E02_(R2)Drawings_2_Replace_heating_and_ventilating_system.pdf

PDF 6 MB Posted

Attached to
Replace heating and ventilation system
Solicitation number
W91QVN19R0135
Issued by

About this file

Drawings for solicitaiton W91QVN-19-R-0135

View the file

Other files

File Type Posted
A21_Solicitation.pdf PDF
E02_(R2)Drawing_for_Designated_Space_S-111.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

19-013

1 1

PAE.SE

KWON.128855

Digitally signed by

PAE.SE

KWON.1288557116

Date: 2019.03.13 10:59:37 +09'00'

YI.YONGSOP.12882

68530

Digitally signed by

YI.YONGSOP.1288268530

Date: 2019.03.14 15:17:27 +09'00'

KIM.YONG.HO.1028460836 Digitally signed by KIM.YONG.HO.1028460836 Date: 2019.03.21 15:12:18 +09'00'

PAE.SE

KWON.128855711

Digitally signed by PAE.SE

KWON.1288557116

Date: 2019.02.21 10:57:21 +09'00'

1 11 i ---- - ,_ -----------------------------------------------------------------------------------------7

I A I B I C I D I E I F I G I I

H

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

I

EQUIPMENT

0 HEATING AND VENTILATING UNIT _ _ _ _ _ 4 EA

CEILING MOUNTED, SINGLE ZONE, HORIZONTAL DISCHARGE, SELF

CONTAINED WITH HOT WATER HEATING COIL , DAMPERS WITH

MIXING BOX, CENTRIFUGAL FAN, FAN MOTOR, REMOVABLE AND

CLEANABLE FILTERS, COMPLETELY ENCASED IN A STEEL HOUSING.

HEATING CAPACITY

SUPPLY AIR CAPACITY

BLOWER MOTOR

6 7,800 BTU/ HR

AT 37.7 °F E.A.T AND 66 .5 °F L.A.T

1 , 990 CFM AT 3/4" S.P

1/2 HP, 208 V, 1 PH, 60 Hz

REFERED TO " CARRIER CO " MODEL 39SH OR APPROVED EQUAL.

© HEATING AND VENTILATING UNIT ----- 1 EA

SAME AS ABOVE, EXCEPT,

HEATING CAPACITY

SUPPLY AIR CAPACITY

56 ,41 7 BTU/ HR

AT 37.7 °F E.A. T AND 66 .8 °F L.A. T

1,680 CFM AT1"S.P

BLOWER MOTOR 3/4 HP, 208 V, 1 PH, 60 Hz

REFERED TO " CARRIER CO " MODEL 39SH OR APPROVED EQUAL.

© HEATING AND VENTILATING UNIT _ _ _ _ _ 1 EA

SAME AS ABOVE, EXCEPT,

HEATING CAPACITY

SUPPLY AIR CAPACITY

BLOWER MOTOR

65 , 912 BTU/ HR

AT 37. 7 °F E. A.T AND 62 .2 °F L.A. T

2 ,400 CFM AT 1" S.P

1/2 HP, 208 V, 1 PH, 60 Hz

REFERED TO " CARRIER CO " MODEL 39SH OR APPROVED EQUAL.

0 HEATING AND VENTILATING UNIT

SAME AS ABOVE, EXCEPT,

----- 1 EA

HEATING CAPACITY

SUPPLY AIR CAPACITY

BLOWER MOTOR

160 ,000 BTU/ HR

AT 48 °F E.A.T AND 85 °F L.A.T

4 ,000 CFM AT 2" S.P

2 HP, 208 V, 3 PH, 60 Hz

REFERED TO " CARRIER CO " MODEL 39SH OR APPROVED EQUAL.

rs'J HOT WATER BOILER ------- 1 EA

VERTICAL STEEL FIRE TUBE BOILER - BURNER UNITS, DUAL TYPE (OIL &

GAS WITH TRAIN), ROU ND JACKET FINISH W/ CADCELL PRIMARY CONTROi

AQUASTAT RELAY, HERAL TIMETER, LOW VOLTAGE ROOM THERMOSTAT,

ASME RELIEF VALVE, LOW WATER CUT - OFF, DRAFT CONTROL

NECESSARY TAPPINGS.

HEATING CAPACITY 840 ,000 BTUH(GROSS OUTPUT)

FIRING RATE 7.5 GPH

BURNER MOTOR 1 / 3 HP, 115 V, 1 PH, 60 Hz

3 1--___;__:R=EF:....:E::.:R..::E=:D::....T.:..cO:::..._" :....:A::;LD:;.;R..::l=C:....:H _"....;M.;.;.O;:;.;D;:;.;E::;L:;.;A...;;.V:....:R..c..-..c.S=E:....:R;.;;;;IE"'S---'O:....:R..;..;A_P_P_R _O_V _E _D _E_Q--'-U_A_L _.

© HOT WATER HEATING CIRCULATING PUMP ---- 1 EA

FLOOR MOUNTED, CENTRIFUGAL FRAME MOUNTED, END SUCTION

SINGLE STAGE PUMP, PUMP VOLUTE OR CASING SHALL BE CENTER -

LINE DISCHARGE WITH MECHANICAL SEALED AND STANDARD

ACCESSORIES.

CAPACITY

MOTOR POWER

PIPE CONN

84 GPM @ 40 FT TDH

2 HP, 208 V, 3 PH, 60 HZ@ 1 760 RPM

SUCTION 2 -1/2" FLANGED

DISCHARGE 1 -1/2" FLANGE

REFERED TO" BELL & GOSSETT" MODEL 1510 SERIES OR APPROVED EQUAL

0 EXPANSION TANK -------- 1 EA

FLOOR MOUNTED, FABRICATED STEEL DESIGNED AND CONSTRUCTED

PER ASME COME PRESSURE VESSEL CODE MAXIMUM 125 PSI DESIGN

PRESSURE EQU IPPED WITH HEAVY DUTY BUTYL RU BBER DIAPHRAGM,

EXPANSION TANK LIMITED ACCEPTANCE TANK AND NECESSARY PIPE

TAPPINGS.

TANK CAPACITY

TANK SIZE

55 .7 GALLONS

16 -1/4" DIAx6 9" H

REFERED TO" TACO" MODEL CA SERIES OR APPROVED EQUAL.

©AIR SEPARATOR ------- 1 EA

PIPE MOUNTED, ASME CODE AND STAMPED FOR 125 PSI @ 350 F,

THREADED CONNECTION CONSIST OF STAINLESS STEEL AIR

COLLECTOR TUBE, GALVANIZED STEEL STRAINER, SLOWDOWN

AND COLD WATER CONNECTION.

WATER FLOW RATE

PIPE CONN.

84 GPM

2 -1/ 2" 0

REFERED TO" TACO" MODEL AC SERIES OR APPROVED EQUAL.

I

S CHEDULE

© 3-WAY MIXING VALVE ------- 4 EA

SPRING RETURN, 21 7 PSI MAX. PRESS. 250°F MAX. TEMP.

MAX. FLOW RATE : 3.3 CV

VALVE SIZE 15 mm DIA.

MOTOR POWER : 23 W, 120 V, 1 PH, 60 Hz

@ 3-WAY MIXING VALVE

SAME AS ABOVE, EXCEPT,

------- 1 EA

MAX. FLOW RATE : 2 .7 CV

VALVE SIZE 15 mm DIA.

MOTOR POWER : 23 W, 120 V, 1 PH, 60 Hz e 3-WAY MIXING VALVE

SAME AS ABOVE, EXCEPT,

MAX. FLOW RATE : 3.2 CV

------- 1 EA

VALVE SIZE 15 mm DIA.

MOTOR POWER : 23 W, 120 V, 1 PH, 60 Hz

® 3-WAY MIXING VALVE

SAME AS ABOVE, EXCEPT,

------- 1 EA

MAX. FLOW RATE : 7.8 CV

VALVE SIZE 25 mm DIA.

MOTOR POWER : 23 W, 120 V, 1 PH, 60 Hz

® 3-WAY MIXING VALVE

SAME AS ABOVE, EXCEPT,

MAX. FLOW RATE : 40 .7 CV

------- 1 EA

VALVE SIZE 50 mm DIA.

MOTOR POWER : 23 W, 120 V, 1 PH, 60 Hz

RADIATOR

1 -1 / 4 " 0' STEEL TUBE WITH 32 FINS 4 -1 / 4 "X 4 - 1 / 4" AND

SLOPING TOP ENCLOSURE WITH NON - ELECTRIC THERMOSTATIC

CONTROL VALVE, 2 EA GATE VALVES, HANGERS, BRACKETS

AND ACCESSORIES

1 70 °F AVERAGE TEMP.

ITEM Q'TY ROV LENGTH HEATING CAPACITY CONNECTION

NO. BTUH mm

0� 2 2 5'- O" 6 ,300 15 X 15

Gil 3 2 2'- 6 11 3,150 15 X 15

66) 2 2 4'-0 11 5 ,040 15 X 15

I I I I I

SCOPE OF WORK

REPAIR/ MAINTENANCE (K)

1 . REPLACE EXISTING HEATING SYSTEM WITH NEW.

2 . REMOVE AND RECONNECT EXISTING FUEL OIL SYSTEM.

3. REPLACE EXISTING CONTROL SYSTEM WITH NEW.

4 . REMOVE & REINSTALL EXISTING LONWORKS COMMUNICATION

DEVICE FROM EXISTING SYSTEM FOR S-111 AND PERFORM

OPERATION TEST, AND HAVE JCI (JOHNSON CONTROLS

INC.) OR CERTIFIED TECHNICIAN VERIFY IT.

5 . REPLACE EXISTING DOMESTIC WATER PIPE AND HEATING

WATER PIPE ASBESTOS INSULATION IN MECHANICAL

ROOM WITH NEW NON ASBESTOS INSU LATION.

(APPROX. 40mm DIA-50m )

NOT ES:

1 . THE CONTRACTOR SHALL PROTECT FLOOR CARPET,

DESK TOP MONITORS, WALL SOUND ABSORPTION PANELS

AND LARGE PROJECTOR SCREEN etc. DURING THE

CONSTRUCTION PERIOD .

2 . THE ASBESTOS MATERIAL SHALL BE REGULATED ASBESTOS

CONTAINING MATERIAL (RACM) AND REMOVE IN ACCORDANCE

WITH USAG - HUMPHREYS ASBESTOS MANAGEMENT PROGRAM

AND O & MA. STANDARD SPECIFICATION SECTION 02 82 14 .00 10

ASBESTOS HAZARD CONTROL ACTIVITIES.

SYMBOL ZONE DESCRIPTION DATE BY CHK. APVD.

R E V I S I O N S

DEPARTMENT OF THE ARMY

US ARMY INSTALLATION MANAGEMENT COMMAND

HEADQUARTERS, UNITED STATES ARMY GARRISON HUMPHREYS

UNIT# 15228, APO AP 96271-5228

DESIGNED BY

I

REVIEWED BY

REVIEWED BY

PAE, S K SKY/PYI

REPLACE HEATING & VENTILATING

SYSTEM BLDG. S-111

O&M DIV. SUBMITTED BY

SECURITY DIV. CA/Cl BR.

FIRE SERV. DIV. DESIGN BR.

SAFETY OFC. CHIEF, ENGR. DIV.

MASTER PLAN DIV. USING AGENCY

I

USAG HUMPHREYS

MECHANICAL

EQUIPMENT SCHEDULE

AND SCOPE OF WORK

PROJECT NO. DRAWING NO.

VS-70110

SCALE:

AS SHOWN SHEET OF

REF NO.

M-1

1289988820.LN

Typewritten Text 19-013

1289988820.LN

Typewritten Text 2 11

3 11

PAE.SE

KWON.1288557116

Digitally signed by PAE.SE

KWON.1288557116

Date: 2019.03.13 11:01:00 +09'00'

4 11

PAE.SE

KWON.1288557116

Digitally signed by PAE.SE

Date: 2019.03.13 11:01:26 +09'00'

PAE.SE

Digitally signed by PAE.SE

KWON.1288557116

Date: 2019.02.21 10:59:22 +09'00'

5 11

6 11

PAE.SE

KWON.1288557116

Digitally signed by PAE.SE

KWON.1288557116

Date: 2019.03.13 11:01:56 +09'00'

7 11

PAE.SE

KWON.1288557

Digitally signed by PAE.SE

KWON.1288557116

Date: 2019.03.13 11:02:24

1289988820.LN

19-13

1289988820.LN

8 11

9 11

PAE.SE

KWON.1288557

Digitally signed by PAE.SE

KWON.1288557116

Date: 2019.03.13 11:03:28

10 11

PAE.SE

KWON.1288557116

Digitally signed by PAE.SE

Date: 2019.03.13 11:04:05 +09'00'

11 11

PAE.SE

KWON.12885571

Digitally signed by PAE.SE

KWON.1288557116

Date: 2019.03.13 11:04:43