
FLT
HD
HL
HTG
HUM
HW
HWR
HWS
HX
INPUT/OUTPUT
LOCAL DISPLAY PANEL
LOW LIMIT
MONITORING & CONTROL
MIXED AIR
MINIMUM OUTSIDE AIR
MOTOR STARTER
NOT APPLICABLE
NORMALLY CLOSED
NETWORK CONFIGURATION INPUT
NORMALLY OPEN
OUTSIDE AIR
OCCUPIED
ON DELAY TIMER
OPERATOR WORKSTATION
PRESSURE
PRE-COOLING
PRIMARY CHILLER WATER
PRIMARY CHILLER WATER RETURN
PRIMARY CHILLER WATER SUPPLY
PREHEAT
PUMP
POSITIVE POSITIONER
RELAY
RETURN AIR
REVERSE (CONTROL ACTION)
RETURN FAN
RELATIVE HUMIDITY
RELIEF AIR
ROOM
RESET
RATE
STATUS
SUPPLY AIR
SECONDARY
SUPPLY FAN
SMOKE
STANDARD NETWORK VARIABLE TYPE
SETPOINT
START/STOP COMMAND
THERMOSTAT
SYSTEM
SCHEDULER
TEMPERATURE
UNOCCUPIED
VALVE
VARIABLE AIR VOLUME
VARIABLE FREQUENCY DRIVE
WET BULB (TEMPERATURE)
ZONE
I/O
LDP
LL
M&C
MA
MINOA
MS
N/A
NC
NCI
NO
OA
OCC
ODT
OWS
P
PC
PCW
PCWR
PCWS
PH
PMP
PP
R
RA
REV
RF
RH
RLA
RM
RST
RT
S
SA
SEC
SF
SMK
SNVT
SP
SS
STAT
SYS
SCHD
T
UNOCC
V
VAV
VFD
WB
ZN
ABBREVIATIONS AND ACRONYMS
DIFFERENCE PRESSURE VALVEDPV
F
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, C O
N
TR
O L
A
B B
R E
V
IA
TI
O
N S
A N
D S
Y M
B O
LS
MI601F
NOTES:
CONTRACTOR SHALL COORDINATE WITH OWNER / USING AGENCY FOR THE EXACT LOCATION OFF DDC
WORK STATION, LDP, DDC ALARM PANEL LOCATION AND HVAC EMERGENCY SHUT OFF BUTTON.
THIS DIAGRAM IS TO ONLY REPRESENT THE INTENT OF THE CONTROL SYSTEMS ARCHITECTURE AND IT IS THE RESPONSIBILITY OF THE CONTROLS CONTRACTOR TO PROVIDE A SYSTEM SCHEMATIC
REPRESENTING THE ACTUAL INSTALLED DDC SYSTEM ARCHITECTURE.
THE CONTROLS CONTRACTOR IS TO PROVIDE ALL NECESSARY CONTROL PROGRAMMING AND CONNECTION REQUIREMENT TO REPORT TO THE UMCS (UTILITY MONITORING AND CONTROL SYSTEM) LOCATED ON BASE AS A PART OF THIS CONTRACT. IF THE BASE DOES NOT HAVE A UMCS SYSTEM A FUTURE TIE
IN CONNECTION SHALL BE PROVIDED FOR A FUTURE BASE UMCS SYSTEM.
THE CONTROLS CONTRACTOR TO PROVIDE ALL WIRING AND PROGRAMMING REQUIREMENTS FOR THE
FUTURE INSTALLATION OF A GAS METER.
THE CONTROLS CONTRACTOR TO PROVIDE ALL WIRING AND PROGRAMMING REQUIREMENTS FOR THE
FUTURE INSTALLATION OF A BASE WIDE UMCS MONITORING.
CONTRACTOR TO PROVIDE A LIST OF ALL NVI (NETWORK VARIABLE INPUTS) AND NVO
(NETWORK VARIABLE OUTPUTS) ON THIS DRAWINGS WHEN SUBMITTED FOR SHOP DRAWING APPROVAL.
ALL CONTROLLERS ARE TO BE FIELD LOCATED ON THE UNIT IT SERVES OR IN A ACCESSIBLE
PLACE REMOTE FROM UNIT AS REQUIRED TO MAINTAIN 600mm OF WORKING SPACE INFRONT
OF CONTROLLER.
1.
2.
3.
4.
5.
6.
7.
LO
N
T A
LK
UNIT
HEATERS
EXHAUST
FANS
AH-1
AH-2
ERU-1
ERU-2
SPLIT TYPE
AC UNITS
VRF HEAT
PUMPS
LO
N
T A
LK
AI LONWORKS
METERGAS METER
WATER METER AI LONWORKS
METER
AIELECTRIC
METER
LON SERVER 1 LON SERVER 2
LO
N
-B U
S
AO
BO
AI
BI
DDC I/O
LN-PRG
LO
N
-B U
S
AO
BO
AI
BI
DDC I/O
LN-PRG
LO
N
-B U
S
AO
BO
AI
BI
DDC I/O
LN-PRG
LO
N
-B U
S
AO
BO
AI
BI
DDC I/O
LN-PRG
LO
N
-B U
S
AO
BO
AI
BI
LN-PRG
DDC I/O
LO
N
-B U
S
AO
BO
AI
BI
LN-PRG
DDC I/O
LO
N
-B U
S
AO
BO
AI
BI
LN-PRG
DDC I/O
DWH-1
DP-1
AIR HANDLING UNIT
& HEATING COIL
BUILT-IN CONTROLLER
AIR HANDLING UNIT
& HEATING COIL
BUILT-IN CONTROLLER
VRF HEAT PUMP OUTDOOR
UNIT & INDOOR UNIT
BUILT-IN CONTROLLER
SPLIT TYPE AC UNIT
BUILT-IN CONTROLLER
ENERGY RECOVERY UNIT
& HEATING COIL
BUILT-IN CONTROLLER
DOMESTIC HOT WATER
HEATER & PUMP
UNIT HEATER & EXHAUST FANS
BUILT-IN CONTROLLER
FUTURE CONNECTION TO
BASEWIDE UMCS
SPECIFICATIONQTYKEY NAME
NOTE :
THE SPECIFICATION SHOWN IS A MINIMUM CONFIGURATION. THE CONTROLS CONTRACTOR SHALL SUBMIT MANUFACTURER'S TECHNICAL LITERATURE FOR EACH DEVICE FOR APPROVAL. INDICATE DIMENSIONS, CAPACITIES, PERFORMANCE CHARACTERISTICS, ELECTRICAL CHARACTERISTICS, FINISHES FOR MATERIALS AND INSTALLATION AND STARTUP INSTRUCTIONS FOR EACH TYPE OF PRODUCT INDICATED.
LON IP ROUTER
Universal 0 to 10 VDC, digital 0 to 12 VDC, (on/off), 0~20mA, PWM, or floating PWM output: adjustable period from 2 seconds to 15 minutes Floating control: requires two consecutive outputs Minimum pulse on/off: 500 milliseconds Adjustable drive time period 60 mA maximum at 12 VDC Minimum load 200 ohms Power Supply Output: 15 VDC, maximum 240 mA
3. Outputs
Universal software configurable Input Types:
Digital: Dry Contact Pulse: Dry Contact Analog Current: 4 to 20 mA Analog Voltage: 0 to 10 VDC
2. Inputs
Standard: LonMark Functional Profile: SCC-VAV Controller #8502 Processor: Neuron 3150, 8 bits, 10MHz Memory: Nonvolatile Flash 64k(APB application), Nonvolatile Flash 64k(storage) Media Channel: TP/FT-10; 78Kbps Communication: LonTalk protocol Transceiver: FTX-1 LonMark Interoperability: Version 3.4 Device Class: Multi I/O Module
1.
2.
3.
4.
Ethernet Port : 10/100Base T,auto-selecting, auto polarity, RJ-45, 8conductor.
Memory : 64MB flash memory ; 634MB RAM Serial Port : 1 isolated RS-485 port ; 1EIA-232 port Operating Input Voltage ; 100-240VAC
POWER : 110V, AC 10%, 50/60 HZ, 80 VA±
: TCP/IP
: TCP/IP
INPUT
OUTPUT-HUB
1. General LN Series Free Programmable Controllers-LON
CONTROLLER
: ENGLISH 400 CPS
: KOREAN 266 CPS
PRINT SPEED
PRT 1 INKJET COLOR PRINTER FOR REPORT
INKJET COLOR PRINTER1.
2.
3.
1UPS UNINTERRUPTED POWER SUPPLY
CAPACITY : 110V, 1.5KVA
-LON IP ROUTER
1.
Processor: Neuron 3150, 8 bits, 10MHz Memory: Nonvolatile Flash 64k(APB application), Flash 128k(storage) Battery: CR 2032 Lithium Battery Media Channel: TP/FT-10; 78Kbps Transceiver: Echelon's Free Topology Transceiver (FTT-10) Communication: LonTalk Protocol Type: Backlit LCD Display Definition: 128x128 pixels Display area size: 5.5x5.5cm (2.1x2.1inches)
1. General LN Series Display
-LOCAL
DISPLAY
BUILDING
LEVEL
M&C SYSTEM
BUILDING LEVEL M&C SYSTEM
1.
2.
3.
4.
CPU : INTEL Core i5-480M, Clock speed 2.67GHz, 14"(1366x768) Memory : 4G RAM, 640G HDD Bluetooth 3.0 Points Read / Write
5. Schedule / Event Management
6. Date Setting & Status Monitoring
7. Microsoft Windows 7
8. Office Automation Software : Microsoft Office 2010
9. Virus Protection Software : Symantec Endpoint Protection 12.1
HUB
BUILDING LEVEL
INKJET
PRT UPS
M&C SYSTEM
(LOCATE : WILL BE INSTALLED LATER IN CONSULTATION WITH DPW )
LONWORKS
METER
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, 1 DDC AUTOMATIC CONTROL SYSTEM CONFIGURATION
SCALE = NOT TO SCALE 2 HVAC AUTOMATIC CONTROL SYSTEM DIAGRAM
SCALE = NOT TO SCALE
D D
C
H
VA
C A
U
TO
M A
TI
C
C O
N
TR
O L
S Y
S
TE
M D
IA
G
R A
M
MI602F
OUTSIDE AIR
EXHAUST AIR
AS SCHEDULED N/A REQ'D REQ'D
OTHER
RETURN AIR PARALLEL BLADE
OUTSIDE AIR
EXHAUST AIR PARALLEL BLADE
RETURN AIR PARALLEL BLADE
OUTSIDE AIR OPPOSED BLADE
EXHAUST AIR PARALLEL BLADE
CONTROL DAMPER SCHEDULE
THERMOSTAT SCHEDULE
D-1
D-2
D-3
D-1
D-2
D-3
AH-1
AH-2
TERMINAL
UNIT
IDENTIFIER
SYSTEM IDENTIFIER FUNCTION TYPE DAMPER'S
SETTING REMARKS
MODULATING
WITH SPRING RETURN
MODULATING
WITH SPRING RETURN
MODULATING
WITH SPRING RETURN
MODULATING
WITH SPRING RETURN
MODULATING
WITH SPRING RETURN
MODULATING
WITH SPRING RETURN
OPPOSED BLADE
SPACES
SERVED
STAT
LOCATION
ZN-T-SP
ADJUST
UNOCC
OVERRIDE
PUSH BUTTON
UNOCC
OVERRIDE
TIME
23.9°C
SUPPLY FAN
RETURN FAN
D-1D-2
D-3
OA-F
EA-T
OA-T
AFMA
P H L
OA-FLT-P-HL
T P H L
RA-FLT-P-HL
H LP
MA-FLT-P-HL
DDC
DDC
MA-T
RA-T
SA-T
RETURN AIR
SUPPLY AIR
HEAT PUMP UNIT
BUILT-IN CONTROL
AHU CONTROL
PANEL
SYSTEM
SERVICE
HU
CONSOLE TYPE FLOOR
MOUNTED VRF HEAT PUMP UNIT
DIRECT DIGITAL
ZONE THERMOSTAT
SENSOR (LONWORKS)
WITH TIMED OVERRIDE
SWITCH
DX
LOW LEAKAGE MOTORIZED
DAMPER WITH MAX. LEAKAGE
RATE AT 3 CFM/SF AT 1" WG.
(TYP)
SA-SMK
FIRE ALARM
MODULE
TO BLDG. FIRE
ALARM PANEL
UV-S
AS SHOWN ON PLAN
ZN-T
NOTES :
CONTRACTOR SHALL AFFIX PERMANENT TAGS/LABELS TO ALL
DEVICES AS SPECIFIED.
CONTRACTOR SHALL LABEL ALL DDC I/O SIGNAL LINES:
4-20 mA, VDC, OR SNVT.
1.
2.
3.
4.
5.
CONTRACTOR SHALL UNIQUELY NUMBER ALL ANSI 709.1
DEVICES. THIS NUMBERING SHALL BE CONSISTENT BETWEEN
ALL DRAWINGS
ALL MOTORIZED DAMPER SHALL BE LOW LEAKAGE TYPE,
15 LPS/SQ M @ 250 Pa (3 CFM/SQ FT @ 1" W.G.) PER
UFC 4-010-01.
CONTRACTOR SHALL SHOW A UNIQUE IDENTIFIER FOR EACH
DEVICE. WERE MULTIPLE IDENTICAL DEVICES ARE SHOWN
(FOR EXAMPLE; DDC CONTROLLER, OA SENSOR, OR EP TRANSDUCER)
EACH SHALL BE SEQUENTIALLY NUMBERED.
WHERE SEPARATE DDC CONTROLLER BUBBLES ARE USED TO
REPRESENT/SHOW A COMMON (OR SINGLE) CONTROLLER
EACH BUBBLE SHALL USE THE SAME IDENTIFIER AND NUMBER.
DEVICE AND SIGNAL IDENTIFIERS SHALL BE CONSISTENT
BETWEEN DRAWINGS.
AS SHOWN ON PLAN
RST-BUT
TO: DDC-##
LDP
LOCAL DISPLAY PANEL SAFETY RESET
TO: DDC-##
EMER-SW
EMERGENCY SWITCH
LOCATION : LOBBY 138
TO: DDC-##
BLDG-T
NIGHT STAT
LOCATION:
DDC
DDC
MERV-13
FILTER
MERV-8 FILTER
SCHEMATIC DIAGRAM (AH-1 AND AH-2)
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
1 VRF HEAT PUMP AHU AUTOMATIC CONTROL DIAGRAM
SCALE = NOT TO SCALE
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, V
R F
H E
A T
P U
M P
A H
U A
U
TO
M A
TI
C
C O
N
TR
O L
D
IA
G R
A M
MI603F
SEQUENCE OF OPERATION
1.
2.
A.
A.
3.
B.
TEMPERATURE CONTROL
C.
D.
OCCUPANCY MODES:
B.
5.
A.
PROOFS AND SAFETIES:
PROOFS:
AH UNIT FAN STATUS (AH-SS).
A.
B. SAFETIES:
2. HVAC EMERGENCY SHUTOFF SWITCH.
FILTER'S MONITORING:
1. SUPPLY AIR SMOKE (SA-SMK) DETECTOR FOR AH-1 & AH-2.
PACKAGE HEAT PUMP AIR HANDLING UNIT COUPLED WITH HEAT RECOVERY (AH-1 & AH-2)
"HAND-OFF-AUTO" (H-O-A) SWITCH:
6. FIRE ALARM
WHEN SMOKE IS DETECTED IN THE SUPPLY DUCT, THE SMOKE DETECTOR WILL SEND
SIGNAL TO THE FIRE ALARM MODULE (FAP) AND THE FIRE ALARM MODULE THROUGH
THE DDC, WILL STOP THE SUPPLY FAN OPERATION AND INITIATE A SMOKE ALARM.
RESTARTING THE SUPPLY FAN WILL REQUIRE MANUAL RESET AT THE DDC HARDWARE.
THE DDC SHALL SEND AN ALARM WHEN THE PRESSURE DROP ACROSS THE FILTER REACHES
THE FILTER CHANGE OUT SETPOINT (TO BE DETERMINED BY THE FILTER MANUFACTURER).
7. EMERGENCY SHUT-OFF SWITCH
UPON ACTIVATION, THE AIR HANDLING UNIT FANS SHALL STOP.
8. UV SYSTEM
DDC SHALL MONITOR THE ON/OFF SWITCH MOUNTED ON THE UNIT TO SHOW WHETHER
LIGHT IS "ON" OR "OFF".
4.
CONTRACTOR SHALL INSTALL DDC HARDWARE TO PERFORM THE SEQUENCE OF OPERATION AS INDICATED ON THE DRAWINGS AND TO PROVIDE SNVT INPUTS, OUTPUTS AND ALARMS AS SPECIFIED AND SHOWN ON THE POINTS SCHEDULE. UNLESS OTHERWISE SPECIFIED, ALL MODULATING CONTROL SHALL BE PROPORTIONAL-INTEGRAL (PI) CONTROL. IF THERE ARE CONFLICTS BETWEEN THE SEQUENCE OF OPERATION AND THE LOGIC CONTROL DIAGRAMS, THE SEQUENCE OF OPERATION SHALL GOVERN THE
REQUIREMENTS AND THE CONTROL CONTRACTOR SHALL CORRECT THE LOGIC CONTROL DIAGRAMS
ACCORDINGLY.
SUPPLY FAN MOTOR STARTER SHALL ACCEPT SMOKE DETECTOR SIGNAL THAT TAKES
PRECEDENCE OVER ALL OTHER INPUTS AND SHALL CAUSE THE FAN MOTOR TO STOP
SUPPLY FAN. THE MOTOR STARTER SHALL ACCEPT AN OCCUPANT ACCESSIBLE
EMERGENCY SHUTOFF SWITCH AS SHOWN.
THE SUPPLY AND RETURN FANS MOTOR STARTER UNIT SHALL HAVE AN INTEGRAL
"H-O-A" SWITCH:
HAND: WITH THE "H-O-A" SWITCH IN "HAND" POSITION, THE SUPPLY AND RETURN FANS
SHALL START AND RUN CONTINUOUSLY, SUBJECT TO SAFETIES.
OFF: WITH THE "H-O-A" SWITCH IN "OFF" POSITION, THE SUPPLY AND RETURN FANS
SHALL STOP.
AUTO: WITH THE "H-O-A" SWITCH IN "AUTO" POSITION, THE SUPPLY AND RETURN FANS
SHALL RUN SUBJECT TO THE SUPPLY FAN START/STOP SIGNAL (SF-SS/RF-SS) AND SAFETIES.
ALL FANS AND ALL DDC HARDWARE CONTROL LOOPS SHALL BE SUBJECT TO PROOFS AND SAFETIES.
SAFETIES SHALL BE DIRECT-HARDWIRE INTERLOCKED AS SHOWN. DDC HARDWARE SHALL MONITOR ALL PROOFS AND SAFETIES AND FAILURE OF ANY PROOF OR ACTIVATION OF ANY SAFETY SHALL RESULT IN ALL CONTROL LOOPS BEING DISABLED AND THE AH FAN BEING COMMANDED OFF UNTIL
RESET.
DDC HARDWARE RESET OF ALL PROOFS AND SAFETIES SHALL BE VIA A LOCAL BINARY
PUSH-BUTTON (RST-BUT) INPUT TO THE DDC HARDWARE, VIA A REMOTE COMMAND TO
THE DDC HARDWARE VIA SNVT OR BOTH (WHERE THE CONTRACTOR PROVIDES BOTH RESET
FUNCTIONS AND THE OPERATOR CAN USE EITHER ONE TO PERFORM THE RESET), AS SHOWN
ON THE POINTS SCHEDULE DRAWING.OCCUPIED: THE UNIT DDC HARDWARE SHALL BE IN THE OCCUPIED MODE BY THE INPUT FROM
THE SYSTEM SCHEDULER IS OCCUPIED. DDC SHALL RUN THE AIR HANDLING UNIT FANS AND
THE VRF HEAT PUMP UNIT, AND DDC HARDWARE SHALL POSITION THE OUTSIDE/RETURN AIR
DAMPER TO PRESET POSITION AS SCHEDULED. DDC HARDWARE SHALL ENABLE THE TEMPERATURE
CONTROL SYSTEM. THE ZONE TEMPERATURE THERMOSTAT SENSOR T SHALL BE AT THE DDC
CONFIGURED SETPOINT, AS SHOWN.
UNOCCUPIED: THE UNIT DDC HARDWARE SHALL BE IN THE UNOCCUPIED MODE BY THE INPUT
FROM THE SYSTEM SCHEDULER IS UNOCCUPIED. THE VRF HEAT PUMP UNIT AND THE AIR
HANDLING UNIT FANS SHALL NOT OPERATE UNLESS CALLED FOR BY NIGHT SETBACK SETTING.
THE OUTSIDE/RETURN AIR DAMPER SHALL BE AT THEIR NORMAL POSITION, EITHER N.C.
OR N.O. AS INDICATED. IN THE UNOCCUPIED MODE THE ZONE TEMPERATURE THERMOSTAT
SENSOR T SHALL BE AT THE DDC CONFIGURED SETPOINT, AS SHOWN.
THE DDC HARDWARE SHALL OPERATE VRF HEAT PUMP UNIT: COOLING AND HEATING, IN
ACCORDANCE WITH THE ZONE TEMPERATURE THERMOSTAT SENSOR T SETPOINT (ZN-T-SP).
THE VRF HEAT PUMP UNIT WILL DELIVER VARIABLE REFRIGERANT FLOW
DEPENDING OF THE AIR HANDLING UNIT.
* OCCUPIED MODE ZONE TEMPERATURE SETPOINT (ZN-T-SP)
- WINTER SEASON : 20°C (68°F)
- SUMMER SEASON : 23.9°C (75°F)
* UNOCCUPIED MODE ZONE TEMPERATURE SETPOINT (ZN-T-SP)
- WINTER SEASON : 12.7°C (55°F)
- SUMMER SEASON : 29.4°C (85°F)
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, 1 VRF HEAT PUMP AHU SEQUENCE OF OPERATION
SCALE = NOT TO SCALE
V R
F H
E A
T P
U M
P A
H U
S E
Q U
E N
C E
O F
O P
E R
A
TI
O N
MI604F
<___> [~]<___> [~][~]~ ~ ~ ~X[~] <___> <___>[~]MIXED AIR TEMPERATUREMA-T
OTHER POINTS
AI
RETURN AIR TEMPERATURERA-T [~] [~]<___> [~]<___>~~~~[~] <___><___>[~] XAI
<___> [~]<___> [~][~]~ ~ ~ ~X[~] <___> <___>AI<___>
SUPPLY AIR TEMPERATURE [~]SA-T
<___><___>~ ~ ~ ~ ~ [ALM] [___]<___> [~]
ALARM GENERATOR DDC HARDWARE INFORMATION:
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
ALARMS
DISP
REQ'D
LDP AND M&C DISPLAY
MIXED AIR FILTER PRESSURE HIGH LIMIT SWITCH
ZONE
MA-FLT-P-HL <___> ALM/NORMAL BI [~] [~]
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
SUPPLY FAN START/STOP
OCCUPANCY INPUT (FROM SYSTEM SCHEDULER)
SYSTEM RESET BUTTON
EXHAUST FAN STATUS
SUPPLY AIR SMOKE
SUPPLY FAN STATUS
EF-SPROOFS
START/STOP
SAFETIES
SF-SS
SYS-OCC
RST-BUT
SA-SMK
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##>
FUNCTION
SF-S
NAME (WITH UNITS)
SETTING
DESCRIPTION
BI
ALM/NORMAL
START/STOP
BO
NVI
BI
[X] [X] X
X
(WITH UNITS)
RANGE nci/CP
NAME
BI
I/O
TYPE
LDP
REQ'D
VIEW
[X] X
SEE NOTES
X <___>
TYPE
SNVT
NAME
SNVT
M&C
REQ'D
TREND
LDP
OVRD
REQ'D
M&C
REQ'D
OVRD
NAME
SNVT
OVERRIDES
ALM
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##><INTEGRATED>
PROOF FAILED
(SEE NOTES)
ALARM CONDITION
TYPE
SNVT
PRIORITY
ALARM
NAME
SNVT
NAME
ROUTING
M&C
TYPE
SNVT
BLDG
ROUTING
REQ'D
AI<___>OA-T OUTSIDE AIR TEMPERATURE ~ [~] <___><___>[~] X ~~~~ [~] [~]<___> [~]<___>
[X] X [~] <___> <___> [~] X <___> <___> ~ ~ ~ ~ ~
[X] X <___><___>[~]
BOEXHAUST FAN START/STOPEF-SS ~ START/STOP
PROOF FAILED
<___><___>~ [ALM] [___]<___> [~]OUTSIDE AIR FILTER PRESSURE HIGH LIMIT SWITCHOA-FLT-P-HL <___> ALM/NORMAL BI [~] [~] <___>
POINT SCHEDULE FOR (AIR HANDLING UNIT-1,2)
TEMPERATURE
START/STOP
START/STOP
OA DAMPER COMMAND (2-POSITION)OA-D-2P ~ OPEN/CLOSE BO [X] X [~] <___> <___> ~ ~ ~ ~ ~[~] X <___> <___>
EA DAMPER COMMAND (2-POSITION)EA-D-2P OPEN/CLOSE BO [X] X [~] <___> <___> ~ ~ ~ ~ ~[~] X <___> <___>
OUTSIDE
AIR
OA-F OUTSIDE AIR FLOW
OA-F-SP OUTSIDE AIR FLOW SETPOINT
AI~ <___><___>X ~~~~ [~]<___> [~]<___>
~~ OA-F LESS THAN 80% OF OA-F-SP
<___><___>[X] ~ ~ ~~ ~COMPRESSOR(PKG UNIT) COOLING/HEATING MODE
HEAT PUMP COMP-CLG/HTG ~ [X] X
CONTROL
BI
CONTROL
ZN-T ZONE TEMPERATURE
ZN-T-SP ZONE TEMPERATURE SETPOINT
AI~ TEMP_P<___>X ~~~~ [~]<___> [~]<___>
~~ ZN-T MORE THAN 5°C OR BELOW ZN-T-SP
<___><___>[X] ~ ~ ~~ ~COMPRESSOR(PKG UNIT) START/STOPCOMP-SS ~ [X] XBO
<___><___>[X] [~] X <___> <___> ~ ~ ~~ ~HEATING COMMAND HTG-2P ~ <0~100%> [X] XAO
<___><___>~ [ALM] [___]<___> [~]RETURN AIR FILTER PRESSURE HIGH LIMIT SWITCHRA-FLT-P-HL <___> ALM/NORMAL BI [~] [~] <___>~ ~ ~ ~
[~] X <___> <___> ~ ~ ~ ~ ~RA DAMPER COMMAND (2-POSITION)RA-D-2P OPEN/CLOSE BO [X] X [~] <___> <___>
UV SWITCH STATUSUV-S BI ~ ~ ~ ~[X] X <___><___>[~]ON/OFF ~ ~ ~ ~ ~
1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS DRAWING
2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW
NOTES
HVAC EMERGENCY SWITCHEMER-SW BI <___> [___]<___> [~]~ ~ ~ ~ ~ ~ ~ ~ ~~ ~ ~ ~ ~~ ~ ~
~ ~ ~ ~X[X] <___> <___>AI<___>~BUILDING TEMPERATURE (NIGHT STAT) [~]BLDG-T BLDG-T LESS THAN BLDG-T-LL
~ ~ ~ ~X[X] <___> <___>~<___>~BUILDING TEMP LOW LIMIT SETPOINT [~]BLDG-T-LL-SP ~
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, V R
F H
E A
T P
U M
P A
H U
P O
IN
T
S C
H E
D U
LE
MI605F
1 VRF HEAT PUMP AHU POINT SCEHDULE
SCALE = NOT TO SCALE
1. GENERAL
A.
B.
A.
2. SCHEDULING
B.
C.
F.
C. SYSTEM SHALL OPERATE ALL THE TIME IN EITHER OCCUPIED, UNOCCUPIED OR
MORNING WARM-UP (CALCULATED OPTIMAL START PROGRAM) OPERATING MODES.
THE OCCUPANCY OUTPUT SHALL BE BOUND FROM THE SYSTEM SCHEDULER TO THE DDC
HARDWARE THAT EXECUTES THE OCCUPANCY MODE AS PART OF THE ERU'S AIR HANDLING
SEQUENCE OF OPERATIONS.
3. HAND-OFF-AUTO SWITCHES
B. REFER TO CONTROL LIST AND DRAWING FOR ALL PROOFS (STATUS POINTS)
C. SAFETIES:
(1A)
D. DDC HARDWARE RESET OF ALL PROOFS AND SAFETIES SHALL BE VIA A LOCAL DIGITAL
PUSH-BUTTON INPUT TO THE DDC HARDWARE, VIA A REMOTE COMMAND TO THE DDC
HARDWARE AS SHOWN ON THE CONTROL POINTS SCHEDULE (IF SHOWN).
5. SYSTEM ENABLE AND LOOP ENABLE (OCCUPIED, UNOCCUPIED AND WARM-UP)
OCCUPIED MODE:
UNLESS THE OCCUPANCY SCHEDULE IS IN OVERRIDE MODE THE UNIT SHALL OPERATE
IN OCCUPIED, WARM-UP OR UNOCCUPIED MODE AS NOTED IN THE OCCUPANCY
SCHEDULE
IF MORE THAN 95 MINUTES HAVE PASSED SINCE THE LAST RECEIPT OF THE SCHEDULE
OCCUPANCY INPUT THE AIR HANDLING UNIT OCCUPANCY SHALL BE DETERMINED BY THE
DEFAULT SCHEDULE AND THE SPACE OCCUPANCY INPUTS.
A. GENERAL INFO
ERU
ERU-2
CONTRACTOR SHALL INSTALL ALL DDC HARDWARE AND COORDINATE WITH THE
MANUFACTURER CONTROL SYSTEMS TO PERFORM THIS SEQUENCE OF OPERATION AND
PROVIDE ALL POINTS AS LISTED ON THE SCHEDULE. UNLESS OTHERWISE NOTED,
ALL MODULATING CONTROL SHALL BE PROPORTIONAL-INTEGRAL (PI) CONTROL.
B. OCCUPIED MODE:
UNOCCUPIED MODE:C.
IN UNOCCUPIED MODE ERU-1 SHALL DISABLE. WHEN THE CO2 LEVELS IN THE
OCCUPIED SPACES SUPPLIED BY ERU-1 RISE ABOVE 1000 PPM THE ERU SHALL BECOME
ENABELED AND SUPPLY AIR UNTIL THE CO2 LEVEL HAS DROPPED BELOW 500 PPM.
MINIMUM SUPPLY AIR TEMPERATURE SETPOINT IS TO BE MAINTAINED AT ALL TIMES.
D. WARM UP MODE:
ERU-2 SHALL HAVE A SEPARATE OPERATIONAL MODE FOR THE SHOP AREA AS
OUTLINED BELOW.
E.
A.
A. THE DDC HARDWARE SHALL MONITOR THE PRESSURE DIFFERENTIAL ON THE FILTER
MONITOR AND SEND AN ALARM TO THE WORKSTATION WHEN THE PRESSURE SENSORS
REACHES FILTER CHANGE OUT SETPOINT(TO BE DETERMINED BY THE FILTER MANUFACTURER).
A.
11. POWER FAILURE
OUTSIDE AIR AND EXHAUST AIR DAMPERS CLOSE.
9. SMOKE CONTROL
G. UNOCCUPIED MODE:
H. WARM UP MODE:
A.
6. EXHAUST FAN VFD CONTROL
WHILE THE BUILDING ZONE TEMPERATURE IS BELOW THE REQUIRED SET POINT ALL
CONTROL LOOPS SHALL BE DISABLED AND THE SUPPLY, EXHAUST FAN AND THE HEAT
WHEEL SHALL NOT RUN. WHEN THE BUILDING ZONE TEMPERATURE RISES ABOVE THE
BUILDING UNOCCUPIED TEMPERATURE SET POINT (DEAD BAND OF 5 DEG F) ALL
ASSOCIATED CONTROL LOOPS SHALL BE ENABLED. THE SUPPLY FAN, EXHAUST AND
HEAT WHEEL SHALL START TO OPERATE AS REQUIRED. MOTORIZED DAMPERS SHALL
OPEN AND CLOSE AS REQUIRED. IF CO2 LEVELS ARE ABOVE 1000 PPM IN WARM UP
MODE THE UNIT SHALL OPERATE IN OCCUPIED MODE FOR THE DURATION OF THE
MORING WARM UP MODE.
ERU MODE SHALL MIMIC THE VRF SYSTEM (HP-* AND FC-*) SYSTEM OPERATION MODE
(IE OCCUPIED, UNOCCUPIED, ECT.) AND SHALL OPERATE IN EACH AS OUTLINED BELOW.
SYSTEM IS DESIGNED AS A HEAT RECOVERY VENTILATION UNIT WITH A FIXED
WHEEL HEAT EXCHANGER AND DUCT MOUNTED ELECTRIC HEATING COIL. UNIT IS TO PROVIDE
SPACE HEATING AND VENTILATION AIR ONLY.
THE SUPPLY FAN AND EXHAUST FAN SHALL BE ENABLED AND COMMANDED TO RUN. ALL
CONTROL LOOPS SHALL BE ENABLED. THE SUPPLY AIR TEMPERATURE CONTROL LOOPS
FOR THE ERU SHALL ALSO BE ENABLED. DURING THE OCCUPIED MODE (OPERATOR
ADJUSTABLE TIME SCHEDULE), UNIT FANS AND RUN CONTINUOUSLY TO MAINTAIN THE
DESIRED SUPPLY AIR TEMPERATURE. ALL VALUES SHALL BE ADJUSTABLE BY THE
USER. MOTORIZED DAMPERS SHALL OPEN AND CLOSE AS REQUIRED.
ERU-1 SHALL NOT OPERATE IN MORNING WARM UP UNLESS CO2 LEVELS ARE ABOVE
1000 PPM. IF CO2 LEVELS ARE ABOVE 1000 PPM IN WARM UP MODE THE UNIT SHALL
OPERATE IN OCCUPIED MODE FOR THE DURATION OF THE MORING WARM UP MODE.
THE SUPPLY FAN AND EXHAUST FAN SHALL BE ENABLED AND COMMANDED TO RUN.
ALL CONTROL LOOPS SHALL BE ENABLED. THE ZONE TEMPERATURE CONTROL LOOPS
FOR THE ERU SHALL ALSO BE ENABLED. DURING THE OCCUPIED MODE (OPERATOR
ADJUSTABLE TIME SCHEDULE), UNIT FANS SHALL RUN CONTINUOUSLY TO MAINTAIN
THE DESIRED ROOM TEMPERATURE. ALL VALUES SHALL BE ADJUSTABLE BY THE USER.
MOTORIZED DAMPERS SHALL OPEN AND CLOSE AS REQUIRED.
THE SUPPLY AND EXHAUST FAN WITH ASSOCIATED CONTROL LOOPS SHALL BE ENABLED
AND COMMANDED TO RUN. THIS INCLUDES ALL ZONE TEMPERATURE CONTROL LOOPS.
MOTORIZED DAMPERS SHALL OPEN AND CLOSE AS REQUIRED.
SUPPLY AIR SMOKE DETECTOR.
10. FILTER MONITORING
THE SMOKE DETECTOR LOCATED IN THE SUPPLY DUCT SHALL UPON SIGNALING A SMOKE
ALARM SHALL SEND A SIGNAL TO THE FIRE ALARM CONTROL PANEL (FAP). THE FAP
WILL SIGNAL THE UNIT TO DISABLE, SHUTTING OFF THE SUPPLY AND EXHAUST FANS
AND CLOSING THE OUTSIDE AND EXHAUST AIR DAMPERS. IN ORDER TO RESTART THE
SYSTEM THE FIRE ALARM SIGNAL SHALL BE TERMINATED AND A MANUAL RESET WILL
OCCUR AT THE DDC CONTROL WORK STATION.
EXHAUST
AIR
SCHEMATIC DIAGRAM (ERU-1,2 AND HC-1,2)
SEQUENCE OF OPERATION (ERU-1,2 AND HC-1,2)
NOTES :
CONTRACTOR SHALL AFFIX PERMANENT TAGS/LABELS TO ALL
DEVICES AS SPECIFIED.
CONTRACTOR SHALL LABEL ALL DDC I/O SIGNAL LINES:
4-20 mA, VDC, OR SNVT.
1.
2.
3.
4.
5.
CONTRACTOR SHALL UNIQUELY NUMBER ALL ANSI 709.1
DEVICES. THIS NUMBERING SHALL BE CONSISTENT BETWEEN
ALL DRAWINGS
ALL MOTORIZED DAMPER SHALL BE LOW LEAKAGE TYPE,
15 LPS/SQ M @ 250 Pa (3 CFM/SQ FT @ 1" W.G.) PER
UFC 4-010-01.
CONTRACTOR SHALL SHOW A UNIQUE IDENTIFIER FOR EACH
DEVICE. WERE MULTIPLE IDENTICAL DEVICES ARE SHOWN
(FOR EXAMPLE; DDC CONTROLLER, OA SENSOR, OR EP TRANSDUCER)
EACH SHALL BE SEQUENTIALLY NUMBERED.
WHERE SEPARATE DDC CONTROLLER BUBBLES ARE USED TO
REPRESENT/SHOW A COMMON (OR SINGLE) CONTROLLER
EACH BUBBLE SHALL USE THE SAME IDENTIFIER AND NUMBER.
DEVICE AND SIGNAL IDENTIFIERS SHALL BE CONSISTENT
BETWEEN DRAWINGS.
RST-BUT
TO: DDC-##
LDP
LOCAL DISPLAY PANEL SAFETY RESET
SPACE-CO2
TO: DDC-##
CO2SPACE SENSOR
LOCATION :
SPACE-T
TO: DDC-##
SPACE TEMP
SENSOR
LOCATION : 156,161
OUTSIDE
AIR
MOTORIZED
DAMPERP
LH
OA-TOA TEMP
SENSOR
SA-T-2
SUPPLY
AIR
SA TEMP
SENSOR 2
SA-T-1
HOA
SUPPLY FAN
EA-T
EXHAUST FAN
MOTORIZED
DAMPEREA TEMP
SENSOR
VFD
P H L
RETURN
AIR
RA-TRA TEMP
SENSOR
FILTER
DIFFERENTIAL
PRESSURE SENSOR
DDC
DDC CONTROL
PANEL
WHEEL TYPE
HEAT EXCHANGER
FILTER
DIFFERENTIAL
PRESSURE SENSOR
OA-FLT-P-HL
RA-FLT-P-HL
FIRE ALARM
MODULETO BLDG. FIRE
ALARM PANEL
SMOKE
DETECTOR SA-SMK
AFMA
SA-F
SA TEMP
SENSOR 1 MERV-13 FILTER
MERV-8 FILTER
TO: DDC-##
EMER-SW
HVAC EMERGENCY
SWITCH
BY-PASS
MOTORIZED
DAMPER
4. PROOF AND SAFETIES
A. THE SUPPLY FAN, EXHAUST FAN AND ALL DDC HARDWARE CONTROL LOOPS SHALL BE
SUBJECT TO PROOFS AND SAFETIES. SAFETIES SHALL BE DIRECT-HARDWIRED
INTERLOCKED TO THE HOA AS SHOWN. DDC HARDWARE SHALL MONITOR ALL PROOFS AND
SAFETIES AND FAILURE OF ANY PROOF OR ACTIVATION OF ANY SAFETY SHALL RESULT
IN ALL CONTROL LOOPS BEING DISABLED AND THE SUPPLY OR EXHAUST FANS TO BE
COMMAND OFF AND AN ALARM WILL REGISTERED AND THE DDC CONTROL PANEL.
HAND :
OFF :
AUTO :
WITH THE H-O-A SWITCH IN OFF POSITION, THE FAN SHALL STOP.
WITH THE H-O-A SWITCH IN AUTO POSITION, THE FAN SHALL RUN SUBJECT
TO THE SUPPLY FAN RUNNING. FAN SPEED SHALL BE UNDER CONTROL OF
THE DDC HARDWARE.
(A)
(B)
(C)
THE SUPPLY FAN AND EXHAUST FAN SHALL ACCEPT A FIRE ALARM PANEL SIGNAL THAT
TAKES PRECEDENCE OVER ALL OTHER VFD INPUTS AND SWITCHES AND SHALL CAUSE THE
VFD TO BE STOPPED. THE EXHAUST FAN FAN VARIABLE FREQUENCY DRIVE
(VFD) UNIT SHALL HAVE AN INTEGRAL H-O-A SWITCH:
WITH THE H-O-A SWITCH IN HAND POSITION, THE FAN SHALL RUN SUBJECT
TO SAFETIES. FAN SPEED SHALL BE UNDER MANUAL-OPERATOR CONTROL.
BY-PASS MODE : WHEN BY-PASS MODE SWITCH IS ON FOR MAINTENANCE PURPOSES,
RESPECTIVE FAN SHALL RUN ON BY-PASS MODE.
IF THE READING IS BELOW THE CO2 SETPOINT, THE ERU SHALL MAINTAIN THE OUTSIDE
/EXHAUST AIRFLOW. IF THE READING IS ABOVE SETPOINT, THE EXHAUST FAN
SHALL VFD CONTROL TO REDUCE THE CO2 CONCENTRATION IN THE SPACE.
7. HEAT EXCHANGER BY-PASS
A.
B.
HEATING MODE: (FROST PROTECTION)
COOLING MODE: (INTERMEDIATE SEASON)
A.
B.
WHEN THE EXHAUST AIR IS 2°C OR LOWER. THE DDC SHALL ENERGIZE
OA BY-PASS MOTORIZED DAMPER. (OPEN TO BY-PASS AND CLOSE TO HEAT EXCHANGER
WHEN THE EXHAUST AIR IS 3°C. THE DDC SHALL DE-ENERGIZE MOTORIZED
DAMPER AND RETURN TO NORMAL OPERATION.
WHEN THE OUTDOOR AIR TEMPERATURE IS LOWER THAN THE RETURN AIR
TEMPERATURE THE DDC SHALL ENERGIZE THE MOTORIZED DAMPER, OPEN
TO BY-PASS AND CLOSED TO HEAT EXCHANGER.
WHEN THE OUTDOOR AIR TEMPERATURE IS HIGHER THAN THE RETURN AIR
TEMPERATURE, DDC SHALL DE-ENERGIZE THE MOTORIZED DAMPER AND
RETURN TO NORMAL OPERATION.
LOCATION : LOBBY 138
TO PREVENT FREEZING IN THE HEAT EXCHANGER)
A.
12. EMERGENCY HVAC SHUT-OFF
WHEN ACTIVATED, FANS SHALL BE SHUT DOWN
AND OA/EA DAMPERS CLOSED.
A.
8. ELECTRIC HEATING COIL WITH SCR CONTROLLER
WHEN THE SUPPLY AIR TEMPERATURE DROPS BELOW SETPOINT THE ELECTRIC
HEATING COIL SHALL MODULATE PROPORTIONALLY TO MAINTAIN THE SUPPLY
AIR TEMPERATURE SET POINT.
B. SAIL SWITCH(SS):
THE SAIL SWITCH WILL DEACTIVATE THE ELECTRIC HEATING COIL WHEN
NO AIRFLOW IS DETECTED.
HTG-COIL
SCR CONTROLLER
ELECTRIC HEATING
COIL
HC-*
SS
SAIL
SWITCH
T
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, 1 ENERGY RECOVERY UNIT AUTOMATIC CONTROL DIRGRAM
SCALE = NOT TO SCALE
E N
E R
G Y
R E
C O
V E
R Y
U N
IT
A
U
TO
M A
TI
C
C O
N
TR
O L
D
IA
G R
A M
MI606F
<___> [~]<___> [~][~]~ ~ ~ ~X[~] <___> <___>[~]RETURN AIR TEMPERATURERA-T
OTHER POINTS
<___>~ AI
SUPPLY AIR TEMPERATURESA-T-2 [~] [~]<___> [~]<___>~~~~[~] <___><___>[~] XAI~ <___>
<___> [~]<___> [~][~]~ ~ ~ ~X[~] <___> <___>AI<___>~SUPPLY AIR TEMPERATURE [~]SA-T-1
<___><___>~ ~ ~ ~ ~ [ALM] [___]<___> [~]
ALARM GENERATOR DDC HARDWARE INFORMATION:
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
ALARMS
DISP
REQ'D
LDP AND M&C DISPLAY
OUTSIDE AIR FILTER PRESSURE HIGH LIMIT SWITCHOA-FLT-P-HL <___> ALM/NORMAL BI [~] [~]
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
SUPPLY FAN START/STOP
OCCUPANCY INPUT (FROM SYSTEM SCHEDULER)
SYSTEM RESET BUTTON
EXHAUST FAN STATUS
SUPPLY AIR SMOKE
SUPPLY FAN STATUS
EF-SPROOFS
START/STOP
SAFETIES
SF-SS
SYS-OCC
RST-BUT
SA-SMK
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##>
FUNCTION
SF-S
NAME (WITH UNITS)
SETTING
DESCRIPTION
BI
ALM/NORMAL
START/STOP
BO
NVI
BI
[X] [X] X
X
(WITH UNITS)
RANGE nci/CP
NAME
BI
I/O
TYPE
LDP
REQ'D
VIEW
[X] X
SEE NOTES
TYPE
SNVT
NAME
SNVT
M&C
REQ'D
TREND
LDP
OVRD
REQ'D
M&C
REQ'D
OVRD
NAME
SNVT
OVERRIDES
ALM
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##><INTEGRATED>
PROOF FAILED
(SEE NOTES)
ALARM CONDITION
TYPE
SNVT
PRIORITY
ALARM
NAME
SNVT
NAME
ROUTING
M&C
TYPE
SNVT
BLDG
ROUTING
REQ'D
AI<___>OA-T OUTSIDE AIR TEMPERATURE ~ [~] <___><___>[~] X ~~~~ [~] [~]<___> [~]<___>
[X] X [~] <___> <___> ~ ~ ~ ~ ~
[X] X <___><___>[~]
BOEXHAUST FAN START/STOPEF-SS ~ START/STOP
PROOF FAILED
EA DAMPER COMMAND (2-POSITION)
OA DAMPER COMMAND (2-POSITION)
EA-D-2P
OA-D-2P ~ OPEN/CLOSE
~ OPEN/CLOSE
BO
BO
[X] X [~] <___> <___> [X] X [~] <___> <___> ~ ~ ~ ~ ~
<___><___>~ [ALM] [___]<___> [~]RETURN AIR FILTER PRESSURE HIGH LIMIT SWITCHRA-FLT-P-HL <___> ALM/NORMAL BI [~] [~] <___>
AISPACE-CO2 CO2 SENSOR ~ <___><___>X ~~~~ [~]<___> [~]<___>
SPACE-CO2-SP CO2 LEVEL SET POINT 1000 PPM <___><___> ~~~~
1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS DRAWING
2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW
NOTES
POINT SCHEDULE FOR (ENERGY RECOVERY UNIT-1,2)
START/STOP
START/STOP
CO2 MORE THAN CO2-SP
AI<___>SPACE-T SPACE AIR TEMPERATURE ~ [~] <___><___>[~] X ~~~~ [~] [~]<___> [~]<___>
OA BYPASS DAMPER COMMAND (2-POSITION)OA-BD-2P ~ OPEN/CLOSE BO [X] X [~] <___> <___> ~ ~ ~ ~ ~~ ~ ~ ~
<___><___>[X]
<0~100%>
[X]
XAO ~ ~ ~ ~FAN CAPACITY
CONTROL
EXHAUST FAN COMMAND
EXHAUST FAN PID LOOP SETTINGS
EF-C
<___><___>[X]
~HEATING COIL <___>
<0~100%>
[X] X
CONTROL
AO ~ ~ ~ ~ELECTRIC HEATING COIL COMMAND
ELECTRIC HEATING COIL PID LOOP SETTINGS
HTG-COIL
SAIL SWITCH STATUSSS-S BI <___> [___]<___> [~]~ ~ ~ ~ ~ ~ ~ ~ ~~ ~ ~ ~ ~~
HVAC EMERGENCY SWITCHEMER-SW BI <___> [___]<___> [~]~ ~ ~ ~ ~ ~ ~ ~ ~~ ~ ~ ~ ~~ ~ ~
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, E N
E R
G Y
R E
C O
V E
R Y
U N
IT
P
O
IN
T S
C H
E D
U
LE
MI607F
1 ENERGY RECOVERY UNIT POINT SCHEDULE
NOTES:
1.
2.
KEY
NAME QTY MODEL SPECIFICATION
CONTROL ARCHITECTURAL LAYOUT & NUMBER OF I-LON
MAY BE MODIFIED PER CONTROL MANUFACTURER'S
HEAT PUMP UNIT: PROVIDE A LONWORK
CENTRAL
CONTROLLER
CONTROLLER & CENTRAL
MONITORING SYSTEM
DDC ROUTER
1.WITH POWER SUPPLY (OPTIONAL)
CONTROL SYSTEM GATEWAY(OPTIONAL)
DDC
ROUTER
CONTROL SYSTEM
GATEWAY
SIMPLE CONTROLLER
LOCAL T'STAT
(TYP)
1. GENERAL
A.
B. THE SYSTEM IS DESIGNED AS A HEATING AND COOLING VRF SYSTEM
(VARIABLE REFRIGERANT FLOW). THE SYSTEM SHALL BE SUPPLIED WITH MANUFACTURER
CONTROLS AND SAFETIES AND THE DDC SYSTEM SHALL ONLY PROVIDE TEMPERATURE
SET POINT CONTROLS AND OCCUPANCY SCHEDULES AS REQUIRED FOR EACH SPACE.
A.
2. SCHEDULING
THE OCCUPANCY OUTPUT SHALL BE BOUND FROM THE SYSTEM SCHEDULER TO THE DDC
HARDWARE THAT EXECUTES THE OCCUPANCY MODE AS PART OF THE VRF'S SEQUENCE
OF OPERATIONS.
B. UNLESS THE OCCUPANCY SCHEDULE IS IN OVERRIDE MODE THE UNIT SHALL OPERATE
IN OCCUPIED, WARM-UP OR UNOCCUPIED MODE AS NOTED ON THE IN THE OCCUPANCY
SCHEDULE
C.
CONTRACTOR SHALL INSTALL ALL DDC HARDWARE AND COORDINATE WITH THE
MANUFACTURER CONTROL SYSTEMS TO PERFORM THIS SEQUENCE OF OPERATION AND
PROVIDE ALL POINTS AS LISTED ON THE SCHEDULE. UNLESS OTHERWISE NOTED,
ALL MODULATING CONTROL SHALL BE PROPORTIONAL-INTEGRAL (PI) CONTROL.
IF MORE THAN 95 MINUTES HAVE PASSED SINCE THE LAST RECEIPT OF THE SCHEDULE
OCCUPANCY INPUT THE HEAT PUMP UNIT OCCUPANCY SHALL BE DETERMINED
BY THE DEFAULT SCHEDULE AND THE SPACE OCCUPANCY INPUTS.
A.
3. PROOF AND SAFETIES
THE MANUFACTURER SUPPLIED CONTROL SYSTEM SHALL BE SUBJECT TO PROOFS AND
SAFETIES. SAFETIES SHALL BE DIRECT-HARDWIRED INTERLOCKED TO THE
MANUFACTURER CONTROLS. DDC HARDWARE SHALL MONITOR ALL PROOFS
AND SAFETIES AND FAILURE OF ANY PROOF OR ACTIVATION OF ANY SAFETY SHALL
RESULT IN ALL CONTROL LOOPS BEING DISABLED AND THE SYSTEM TO BE COMMAND
OFF AND AN ALARM WILL REGISTERED AND THE DDC CONTROL PANEL.
A. SYSTEM SHALL OPERATE TO MAINTAIN THE TEMPERATURE SET POINTS IN EACH SPACE.
EACH OCCUPANT SHALL HAVE CONTROL OF THE TEMPERATURE SET POINT WITH OVERRIDE
CAPABILITY AT THE DDC SYSTEM.
A. THE DDC HARDWARE SHALL MONITOR THE PRESSURE DIFFERENTIAL ON THE FILTER MONITOR
AND SEND AN ALARM TO THE WORKSTATION WHEN THE PRESSURE SENSORS REACHES FILTER
CHANGE OUT SET POINT (TO BE DETERMINED BY THE FILTER MANUFACTURER),
A.
6. POWER FAILURE
SYSTEM SHALL SHUT DOWN AS RECOMMENDED BY THE MANUFACTURER.
4. TEMPERATURE CONTROL
SPLIT TYPE
HEAT PUMP UNIT
(INDOOR UNIT)
THE VRF HEAT PUMP UNIT WILL DELIVER VARIABLE REFRIGERANT FLOW DEPENDING ON
THE DEMAND OF THE INDOOR UNIT TO MAINTAIN THE SPACE SETPOINT TEMPERATURE.
5. FILTER MONITORING (INDOOR UNIT)
SEQUENCE OF OPERATION (MU-1~4 & HU-1-1 THRU HU-2-14)
MU-1~4
ADVANCE
CENTRAL
CONTROLLER
LONWORK GATEWAY
ALIVE/WINK
SERVICE
SERVICE SWITCH
FUTURE UMCS
SYSTEM
DDC
ROUTER
CONTROL
SYSTEM
GATEWAY
BUILDING
DDC
SYSTEM
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, H V
A C
A U
TO
M
A
TI
C C
O N
TR
O
L D
IA
G
R A
M
MI608F
1 HVAC AUTOMATIC CONTROL DIAGRAM
EXHAUST FAN
NC
JC ROOM (107) EA FAN
ON-OFF
SWITCH
S
(2)
A. ON-OFF MANUAL SWITCH
(1) ON: SWITCH IN THE "ON" POSITION. THE EXHAUST FAN SHALL
RUN THE UNIT CONTINUOUSLY UNTIL MANUALLY STOP.
THE UNIT SHALL RUN SUBJECT TO THE UNIT MANUFACTURER'S SAFETIES.
B. SAFETIES
C. EXHAUST FAN OPERATIONS:
(1)
SEQUENCE OF OPERATION :
EXHAUST FAN SHALL RUN WHEN HAND-OFF SWITCH IS SWITCHED ON.
OFF: SWITCH IN THE "OFF" POSITION, THE EXHAUST FAN SHALL STOP.
NOTE :
EXHAUST AIR DAMPER SHALL HAVE A LEAKAGE
RATE OF 3 CFM/SF (MAX) AT 1" WG.
D. HVAC EMERGENCY SHUT-OFF SWITCH:
(1) WHEN THE HVAC EMERGENCY SHUT-OFF SWITCH IS ACTIVATED, EXHAUST
FAN WILL SHUT DOWN AND EXHAUST AIR DAMPER SHALL CLOSE.
(2) WHEN RESPECTIVE EXHAUST FAN OPERATE, EXHAUST AIR DAMPER
SHALL OPEN.
OTHER POINTS
ALARM GENERATOR DDC HARDWARE INFORMATION:
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
ALARMS
DISP
REQ'D
LDP AND M&C DISPLAYNODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
EXHAUST FAN LOW SPEED START/STOP
EXHAUST FAN LOW SPEED STATUSPROOFS &
START/STOP
SAFETIES
EF-LO-SS
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##>
FUNCTION
EF-LO-S
NAME (WITH UNITS)
SETTING
DESCRIPTION
START/STOP BO [X] X
(WITH UNITS)
RANGE nci/CP
NAME
BI
I/O
TYPE
LDP
REQ'D
VIEW
[X] X
<___>[~] [~] X <___>
TYPE
SNVT
NAME
SNVT
M&C
REQ'D
TREND
LDP
OVRD
REQ'D
M&C
REQ'D
OVRD
NAME
SNVT
OVERRIDES
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##><INTEGRATED>
PROOF FAILED
(SEE NOTES)
ALARM CONDITION
TYPE
SNVT
PRIORITY
ALARM
NAME
SNVT
NAME
ROUTING
M&C
TYPE
SNVT
BLDG
ROUTING
REQ'D
ZN-T-SP ZONE TEMPERATURE SET POINT <___><___> ~~~~<___> ~ ~~ ~
POINT SCHEDULE FOR (EXHAUST FAN)
START/STOP
<___> [~]<___> [~][~]X[~] <___> <___>AI<___>~ZONE TEMPERATURE [~]ZN-T ~~~~
[~] X <___> <___> ~ ~ ~ ~ ~EA DAMPER COMMAND (2-POSITION)EA-D-2P ~ OPEN/CLOSE BO [X] X [~] <___> <___> [~] X <___> <___> ~ ~ ~ ~ ~OA DAMPER COMMAND (2-POSITION)OA-D-2P ~ OPEN/CLOSE BO [X] X [~] <___> <___>
1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS DRAWING
2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW
NOTES
(2) (3)
A. HAND-OFF-AUTO SWITCH
(1) HAND: SWITCH IN THE HAND POSITION. THE EXHAUST FAN SHALL
RUN THE UNIT CONTINUOUSLY UNTIL MANUALLY STOP.
THE UNIT SHALL RUN SUBJECT TO THE UNIT MANUFACTURER'S SAFETIES.
B. SAFETIES
C. ZONE TEMPERATURE CONTROL
(1)
SEQUENCE OF OPERATION :
THE ROOM THERMOSTAT SHALL ENERGIZED THE FAN, AND OPEN
OUTSIDE/EXHAUST AIR MOTORIZED DAMPERS WHEN THE ROOM
OFF: SWITCH IN THE "OFF" POSITION, THE EXHAUST FAN SHALL STOP.
CONTRACTOR SHALL INSTALL DDC HARDWARE TO PERFORM THIS SEQUENCE OF
OPERATION AND TO PROVIDE SNVT INPUTS, OUTPUTS AND ALARMS AS SPECIFIED
AND SHOWN ON THE POINTS SCHEDULE.
NOTE :
OUTSIDE AND EXHAUST AIR DAMPERS SHALL HAVE A LEAKAGE
RATE OF 3 CFM/SF (MAX) AT 1" WG.
TEMPERATURE RISES TO 35°C (95°F).
AUTO: SWITCH IN THE "AUTO" POSITION, THE DDC HARDWARE SHALL
OPERATE THE EXHAUST FAN AND OPEN THE MOTORIZED DAMPER.
D. HVAC EMERGENCY SHUT-OFF SWITCH:
(1) WHEN THE HVAC EMERGENCY SHUT-OFF SWITCH IS ACTIVATED, EXHAUST
FAN WILL SHUT DOWN AND EXHAUST/OUTSIDE AIR DAMPERS SHALL CLOSE.
(2) (3)
A. HAND-OFF-AUTO SWITCH
(1) HAND: SWITCH IN THE HAND POSITION. THE EXHAUST FAN SHALL
RUN THE UNIT CONTINUOUSLY UNTIL MANUALLY STOP.
THE UNIT SHALL RUN SUBJECT TO THE UNIT MANUFACTURER'S SAFETIES.
B. SAFETIES
C. ZONE TEMPERATURE CONTROL
(1)
SEQUENCE OF OPERATION :
THE ROOM THERMOSTAT SHALL ENERGIZED THE FAN, AND OPEN WHEN
THE ROOM TEMPERATURE RISES TO 35°C (95°F). OR HIGHER AND STOPS
OFF: SWITCH IN THE "OFF" POSITION, THE EXHAUST FAN SHALL STOP.
CONTRACTOR SHALL INSTALL DDC HARDWARE TO PERFORM THIS SEQUENCE OF
OPERATION AND TO PROVIDE SNVT INPUTS, OUTPUTS AND ALARMS AS SPECIFIED
AND SHOWN ON THE POINTS SCHEDULE.
NOTE :
OUTSIDE AND EXHAUST AIR DAMPERS SHALL HAVE A LEAKAGE
RATE OF 3 CFM/SF (MAX) AT 1" WG.
THE EXHAUST FAN WHEN THE ZONE TEMPERATURE DROPS TO 26°C (80°F).
AUTO: SWITCH IN THE "AUTO" POSITION, THE DDC HARDWARE SHALL
OPERATE THE EXHAUST FAN AND OPEN THE MOTORIZED DAMPER.
D. HVAC EMERGENCY SHUT-OFF SWITCH:
(1) WHEN THE HVAC EMERGENCY SHUT-OFF SWITCH IS ACTIVATED, EXHAUST
FAN WILL SHUT DOWN AND EXHAUST/OUTSIDE AIR DAMPERS SHALL CLOSE.
(2) THE FAN RUNS AT LOW SPEED WHEN THE ROOM TEMPERATURE IS
WITHIN SETPOINTS.
THE FAN RUNS AT HIGH SPEED WHEN THE ROOM TEMPERATURE IS
OUTSIDE OF SETPOINTS.
<___>EXHAUST FAN HIGH SPEED START/STOP
EXHAUST FAN HIGH SPEED STATUS
EF-HI-SS
EF-HI-S
START/STOP BO [X] X
BI [X] X
<___>[~] [~] X <___>
PROOF FAILED~ [___]<___> [~]START/STOP
WALL
MOUNTED
FAN
M
NC
ACTUATOR
OUTSIDE AIR
MOTORIZED
DAMPER
DDC
MECH RM (122) EA FAN
WALL
MOUNTED
FAN
M
NC
ACTUATOR
OUTSIDE AIR
MOTORIZED
DAMPER
DDC
ELEC RM (120) EA FAN
EF
2 MECH RM (149) EA FAN
EF
4 TOILET ROOM (112,113) EA FAN
EF
5 TOILET ROOM (104) EA FAN
EF
6 TOILET ROOM (106) EA FAN
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, 1 EXHAUST FAN & UNIT HEATER AUTOMATIC CONTROL DIAGRAM
SCALE = NOT TO SCALE
E X
H A
U S
T
FA
N
U N
IT
H
E A
TE
R
A U
TO
M
A
TI
C C
O N
TR
O
L D
IA
G
R A
M
MI609F
CW LINE
MAKE-UP
T P
T P
TO TOILET AREA
T P 48.8°C(120°F)
DP
DDC
DHWR-T
DOMESTIC HOT WATER HEATER SYSTEM
THERMOSTATIC
MIXING VALVE
THEROMOSTATIC
CONTROL SENSOR
EXPANSION1
ET
TANK
DHWS-T-2
60°C(140°F)
SPARE WELL
DHWS-T-1
DOMESTIC HOT
WATER HEATER
37.8°C(100°F)
TO TOILET AREA
HOT WATER
DOMESTIC
1.
2.
NOTES :
1.
2.
3.
CONTRACTOR SHALL AFFIX PERMANENT TAGS/LABELS
TO ALL DEVICES AS SPECIFIED.
CONTRACTOR SHALL LABEL ALL DDC I/O SIGNAL LINES :
4-20 mA, VDC, OR SNVT.
CONTRACTOR SHALL SHOW A UNIQUE IDENTIFIER
FOR EACH DEVICE. WERE MULTIPLE IDENTICAL DEVICES
ARE SHOWN (FOR EXAMPLE; DDC CONTROLLER, OA SENSOR,
OR EP TRANSDUCER) EACH SHALL BE SEQUENTIALLY
NUMBERED. WHERE SEPERATE DDC CONTROLLER BUBBLES
ARE USED TO REPRESENT/SHOW A COMMON (OR SINGLE)
CONTROLLER EACH BUBBLE SHALL USE THE SAME
IDENTIFIER AND NUMBER. DEVICE AND SIGNAL
IDENTIFIERS SHALL BE CONSISTENT BETWEEN DRAWINGS.
DOMESTIC HOT WATER RECIRCULATION PUMP SECTION
CONTRACTOR SHALL INSTALL DDC HARDWARE TO PERFORM THIS
SEQUENCE OF OPERATION AND TO PROVIDE SNVT INPUTS, OUTPUTS
UNLESS OTHERWISE SPECIFIED, ALL MODULATING CONTROL SHALL BE
PROPORTIONAL-INTEGRAL (PI) CONTROL.
DOMESTIC HOT WATER HEATER SECTION
"HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS
THE DOMESTIC HOT WATER RECIRCULATING PUMP CONTINUOUSLY
UNTIL MANUALLY STOPPED.
"HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION,
PIPE MOUNTED THERMOSTAT STOPS THE DOMESTIC HOT WATER
RECIRCULATING PUMP WHEN THE DOMESTIC HOT WATER RETURN
TEMPERATURE REACHES 37.8°C (100°F) AND RUNS THE DOMESTIC
HOT WATER RECIRCULATING PUMP WHEN DOMESTIC HOT WATER
RETURN TEMPERATURE DROPS TO 27°C (80.6°F) OR LOWER.
1.
2.
"ON-OFF" SWITCH TO "ON" POSITION, DDC HARDWARE ENERGIZES
THE BURNER OF THE DOMESTIC HOT WATER HEATER, AFTER CHECKING
OWN SAFETY. LOW WATER CUT-OFF AND HIGH LIMIT CONTROLLER.
THE THERMOSTATIC 3-WAY MIXING CONTROL VALVE IS A MECHANICAL
VALVE THAT OPERATES INDEPENDENT OF THE DDC SYSTEM CONTROL.
THE THERMOSTATIC 3-WAY MIXING CONTROL VALVE IS CONTROLLED BY
1.
2.
CONTRACTOR SHALL UNIQUELY NUMBER ALL
ANSI 709.1 DEVICES. THIS NUMBERING
SHALL BE CONSISTENT BETWEEN ALL DRAWINGS.
4.
SEQUENCE OF OPERATION
PIPE MOUNTED SENSOR TO MAINTAIN DOMESTIC HOT WATER SUPPLY
TEMPERATURE AT SETPOINT OF 48.8°C (120°F).
DHW
DOMESTIC HOT WATER RECIRCULATION PUMP
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, 1 DOMESTIC HOT WATER HEATER AUTOMATIC CONTROL DIAGRAM
SCALE = NOT TO SCALE
D O
M
ES
TI
C
H O
T W
A
TE
R H
E A
TE
R
A U
TO
M
A
TI
C C
O N
TR
O
L D
IA
G
R A
M
MI610F
M&C
LDP AND M&C DISPLAY
DOMESTIC HOT WATER BOILER START/STOP
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
DOMESTIC HOT WATER BOILER STATUS (STATE)
DOMESTIC HOT WATER RECIRC PUMP STATUS
DOMESTIC HOT WATER CIRC PUMP START/STOP
SYSTEM ENABLE
DHW-S
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##>
SYS-ENA
(WITH UNITS)
SETTING
START/STOP
START/STOP
[X]
[X]
<BO>
<BI> X
X
NAME
nci/CPRANGE
(WITH UNITS)
START/STOP
ENABLE/DISABLE
~ ON/OFF
VIEWI/O DISP
[X]
REQ'D
[X]
BO
<NVI>
BI
TYPE
X
REQ'D
X
LDP
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
SNVT
TYPE
SNVT
TYPE
<___>[X]
[X] <___>
TREND SNVT SNVT
REQ'D NAME
TYPE
SNVTOVRDOVRD
REQ'D
REQ'D
<___>X
X
NAME
OVERRIDES
M&CLDP
ALARM GENERATOR DDC HARDWARE INFORMATION:
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##><INTEGRATED>
ALARM CONDITION
(SEE NOTES)
NODE ID: <___>
SNVTALARM
PRIORITY
NAME
ALARMS
ROUTINGROUTING
NAME
REQ'D
M&C BLDG
DHW-SS
DP-1-SS
DP-1-S
DHWS-T ~ <___> AI [X] X [X] <___> <___> ~ ~ ~ ~ ABOVE OR BELOW DHWS-T-SP <___> <___> [___] [~]DOMESTIC HOT WATER SUPPLY TEMPERATURE
DHWR-T DOMESTIC HOT WATER RETURN TEMPERATURE ~ <___> AI [X] X [X] <___> <___> ~ ~ ~ ~ [~] ~ ~ ~ ~
DHWS-T MORE THAN 5 DEG C
1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS DRAWING
2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW
NOTES
HOT WATER
TEMPERATURE
START/STOP
PROOFS &
FUNCTION
SAFETIES
NAME DESCRIPTION
POINT SCHEDULE FOR (DOMESTIC HOT WATER HEATER)
DOMESTIC HOT WATER SUPPLY TEMPERATURE SETPOINTDHWS-T-SP ~ [X]~ X <___><___>X <___> [~] <___>X ~ ~ ~ ~ ~~CONTROL
THE OFFICIAL SIGNED/SEALED
COPY IS STORED WITH PMC
DOCUMENT CONTROLS
S O
LI
C
IT
AT
IO
N
N O
FI
LE
N A
M E:
D W
N B
Y:
C
KD
B
Y:
D
ES
IG
N
E D
B Y:
D
ES
C R
IP
TI
O N
D
2 3
C
4 5
A
B
M
AR
K A
PP
R
D A
TE
FI
LE
N U
M B
ER
S
IZ
E:
S U
BM
IT
TE
D
B Y:
P
LO
T
SC
AL
E:
P
LO
T D
A
TE
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
C O
N
TR
AC
T
N O
SHEET
IDENTIFICATION
D
AT
E A
PP
R
SHEET OF 355
K O
R E
A
LA
N D
H
O U
SI
N
G C
O R
P O
R A
TI
O
N
H U
D
IG
M A
R C
H
IT
E C
TS
E N
G
IN
EE
R
S
C Y
A
Y
4, S P
T0
M
ID
TO
W
N C
O M
M U
N
IT
Y S
U P
P O
R T
FA
C
IL
IT
IE
S
U S
A G
H U
M P
H R
E
YS
, K O
R
EA
M A
IN
L
IB
R
AR
Y
K U
M H
O E
N G
IN
EE
R
IN
G
C O
N S
TR
U
C
TI
O N
A
Y4
M I6
F-
/0
5/
IS
O
A 1, A3
100% DESIGN FOR CONSTRUCTION
H .S
. S H
IN
H .C
. K
IM
E .B
. H W
AN
G
M ay
. 2 0, 1 DOMESTIC HOT WATER HEATER POINT SCHEDULE
SCALE = NOT TO SCALE
D O
M
ES
TI
C
H O
T W
A
TE
R H
E A
TE
R
P O
IN
T
S C
H E
D U
LE
MI611F
M&C LDP AND M&C DISPLAYNODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
A/C UNIT STATUS
NODE ID: <___>
DDC HARDWARE LOCATION: <___>
DDC HARDWARE: <DDC##>
(WITH UNITS)
SETTING
NAME
nci/CPRANGE
(WITH UNITS)
~ ON/OFF
VIEWI/O DISP
[X]
REQ'D
BI
TYPE REQ'D
X
LDP
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___>
SNVT
TYPE
SNVT
TYPETREND SNVT SNVT
REQ'D NAME
TYPE
SNVTOVRDOVRD
REQ'D
REQ'D
NAME
OVERRIDES
M&CLDP
ALARM…