LEGEND AND ABBREVIATIONS
NAM, TAE CHIN
SCH
SA
SAN
QTY
R12, R22
RA
RDTR
RPM
RT
PG
PH
POC
POL
PPM
PRV
QT
OA
OAIL
OD
OS&Y
Pa
NTS
BUTTERFLY
CUBIC METER PER HOUR
AIR CONDITION (-ING,-ED)
AIR CONDITION UNIT (S)
AIR COOLED CONDENSING UNIT
CHILLED/HOT WATER RETURN
CHILLED/HOT WATER SUPPLY
REFRIGERANT LIQUID
CAP CAPACITY
CUBIC METER
COMPRESSOR
CONTINUE
CONNECTION
CPRSR
CU M
CONT
CONN
COUNTER CLOCKWISE
COEFFICIENT
CIRCUIT
CAST IRON PIPE
CHILLED WATER
CKT
CMH
COEF
CHW
CCW
CIP
ALARM CHECK VALVEACV
AVG AVERAGE
BAROMETER(-TRIC)
CENTIGRADEC
BARO
AMPERE(AMP, AMPS)
ALUMINUM
APPROX
AMP
AIR COND
AHU
AL
AIR COOLED
ACU
ACLD
ACCU
CHWS
CHWR
CHR
CHS
D
RL
DRAIN
KILOCALORIE PER HOUR
KILOGRAM PER SQ. CENTIMETER
KILOGRAM
THERMAL CONDUCTIVITY
IRON PIPE SIZE
ISOMETRIC
DIAMETER, INSIDE
FACE AREA OR FRESH AIR
EXTERNAL STATIC PRESSURE
EVAPORAT (-E,-ING,-ED,-OR)
ENTERING WATER TEMP
FIRE HOSE CABINET
EXPLOSION PROOF
FHC
FA
ESP
EVAP
EWT
EFF
ENT
EQPT
EP
EFFICIENCY
ENTERING
EQUIPMENT
KG
K
IPS
ISO
ID
NIC
N.O.
NO
MPS
N.C.
N/A
MM
MPH
MIN
MAX
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NORMALLY CLOSED
METERS PER SECOND
METERS PER HOUR
MINIMUM OR MINUTE
NOT APPLICABLE
MILLIMETER
MAXIMUM
HERTZ
HOSE BIBB
HEAD
HORSEPOWER
HOUR(S)
HOT WATER
HOT WATER HEATER
HORIZONTAL
FIBERGLASS REINFORCED PLASTIC
FREQUENCY
FLUSH VALVE
FEED WATER PUMP
FIXTURE
GAGE OR GAUGE
GALVANIZED STEEL
FUEL OIL
FEMALE PIPE THREAD
CIRCULATING WATER PUMPCWP
FRP
DECIBEL OR DRY BULB
DRY BULB TEMPERATURE
ENTERING AIR TEMPERATURE
DRY PIPE VALVE
DIRECT EXPANSION
DO DIESEL OIL
EAT
DPV
DX
DIV
DIAG
DIFF
DB
DBT
DIVISION
DIAMETER
DIAGRAM
DIFFERENCE
DEGREE
HR
HZ
HW
HWH
HORIZ
HB
HD
HP
GA
GALVS
FV
FWP
FXTR
CLOCKWISE OR COLD WATERCW
PLUG VALVE
THREE WAY
FREQ
FO
FPT
GATE, GLOBE
GATE, ANGLE
GLOBE
CONTROL
GATE
M
LPS
LWT
LT
LPH
LPD
LL
LG
LBS
LAT
LAV
L
KWH
KW
LITERS PER SECOND
LITERS PER HOUR
LEAVING WATER TEMPERATURE
METERS
LAUNDRY TRAY
LITERS PER DAY
LIQUID LINE
LEAVING AIR TEMPERATURE
POUNDS
LAVATORY
LENGTH
KILOWATT HOUR
KILOWATT
LITERS
P
STRAINER, BLOW OFF
STRAINER
PUMP (INDICATE USE)
KG/ SM KILOGRAM PER SQ. METER
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
PIPE TO BE REMOVED
MEDIUM TEMPERATURE HOT WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
RS
RD
(NAME)
(NAME)E EXISTING PIPE
HWR
HWS
MTWR
MTWS
CR
CS
PIPING
SANITARY DRAIN
CHECK, SWING
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
PLAN
HOSE BIBB
BALL
ELEV.
PIPE SLEEVE
BACKFLOW PREVENTER
FLOOR DRAIN
FLOOR CLEANOUT
FD
FCO
FLEXIBLE CONNECTOR
ANCHOR, INTERMEDIATE
ANCHOR, MAIN
EXPANSION JOINT
EXPANSION LOOP
EJ
RELIEF
SAFETY
HOSE END DRAIN
LOCK SHIELD
NEEDLE
PRESSURE REDUCING
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
CHECK, NON-SLAM
S
R
EP
PE
COLD WATER
VENT
AD FD
QUANTITY
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
SCHEDULE
SUPPLY AIR
SANITARY
REFRIGERANT (12, 22, ETC)
RETURN AIR
REVOLUTIONS PER MINUTE
REFRIGERATION TON
RADIATOR
TYP TYPICAL
UNIT HEATER
URINAL
UH
UR
SYMBOL
TEMPERATURE
THICKNESS
TONS
THK
TEMP
SYM
TD
OUTSIDE AIR INTAKE LOUVER
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PETROLEUM, OIL AND LUBRICANTS
POINT OF CONNECTION
PARTS PER MILLION
PERCENT/
QUART
PRESSURE GAGE
DIAMETER, OUTSIDE
OUTSIDE SCREW & YOKE
PASCAL
POLE
SPR SPRINKLER
STAINLESS STEEL
SQUARE
STEAM
STANDARD
STEEL
ST
STD
STL
SQ
SST
SPECIFICATION
SQUARE METER
STATIC PRESSURE
SPEC
SP
SM
OUTSIDE AIR
NOT TO SCALE
SECONDSEC
VAV VARIABLE AIR VOLUME
WATER CLOSET
VENTILATION
W/
WT
WC
WD
WITH
WEIGHT
WIDTH
W
WB
VOL
VEL
VENT
VERT
WATT
WET BULB
VOLUME
VELOCITY
VERTICAL
SMOKE DAMPER (PROVIDE ACCESS DOOR)
MANUAL VOLUME DAMPER
VAC
V
VACUUM
VOLT
SPLITTER DAMPER
AD
SD
VD
TEE, SINGLE SWEEP
TEE, OUTLET DOWN
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
ELBOW, TURNED DOWN
UNION, FLANGED
UNION, SCREWED
TEE, OUTLET UP
TEE
LATERAL
ELBOW, TURNED UP
CONNECTION, TOP
CONNECTION, BOTTOM
BUSHING
CAP
FIRE DAMPER (PROVIDE ACCESS DOOR)
BDD
TURNING VANES
TRANSITION
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FC
DUCT WORK
A B B R E V I A T I O N S
L E G E N D
PG
TM
AAV
FOS
3-WAY VALVE (MOTORIZED)
PRESSURE GAUGE
THERMOMETER
AUTOMATIC AIR VENT
GATE VALVE
CHECK VALVE
FUEL OIL SUPPLY
FLEXIBLE JOINTFJ
& STRAINER
M
CS
SD
SHOWER DRAIN
DEG
DIA or o
CEAT CONDENSER ENTERING AIR TEMP
LCWT LEAVING CHILLED WATER TEMP
FAIL FRESH AIR INTAKE LOUVER
EXPANSION JOINTEXPJT
EXST EXISTING
A / C AIR CONDITIONING
APPROXIMATELY
ARCH ARCHITECTURAL
BLDG BUILDING
CONC CONCRETE
DWG DRAWING
EA EACH
F.C.U. FAN COIL UNIT
MECH MECHANICAL
KCAL/ HR
KG/ SQ CM
HOT WATER SUPPLY
HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
V
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
AAV
ED EXHAUST DUCT
AUTOMATIC AIR VENT
AIR HANDLING UNIT
GROUND LEVELGL
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
SUPPLY AIR GRILLE OR
(200mm NECK DIAMETER)
CEILING DIFFUSER, ROUND TYPE
REGISTER, CEILING
EXHAUST AIR GRILLE OR
GRILLES, REGISTERS AND DIFFUSERS
SQUARE TYPE
CEILING DIFFUSER,
EG
ER
SG
SR
SG
SR
RG
RR
CD
200mm NCD
COWL, (GOOSENECK) AND FLASHING
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN810mm x 400mm
M
ELECTRIC MOTOR OPERATED DAMPER
S
MOTORIZED DAMPER
MD
SUPPLY AIR DUCT RISER
RETURN OR EXHAUST AIR DUCT RISER
SUPPLY AIR DUCT SECTION
RETURN AIR DUCT SECTION
GATE, GLOBE OR BALL VALVE
CHECK VALVE (FLOW)
ANGLE VALVE
STRAINER
DRIP CHECK VALVE
RESTRICTED ORIFICE
FILL CUP
PRESSURE GAUGE
SOLENOID VALVE
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLEXIBLE PIPE CONNECTION
RELAY
HOSE VALVE
TEST HEADER
SMOKE DAMPER
R
SD
S
: WATER MOTER ALARM GONG
SPRINKLER SYSTEM
: UP-RIGHT TYPE SPRINKLER
: PENDENT TYPE SPRINKLER
: SIDE WALL TYPE SPRINKLER
REMOVAL WORK
RELOCATED WORK
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
SA
RA
EA
DEMPERS
VALVES, SPECIAL DUTY
HEATING
AIR CONDITIONING & REFRIGERATION
PLUMBING
VALVES : (for selective actuators)
BACK DRAFT DAMPER
CIRCUIT SETTER
POINT OF CONNECTIONPOC
POR POINT OF REMOVAL
TcH THERMOSTAT HEATING/COOLING
THERMOSTAT OF HEATING
REGISTER, CEILING
RETURN AIR GRILLE OR
Th
REDUCER, CONCENTRIC
12 JUN 17
YI, TONG KI CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
32 73
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-1
D - 17 - 11
G
D E S C R I P T I O N
E Q U I P M E N T S C H E D U L E
Q’ TY
NO.
ITEM
Q’ TY
NO.
ITEM
D E S C R I P T I O N Q’ TY
NO.
ITEM
D E S C R I P T I O N
1 1
2 1
HOT WATER HEATING BOILER
DOMESTIC HOT WATER HEATER
2 EXPANSION TANK
PIPE TAPPING.
PRESSURE, EQUIPPED W/ HEAVY DUTY REMOVABLE BLADDER AND NECESSARY
AND PRESSURE VESSEL CODE (ASME BPVC SEC VIII D1), MAX. 125 PSI WORKING
CLOSED ROUND DIAPHRAGM TYPE, SHELL CONFORMING TO ASME CODE
TANK SIZE: 12" DIA x 57" LG
TANK CAPACITY: 19 GALLONS (ACCEPTANCE VOLUME)
AIR SEPARATOR2
GALVANIZED STEEL STRAINER, BLOWDOWN AND COLD WATER CONNECTION.
CONNECTION CONSIST OF STAINLESS STEEL AIR COLLECTOR TUBE,
PIPE MOUNTED, ASME CODE AND STAMPED FOR 125 PSI @ 350 F, THREADED
FAN COIL UNIT (FOR 2 PIPE SYSTEM)
8.1 8.3
(CFM)
AIR CAP
COOLING CAP (MBH)
3005.9 110W
SENSIBLE TOTAL
(GPM)
FLOW RATE
REMARK
11 1.5
8.8 11.6 2.4 135W
13.4 18.7 3.0 600
200W8004.020.814.4
275W10004.830.231.721.1
190W
INPUT
POWER
ELECTRIC DATA : 115V, 1PH, 60HZ
110 BACKFLOW PREVENTER & PRESSURE REDUCING STATION
CONFORM TO PL 93-523 AND NSF/ANSI 61
STEEL COVER BOLTS, AIR GAP, ASSE APPROVED, AWWA STANDARD
SILICONE RUBBER DISK, REPLACEABLE POLYMER CHECK SEATS, STAINLESS
REDUCE PRESSURE ZONE BACKFLOW ASSEMBLY, LEAD FREE BRONZE BODY,
SIZE: 2 1/2 (65 mm)
MAX. WORKING PRESSURE: 175 PSI (12.1 BAR)
TEMP. RANGE: 33 F~180 F (0.5 C ~ 82 C)
COOLING :
TEMP. RISE
EWT 45 F AT 10 F
DB 80 F, WB 67 F,
21 12
(MBH)
MIN.
HEATING
20.8
(KW)
OUTPUT
GROSS
111.6
(LPH)
RECOVERY
HEAT
ELEC. POWER
FLA: 2, 120 V, 1 PH, 60 HZ
TEMP.
SUPPLY
RISE
TEMP.
60 C 16.7 C
(KW)
OUTPUT
GROSS
ELEC. POWER
TEMP.
SUPPLY
80 C
(CMH)
INPUT
GAS
PRESS
WORKING
ROOF EXHAUST VENTILATOR
12 JUN 17
MOTOR POWER: 28 W, 115 V, 1 PH, 60 HZ
VALVE SIZE: 2 1/2"
CAPACITY: 63 CV
TEMPERATURE RANGE.
MOTOR, SPRING RETURN, 250 PSI MAX. PRESSURE, 36 TO 337 F WATER
THREE-WAY THREADED GLOBE MIXING VALVE, LINKAGE & PROPORTIONAL
PIPE SIZE: 2 1/2" DIA
BODY SIZE: 6.3" DIA x 19"H
WATER FLOW RATE: MAX. 90 GPM
MOTOR: 1 HP, 115 V, 1 PH, 60 HZ, 1,760 RPM
CAPACITY: 46 GPM AT 32 FT TDH
EQUAL.
SIMILAR TO "KYUNGDONG NAVIEN" MODEL NO. NHB-150 x 3EA OR APPROVED
121.5 10.8 FLA: 13.5, 120 V, 1 PH, 60 HZ 206.84 KPA
EQUAL.
SIMILAR TO "KYUNGDONG NAVIEN" MODEL NO. NPE-240S x 2EA OR APPROVED
MOTOR: 1/4 HP, 115 V, 1 PH, 60 HZ, 1,750 RPM
CAPACITY: 8 GPM AT 18 FT TDH
MOTOR: 1/8 HP, 115 V, 1 PH, 60 HZ, 1,750 RPM
CAPACITY: 6 GPM AT 10 FT TDH
DOMESTIC HOT WATER STORAGE TANK
HEAT LOSS SHALL CONFORM TO ASHRAE 90.1 - SI
AND COMBINATION TEMP. & PRSSURE RELIEF VALVE W/ STEEL TANK SUPPORT.
TAPPINGS, ASME SPECIFICATION INSPECTION OPENING, SADDLES, THERMOMETER
PRESSURE (AWWA D100), 150 PSI, TANK SHALL BE COMPLETED WITH REQUIRED
GLASS LINED, MANUFACTURED CONFORMING TO ASME CODE, MAX. WORKING
VERTICAL ROUND TYPE, WELDED STEEL CONSTRUCTION, CEMENT LINED OR
TANK SIZE: 36" DIA x 71" LG
TANK CAPACITY: 300 GALLONS
HOT WATER CIRCULATING PUMP
ACCESSORIES.
ALIGNING FLEXIBLE COUPLING BY AN OIL LUBRICATED MOTOR AND STANDARD
MAGNETIC MOTOR STARTER, THERMAL OVERLOAD PROTECTORS, SELF
IN-LINE TYPE BOOSTER PUMP W/ DIRECT DRIVEN THRU A SPRING-LOADED,
ACROSS-THE-LINE MAGNETIC CONTROLLER IN A NEMA 250 AND NEMA MG 1.
ALL BRONZE CONSTRUCTION. MOTORS SHALL BE EQUIPPED WITH AN
IN-LINE CLOSED COUPLED CENTRIFUGAL TYPE, FLANGE CONNECTION AND
ACROSS-THE-LINE MAGNETIC CONTROLLER IN A NEMA 250 AND NEMA MG 1.
ALL BRONZE CONSTRUCTION. MOTORS SHALL BE EQUIPPED WITH AN
IN-LINE CLOSED COUPLED CENTRIFUGAL TYPE, FLANGE CONNECTION AND
3-WAY MIXING VALVE
PIPE TAPPING.
PRESSURE, EQUIPPED W/ HEAVY DUTY REMOVABLE BLADDER AND NECESSARY
AND PRESSURE VESSEL CODE (ASME BPVC SEC VIII D1), MAX. 125 PSI WORKING
CLOSED ROUND DIAPHRAGM TYPE, SHELL CONFORMING TO ASME CODE
ELECTRIC UNIT HEATER
BRACKET AND STANDARD ACCESSORIES.
DISCONNECT SWITCH, UNIT MOUNTED THERMOSTAT, WALL MOUNTING
MOTOR, THERMAL OVERLOAD PROTECTION, WALL MOUNTED
AND OUTLET DIFFUSER, CONSIST OF HEATING ELEMENTS, FAN AND
HORIZONTAL DISCHARGE, TOTALLY ENCLOSED, INLET LOUVER, VENTURI
ACCESSORIES.
BODY COMPLETED WITH BACK DRAFT DAMPER, BIRD SCREEN AND STANDARD
ROOF CURB MOUNTED, GRAVITY TYPE RELIEF VENT, WEATHER PROOF, ALUMINUM
CAPACITY SIZE
600 CFM AT 1/4" S.P 12" x 12"
400 CFM AT 1/4" S.P 12" x 12"
WALL EXHAUST FAN
FAN MOTOR: 1/6 HP, 115 V, 1 PH, 60 HZ
CAPACITY: 660 CFM AT 1/8" SP
CEILING EXHAUST FAN
DRAFT DAMPER.
MOTOR MOUNTED WITH RESILIENT ANTI-VIBRATION MOUNTS, AUTOMATIC BACK
TYPE BLOWER WHEEL, PERMANENTLY LUBRICATED AND THERMALLY PROTECTED
HOUSING W/ ACOUSTIC INSULATION, DYNAMICALLY BALANCED CENTRIFUGAL
CEILING MOUNTED, VERTICAL DISCHARGE, METAL GRILLE, GALVANIZED STEEL
RANGE HOOD
FAN MOTOR: 80 W, 115 V, 1 PH, 60 HZ
CAPACITY: 100 CFM AT 3/8" SP
DUCTED INSTALLATION AND PROVIDED WITH WALL CAP.
ANTI-BACKDRAFT DAMPER, FAN AND LIGHT. UNIT SHALL BE SUITABLE FOR
INTEGRAL CORROSION RESISTANT ALL METALLIC FILTER, CONTROL PANEL,
UL-LISTED STANDARD MANUFACTURED RESIDENTIAL KITCHEN HOOD WITH
MOTOR POWER: 2.0 AMP, 115 V, 60 HZ, 1 PH
HOOD SIZE: 30"(W) x 6"(H) x 17"(D)
AIR CAPACITY: 160 CFM AT 0.67" SP
DOMESTIC HOT WATER RE-CIRCULATING PUMP
DOMESTIC HOT WATER CIRCULATING PUMP
ACCESSORIES. CONFORMANCE TO AHRI.
GRILLE, LEVEL LEGS, DIELECTRIC UNION, INSECT SCREEN AND STANDARD
MANUAL FRESH AIR DAMPER, FRESH AIR WALL BOX & INCLUDES LOUVER AND
PERMANENT SPLIT CAPACITOR MOTOR AND CENTRIFUGAL FAN, CLEANABLE FILTER,
TOP STEEL CABINET, 3-SPEED FAN SWITCH W/ OVERLOAD PROTECTION
UNIT, 3WAY VALVE, BALL VALVES, AUTO AIR VENT, BAKED ENAMEL FINISH FLAT
FLOOR MOUNTED, VERTICAL AIR DISCHARGE, COMBINATION COOLING/ HEATING
APPROVED EQUAL
SIMILAR TO "CARRIER AIR CONDITIONER" MODEL NO. 40MFC012- - -3 OR
SPLIT TYPE A/C UNIT
BACK DRAFT DAMPER AND EXHAUST GRILLE.
ALUMINUM HOUSING EQUIPPED WITH DISCONNECT SWITCH, BIRD SCREEN,
WALL MOUNTED, DIRECT DRIVEN CENTRIFUGAL FAN, WEATHERPROOF,
ELECTRICAL DATA: 10 A, 208 V, 1 PH, 60 HZ
940 / 935 (OUTDOOR)
MOTOR RPM / CFM: 1200 / 232 (INDOOR)
COOLING CAPACITY: 12,000 BTU/H
YI, TONG KI
FAN MOTOR: 1/100 HP, 208 V, 1 PH, 60 HZ
FAN CAPACITY: 350 CFM, 1,600 RPM
HEATING COIL: 3 KW
HEATING CAPACITY: 7,500 BTU/H
CAMP CARROLL
HS-00658-5J
PRODUCT.
REDUCER, WATER SOFTENER AND STANDARD ACCESSORIES, ASME CERTIFIED
CASCADE SYSTEM, MODULE TYPE CONDENSING WATER BOILER WITH SCALE
PRODUCT.
REDUCER, WATER SOFTENER AND STANDARD ACCESSORIES, ASME CERTIFIED
CASCADE SYSTEM, MODULE TYPE CONDENSING WATER HEATER WITH SCALE
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
33 73
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
EQUIPMENT SCHEDULE
M-2
D - 17 - 11
NAM, TAE CHIN
G
GENERAL NOTES
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR AREA.
4. ALL WALL / FLOOR / ROOF OPENINGS RESULTING FROM THE REMOVAL OF PIPING AND
AS DIRECTED BY THE CONTRACTING OFFICER.
EXISTING AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS
5. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO
CEILING, ROOF, EQUIPMENT, PIPE, DUCT AND ELECTRICAL ITEMS.
PREVENTION SYSTEM WITH NO ADDITIONAL COST TO THE GOVERNMENT SUCH AS WALLS,
ITEMS TO MAKE WAY FOR THE INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE
18. THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND REINSTALL THE OBSTRUCTED
SPECIFICATIONS.
CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE CONTRACT
OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH MAY DEVIATE FROM THAT SHOWN ON
SYSTEM TO SATISFY ALL FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS
17. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL
9. ANY PIPES THAT PENETRATE FIRE RATED WALLS (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
TO ENSURE PROPER OPERATION, AS ORIGINALLY INTENDED.
EQUIPMENT. THE CONTRACTOR SHALL TEST, ADJUST AND BALANCE EQUIPMENT AS REQUIRED
14. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY START-UP AND TESTING OF THE NEW
AND SHALL BE VERIFIED AT THE JOB SITE.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC, ARE APPROXIMATE
PRIOR TO COMMENCING CONSTRUCTION FOR APPROVAL.
ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR
3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY TO THE
CONTRACTING OFFICER’S APPROVAL.
REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER’S
PRIOR TO COMMENCING ANY CONSTRUCTION OR REPAIR.
EQUIPMENT, DUCTWORK, PIPING, DIMENSIONS AND ETC. UNDER THE SUPERVISION OF C.O.R
1. THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION,
A SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
10. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWING.
THE REQUIREMENTS OF SEAL CLASS C.
TO SMACNA STATIC PRESSURE CONSTRUCTION CLASS 500PA AND DUCTWORK SHALL MEET
7. THE SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING
START OF CONSTRUCTION.
PLAN SHALL BE SUBMITTED TO AND APPROVED BY DPW AND THE USER, PRIOR TO THE
USER TO FULLY UTILIZE THE FACILITY DURING THE CONSTRUCTION PERIOD. THIS PHASING
SHALL PROVIDE A PHASING PLAN FOR CONSTRUCTION COMPLETION ALLOWING FOR THE
FACILITY BE FULLY OPERATIONAL DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR
19. DUE TO THE CRITICAL NATURE OF THE FACILITY FUNCTION, IF IT IS REQUIRED THAT THE
CONTRACTOR.
THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY THIS
THE EXISTING EQUIPMENT, NEW EQUIPMENT, DUCT WORK, PIPING AND ETC. DAMAGES DUE TO
11. CONNECTIONS TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE
NEEDED LOCATIONS.
13. ENSURE TO INSTALL LABELED ACCESS DOORS FOR ALL THE TEST AND MAINTENANCE
THE BUILDING AS SHOWN ON THE DRAWINGS.
5. AUTOMATIC WET PIPE SPRINKLER PROTECTION SYSTEM SHALL BE PROVIDED THROUGHOUT
ARE NEW AND ARE TO BE PROVIDED BY THE CONTRACTOR.
6. UNLESS OTHERWISE NOTED AS EXISTING, THE ITEMS SHOWN ON THE DRAWINGS
FOR APPROVAL.
DESIGN & TECHNICAL REVIEW BRANCH VIA C.O.R. PRIOR TO COMMENCING CONSTRUCTION
12. THE CONTRACTOR SHALL SUBMIT MANUFACTURER’S INSTALLATION SHOP DRAWINGS TO THE
REQUIREMENTS AND SUBMIT FOR APPROVAL PRIOR TO INSTALLATION.
A COMPLETE FIRE SPRINKLER SHOP DRAWINGS BASED ON NFPA 13 AND SPECIFICATION
MEANS CONCEPTUAL REQUIREMENT ONLY. THE SPRINKLER CONTRACTOR SHALL SUBMIT
2. THE FIRE SPRINKLER SYSTEM SHOWN THESE DRAWING IS PERFORMANCE BASED WHICH
SPRINKLERS WITH O-RINGS ARE NOT PERMITTED.
SEISMIC BRACING CALCULATION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS:
10. PROVIDE EARTH QUAKE PROTECTION (SWAY BRACING), END OF BRANCH LINE AND
14. FIRE PROTECTION PLANS SHOWN ARE USED FOR COST ESTIMATE PURPOSE ONLY.
SMOKE DETECTORS AND ALL OTHER TRADES.
11. FINAL SPRINKLER HEADS LOCATIONS SHALL BE COORDINATE WITH CEILING FANS,
FIRE PREVENTION OFFICE PRIOR TO IMPLEMENTATION.
PLAN, THE CHANGE SHALL BE APPROVED TO DESIGN & TECHNICAL REVIEW BRANCH AND
15. IF FIELD CONDITIONS NECESSITATE SIGNIFICANT CHANGE FROM APPROVED
VERIFICATION.
FAILURE TO DO THIS WILL REQUIRE THE CONTRACTOR TO RE-EXPOSE THE PIPING FOR
PIPE THAT SUPPLIES THE AUTOMATIC FIRE EXTINGUISHING SYSTEM / STANDPIPE SYSTEM.
16. THE FIRE INSPECTOR SHALL PERFORM A VISUAL INSPECTION OF ALL UNDERGROUND
SPRINKLER HEAD IN THE SYSTEM.
RISER WILL RESULT IN FLUSHING THE ABOVEGROUND SPRINKLER SYSTEM THROUGH EVERY
SYSTEM. FAILURE TO FLUSH UNDERGROUND FIRE LINE PRIOR TO "STACKING" THE SPRINKLER
GROUND PIPES WHICH SUPPLY THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM/ STANDPIPE
18. THE FIRE INSPECTOR MUST WITNESS A HYDROSTATIC TEST AND FLUSH OF ALL UNDER-
PREVENTION OFFICE TO COORDINATE INSPECTION OF MATERIAL.
PRIOR TO INSTALLATION TO VERIFY COMPLIANCE WITH STANDARDS. CONTACT FIRE
20. ALL EQUIPMENT AND PIPING MUST BE INSPECTED BY THE FIRE PREVENTION OFFICE
SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)".
15. ALL EQUIPMENT AND MATERIALS SHALL MEET THE REQUIREMENTS OF "STANDARD TECHNICAL
ADDITIONAL COST TO THE PROJECT CONTRACT.
THE DETAILS WILL BE UTILIZED TO ACCOMPLISH THE MECHANICAL SCOPE OF WORK AT NO
O & MA PROJECTS, KOREA (NOVEMBER 30, 2015)" FORM AS A PART OF THIS PROJECT.
16. THE MECHANICAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL DRAWINGS FOR
PROJECTS, KOREA (REVISION 1 - 20151030)".
ENGINEERING AS INDICATED ON "STANDARD TECHNICAL SPECIFICATIONS FOR O & MA
BY A REGISTERED PROFESSIONAL ENGINEER LICENSED TO PRACTICE FIRE PROTECTION
AND SEALED BY A U.S. FIRE PROTECTION ENGINEER (NICET), LEVEL III OR IV AND STAMPED
SYSTEM COMPLETE WITH HYDRAULIC CALCULATIONS AND FINAL DESIGN DRAWINGS SIGNED
8. THE FIRE SPRINKLER SYSTEM CONTRACTOR IS TO PROVIDE A COMPLETE ENGINEERED
REVIEW BRANCH FOR APPROVAL BEFORE COMMENCING THE WORK.
13. THE CONTRACTOR SHALL SUBMIT ALL MATERIAL INFORMATION TO THE DESIGN & TECHNICAL
FIRE PROTECTION GENERAL NOTES
SUCH AS ANCHORS, HANGERS, SUPPORTS, ETC.
8. ALL PIPES, DRAINS AND DUCTWORK TO BE REMOVED SHALL INCLUDE ALL ITS ACCESSORIES
SYSTEM THROUGHOUT THE BUILDING TO FULLY PROTECT THIS FACILITY.
1. THE CONTRACTOR SHALL PROVIDE AND INSTALL AN AUTOMATIC WET PIPE SPRINKLER
YI, TONG KI
12 JUN 17
DRAWINGS AND SPECIFICATIONS.
7. THE FIRE SPRINKLER SYSTEM SHALL BE DESIGNED TO MEET THE INTENT OF THE
LIGHTING AND HVAC OUTLETS FOR THE SPRINKLER’S EXACT LOCATION.
4.THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECTURAL’S CEILING PLAN,
ETC. FAILURE TO INSPECTION WILL RESULT IN RESCHEDULING INSPECTION.
SPRINKLER PIPE, NAIL PLATES IF REQUIRED, LOCATION OF FIRE DEPARTMENT CONNECTIONS, CLIPS IF REQUIRED, PLACEMENT & TYPE OF SPRINKLER HEADS, FIRE CAULKING AROUND
19. AT THE TIME OF THE TEST, THE INSPECTOR SHALL CHECK PIPE SIZE, PIPE HANGERS, SURGE
AND EQUIPMENT LISTINGS.
ACCORDANCE WITH NEPA 13 & 13R, UFC 3-600-1, MANUFACTURER’S RECOMMENDATIONS
SHOWN IN SUGGESTED LOCATIONS. FINAL QUANTITY AND LAYOUT SHALL BE IN
3. THE EQUIPMENT, VALVES, PIPING, HEADS AND OTHER ACCESSORIES & PARTS ARE
SHOP DRAWINGS.
SYSTEM. THE HYDRANT LOCATIONS, FLOW TESTS AND DATE SHALL BE INDICATED ON THE
BASED ON NFPA 291 REQUIREMENTS AND UTILIZE THIS DATE TO DESIGN THE SPRINKLER
17. THE CONTRACTOR SHALL CONDUCT WATER SUPPLY HYDRANT TEST FOR THIS PROJECT
AS ORIGINALLY INTENDED.
AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT CONNECTION TO FUNCTION
ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION, REMOVE THE EXISTING DUCTWORK
& LOCATION PRIOR TO INSTALL NEW HAVC AND PLUMBING PIPING. IF THE EXISTING DUCT
6. THE CONTRACTOR SHALL COORDINATE WITH THE EXISTING DUCTWORK AND PIPING ELEVATION
PANELS AND DOORS.
TO BE VISIBLE AND ACCESSIBLE FROM THE FLOOR WITHOUT HAVING TO REMOTE CEILING
FOR MECH. ROOMS AND OTHER UTILITY ROOMS. SHUT-OFF VALVES SHALL BE INSTALLED
12. ALL SPRINKLER PIPING IN FINISHED AREAS SHALL BE CONCEALED FOR VIEW EXCEPT
TECHNICAL SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)".
9. ALL EQUIPMENT SHALL BE UL LISTED AND/ OR FM APPROVED AS INDICATED ON "STANDARD
CONSTRUCTION.
20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF CORE DRILLING DURING
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
34 73
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
GENERAL NOTES
M-3
D - 17 - 11
NAM, TAE CHIN
G
7. THE CONTRACTOR SHALL PERFORM THE TRAINING ABOUT GAS SUPPLY SYSTEM TO O&M DIVISION.
AND GAS PIPING LINES TO DESIGN & TECHNICAL REVIEW BRANCH FOR APPROVAL PRIOR TO CONSTRUCTION.
5. THE CONTRACTOR SHALL SUBMIT THE DETAILED SHOP DRAWING OF GAS DISTRIBUTION SYSTEM
NAM, TAE CHIN
US ORIGIN MATERIALS:
AS INDICATED ON THE DRAWINGS.
INTERNET SITE HTTP:// WWW.CCKBID.COM). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE
DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS",
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL
NATURAL-GAS / LIQUID PETROLEUM GAS DISTRIBUTION.
TECHNICAL SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)" SECTION 33 51 15,
1. GAS DISTRIBUTION SYSTEM SHALL CONFORM TO KOREA GAS SAFETY CODE AS WELL AS "STANDARD
20151030)" SECTION 33 51 15, PART 2 PRODUCTS.
AS WELL AS "STANDARD TECHNICAL SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 -
2. ALL MATERIALS OF GAS DISTRIBUTION SYSTEM SHALL CONFORM TO KOREA GAS SAFETY CODE
THE DESIGN & TECHNICAL REVIEW BRANCH FOR APPROVAL PRIOR TO CONSTRUCTION.
6. THE CONTRACTOR SHALL SUBMIT ALL MATERIAL INFORMATION OF GAS DISTRIBUTION SYSTEM TO
GAS DISTRIBUTION GENERAL NOTES
ADJUSTMENTS, RELOCATIONS AND/ OR REPAIRS WILL BE MADE AT THE CONTRACTOR’S COST.
AS A RESULT OF THE CONTRACTOR’S CONSTRUCTION. ALL DAMAGE TO GAS FACILITIES REQUIRING
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGES TO GAS FACILITIES DURING OR
SCOPE OF WORK
WORK CLASS: "L" (CONSTRUCTION / ALTERATION WORK)
ACCESSORIES.
8. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR THE INSTALLATIONS OF GAS PIPING AND
9. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR GAS PIPING SIZE.
TO D&TR BRANCH THROUGH THE COR.
10. THE CONTRACTOR SHALL PERFORM A GAS LEAKING TEST AND SUBMIT THE GAS LEAKING TEST REPORT
GENERAL NOTES AND SCOPE OF WORK
YI, TONG KI
12 JUN 17
5. CONTRACTOR SHALL REMOVE ALL DDC SYSTEM INSTALLED BY JOHNSON CONTROL.
COSTS WITH EXISTING (OR NEW) DDC SYSTEM INSTALLED BY JOHNSON CONTROL.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL & REINSTALLATION AND ALL ASSOCIATED
4. INSTALL NEW WET PIPE FIRE SPRINKLER SYSTEM WITH ALL NECESSARY ACCESSORIES AND PARTS.
CODES AND REGULATIONS TO COMPLETE SUBJECT PROJECT CONSTRUCTION. )
FROM NOT SHOWN OR/AND INDICATED IN THE CONCEPTUAL DRAWINGS TO MEET WITH APPLICABLE
PURPOSE ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL OTHER ADDITIONAL COST CAUSED
(THE FIRE SPRINKLER SYSTEM ROUTING AND PIPE SIZES SHOWN ARE CONCEPTUAL FOR IGCE
WALL CAPS, INSULATION AND ALL NECESSARY ACCESSORIES AND PARTS.
CEILING EXHAUST FANS, ROOF VENTILATORS, RANGE HOODS, ASSOCIATED DUCTWORK, DAMPERS,
2. REPLACE EXISTING VENTILATING SYSTEM WITH NEW ONE INCLUDING WALL EXHAUST FANS,
ASSEMBLY, DAMPERS, PIPING AND ALL NECESSARY ACCESSORIES AND PARTS.
HEATERS, CONCRETE PADS, INSULATION, SMOKE STACKS, VALVES, GAUGES, GAS LINE & TRAIN
UNITS, A/C UNIT, THERMOSTATS, AIR INTAKE LOUVERS, OARC, ACCESS DOORS, ELECTRIC UNIT
HEATING BOILER, WATER CIRCULATING PUMP, EXPANSION TANKS, AIR SEPARATORS, FAN COIL
1. REPLACE EXISTING HEATING AND COOLING SYSTEM WITH NEW ONE INCLUDING HOT WATER
AND PARTS.
SERVICE BOXES, ACCESS DOORS, VALVES, GAUGES, WATER PIPING AND ALL NECESSARY ACCESSORIES
ASSEMBLY, BACKFLOW PREVENTER & PRESSURE REDUCING STATION, CONCRETE PADS, WASHER
VENT PIPING, DOMESTIC WATER PIPING, SMOKE STACK, DAMPERS, INSULATION, GAS LINE & TRAIN
HOT WATER CIRCULATING PUMPS, DOMESTIC WATER STORAGE TANK, PLUMBING FIXTURES, SEWER &
3. REPLACE EXISTING PLUMBING SYSTEM WITH NEW ONE INCLUDING DOMESTIC WATER HEATER, CAMP CARROLL
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE FACILITY SHARE OF THE EXPENSES.
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
35 73
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-4
D - 17 - 11
G
MECHANICAL
EXISTING / REMOVAL HVAC PLAN
UP
DN.
UP
UP
T
T
T
T
T T
T T T
T
T
T T
TTT
T
T
T
T T
T T
TT
REMOVE EXISTING CEILING EXHAUST FANS & DUCTWORK
ROOF VENTILATORS & DUCTWORK
REMOVE EXISTING CEILING EXHAUST FANS,
P-1
EXISTING / REMOVAL HVAC PIPING PLAN
SCALE : 1 / 100
1st FLOOR
2nd FLOOR
EXISTING CONC. PAD AND FENCE TO REMAIN
36 73
M-5
P-1
M-7
SEE FOR MECH. ROOM HVAC REMOVAL PLAN
N
YI, TONG KI
12 JUN 17
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
LEGEND
TO BE REMOVED
SPECIFIC NOTES
& PIPING SHALL BE VERIFIED IN FIELD.
THEREFORE, EXACT SIZE, LOCATION AND DIRECTION OF HVAC DUCT
1. EXISTING HAVC PLANS MAY NOT EXACTLY MATCH THE FIELD AND
SHALL BE PATCHED AND FILLED OR RESTORED.
2. THE OPENING RESULTING FROM THE REMOVAL OF HVAC UNITS
FRESH AIR INTAKE DUCTWORK AND PIPING
REMOVE EXISTING FAN COIL UNITS, THERMOSTATS
PIPING & ACCESSORIES TO REMAIN
EXISTING AIR COOLED CHILLER W/ ASSOCIATED
FRESH AIR INTAKE DUCTWORK AND PIPING
REMOVE EXISTING FAN COIL UNITS, THERMOSTATS
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-5
D - 17 - 11
SHEET OF
DN. DN.
4"
MECHANICAL
UP UP
DOMESTIC WATER PIPING, SEWER & VENT PIPING
REMOVE EXISTING PLUMBING FIXTURES,
P-1
P-1 EXISTING / REMOVAL PLUMBING PIPING PLAN
SCALE : 1 / 100
1ST FLOOR
2ND FLOOR
DOMESTIC WATER PIPING, SEWER & VENT PIPING
REMOVE EXISTING PLUMBING FIXTURES,
TO REMAIN
EXISTING SEWER LINE
37 73
M-6
EXISTING / REMOVAL PLUMBING PLAN
M-7
SEE FOR MECH. ROOM PLUMBING REMOVAL PLAN
N
YI, TONG KI
12 JUN 17
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
SPECIFIC NOTES
SEWER, VENT AND DOMESTIC WATER PIPING SHALL BE VERIFIED IN FIELD.
FIELD AND THEREFORE, EXACT SIZE, LOCATION AND DIRECTION OF
1. EXISTING PLUMBING PIPING PLANS MAY NOT EXACTLY MATCH THE
PIPING SHALL BE PATCHED AND FILLED OR RESTORED.
2. THE OPENING RESULTING FROM THE REMOVAL OF SMOKE STACK AND
LEGEND
TO BE REMOVED
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-6
D - 17 - 11
EXISTING CONC. PAD AND FENCE TO REMAIN
N
EXISTING MAIN GAS PIPING TO REMAIN
EXISTING AUTO EMERGENCY SHUT-OFF VALVE TO REMAIN
EXISTING GAS METER & REGULATOR ASSEMBLY CABINET TO REMAIN
EXISTING GAS ALARM GONG TO REMAIN
P-1
SCALE : 1 / 20
EXISTING / REMOVAL MECH. ROOM PARTIAL PLAN
UP UP
KEY PLAN
REMOVE AND REINSTALL EXISTING CIRCULATING PUMP
ACCESSORIES AND PARTS.
OARC, GAS LINE & TRAIN ASSEMBLY, INSULATION AND ASSOCIATED
GAUGES, VALVES, SMOKE STACK & DAMPER, EXHAUST FAN, THERMOSTATS,
CONC. PAD, PUMP, EXPANSION TANK, AIR SEPARATOR, PIPES, UNIT HEATER,
REMOVE EXISTING HVAC SYSTEM INCLUDING HOT WATER BOILER &
EXISTING GAS LEAK DETECTION CONTROL PANEL TO REMAIN
M
SPECIFIC NOTES
SEE SPECIFIC NOTES
REMOVE EXISTING MAIN WATER LINE (FROM WATER GATE VALVE TO MECH. ROOM)
THE WATER LINE.
2. TURN OFF THE EXISTING WATER GATE VALVE BEFORE REMOVING
EXISTING GAS LEAK DETECTOR TO REMAIN
38 73
MECH. ROOM PARTIAL PLAN
EXISTING / REMOVAL
M-7
YI, TONG KI
12 JUN 17
GRAPHIC SCALE
SCALE: 1 : 20
200 400 800mm
& PIPING SHALL BE VERIFIED IN FIELD.
THEREFORE, EXACT SIZE, LOCATION AND DIRECTION OF HVAC DUCT
1. EXISTING HAVC PLANS MAY NOT EXACTLY MATCH THE FIELD AND
AND PARTS.
GAS LINES & TRAIN ASSEMBLY, INSULATION AND ASSOCIATED ACCESSORIES
VALVES, HOT WATER STORAGE TANK, BACKFLOW PREVENTION ASSEMBLY,
HEATER & CONC. PAD, PUMPS, PIPES, GAUGES, SMOKE STACK & DAMPER,
REMOVE EXISTING PLUMBING SYSTEM INCLUDING DOMESTIC WATER
PIPING & ACCESSORIES TO REMAIN
EXISTING AIR COOLED CHILLER W/ ASSOCIATED
SHALL BE PATCHED AND FILLED OR RESTORED.
3. THE OPENING RESULTING FROM THE REMOVAL OF UNITS & PIPES
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-7
D - 17 - 11
2ND FLOOR
1ST FLOOR
D-1
NOT TO SCALE
REFRIGERANT PIPE DETAIL
12"x2" FAIL
60 CFM
10"x2" FAIL
30 CFM
10"x2" FAIL
30 CFM
12"x2" FAIL
60 CFM
10"x2" FAIL
30 CFM
10"x2" FAIL
30 CFM
10"x2" FAIL
30 CFM
12"x2" FAIL
60 CFM
12"x2" FAIL
60 CFM
12"x2" FAIL
60 CFM
10"x2" FAIL
30 CFM
11 11 13
11 1113 13 13
SPLIT TYPE A/C UNIT
L E G E N D
(SIZE : 600 x 600)
CEILING ACCESS DOOR
4" PVC PIPE
INSULATED SUCTION LINE
LIQUID LINE
D-1
-SEE
DN.DN.
UP UP
ELECTRIC UNIT HEATER
12"x2" FAIL
60 CFM
39 73
P-1
M-8
NEW HVAC PIPING PLAN
NEW HVAC PIPING PLAN
SCALE : 1 / 100
M-8
M-8
25, 25, 25 25, 20, 20
25, 25, 25
20, 20
65, 65
25, 20, 20
20, 20, 25 25, 25, 25
25, 20, 2025, 25, 2525, 25, 252525, 25, 2520, 20, 25
Tch
TchTch
Tch
Tch
Tch
Tch
Tch
Tch Tch
TchTch
(TYP. OF 24EA)
FOR FCU
THERMOSTAT
N
YI, TONG KI
12 JUN 17
P-1
- M-17
PIPING PARTIAL PLAN
SEE NEW MECH. ROOM
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
SPECIFIC NOTES
FROM / TO 2ND FLOOR CEILING (TYP.)
HVAC WATER PIPES
10"x2" FAIL
30 CFM
12"x2" FAIL
60 CFM
12"x2" FAIL
60 CFM
10"x2" FAIL
30 CFM
10"x2" FAIL
30 CFM
12"x2" FAIL
60 CFM
10"x2" FAIL
30 CFM
12"x2" FAIL
60 CFM
10"x2" FAIL
30 CFM
10"x2" FAIL
30 CFM
12"x2" FAIL
60 CFM
12"x2" FAIL
60 CFM
13 13
12 14 13
11 11
LOOP
EXPANSION
CH / HWS
CH / HWR
CH / HWS
CH / HWR
C H
/ H
W S
C H
/ H
W R
CH / HWS
CH / HWR
CH / HWS
CH / HWR
CH / HWS
CH / HWR
C H
/ H
W S
C H
/ H
W R
CH / HWS
CH / HWR
CH / HWS
CH / HWR CH / HWR
65, 65
32, 3232, 3220, 2032, 32
25, 25
32, 32
25, 25
32, 32
25, 20, 2025, 25, 25
25, 25, 25
20, 20
20, 20
25, 20, 20
25, 25
20, 20, 25
32, 32
25, 25, 25
25, 20, 2025, 25, 2525, 25, 252525, 25, 2520, 20, 25
50, 65 40, 65
25 32
Tch Tch
Tch Tch
Tch
Tch
Tch
TchTch
TchTchTch
TO / FROM MECH. RM (TYP.)
HVAC WATER PIPES
25 2525
25 25 25 25 25
UNIT HEATER
ELECTRIC
COLOR AND KEY-TYPE.
2. THERMOSTAT GUARDS FOR FAN COIL UNITS IN EACH ROOM SHALL BE TRANSPARENT
MANUFACTURER’S RECOMMENDATION AND SITE CONDITIONS.
1. SIZES AND LAYOUTS OF FRESH AIR INTAKE LOUVERS MAY CHANGE DEPENDING ON
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-8
D - 17 - 11
NOTES
M
IN
m m
SHALL BE PLACED 2000mm ABOVE THE GROUND LEVEL.
FRESH AIR INTAKE LOUVERS FOR FAN COIL UNITS ON THE 1ST FLOOR WALL
12" x 2"
12" x 2"
12" x 2"10" x 2"
10" x 2"
10" x 2"
10" x 2"
12" x 2" 10" x 2"
10" x 2" 12" x 2"
12" x 2"
12" x 2"
12" x 2"
12" x 2"
12" x 2"12" x 2"
12" x 2"
10" x 2"
10" x 2"
10" x 2"10" x 2"
10" x 2"
10" x 2"
40 73
ELEVATION FOR FRESH AIR INTAKE LOUVERS
- M-9 SCALE : 1 / 50
E-2
- M-9 SCALE : 1 / 50
E-1 ELEVATION FOR FRESH AIR INTAKE LOUVERS - FRONT
ELEVATION FOR FRESH AIR INTAKE LOUVERS - REAR
KEY PLAN
M-9
-E-2
-E-1 M-9
W/ INSECT NET (TYP.)
FRESH AIR INTAKE LOUVER
YI, TONG KI
12 JUN 17
GRAPHIC SCALE
1000 2000mm
SCALE: 1 : 50
CAMP CARROLL
S-83
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-9
D - 17 - 11
65, 25
65, 32
, 6
40, 65
50, 65
50, 50
50, 50
65, 50
50, 50
, 6
40, 65
32, 65
20, 65
20, 20
, 2
, 2 0, , 2
, 2
, 2 0, , 2 5, , 3
, 2
, 2 0, , 2 5, , 3
, 2 5, , 3
EXP
ANSIO
N
LO
OP
, 2
, 2 5, , 3
, 2 0, , 2
, 2 5, , 3
, 2 0, , 2
, 3
, 2 5, FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
11FCU
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
FC
U
SP
LIT
T
YP
E
A/C U
NIT
CH
/ H
WS
CH
/ H
WR
CH
/ H
WS
CH
/ H
WR
CH
/ H
WS
CH
/ H
WR
CH
/ H
WS
CH
/ H
WR
CH
/ H
WS
CH
/ H
WR
CH
/ H
WR
CH / HWS
CH / HWR
CH / HWS
CH / HWR
, 6
, 3
EXISTING / REMOVAL HVAC PLAN
MECHANICAL-
HVAC PIPING ISOMETRIC DIAGRAMI-1
NOT TO SCALEM-10
YI, TONG KI
12 JUN 17
TO
FR
OM
MEC
H.
RM
(TY
P.)
HVAC
WAT
ER
P
IPE
S
CH / HWS
CH / HWR
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
41 73
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-10
D - 17 - 11
1ST FLOOR
2ND FLOOR
MECHANICAL
D
D
D D
DD
D
D
D
DD
D
(TYP. OF 12 EA)
CEILING EXHAUST FAN 18 ROOF EXHAUST VENTILATOR 18 ROOF EXHAUST VENTILATOR
FROM 1ST FLOOR
DUCT RISER
300x150 EXHAUST
VENTILATOR
ROOF EXHAUST
DUCT RISER UP TO
300x200 EXHAUST
UP TO 2ND FLOOR
300x150 EXHAUST DUCT RISER
UP TO 2ND FLOOR
DUCT RISER
300x150 EXHAUST
UP TO 2ND FLOOR
DUCT RISER
300x150 EXHAUST
300x100
VENTILATOR
ROOF EXHAUST
DUCT RISER UP TO
300x200 EXHAUST 300x100
300x100300x100
300x100
300x100300x200
19 ROOF EXHAUST VENTILATOR
J
DUCT W/ WALL CAP
150 RANGE HOOD EXHAUST
J
W/ WALL CAP
200 FLEXIBLE DUCT
(TYP. OF 12 EA)
RANGE HOOD
20 WALL EXHAUST FAN
T
THERMOSTAT FOR WALL EXHAUST FAN
DN.DN.
UP UP
- NOT TO SCALE
TYPICAL SECTION FOR EXHAUST DUCT
BATH ROOM BATH ROOM
BATH ROOMBATH ROOM
2nd FL
1st FL
ROOF EXHAUST VENTILATOR
CEILING EXHAUST FAN
CEILING LINE
CEILING LINE
ROOF TOP
P-1
M-11
NEW VENTILATION PLAN
SCALE : 1 / 100
M-11
S-1
NEW VENTILATION PLAN AND SECTION
N
YI, TONG KI
12 JUN 17
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
SPECIFIC NOTES
2. INSTALL VOLUME DAMPER AT EACH BRANCH DUCT CONNECTION.
3. FIRE DAMPER SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 90A.
MANUFACTURER’S RECOMMENDATION AND SITE CONDITIONS.
1. SIZES AND LAYOUTS OF DUCTWORK MAY CHANGE DEPENDING ON
BE PROVIDED IN CEILING FOR DUCT ACCESS DOORS, DAMPERS, ETC.
4. WHERE DUCTS ARE INSTALLED ABOVE CEILING, ACCESS PANELS SHALL
DIMENSION AT THE ELBOW EQUALS OR EXCEEDS 300MM.
VANES SHALL ALSO BE INSTALLED AT ROUND ELBOWS WHEN A DUCT
5. TURNING VANES SHALL BE INSTALLED IN ALL SQUARE ELBOWS. TURNING
BY ASHRAE HANDBOOKS, AND NFPA 90-A.
DUCT CONSTRUCTION STANDARDS BY SMACNA, INDUSTRIAL VENTILATION
6. OTHER DUCT WORK DETAILS NOT SHOWN SHALL CONFORM TO HVAC
J
W/ WALL CAP
(UL 2158A LISTED)
100 FLEXIBLE DUCT
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
42 73
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-11
D - 17 - 11
1ST FLOOR
2ND FLOOR
VTR
80x100
VTR
80x100
VTR
80x100
VTR
80x100
DN.DN.
UP UP
100 100
P-5
P-11
P-4
P-1
P-3
P-10
P-10
P-5 P-5
P-5
P-5 P-5
P-5
P-5
P-5
P-5
P-5
P-5
P-4
P-4
P-4
P-4
P-4
P-4
P-4
P-4
P-4
P-1
P-1
P-1
P-1
P-1
P-1
P-1
P-1
P-1 P-1
P-1
P-4
P-3
P-3
P-3
P-3
P-3
P-3
P-3
P-3
P-3
P-3
P-3
P-11
P-11
P-11 P-11
P-11
50 FCO
100 100100
150 FCO
100 FCO
80 FCO
80 FCO
50 FD
100 FCO
P-4
50 50
50 FCO
100 FCO
80 FCO
80 FCO
80 FCO
50 FD
50 FD
50 FD 50 FD
50 FD
50 FD
50 FD
100, 80
100, 80 100, 80
100, 80
50, 50
P-11P-11
P-11
P-11 P-11
P-11
50 FD
TO REMAIN
EXISTING SEWER LINE
FOR CONT., SEE CIVIL DWG
6" SEWER MAIN PIPE
50 50
50 50
100, 80
100, 80
100, 80
100, 80
50, 50
50100
100 FCO
100 FCO
50 FD
100 FCO
50 FD
100 FCO
FD
100 FCO
50 FD
43 73
NEW SEWER AND VENT PIPING PLAN
P-1
SCALE : 1 / 100
NEW SEWER AND VENT PIPING PLAN
M-12
N
YI, TONG KI
12 JUN 17
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
SYMBOL DESCRIPTION QTY. REMARKS
P-1
P-5
C.W. H.W. WASTE
VENT
WATER CLOSET
15 50
PLUMBING FIXTURE SCHEDULE
P-4 50
(NOT EXCEED 3.5 LITERS PER FLUSH /
FLUSH TANK TYPE
WATER EFFICIENT TOILET)
COUNTER TOP TYPELAVATORY
BATHTUBP-3
SINK, KITCHEN
P-10
P-11
SINK, LAUNDRY
CLOTHES WASHER 15 50
WHITE VITREOUS CHINA OR 302 STAINLESS STEEL TYPE
15 20 50 50
80 FCO
100 FCO
100 FCO100 FCO
ACRYLIC BATHTUB CONFORMING TO KS F 4806,
EXPOSED TYPE FAUCET
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-12
D - 17 - 11
P-5
P- 3 P-
P-4
P-11
50 FD
F
D P-
P-
P-4
P-11
P-
5 100 FCO
P-
F
D
F
CO
F
CO
F
CO
F
CO
P-5 50 F
CO
F
CO
F
CO
P-11 80 F
CO
P-4
P-
P-
P-
P-1
50 FD
50 FD
F
COP-11
P-4
P-5
P-5
P-10
P-10
F
D
100 FCO
P-
P-
P-
F
CO
F
CO
P-11
P-
50 FD
F
CO
F
CO
P-
P-
50 FD
TO REMAIN
SEWER LINE
EXISTING
P-5
P-11
P-4 P-
P-
P-
P-
50 FD
50 FD
100 FCO
100 FCO
P-11
P-4
P-5
F
CO
P-
F
D
P-4 P-5
P- 11 P-11
P-3
P-1
P-4
50 FD
P-5
P-11
P-
P-
P-
P-
F
D
F
CO
50 FD
F
CO
P-4
P-5
P-11
P-5
P-5
50 50
100, 80
100, 80
50 50
P-
V
TR
RE
DUCER
x80
V
TR
RE
DUCER
TR
RE
DUCER
TR
RE
DUCER
100, 80
100, 80
100, 80
100, 80
100, 80
100, 80
50 50
100 FCO
, 5
, 5
F
CO
8050 50
P-
F
D
44 73
SEWER & VENT PIPING ISOMETRIC DIAGRAM
I-1
NOT TO SCALE
SEWER & VENT PIPING ISOMETRIC DIAGRAM
M-13
YI, TONG KI
12 JUN 17
SYMBOL DESCRIPTION QTY. REMARKS
P-1
P-5
C.W. H.W. WASTE
VENT
WATER CLOSET
15 50
PLUMBING FIXTURE SCHEDULE
P-4 50
(NOT EXCEED 3.5 LITERS PER FLUSH /
FLUSH TANK TYPE
WATER EFFICIENT TOILET)
COUNTER TOP TYPELAVATORY
BATHTUBP-3
SINK, KITCHEN
P-10
P-11
SINK, LAUNDRY
CLOTHES WASHER 15 50
WHITE VITREOUS CHINA OR 302 STAINLESS STEEL TYPE
15 20 50 50
ACRYLIC BATHTUB CONFORMING TO KS F 4806,
EXPOSED TYPE FAUCET
CAMP CARROLL
HS-00658-5J
THAAD/ 2-1 ADA BATTERIES
REPAIR BARRACKS BLDG. #83 FOR
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-13
D - 17 - 11