STATUS
REVISION
DESCRIPTION OF DRAWINGSSHT.NO.DWG.NO.REF.NO.RING NO.
S C H E D U L E O F D R A W I N G S
GENERAL
MECHANICAL
G-1
M-1
M-2
KIM, SM
MECHANICAL
1 G-1
NTS
N
S-2110
S-2113
S-2111
S-2112
S-2114
D D D
GW
D
D
D D s
GW
W
GW
HW
HW HW
W
S S
D xxx x x x x x x x x x x x D
SPRKVS
S N
P R
V S
SFHDR
SFHDR
T-2115
T-2116
THIS PROJECTTITLE SHEET & PROJECT LOCATION PLAN
G1
PROJECT LOCATION PLAN
GFEBS. NO. 195822, JMMT
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
195822
TITLE SHEET & PROJECT LOCATION PLAN
M-3
M-4
M-5
M-6
M-7
LEGEND & ABBREVIATION
MECH. DETAILS
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
A.H.U (2EA), B2110 AT JMMT, KOREA
REPAIR FAILED/FAILING A.C.C.U (2EA) &
PWO 195822,
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
GENERAL NOTES AND SCOPE OF WORK
EQUIPMENT SCHEDULES
EXIST/REMOVAL 1st & 2nd FL. H.V.A.C PLAN
AHU/RF & ACCU SCHEMATIC CONTROL DIAGRAM (FOR AHU-1 & AHU-2)
EXIST/REMOVAL H.V.A.C PLAN / H.V.A.C & PLUMBING PIPING ENLARGED PLANS
9 9 OF 10M-8
10 10 OF 10M-9
EXIST/NEW H.V.A.C ENLARGED PLANS (MECH ROOM & AHU ROOM)
(MECH ROOM & AHU ROOM)
EXIST/NEW H.V.A.C & PLUMBING PIPING ENLARGED PLANS
NOT TO SCALE
KIM, SM
MECHANICAL
2 10 M-1
NTS
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H o
ACCU AIR COOLED CONDENSING UNIT
ACLD AIR COOLED
ACU AIR CONDITION UNIT (S)
ACV ALARM CHECK VALVE
ADP APPARATUS DEW POINT
AHU AIR HANDLING UNIT
AIR COND AIR CONDITION (-ING,-ED)
AL ALUMINUM
ALT ALTITUDE
AMB AMBIENT
AMP AMPERE(AMP, AMPS)
APPROX APPROXIMATE
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BARO BAROMETER(-TRIC)
BARO PR PRESSURE, BAROMETRIC
BHP BRAKE HORSEPOWER
BP BOILING POINT
CAP CAPACITY
CCW COUNTER CLOCKWISE
CHW CHILLED WATER
CKT CIRCUIT
CLASS CLASSIFICATION
CLG LOAD COOLING LOAD
COEF COEFFICIENT
CONN CONNECTION
CONT CONTINUE
C
CMH CUBIC METER PER HOUR
CU M CUBIC METER
CENTIGRADE/ CELCIUS
CFCI
CONTRACTOR INSTALLED
CONTRACTOR FURNISHED
CIP CAST IRON PIPE
CWP
CU MM CUBIC MILLIMETER
Cv COEFFICIENT, VALVE FLOW
CW CLOCKWISE OR COLD WATER
CIRCULATING WATER PUMP
DB DECIBEL OR DRY BULB
COMPRESSORCPRSR
DBT DRY BULB TEMPERATURE
DCWS DOMESTIC COLD WATER SUPPLY
DEG or ° DEGREE
DFW DIESEL OIL
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER SUPPLY
DHWR
DHWS
DIRECT EXPANSIONDX
DRY PIPE VALVEDPV
DOUBLE POLE DOUBLE THROWDPDT
DEWPOINT TEMPERATUREDPT
DIVISIONDIV
DIFFERENCEDIFF
DIAGRAMDIAG
DIAMETERDIA or
DWG DRAWING
EXPANSION JOINTEXPJT
ENTERING WATER TEMPEWT
EVAPORAT (-E,-ING,-ED,-OR)EVAP
EXTERNAL STATIC PRESSUREESP
EXPLOSION PROOFEP
EQUIPMENTEQPT
ENTERINGENT
EFFICIENCYEFF
EQUIVALENT DIRECT RADIATIONEDR
ECONOMIZERECON
ECCENTRICECC
ENTERING AIR TEMPERATUREEAT
FUEL OILFO
FA FACE AREA OR FRESH AIR
FHC FIRE HOSE CABINET
FHY FIRE HYDRANT
FLA FULL LOAD AMPERES
F FARENHEIT
FLR FLOOR
FEED WATER PUMPFWP
FACE VELOCITYFVEL
FLUSH VALVEFV
FRP
FREQUENCYFREQ
FEMALE PIPE THREADFPT
FIBERGLASS REINFORCED PLASTIC
Ft or ' FEET
FXTR FIXTURE
GALVANIZED STEELGALVS
GAGE OR GAUGEGA
GR GRAMS
GOVERNMENT INSTALLED
GOVERNMENT FURNISHED GFGI
CONTRACTOR INSTALLED
GOVERNMENT FURNISHEDGFCI
GAL GALLONS
GALLONS PER MINUTEGPM
HERTZHZ
HORIZONTALHORIZ
HOT WATER HEATERHWH
HOT WATERHW
HOUR(S)HR
HORSEPOWERHP
MERCURYHG
HEADHD
HB HOSE BIBB
DIAMETER, INSIDEID
ISOMETRICISO
IRON PIPE SIZEIPS
J JOULE
K THERMAL CONDUCTIVITY
K THERMAL CONDUCTIVITY
kG kCAL/HR
KILOGRAM
kG/SQ CM KILOGRAM PER SQ. CENTIMETER kG/SQ CM A
KILOCALORIE PER HOUR
(ABSOLUTE)
KILOGRAM PER SQ. CENTIMETER
kG/SQ CM G
(GAUGE)
KILOGRAM PER SQ. CENTIMETER
kG/SM KILOGRAM PER SQ. METER kG/SM A kG/SM G
(ABSOLUTE)
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (GAGE)
kW KILOWATT kWH KILOWATT HOUR kJ KILOJOULE kPa KILO PASCAL
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LG LENGTH
LH LATENT HEAT
LWT LEAVING WATER TEMPERATURE
LIQUID LINELL
L LITERS
LPD LITERS PER DAY
LPH LITERS PER HOUR
LPS
LM LINEAR METER
LITERS PER SECOND
LAV LAVATORY
LPM LITERS PER MINUTE
LT LAUNDRY TRAY
NUMBERNO
NORMALLY OPENN.O.
NOT IN CONTRACTNIC
NORMALLY CLOSEDN.C.
NOISE CRITERIANC
NCK
MAX
NOT TO SCALENTS
MIN
MPH
M METERS
MAXIMUM
MINIMUM OR MINUTE
METERS PER HOUR
MPS METERS PER SECOND
MM MILLIMETER
NPT NATIONAL TAPER PIPE (THREAD)
NOT APPLICABLEN/A
NECK
MECH MECHANICAL
OS&Y OUTSIDE SCREW & YOKE
OD
OAIL OUTSIDE AIR INTAKE LOUVER
OA OUTSIDE AIR
OUTSIDE DIAMETER
OPNG OPENING
OXY OXYGEN
PERCENT
PRESSURE REDUCING VALVEPRV
PARTS PER MILLIONPPM
POINT OF CONNECTIONPOC
PLUMBINGPLMB
PHASE (ELECTRIC)PH
PRESSURE GAGEPG
PD
POLEP
PRESSURE DROP OR DIFFERENCE
Pa PASCAL
POL PETROLEUM, OIL AND LUBRICANTS
QUANTITYQTY
QUARTQT
REFRIGERATION TONRT
REVOLUTIONS PER MINUTERPM
RADIATORRDTR
RETURN AIRRA
THERMAL RESISTANCER
REFRIGERANT (134A, 22, ETC)R134A,R22
RH RELATIVE HUMIDITY
SUPPLY AIRSA
SYMBOLSYM
SUCTIONSUCT
STORAGESTOR
STEELSTL
STANDARDSTD
STEAMST
SAYBOLT SECONDS UNIVERSALSSU
STAINLESS STEELSST
SAYBOLT SECONDS FUROLSSF
SQUARESQ
SPECIFICATIONSPEC
SINGLE POLE DOUBLE THROWSPDT
SM
LPH, STANDARD CONDITIONSSLPH
LPS, STANDARD CONDITIONSSLPS
SG
SLPD LPD, STANDARD CONDITIONS
SL SENSIBLE LOAD
SH SENSIBLE HEAT
SPECIFIC GRAVITY
SF SAFETY FACTOR
SEC SECOND
SCH SCHEDULE
STATIC PRESSURE
SQUARE METER
SP
SBM
SAN SANITARY
SUBMERSIBLE
TYPICALTYP
THERMOSTATTSTAT
TONS OF REFRIGERATIONTONS
THICKNESSTHK
THERMOMETERTHERM
TEMPERATURETEMP
TEMPERATURE DIFFERENCETD
UNIT HEATERUH
HEAT TRANSFER COEFFICIENTU
WTRPRF
WT
WSHR
WITHW/
WH
WIDTHWD
WCLD
WC
WBT
WB
WATTW
VP
VOL
VISC
VERTICALVERT
VENTILATIONVENT
VELOCITYVEL
VARIABLE AIR VOLUMEVAV
VAC VACUUM
VLV VALVE
V VOLT
WATERPROOF
WEIGHT
WASHER
WATTHOUR OR WATER HEATER
WATER-COOLED
WATER CLOSET
WET BULB TEMPERATURE
WET BULB
PRESSURE, DYNAMIC(VELOCITY)
VOLUME
VISCOSITY
VTR VENT THRU ROOF
UR URINAL
A B B R E V I A T I O N S
MECHANICAL MATERIAL INDICATIONS AND SYMBOLS
FS
VFM
OFM
AVA
PRESSURE RELIEF
TEMPERATURE
EXPANSION LOOP
EXPANSION JOINT
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR VENT, AUTOMATIC
SQUARE HEAD BALANCING COCK
QUICK OPENING
NEEDLE
LOCK SHIELD
FLEXIBLE CONNECTOR
FLOWMETER, ORIFICE
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE GAUGE AND COCK
STRAINER
THERMOMETER
PRESSURE REDUCING
RELIEF OR SAFETY
SLEEVE
BLOW OFF STRAINER
INLINE PUMP
SAFETY
FLOAT
valves, special duty
S
M
GATE, NORMALLY CLOSED
GLOBE
SOLENOID
3 WAY MANUAL
GATE, NORMALLY OPEN
PLUG
MOTOR OPERATED GATE
MOTOR OPERATED GLOBE
3 WAY ELECMOTOR CONTROL
3 WAY AIR MOTOR CONTROLLER
HOSE GATE
HOSE GLOBE
POST INDICATOR
OS Y
ANGLE GLOBE
ANGLE GATE
SWING GATE CHECK
S
M
P
M
M
ALARM CHECK
DRY PIPE
DELUGE
PREACTION
TAMPER DETECTION SWITCH
QUICK OPENING DEVICE
NON-RISING STEM
DIAPHRAGM
SOLENOID
MOTOR ELECTRIC
valve actuators fittings
TEE, SINGLE SWEEP
UNION, SCREWED
UNION, FLANGED
CONNECTION, TOP
ELBOW, 90°
ELBOW, TURNED UP
ELBOW, TURNED DOWN
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
REDUCER, CONCENTRIC
(STRAIGHT, INVERT)
REDUCER, ECCENTRIC
(STRAIGHT, DOWN)
REDUCER, ECCENTRIC
TEE
ELBOW, 45°
LATERAL
SOLVENT CEMENT
BELL AND SPIGOT
SCREWED
FLANGED
WELDED
SOLDERED/BRAZED
M
NS
BUTTERFLY
BALL
DIAPHRAGM
GATE
INDICATING BUTTERFLY
KEY OPERATED
CHECK
SIDEWALL SPRINKLER
UPRIGHT SPRINKLER
DELUGE VALVE
WALL MOUNTED TEST HEADER
FIRE ALARM BELL
HOSE STATION DRY STANDPIPE
MINI HORN
HORN SPEAKER
WALL HYDRANT 2 HOSE OUTLET
SMOKE DETECTOR
PENDENT SPRINKLER DROP NIPPLE
NIPPLED UP UPRIGHT SPRINKLER
OUTSIDE SPRINKLER
CUTTING POINT
CAP
NON-SPRINKLERED SPACE
RISER
(SEE SPRINKLER SCHEDULE)
PENDENT SPRINKLER
CONNECTION (2-WAY SHOWN)
SIAMESE FIRE DEPARTMENT
CONNECTION
SINGLE FIRE DEPARTMENT
valves
POTABLE COLD WATER
POTABLE HOT WATER
POTABLE HOT WATER RETURN
PIPE SLEEVE
BACKFLOW PREVENTER
PITCH OR PIPE, UP(U), DOWN(D)
VENT THRU ROOF
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
PIPE SLEEVE WITH FIRE STOPPING
HOSE BIBB
FLOOR SINK (200mm x 200mm)
HOT WATER (60°C)
HOT WATER (82.22°C)
VENT
SANITARY SEWER
COMPRESSED AIR
FUEL OIL SUPPLY
FUEL OIL RETURN
FLOOR DRAIN WITH CLEANOUT
FLOOR DRAIN WITH DEEP TRAP
FLOOR DRAIN WITH NO TRAP
FLOOR DRAIN WITH TRAP TIME
FD
FCO
SCO
200x200
FIRE PROTECTION WATER SUPPLY
MAIN SUPPLY SPRINKLER
WET STANDPIPE
DRY STANDPIPE
COMBINATION STANDPIPE
plumbing sprinkler
DSP
WSP
CSP
S
F
PLAN ELEV
82.22°C
60°C
S
A
FOS
FOR
RD
RS
RL
D
CWS
CWR
LPC
BBD
PC
VPD
MU
FOD
FOV
FOG
FOS
FOR
HWS
M
HCS
HCR
FILL
MU
HWR
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
VACUUM PUMP DISCHARGE
MAKE UP WATER
FUEL OIL DRAIN
FUEL OIL TANK VENT
FUEL OIL GAUGE
FUEL OIL SUPPLY
FUEL OIL RETURN
CONTROL AIR MAIN
DUAL TEMPERATURE RETURN
FILL LINE
MAKE UP WATER
DUAL TEMPERATURE SUPPLY
WATER SUPPLY
LOW TEMPERATURE HOT
WATER RETURN
LOW TEMPERATURE HOT
SPLITTER DAMPER
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
dampers piping heating air conditioning and refrigeration
DU 13mm
47.2
94.4
DG
300x150
500/300L
R
AD
FC
SG
SR
RG
RR
810mm x 400mm
810mm x 400mm
810mm x 400mm
EG
ER
810mm x 400mm
DIRECTION OF FLOW
FLEXIBLE CONNECTION
TRANSITION
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN
RISE(R), DOWN(D)
CHANGE OF ELEVATION
VERTICAL OR HORIZONTAL
ACCESS DOOR,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
OUTSIDE AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
SUPPLY AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
SECTION, NEGATIVE PRESS.,
RETURN OR EXHAUST AIR DUCT
SUPPLY OR RETURN
FLEXIBLE AIR DUCT,
TRANSITION
SQUARE TO ROUND
REGISTER, CEILING
EXHAUST AIR GRILLE OR
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
RETURN AIR GRILLE OR
OR REGISTER, CEILING
SUPPLY AIR MODULAR DIFFUSER
DOOR GRILLE (300mmx150mmH)
(500mmWx300mmH, 94.4 LPS)
LOUVER, DOOR OR WALL
(13mm, 47.2 LPS)
DOOR UNDERCUT
duct works grilles, registers and diffusers
LEGEND & ABBREVIATION
W/ MEASURING TAP
SQUARE HEAD BALANCING COCK
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
195822
M-2
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
NTS
3 10
GENERAL NOTES
NOTE :
A. REPAIR/MAINTENANCE (K-WORK)
SCOPE OF WORK (MECHANICAL)
195822
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
SCOPE OF WORK (ELECTRICAL)
A. REPAIR/MAINTENANCE (K-WORK)
GENERAL NOTES AND SCOPE OF WORK
10. SALVAGEABLE MATERIALS SHALL BE RETURNED TO DPW.
AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE U.S. GOVERNMENT.
9. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION ACTIVITIES, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.
COST TO THE GOVERNMENT, INCLUDING, BUT NOT NECESSARILY LIMITED TO ITEMS SUCH AS WALLS, CEILING, ROOF, TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE PROTECTION SYSTEM AT NO ADDITIONAL
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS AS NECESSARY
SUBMITTED TO THE PROJECT COR FOR GOVERNMENT REVIEW AND APPROVAL.
FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, ADJUSTING AND BALANCING (TAB) REPORT SHALL BE
WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL. O & MA STANDARD TECHNICAL SPECIFICATIONS
7. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN STRICT ACCORDANCE
THE U.S. GOVERNMENT.
THE DETAILS WILL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK AT NO ADDITIONAL COST TO
6. FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS PROJECT.
GOVERNMENT.
5. IF NECESSARY, CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY
CONTRACT SPECIFICATIONS.
MAY DEVIATE FROM THAT SHOWN ON CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE
FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH
4. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL SYSTEM TO SATISFY ALL
TO THE CONTRACTING OFFICER FOR APPROAL.
SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED
3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH DETAILS
THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AS DIRECTED BY THE CONTRACTING OFFICER.
2. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS CAUSED BY
COMMENCING ANY CONSTRUCTION OR RENOVATION.
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS PRIOR TO
PROVIDE THE TEMPORARY COOLING OR HEATING SYSTEM TO THE ENTIRE BUILDING.
4. IF THE CONTRACTOR IS GOING TO CONSTRUCTION DURING THE COOLING/HEATING SEASON, THE CONTRACTOR SHALL
ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.
3. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, CONDUITS AND
LICENSED OR CERTIFIED INSTALLER.
2. INSTALLATION OF THE H.V.A.C SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION BY A
DUCT & PIPE LAYOUT, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE CLEARANCE,
1. DISCONNECT AND RECONNECT POWER SUPPLY AND CONTROL LINE FOR REPLACED MECHANICAL EQUIPMENT.
NOTE :
EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.
2. EXACT RATINGS AND SETTINGS OF ELECTRICAL EQUIPMENT AND DEVICES SHALL BE IN ACCORDANCE WITH MECHANICAL
SPECIFICATIONS.
CODE, NATIONAL ELECTRICAL SAFETY CODE, LIFE SAFETY CODE, UNIFIED FACILITIES CRITERIA AND CONTRACT
1. ALL ELECTRICAL WORK SHOULD BE DONE IN ACCORDANCE WITH THE CURRENT EDITIONS OF NATIONAL ELECTRICAL
CLEANING CONDITION.
3. CLEAN DUCTS AND DIFFUSERS. APPLY ROBOT CLEANING TO DUCTS, AND SUBMIT VIDEO FILES IN CD TO VERIFY
CONSTRUCTION TO VERIFY IF THE H.V.A.C SYSTEM WORKS PROPERLY.
2. PERFORM DALT (DUCT AIR LEAKAGE TEST) AND T.A.B (TESTING, ADJUSTING, AND BALANCING) AFTER
AS SHOWN ON DRAWINGS.
VALVES, DUCT LINING, LOUVER, HANGER, AND ALL ASSOCIATED ACCESSORIES, FOR H.V.A.C & PLUMBING SYSTEM
MOTORIZED DAMPERS, THERMOSTAT, SMOKE DETECTOR, FREEZESTAT, DUCTS, PIPES, CONTROL WORK, INSULATIONS, PUMP, DOMESTIC HOT WATER TANK, EXPANSION TANKS (2EA), AIR SEPARATOR, UNIT HEATER, CHEMICAL FEEDER, MOUNTED IN-LINE RETURN FANS (2EA), HOT WATER CIRCULATION PUMP, DOMESTIC HOT WATER RECIRCULATION
1. REPAIR DETERIORATED EXISTING AIR HANDLING UNITS (2EA), AIR COOLED CONDENSING UNITS (2EA), DUCT
DB(°C)
WB(°C) WB(°C)
DB(°C)
E Q U I P M E N T S C H E D U L E S
KIM, SM
MECHANICAL
M-3
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
NTS
4 10
195822
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
EQUIPMENT SCHEDULES
AIR COOLED CONDENSING UNIT
ITEM QTY TYPE
COMPRESSOR CONDENSER FAN
R E M A R K S
(KW)
COOLING CAPACITY
RLA LRA VOLT/PH/HZ VOLT/PH/HZNO. TYPE FLA (DEG C)
AMBIENT AIR TEMP
2 33.4200/3/604.3x1EA, 3.7x1EAPROPELLER, DIRECT, RIVE200/3/6034567.955.2
SEMI-HERMETIC
RECIPROCATING
SEMI-HERMETIC
RECIPROCATING
55.2 2 200/3/604.3x1EA, 3.7x1EAPROPELLER, DIRECT, RIVE200/3/6034567.9 33.4
ACCU
ACCU
AIR HANDLING UNIT
ITEM QTY
AHU
AHU
SERVICE TYPE
3. THE FILTER & MIXING BOX SECTION SHALL BE ANGLE TYPE FILTER.
2. ALL AHU'S COMPONENTS CONSIST OF FAN, DX-COOLING COIL, HOT WATER HEATING COIL AND FILTER & MIXING BOX.
NOTE: 1. ALL AHU'S SHALL BE PROVIDED WITH INTERNAL SPRING TYPE VIBRATION ISOLATORS.
(FOR 1st FL)
OFFICE AREA
(FOR 2nd FL)
OFFICE AREA
SUPPLY FAN COOLING COIL HEATING COIL
R E M A R K S
SETTINGS
OUTSIDE AIR
MINIMUM
2557.8
2659.3
HORIZONTAL
DRAW-THRU
HORIZONTAL
DRAW-THRU
LPS
467.8
467.8
(Pa)
TOTAL SP
RPM
910 3 200/3/60
200/3/603
VOLT/PH/HZHP
MOTOR ROW
55.3
55.7
(KW)
TOTAL
37.7
37.5
(KW)
SENSIBLE
(Pa)
MAX.APD
134.5
144.5
EAT. LAT.
25.6
19.1
19.0
25.4
12.9
13.7
14.0
13.0
2.5
2.5
FINS
ROW
FINS(M/SEC)
FACE VEL
MAX.
39.7 82.2 0.86
1.01
52.3
57.3
0.4
0.4 28.3
2.5
2.5
(KW)
TOTAL
47 82.2
(Pa)
MAX.APD
(LPS)
FLOW RATE
TEMP(DEG C)
ENT.WATER
(M)
MAX.WPD
(DEG C)
LAT
(M/SEC)
MAX.FACE VEL
LPS
PUMPS
ITEM QTY
P
P
SERVICE
HOT WATER CIRC.
TYPE R E M A R K S
ALL BRONZE CONSTRUTION 0.23
7.94 20.7
5.6
HP VOLT/PH/HZ
MOTOR
1/15 115/1/60
200/3/605
RPM
1,750
3,250
HOT WATER RECIRC.
DOMESTIC
IN-LINE CENTRIFUGAL
PIPE MOUNTED
END SUCTION CENTRIFUGAL
BASE MOUNTED
(LPS)
CAPACITY
(M)
HEAD
ITEM QTY
RF
RF
SERVICE
FANS
(AHU-2)
OFFICE AREA
(AHU-1)
OFFICE AREA
TYPE
BELT DRIVEN, CENTRIFUGAL FAN
DUCT MOUNTED, IN-LINE TYPE,
IN-LINE TYPE, BELT DRIVEN, CENTRIFUGAL FAN
DUCT MOUNTED, LEFT SIDE DISCHARGE
(LPS)
AIR CAP
(Pa)
ESP
RPM
2,048
2,159
154.95
154.95
1,000
1,045
HP VOLT/PH/HZ
200/3/60
200/3/602
FAN MOTOR
MOUNTING BRACKETS
MOUNTING BRACKETS
REMARKS
ITEM QTY
HWG
DOMESTIC HOT WATER GENERATOR
SERVICE TYPE
(LIT)
CAPACITY
STORAGE
1,703 1,067 D x 2,007 H
(mm DIA x mm HEIGHT)
TANK SIZE
(DEG C)
TEMP
SUPPLY
60(140°F) 55.6(100°F)
(DEG C)
TEMP RISE
(PSI)
PRESSURE
WORKING
TYPE
COPPER TUBE
2-PASS DOUBLE WALL
HOT WATER SYSTEM
DOMESTIC
STEEL ROUND
VERTICAL,
SURFACE AREA
HEATING
1.2 M 0.67
LPS
600mm200mm
DIAMETER LENGTH
DOUBLE-WALL COPPER TUBE TANK HEATER
85°C
OUT
HOT WATER
IN
115°C
IN OUT
4.4°C 60°C
DOMESTIC HOT WATER
0.69
DROP.(KPA)
MAX. WATER PRESS R E M A R K S
EXPANSION TANK
ITEM QTY
ET
ET
SERVICE
HOT WATER SYSTEM
HOT WATER SYSTEM
DOMESTIC
TYPE
VERTICAL TYPE
DIAPHRAGM,
VERTICAL TYPE
DIAPHRAGM,
TANK CAP (LITS)
ACCEPTANCE
(mmD x mmH)
TANK SIZE
610 x 2,095
356 x 735
PRESS (KPA)
WORKING
411.76
275.7
R E M A R K S ITEM QTY
AS
SERVICE
HOT WATER SYSTEM
TYPE
AIR SEPARATOR
PIPE MOUNTED
PIPE SIZE
INLET OUTLET
80 DIA80 DIA
R E M A R K S
W/BUILT-IN STRAINER
ITEM QTY
UH
SERVICE
UNIT HEATER
MECH ROOM(116)
TYPE
CAP. (KW)
HEATING
2.23
LPS
0.048
(DEG C)
EWT
82.2 179.33
LPS
FAN CAPACITY
1,550
RPM
1/40
HP VOLT/PH/HZ
115/1/60
DISCHARGE TYPE
HORIZONTAL
REMARKS
REFRIGERANT R-410A
REFRIGERANT R-410A
REFRIGERANT R-410A
REFRIGERANT R-410A
N
MECHANICAL
5 10 M-4
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
GRAPHIC SCALE
SCALE: 1:100
0 2000 4000
M4
1:100
SUPPLY
ARMY
HALL
JAN
VEST
STAIR-2
REGISTRY RM
ELEC
MECH RM
FIRE PUMP RM
M.TOILET
W.TOILET
TOILET
BREAK RM
DRIVER'S
BED RM
ROOM
LIVING
OFFICE
USFK
OPERATION
ARMY
ROOM
BREAK
CORR-1
CORR-3
DISPATCH
RECEIPT &
OFFICE
CMD
CMD
CORR-2
SUPPLY
GENERAL
RETAIN'G
CUSTOMS
SUPPLY
AIR FORCE
STORAGE
EQUIPMENT
CONTINGENCY
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
195822
STAIR-2
HALL
CORRIDOR
ROOM
TRAINING
ROOM
MACH
CHIEF
AMT
ROOM
CONFERENCE
STORAGE
BUNK
ROOM
BREAK
ROOM
TRAINING
PHYSICAL
M.TOILET
W.TOILET
AHU
STOR.
COMM
JAN
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
KEY PLAN
N
M4
EXISTING 1st FL. H.V.A.C PLAN
EXISTING 2nd FL. H.V.A.C PLAN
1st & 2nd FL. H.V.A.C PLAN
EXIST/REMOVAL
ADMIN
ARMY
ADMIN
AIR FORCE
STAIR-1
R A
S A
RA RA
SASA
REP.WAITING
AIRLINES
OFFICE
TRANSPORTATION
AIR FORCE
SA
RA
S A
SA
RA
R A
M
M
M
SD
TS
L T
OA
VT
EA
EAOA
L T
TS
SD
M
M
T
M
O A
M
O A
ES ES ES
SEE
FOR ENLARGED PLAN
M5
SEE
FOR ENLARGED PLAN
M5
IN CD TO VERIFY CLEANING CONDITION. (TYP.)
CLEANING TO DUCTS, AND SUBMIT VIDEO FILES
CLEAN DUCTS AND DIFFUSERS. APPLY ROBOT
EXISTING DUCTS AND DIFFUSERS TO REMAIN.
IN CD TO VERIFY CLEANING CONDITION. (TYP.)
CLEANING TO DUCTS, AND SUBMIT VIDEO FILES
CLEAN DUCTS AND DIFFUSERS. APPLY ROBOT
EXISTING DUCTS AND DIFFUSERS TO REMAIN.
- M5
- M6
- M7
- M7
M6 - M7
3 3
SCALE = 1:100
SCALE = 1:100
TO REMAIN (TYP OF 3)
SHUT-OFF PUSH BUTTON
EXISTING EMERGENCY
6 10
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
195822
N
M5
M-5
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
1:50
DUCT LINING, LOUVER, HANGER, AND ALL ASSOCIATED ACCESSORIES
THERMOSTAT, SMOKE DETECTOR, FREEZESTAT, DUCTS, INSULATIONS, VALVES,
EXPANSION TANKS (2EA), AIR SEPARATOR, UNIT HEATER, MOTORIZED DAMPERS,
DOMESTIC HOT WATER RECIRCULATION PUMP, DOMESTIC HOT WATER TANK,
DUCT MOUNTED IN-LINE RETURN FAN, HOT WATER CIRCULATION PUMP,
REMOVE EXISTING AIR HANDLING UNIT, AIR COOLED CONDENSING UNITS (2EA),
PIPES, INSULATIONS, VALVES, HANGER, AND ALL ASSOCIATED ACCESSORIES
TANKS (2EA), AIR SEPARATOR, UNIT HEATER, MOTORIZED DAMPERS, THERMOSTAT,
HOT WATER RECIRCULATION PUMP, DOMESTIC HOT WATER TANK, EXPANSION
DUCT MOUNTED IN-LINE RETURN FAN, HOT WATER CIRCULATION PUMP, DOMESTIC
REMOVE EXISTING AIR HANDLING UNIT, AIR COOLED CONDENSING UNITS (2EA),
M5
EXIST/REMOVAL H.V.A.C ENLARGED PLAN
EXIST/REMOVAL H.V.A.C & PLUMBING PIPING ENLARGED PLAN2
(MECH ROOM)
(MECH ROOM)
M5
3 H.V.A.C PIPING ENLARGED PLAN
EXIST/REMOVAL H.V.A.C &
(AHU ROOM)
AND ALL ASSOCIATED ACCESSORIES
INSULATIONS, VALVES, DUCT LINING, HANGER,
DETECTOR, THERMOSTAT, FREEZESTAT, DUCTS, PIPES,
IN-LINE RETURN FAN, MOTORIZED DAMPERS, SMOKE
REMOVE EXISTING AIR HANDLING UNIT, DUCT MOUNTED
P.O.C
P.O.C
P.O.C
P.O.C
TO REMAIN
HEAT EXCHANGER
EXISTING
TO REMAIN
UNIT HEATER
EXISTING
TO REMAIN (TYP OF 2)
EXHAUST FAN W/DUCT
EXISTING
TO REMAIN
UNIT HEATER
EXISTING
TO REMAIN
HEAT EXCHANGER
EXISTING
TO REMAIN (TYP.)
EXISTING MAIN PIPE
TO REMAIN
EXISTING MAIN PIPE
P.O.C
P.O.C P.O.C P.O.C
P.O.C
P.O.C
P.O.C
P.O.C P.O.C
P.O.C
W/ DUCT TO REMAIN
ROOF VENTOLATOR
EXISTING
P.O.C
P.O.C
DUCT TO REMAIN
AIR LOUVER W/
EXISTING OUTSIDE
PIPING ENLARGED PLANS
H.V.A.C PLAN / H.V.A.C & PLUMBING
EXIST/REMOVAL
AHU
M
M
SD
TS
L T
L T
W S
LTWS
LTWR
LTWR
LTWS
LTWR
RL
RS
SCALE = 1:50
SCALE = 1:50
SCALE = 1:50
MECH RM
M.TOILET
MECH RM
FIRE PUMP RM
M.TOILET
OA
VT
EA
EAOA
M
M
O A
M
O A
L T
TS
SD
M
F M
FIRE PUMP RM
(FOR AHU-1)
AIR COOLED CONDENSING UNIT
(FOR AHU-2)
AIR COOLED CONDENSING UNIT
CIRCULATION PUMP
HOT WATERP
UNIT HEATER
UH
HANDLING UNIT
AIR
EXPANSION TANK
ET
EXPANSION TANK
ET
GENERATOR
DOMESTIC HOT WATER
RETURN FAN
RF
RETURN FAN
RF
HANDLING UNIT
AIR
KIM, SM
MECHANICAL
7 10
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
195822
N
M-6
M6
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
EXIST/NEW H.V.A.C ENLARGED PLAN
M6
EXIST/NEW H.V.A.C ENLARGED PLAN
(MECH ROOM)
(AHU ROOM)
(MECH ROOM & AHU ROOM)
EXIST/NEW H.V.A.C ENLARGED PLANS
1:50
ACCU
ACCU
TO REMAIN
EXHAUST FAN W/DUCT
EXISTING WALL
TO REMAIN
HEAT EXCHANGER
EXISTING
TO REMAIN
EXISTING UNIT HEATER
FAN W/DUCT TO REMAIN
EXISTING IN-LINE EXHAUST
AHU
P.O.C P.O.C
P.O.C
P.O.C
HWG
LINING(TYP.)
25 THK. DUCT
TO REMAIN (TYP.)
AIR FLOW TEST HOLE
EXISTING
FREEZESTAT
VENTILATION THERMOSTAT
DAMPER
BY-PASS
MOTORIZED
& MOTORIZED DAMPER
INTAKE LOUVER W/BIRDSCREEN
600x650 OUTSIDE AIR
900x500
900x550
900x550
900x500
600x650
1,100x450
1,100x450
AHU
DUCT TO REMAIN
AIR LOUVER W/
EXISTING OUTSIDE
W/ DUCT TO REMAIN
ROOF VENTOLATOR
EXISTING
P.O.C
P.O.C
P.O.C
TO REMAIN (TYP.)
AIR FLOW TEST HOLE
EXISTING
HEATING THERMOSTAT
LINING(TYP.)
25 THK. DUCT
900x550
900x500
FREEZESTAT
x
SMOKE DETECTOR
TEMP. SENSOR
DUCT MONTED S.A
1,000x450
W/ DUCT TO REMAIN
EXISTING O.A.I.L
TO REMAIN
DUCTWORK
EXISTING
SCALE = 1:50
SCALE = 1:50
AHU
MECH RM
M.TOILET
M
M
SD
TS
L T
OA
VT
EAOA
M
M
O A
M
O A
L T
TS
SD
M
HT
FIRE PUMP RM
RETURN FAN
RF
HANDLING UNIT
AIR
(FOR AHU-1)
AIR COOLED CONDENSING UNIT
(FOR AHU-2)
AIR COOLED CONDENSING UNIT
TANK
EXPANSION ET
TANK
EXPANSION ET
CIRCULATION PUMP
HOT WATERP
UNIT HEATER
UH
HANDLING UNIT
AIR
AIR SEPARATOR
AS
SEPARATOR
AIR AS
GENERATOR
DOMESTIC HOT WATER
RECIRCULATION PUMP
DOMESTIC HOT WATERP
KIM, SM
MECHANICAL
8 10
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
195822
M-7
M7 GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
N
EXIST/NEW H.V.A.C PIPING ENLARGED PLAN
(MECH ROOM)
M7 (MECH ROOM)
M7
EXIST/NEW H.V.A.C PIPING ENLARGED PLAN
(AHU ROOM)
EXIST/NEW PLUMBING PIPING ENLARGED PLAN
(MECH ROOM & AHU ROOM)
PIPING ENLARGED PLANS
EXIST/NEW H.V.A.C & PLUMBING
1:50
AHU
VALVE
BALANCING
CALIBRATED
VALVE
MODULATING
3-WAY
SOLENOID VALVE
ACCU
ACCU
TO REMAIN
UNIT HEATER
EXISTING
TO REMAIN
UNIT HEATER
EXISTING
AHU
P.O.C P.O.C
P.O.C
P.O.C
P.O.C
P.O.C P.O.C
P.O.C
P.O.C
HWG
HB
HB
MIXING VALVE
THERMOSTATIC
REDUCING VALVE
PRESSURE
ASSEMBLY
BACK-FLOW PREVENTER
SUNSHIELD TO REMAIN
CONTROLLER, SENSOR AND
EXISTING DIGITAL INDICATORS,
HEATING THERMOSTAT CHEMICAL FEEDER
TO REMAIN
EXISTING UNIT HEATER
BALANCING VALVE
CALIBRATED
CONTROL VALVE
MODULATING 3-WAY
FOR HEATING
CALORIE METER
CONTROL VALVE
PRESS. DIFF.
VALVE(TYP. OF2)
TEMP. CONTROL
VALVE
CONTROL
3-WAY
MODULATING
S.V
AHU
15(N)
32(N)
32(N)
32(N)
20(N)
20(N)
50(N)
20(N)
20(N)
15(N)
50(N)
25(N) 50(N)
32(N)
50(N)
50(E)
32(E)
50(E)
15.8(N)
28.5(N)
15.8(N)
28.5(N)
15.8(N)
28.5(N)
80(E)
80(E)
80(N)
80(N)
32(N)
32(N)
20(N)
20(N)
20(E)
20(E)
80(N)
65(N)
20(N)
15(N)
15(N)
25(N)
32(N)
15(N)
15(N)
65(N)
65(N)
20(N)
T
T O
SW
RC
IM
IM
IM
T
T O
SW
RC
IM
IM
IM
OO
L T
W S
LTWS
LTWR
LTWR
LTWS
LTWR
RL
RS
RL
RS
RL
RS
SCALE = 1:50
SCALE = 1:50
SCALE = 1:50
MECH RM
FIRE PUMP RM
M.TOILET
MECH RM
FIRE PUMP RM 119
M.TOILET
F M
HT
TO LCP
H W
S
CONTROL PANEL
TO TEMP.
CONTROL PANEL
FROM TEMP.
RL
RS
HWR
(TYPICAL)
BALANCING VALVE
(AHU-2 : CV=11.3)
(AHU-1 : CV=9.6)
3-WAY MODULATING VALVE
FROM LCP
VALVE(SV-1)
SOLENOID
NO
AIR
RELIEF
FROM SPACE
RETURN AIR
NOTE :
MANUFACTURER OF INSTALLED SYSTEM.
DIAGRAM SHALL BE PROVIDED BY THE TEMPERATURE CONTROL
ACCORDANCE WITH HVAC CONTROL MANUFACTURER, THE LADDER
AIR HANDLING UNIT SPECIFIED SEQUENCE OF OPERATION IN
THE CONTRACTOR SHALL SUBMIT THE LADDER DIAGRAM FOR EACH
(INTERLOCKED WITH AHU-2)
RETURN AIR FANRF
(INTERLOCKED WITH AHU-1)
RETURN AIR FANRF
MOTOR STARTER
(INTERLOCKED WITH AHU-2)
EXHAUST AIR FAN (EF-6)
(INTERLOCKED WITH AHU-1)
EXHAUST AIR FANS (EF-3 & 4)
TO SPACE
SUPPLY AIR
AIR
OUTSIDE
MOTOR STARTERFILTER
T
TEMP. SENSOR
RETURN AIR
(0-50mmAQ)
GAGE RANGE
MAGNEHELIC
FILTER
TT
TEMP. TRANSMITER
T
TEMP. SENSOR
SUPPLY AIR
MD
N.C
DAMPER
EXHAUST AIR
MD
N.C
N.O
POTENTIOMETER
AUXILIARYMPPPOTENTIOMETER
POSITION
MINIMUM
MOTORIZED DAMPER
OUTSIDE/RETURN AIR
CONTROLLER
CHAGEOVER
To
MD
BY-PASS DAMPER
SET AT 0.5mmAQ(0.2 INCH.)
STATIC PRESSURE SENSOR
SPS
TFTF
TFTF
(TYPICAL)
VAV DIFFUSER
SW
SW
SYSTEM SWITCH
EMERGENCY "OFF" SWITCH
SD
DETECTOR
SMOKE
M
AHU
AHU
2 SUPPLY FAN
AIR HANDLING UNIT
FS
FREEZESTAT
H
C
M
DX
C
S
ACCU-1&2
TO
FOR AHU
CONTROL TRANSFORMER
FOR AHU
ON-OFF SYSTEM SWITCH
FOR AHU
POTENTIOMETER
MININUM POSITION
C NC
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
KIM, SM
MECHANICAL
9 10 M-8
NTS
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19
195822
SEQUENCE OF OPERATION
AHU, ACCU SEQUENCE OF CONTROL:
POSITION AND E.A DAMPERS SHALL BE CLOSED.
4.2.1 AHU/RF SHALL BE DE-ENERGIZED AND O.A/R.A DAMPERS SHALL BE AT 100% R.A
4.2 UNOCCUPIED HEATING MODE:
AHU-2=50%.
A MINIMUM AMOUNT OF AIR TO MEET MINIMUM VENTILATION RATES ARE AHU-1 &
TO MAINTAIN THE 68 DEG.F.(20 DEG.C.). THE VAV DIFFUSER WILL BE SET TO PROVIDE
DIFFUSER TO VARY THE SUPPLY AIR VOLUME TO CONTROL THE EACH ROOM TEMPERATURE
4.1.3 TEMPERATURE HEATING SENSOR LOCATED IN VAV DIFFUSER SHALL CONTROL THE EACH VAV
(68 DEG.F).
AHU HEATING COIL 3-WAY CONTROL VALVE TO MAINTAIN R.A. TEMPERATURE AT 20 DEG.C
SENSOR (AS HEAT ANTICIPATOR) SHALL SEND A SIGNAL TO LOGIC PANEL TO MODULATE
4.1.2 AHU ELECTRIC, DUCT MOUNTED TYPE R.A. SENSOR/TEMPERATURE TRANSMITTER WITH S.A.
POTENTIOMETER SHALL BE SET TO INTRODUCE MINIMUM LPS OF O.A. AS SCHEDULED.
O.A. POSITION AND RELIEF AIR DAMPERS SHALL BE CLOSED. THE MINIMUM POSITION
4.1.1 AHU/RF FAN MOTORS RUN CONTINUOUSLY AND O.A./R.A. DAMPERS SHALL BE AT MINIMUM
4.1 OCCUPIED HEATING MODE:
SET AHU SYSTEM SWITCH TO "ON" POSITION.
4. SYSTEM OPERATION:
EF-3,4 & 6 UPON EMERGENCY CONDITIONS CHEMICAL WARFARE.
3.3 EMERGENCY "OFF" SWITCH SHALL DE-ENERGIZE ALL AHU-1 & 2, RETURN FAN-1 & 2 AND
MANUAL RESET OF FREEGESTAT.
(37 DEG.F.) AND O.A DAMPER SHALL BE CLOSED RESTARTING OF AHU SHALL REQUIRE
3.2 FREEZESTAT STOPS OPERATION OF AHU FAN MOTOR UPON ITS SETPOINT OF 2.8 DEG.C.
THE AHU FAN MOTOR SHALL BE TURNED OFF.
3.1 WHEN SUPPLY AIR DUCT SMOKE DETECTOR SENSES SMOKE IN THE SUPPLY AIR DUCT OF AHU,
3. SAFETY CONTROLS:
AHU FAN MOTOR IS OPERATED.
RETURN FANS SHALL BE INTERLOCKED WITH AHU CONTROL CIRCUIT SO THAT RF OPERATES WHEN
2. SYSTEM INTERLOCKS:
SYSTEM MODE OF OPERATION IS DETERMINED BY SYSTEM SWITCH.
1. GENERAL:
5.2 EXHAUST FANS EF-6 SHALL BE INTERLOCKED WITH AHU-2
5.1 RESPECTIVE EXHAUST FANS EF-3 & EF-4 SHALL BE INTERLOCKED WITH AHU-1
5. EXHAUST FAN OPERATION (EF-3, EF-4 & EF-6):
0.2 INCH(5.1mmAQ), THE BY-PASS DAMPER SHALL OPEN.
SUPPLY AIR DUCT AND SET PRESSURE 0.2 INCH(5.1mmAQ) WHEN STATIC PRESSURE EXCEED
LOCATE THE STATIC PRESSURE SENSOR FOR THE BY-PASS DAMPER 3/4 DOWNSTREAM OF
4.5 AHU BY-PASS DAMPER STATIC PRESSURE CONTROL
4.4.1 SAME AS PARAGRAPH 4.2.1
4.4 UNOCCUPIED COOLING MODE:
AHU-2=50%.
MINIMUM AMOUNT OF SUPPLY AIR TO MEET MINIMUM VENTILATION RATES ARE AHU-1 &
VOLUME 75 DEG.F.(23.9 DEG.C.). THE VAV DIFFUSER WILL BE SET TO PROVIDE A
DIFFUSER TO VARY THE SUPPLY AIR TO CONTROL THE EACH ROOM TEMPERATURE MAINTAIN
4.3.5 TEMPERATURE COOLING SENSOR LOCATED IN VAV DIFFUSER SHALL CONTROL THE EACH VAV
CONTROLLED BY BUILT-IN HEAD PRESSURE CAPACITY CONTROL PRESSURE SWITCHES.
OPERATING REFRIGERANT CIRCUIT SOLENOID VALVE (SV-1) OF ACCU COMPRESSOR ARE
LOGIC CONTROL PANEL ENERGIZES MECHANICAL COOLING TO SATISFY SPACE DEMAND BY
4.3.4 MECHANICAL COOLING: IF ECONOMIZER CYCLE CANNOT SATISFY THE SPACE DEMAND, AHU
THE ECONOMIZER CYCLE, THE ACCU SHALL BE LOCKED-OUT FROM OPERATION.
CLOSE ECONOMIZER MOTORS WHEN S.A TEMP. DROPS TO 10 DEG.C (50 DEG.F). DURING
DEG.C (75 DEG.F) AS 1ST STAGE COOLING. S.A SENSOR ACTS AS A LOW LIMIT AND
R.A/E.A DAMPERS TO INTRODUCE 100.A TO SATISFY SPACE R.A TEMPERATURE AT 23.9
SET BY O.A CHANGEOVER CONTROLLER, AHU LOGIC CONTROL PANEL SHALL CONTROL O.A/
4.3.3 ECONOMIZER CYCLE: WHEN O.A TEMPERATURE DROPS BELOW 18.3 DEG.C (65 DEG.F) AS
TEMPERATURE AT 23.9 DEG.C (75 DEG.F).
PANEL TO CONTROL AHU DX-COOLING COIL SOLENOID VALVE TO MAINTAIN R.A.
S.A. SENSOR (AS COOLING ANTICIPATOR) SHALL SEND A SIGNAL TO LOGIC CONTROL
4.3.2 AHU ELECTRIC, DUCT MOUNTED TYPE R.A. SENSOR / TEMPERATURE TRANSMITTER WITH
4.3.1 SAME AS PARAGRAPH 4.1.1
4.3 OCCUPIED COOLING MODE:
DIAGRAM (FOR AHU-1 & AHU-2)
AHU/RF & ACCU SCHEMATIC CONTROL
NOT TO SCALE
AHU/RF & ACCU SCHEMATIC CONTROL DIAGRAM (FOR AHU-1 & AHU-2)
XFMR
SW
MPP
TT
LCP
TEMP. CONTROL PANEL
FOR AHU
LOGIC CONTROL PANEL
FOR AHU
TEMP. TRANSMITTER
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15333, APO AP 96205-5333
ENGINEERING DIVISON, DPW, USAG-YONGSAN
HEADQUARTERS, UNITED STATES ARMY GARRISON, YONGSAN
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
KIM, SM
MECHANICAL
10 10 M-9
NTS
A
B
C
D
E
F
C
B
A
E
D
F
JACKET
VAPOR-BARRIER
STAPLE
OVERLAP
ADHESIVE
INSULATION
FASTENER
DUCT
FLEXIBLE TYPE
50mm OVERLAP
CLASS II ADHESIVE UNDER THE
100mm O.C. WITH TYPE II VAPOR-BARRIER COATING
VAPOR-BARRIER JACKET
RIGID TYPE
EXPOSEDCONCEALEDAREA
DUCT IN
ITEM
1 DUCT INSULATION
DUCT LINING
C
B
CC
B
E
B
A
E
LAPPED AND BUTTED CORNER
LINING
(TYPICAL 1,200 OR 1,500)
DUCT SECTION
(FASTENER)
PIN AND WASHER
FOLDED CORNER
ALTERNATE
UP TO 12.7 MPS
12.8 TO 30.5 MPS
VELOCITY
30575 100
DIMENSIONS
A B C
E
NOTE :
ADHESIVE
TO BE COATED WITH
ALL TRANSVERSE EDGES
OR ZEE ATTACHED BY SCREWS, RIVETS OR WELDS.)
LEADING EDGE. (NOSING MAY BE FORMED ON DUCT OR BE CHANNEL
2. WHEN VELOCITY ABOVE 20.3 MPS USE METAL NOSING ON EVERY
APPROXIMATE.
1. MAXIMUM SPACING FOR FASTENERS ACTUAL INTERVALS ARE
R
22 GA
RUNNER TYPE 1
LARGE
SMALL 50
112.5
SINGLE VANE SCHEDULE
R
81.25
SP
MIN
F L
O W
OR
112.5
SP
SP
GA
R=50
SP=40
R
FLAT
SP
RUNNER TYPE 2
DUCT TURNING VANE DETAIL
INLET AREA.
APPROXIMATES ELBOW
DOUBLE WALL VANES
FREE AREA BETWEEN
APPROVAL.
ACCEPTABLE ON DESIGNER
SIZES OR SPACINGS
USED. OTHER VANE
OTHER RUNNERS MAY BE
SEE NOTES ON FIG.2-4
20 TRAILING EDGE
SINGLE VANE WITH
RUNNER TO DUCT
OR WELD
BOLT, SCREW,
THE CENTER VANE.
TIE ROD THROUGH
1,000 FPM) OR RUN A
TO RUNNER (OVER
WELD EVERY 6TH VANE
DUCT IN 150mm WIDTH STRIPS ON 300mm ON CENTER
CLASS II ADHESIVE (LESS THAN 600mm DUCT) AROUND ENTIRE PERIMETER OF THE
80mm FROM DUCT CORNER
450mm O.C. AND NOT MORE THAN
600mm LARGER DUCT BOTTOM/SIDES
THE INSULATION JOINT
NOT MORE THAN 80mm FROM THE EDGES OF
ALL FOUR SIDE OF DUCT 300mm APART AND
OVERLAP
CLASS II ADHESIVE UNDER THE 100mm
JACKET)
COATS (WHEN FIELD APPLY VAPOR-BARRIER
COATING WITH GLASS CLOTH EMBEDDED BETWEEN
APPLYING TWO COATS OF VAPOR-BARRIER
OR LARGER
SECTION OF 0.60 SQ M
DUCT W/CROSS
L65x65x5 HANGER
BRACE (TYP.)
TRAPEZE HANGER
L65x65x5VIBRATION ISOLATOR
M16 BOLT
(ONE SIDE ONLY)
AT EA HANGER
CROSS BRACE
STEEL BEAM
SLAB
CONCRETE
(TYP.)
W/2-M16 BOLT
6mm THK BAR
N O
T E
L65x65x5 HANGER
TRAPEZE HANGER
L65x65x5
ANCHOR(TYP)
W/M16 WEACE
6mm THK PLATE
NOT REQUIRED FOR SHORTER RUNS.
OF DUCT 6000mm LONG OR LONGER, NEAR MIDDLE OF STRAIGHT RUN
BRACE ANGLE NEAR & FAR SIDE
2 SEISMIC DUCT HANGER DETAIL
GROSS-BRACE SCHEDULE
MAX LENGTH
2,500 mm
2,700 mm
3,000 mm
3,200 mm
3,600 mm
BRACE ANGLE
L65 x 65 x 5
L70 x 70 x 6
L75 x 75 x 6
L80 x 80 x 6
L90 x 90 x 6
5 SEISMIC PIPE BRACING
a
W = WEIGHT PER UNIT LENGTH OF PIPE AND WATER, LBS/IN. OR N/MM
I = MOMENT OF INERTIA OF PIPE, IN OR MM
E = MODULUS OF ELASTICITY OF PIPE, PSI OR MPa
L = 0.50 T , IN. OR MM
WITH PERIOD (T ) EQUAL TO 0.05SEC. WHERE
* MAXIMUM UNSUPPORTED OR UNBRACED LENGTHS(L) ARE BASED ON WATER-FILLED PIPES
NOTE :
a
W
EIg
4 4
1 FOOT = 0.3 M
1 INCH = 25 MM
DIMENSION IS 300mm OR LESS.
3. SEISMIC BRACING NOT REQUIRED IF THIS
CONTRACTOR'S OPTION.
HIGH STRENGTH BOLTS MAY BE USED AT
WASHERS. LOCK WASHERS NOT PERMITTED,
2. ALL BOLTS ARE M16, FOR MACHINE BOLTS,
OF BOLTS.
1. MAX BRACE ANGLE LENGTH IS TO CENTERLINE
NOTE :
(MM)
DIA.
3,450
3,300
3,080
2,780
2,550
2,250
1,950
40S
STEEL PIPE
STD. WT.
MAXIMUM SPAN FOR RIGID PIPE DINNED-PINNED
3,525
3,300
3,150
2,850
2,550
2,325
1,950
80S
STEEL PIPE
EX. STRONG
2,700
2,480
1,650
1,480
1,950
1,500
1,725
TYPE K
TUBE
COPPER
3,225
2,480
2,250
2,100
1,950
1,425
1,650
TYPE L
TUBE
COPPER
2,550
2,400
2,250
2,100
1,880
1,350
1,650
TYPE M
TUBE
COPPER
2,550
2,400
2,250
2,100
1,880
1,350
1,650
COPPER PIPE
BRASS & SPS
85 RED
4. CONDUIT 65mm OR LESS NOMINAL DIAMETER.
3. BUILDING PIPING 65mm OR LESS NOMINAL DIAMETER.
2. MECHANICAL ROOM PIPING 32mm OR LESS NOMINAL DIAMETER.
OR TRUSS.
1. PIPING/CONDUIT WITH HANGERS 300mm OR LESS IN LENGTH FROM STRUCTURAL SLAB
NOT APPLICABLE TO :
PIPE
ALL BOLTS M16
CONC SLAB
6x65 STRAP
6x65 STRAP
PIPE OR CONDUIT
INSULATION
ALL BOLTS M16
CONC SLAB
(SEE SCHEDULE)
ANGLE BRACE
BEAM
STEEL
BEAM
STEEL
(SEE SCHEDULE)
ANGLE BRACE
(AT BOTTOM OF HANGER LOCATION)
200 LONGx150 WIDE
METAL JACKET
MECH. DETAILS
195822
A.H.U (2EA), B2110 AT JMMT
REPAIR FAILED/FAILING A.C.C.U (2EA) &
FY19