W912QR25BA008_Specs-0002.pdf

PDF 1 MB Posted

Attached to
BOWST Addition/ OFT Renovation, Building 321, Niagara Falls Air Reserve Station
Solicitation number
W912QR25BA008
Issued by

About this file

This document is a detailed federal contract specification for a Design-Bid-Build construction project at Niagara Falls Air Reserve Station (NFARS), New York. The project involves a 2,500 square foot Boom Operator Weapons System Trainer (BOWST) addition to Building 321 and renovation of the building to accommodate an Operational Flight Trainer (OFT) simulator. The solicitation, issued by the US Army Corps of Engineers Louisville District, is scheduled for release on 15 April 2025 with contract number W912QR25BA008.

The specification provides comprehensive technical requirements for the HVAC control systems, including direct digital control (DDC) hardware, software, installation, testing, and maintenance. Key requirements include submitting detailed design drawings, configuration settings, programming software, and quality control documentation. The contractor must perform start-up testing, a one-week performance verification test, and provide 32 hours of training for government personnel. The project also includes specific provisions for cybersecurity, network configuration, and long-term system maintenance, with a one-year warranty period following final acceptance.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Solicitation For BOWST Addition / B-321 Renovation Niagara Falls ARS, NY

P2: 508014

Design-Bid-Build

Specifications Vol. 1 of 2(Div 00-22) Certified Final Design

15 April 2025

W912QR25BA008

ARIMS: 200A

Disposition: Maintain for 15yrs after construction

W912QR25BA008_Specs-0002 W912QR25BA008_Specs_Vol1-0000

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

(a) By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of theoffer submitted;

or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER.

If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER

NUMBER IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

15B. CONTRACTOR/OFFEROR

(Signature of person authorized to sign)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA

(Signature of Contracting Officer)

16C. DATE SIGNED

Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES

2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)

6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE

8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X) 9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED (SEE ITEM 11)

10A. MODIFICATION OF CONTRACT/ORDER NUMBE

10B. DATED (SEE ITEM 13)

CODE FACILITY CODE

J 1 2

0002 30 MAY 2025 508014

W912QR

W072 ENDIST LOUISVILLE

KO CONTRACTING DIVISION, 600 DR MARTIN LUTHER KING JR PL

LOUISVILLE, KY 40202-2230

UNITED STATES

CHARITY MANSFIELD, EMAIL: CHARITY.A.MANSFIELD@USACE.ARMY.MIL

TELEPHONE: 000-000-0000

SCD: PAS:

W912QR25BA008

15 APR 2025

SEE SECTION G - CONTRACT ADMINISTRATION DATA

SEE SCHEDULE

ADAM M. WANTLAND

02 JUN 2025

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

Solicitation No. W912QR-25-B-A008 for a Block 14 (Description of Amendment/Modification):

construction Design/Bid/Build construction contract for a 2,500 SF (232.3 SM) Boom Operator Weapons System Trainer (BOWST) addition to Building 321 located at Niagara Falls Air Force Reserve Station, NY and renovations of B321 to meet facility design requirements for the Operational Flight Trainer (OFT) simulator is hereby amended as follows:

A. The following SPECIFICATIONS AND DRAWINGS have been replaced due to clerical error:

00 00 00 Specifications Cover Page G-001 Cover Sheet

B. The following SPECIFICATION SECTIONS have been replaced in their entirety:

07 92 00 JOINT SEALANTS

23 09 00 INSTRUMENTATION AND CONTROLS FOR HVAC

C. The following DRAWINGS have been replaced in their entirety:

GI002 GENERAL INFORMATION - LIFE SAFETY

A-502 PARTITION TYPE DETAILS

ED101 FIRST FLOOR DEMOLITION PLAN - ELECTRICAL

EL101 FIRST FLOOR PLAN - LIGHTING

EP101 FIRST FLOOR PLAN - POWER

EP102 LIGHTNING PROTECTION PLAN

E-701 DIAGRAMS - ELECTRICAL

TD101 FIRST FLOOR PLAN - TELECOMMUNICATIONS - DEMOLITION

T-101 FIRST FLOOR PLAN - TELECOMMINCATIONS

T-401 ENLARGED PLANS - TELECOMMUNICATIONS

D. Clarification: Amendment 0001 specified that the Price Breakout Schedule was replaced in its entirety, but the new document was erroneously not provided. It is attached.

E. Wage Decision NY20240019 has been revised to NY20250019 (Dated 23 May 2025) and is hereby incorporated by reference. Please refer to updated Wage Decision.

F. Offerors must acknowledge all amendments.

G. All other terms and conditions remain unchanged.

Section 00 00 00 - Procurement and Contracting Requirements

The following changes have been made:

INFORMATION FROM TO

Response Due Date 04 Jun 2025 09 Jun 2025

W912QR25BA0080002

P2# 508014 - BOWST Add/B-321 Reno

NFARS, NY

SECTION 00 10 00

PRICE BREAKOUT SCHEDULE

TOTAL BASE BID

(ITEMS 0001 through 0004) -------------------------- $_______________________

TOTAL OPTIONS 1-3

(ITEMS 0005 through 0007) -------------------------- $

TOTAL BASE BID AND OPTIONS 1,2 and 3 (ITEMS 0001 through 0007) -------------------------- $

TOTAL OPTIONS 4,5 and 6 (ITEMS 0008 through 0010, first use) --------------- $

ITEM NO SUPPLIES/SERVICES QUANTITY UNIT TOTAL PRICE

0001 BASE BID 1 JOB $ __________________

All demolition, site work, renovation and new construction associated with the Boom Operator Weapons System Trainer (BOWST) Addition as identified on the drawings and specifications, except as included in CLIN 0005 - 0010.

This work is to include modifications to the storm water management system components (other than associated with the modification to the existing parking area) and all related construction necessary to make the new addition and the portions of the existing building indicated as base bid complete and fully operational. Boundaries of Base Bid and Option 1 as shown on Drawings A-101 apply to all disciplines unless otherwise noted.

0002 BASE BID - SOIL DISPOSAL ALLOWANCE

1750 CY Soil JOB $ __________________

Materials excavated from the site must be managed as PFAS waste. Materials that cannot be reused on the site must be characterized, and disposed of outside the NFARS boundary per current Air Force, federal, and New York State regulations.

Amdt. #0001 ***************************************************************

Proposal shall include any and all labor, material, and costs related to, or necessary for, the movement, handling, storage, conveyance, permitting, fees, and any other expense associated with or required for the complete and legal movement, handling, storage, conveyance, and permitting required for the disposal of this material.

Proposal shall include a lump sum allowance for the identified quantities.

0003 BASE BID - GROUNDWATER DISPOSAL ALLOWANCE

550 GAL Groundwater JOB $

DOCUMENT 00 10 00 Page 1

CERTIFIED FINAL - AM 0001

Amdt. #0001

All groundwater collected from the site must be managed as PFAS waste, characterized, and disposed of outside the NFARS boundary per current Air Force, federal, and New York State regulations.

Proposal shall include any and all labor, material, and costs related to, or necessary for, the movement, handling, storage, conveyance, permitting, fees, and any other expense associated with or required for the complete and legal movement, handling, storage, conveyance, and permitting required for the disposal of this material.

Proposal shall include a lump sum allowance for the identified quantity.

0004 BASE BID - SOIL IMPORT ALLOWANCE

600 CY SOIL JOB $ __________________

All soils used for structural fill must be imported to the project site per current Air Force, federal, and New York State regulations. Proposal shall include a lump sum allowance for the identified quantity.

0005 OPTION 1 1 JOB $

MODIFICATIONS TO B-321 FOR OFT INSTALLATION AND FACILITY

IMPROVEMENTS / REPAIRS

All demolition, site work, renovation and modification construction associated with the maintenance and repair of B-321 and modifications for the installation of an Operational Flight Trainer (OFT) as shown on the drawings and specifications not included in CLIN 0001 - 0004, or 0006-0010.

This work will include but is not limited to modifications to the existing parking area and the stormwater management system (e.g. piping and catch basins) associated with the parking area; modifications to the high-bay area for the new bridge crane support structure and all collateral and associated work necessary for the B-321 to be fully operational and complete. Including design of the bridge support structure and foundation as required for the loads imposed by the specific bridge crane selected by the Contractor (Option 3). Boundaries of Base Bid and Option 1 as shown on Drawing A-101 apply to all disciplines unless otherwise noted.

0006 OPTION 2 1 JOB $ __________________

SHELVING IN ROOM 114 SUPPLY AND MAINTENCANCE AND ROOM 131 STORAGE

All work and materials required to provide and install shelving in Room 114 SUPPLY AND MAINTENANCE and Room 131 STORAGE as shown on the drawings and specifications, complete.

0007 OPTION 3 1 JOB $ __________________

BRIDGE CRANE IN ROOM 107 SIMULATOR HIGH BAY

All work and materials required to provide and install the bridge crane in Room 107 SIMULATOR HIGH BAY. This work is to include but is not limited to all required connections to power, operational controls and training as shown on the drawings and specifications for a complete and operational system.

0008 OPTION 4 1 OPTION $ __________________

700 CY SOIL DISPOSAL

DOCUMENT 00 10 00 Page 2

CERTIFIED FINAL - AM 0001

Materials excavated from the site must be managed as PFAS waste. Materials that cannot be reused on the site must be characterized, and disposed of outside the NFARS boundary per current Air Force, federal, and New York State regulations.

Proposal shall include any and all labor, material, and costs related to, or necessary for, the movement, handling, storage, conveyance, permitting, fees, and any other expense associated with or required for the complete and legal movement, handling, storage, conveyance, and permitting required for the disposal of this material.

This option will provide an additional allowance quantity of soil for disposal. This option can be exercised up to three times.

0009 OPTION 5 1 OPTION $ __________________

200 GAL GROUNDWATER DISPOSAL

All groundwater collected from the site must be managed as PFAS waste, characterized, and disposed of outside the NFARS boundary per current Air Force, federal, and New York State regulations.

Proposal shall include any and all labor, material, and costs related to, or necessary for, the movement, handling, storage, conveyance, permitting, fees, and any other expense associated with or required for the complete and legal movement, handling, storage, conveyance, and permitting required for the disposal of this material.

This option will provide an additional allowance quantity of water for disposal. This option can be exercised up to three times.

0010 OPTION 6 1 OPTION $ __________________

150 CY SOIL IMPORTATION

All soils used for structural fill must be imported to the project site.

This option will provide an additional allowance quantity for the importation of soil to the site. This option can be exercised up to three times.

NOTE NO. 1. Offerors must insert a price on all numbered items of the Schedule. Failure to do so will disqualify the bid.

NOTE NO. 2. The field overhead costs through the contract duration are inclusive in the offered price for the contract.

NOTE NO. 3. Options 1, 2 and 3 will be exercised within 90 days of contract award.

NOTE NO. 4. Options 4, 5 and 6 will be exercised as needed during the course of construction.

-- End of Section --

DOCUMENT 00 10 00 Page 3

THIS PAGE INTENTIONALLY LEFT BLANK

DOCUMENT 00 10 00 Page 4

"General Decision Number: NY20250019 05/23/2025

Superseded General Decision Number: NY20240019

State: New York

Construction Type: Building

County: Niagara County in New York.

BUILDING CONSTRUCTION PROJECTS (except single family homes and apartments up to and including 4 stories), Note: Contracts subject to the Davis-Bacon Act are generally required to pay at least the applicable minimum wage rate required under Executive Order 14026 or Executive Order 13658.

Please note that these Executive Orders apply to covered contracts entered into by the federal government that are subject to the Davis-Bacon Act itself, but do not apply to contracts subject only to the Davis-Bacon Related Acts, including those set forth at 29 CFR 5.1(a)(1).

|If the contract is entered |. Executive Order 14026 | |into on or after January 30, | generally applies to the | |2022, or the contract is | contract. | |renewed or extended (e.g., an |. The contractor must pay | |option is exercised) on or | all covered workers at | |after January 30, 2022: | least $17.75 per hour (or | | | the applicable wage rate | | | listed on this wage | | | determination, if it is | | | higher) for all hours | | | spent performing on the | | | contract in 2025. | |If the contract was awarded on|. Executive Order 13658 | |or between January 1, 2015 and| generally applies to the | |January 29, 2022, and the | contract. | |contract is not renewed or |. The contractor must pay all| |extended on or after January | covered workers at least | |30, 2022: | $13.30 per hour (or the | | | applicable wage rate listed| | | on this wage determination,| | | if it is higher) for all | | | hours spent performing on | | | that contract in 2025. |

The applicable Executive Order minimum wage rate will be adjusted annually. If this contract is covered by one of the Executive Orders and a classification considered necessary for performance of work on the contract does not appear on this wage determination, the contractor must still submit a conformance request.

Additional information on contractor requirements and worker protections under the Executive Orders is available at http://www.dol.gov/whd/govcontracts.

Modification Number Publication Date 0 01/03/2025 1 03/14/2025 2 03/28/2025 3 05/23/2025

ASBE0004-001 05/01/2024

Rates Fringes

ASBESTOS WORKER/HEAT & FROST

INSULATOR (include application of all materials, protective coverings, coatings, and finishings to all types of mechanical systems).........................$ 36.85 29.24

HAZARDOUS MATERIAL HANDLER.......$ 34.15 26.09

* BRNY0045-002 07/01/2024

Rates Fringes

Bricklayer, Stonemason...........$ 37.44 32.71 Marble mason.....................$ 36.85 30.80 Pointer, cleaner and caulker.....$ 36.82 31.33 Tile & Terrazzo Worker...........$ 37.85 31.80 Tile, Marble & Terrazzo Finisher.........................$ 34.71 17.54

CARP0276-016 07/01/2024

Rates Fringes

Carpenters (Including Drywall Hanging & Acoustical Ceiling Installation) Carpenters and Soft Floor Layers......................$ 34.26 25.94

Millwrights.................$ 32.28 25.36

ELEC0237-001 05/27/2024

Rates Fringes

Electricians:

Cable Splicers..............$ 37.40 27.44 Electricians................$ 42.20 32.59

ELEV0014-001 01/01/2025

Rates Fringes

ELEVATOR MECHANIC................$ 62.39 38.435+a+b

FOOTNOTE:

a.Vacation: 6%/under 5 years based on regular hourly rate for all hours worked. 8%/over 5 years based on regular hourly rate for all hours worked.

b. PAID HOLIDAYS: New Year's Day; Memorial Day; Independence Day; Labor Day; Veterans' Day; Thanksgiving Day; the Friday after Thanksgiving Day; and Christmas Day.

ENGI0017-010 07/01/2024

Rates Fringes

POWER EQUIPMENT OPERATOR

Backhoe Operators Group A1...................$ 43.00 34.30 Bulldozer Group A1...................$ 43.00 34.30 Forklift Operator/Lull Group A1...................$ 43.00 34.30 Loader Group A1...................$ 43.00 34.30 Roller Group A1...................$ 43.00 34.30

IRON0009-003 07/01/2024

Rates Fringes

Ironworkers:

IRONWORKER..................$ 34.75 31.88

SHEETER.....................$ 34.75 31.88

LABO0091-001 07/01/2023

Rates Fringes

Laborers:

GROUP 1....................$ 32.45 41.36+a GROUP 2....................$ 35.70 41.36+a GROUP 3....................$ 33.45 41.36+a GROUP 4....................$ 33.30 41.36+a GROUP 5....................$ 33.05 41.36+a GROUP 6....................$ 32.95 41.36+a GROUP 7....................$ 32.75 41.36+a GROUP 8.....................$ 34.45 41.36+a GROUP 9.....................$ 37.45 41.36+a

LABORER CLASSIFICATIONS

GROUP 1: Common Laborers, Decontamination of all machines;

Horizontal Directional Drill/Locator; All terrain vehicles with attachments/All wheel or track types

GROUP 2: Blasters, Grade Checker; 10% of Base Rate

GROUP 3: Wagon Drill-Airtrack, Self-Contained Drill

GROUP 4: Laser Beam Operator

GROUP 5: Road Finisher, Form Setter, Gunnite Nozzleman, Sandblasters, Burning Torch, Concrete Saw Operators, Grout Machine and Grout Pumps Operator

GROUP 6: Video Machine Operator in inspection of Pipe

GROUP 7: Potman, Pipelayers, Pavement Breakers or Busters, jackhammer operators; barco rammers; chain saw; powder monkey; black top rakers; scalers; drill tenders; mortar mixers; Concrete polishing machine; Operation & maintenance of all Robotic Remote Systems in hazardous environment;

Peration C men working from swinging scaffold bosum chair;

suspended cage or bucket; work in caissons below 8 feet;

concrete motor buggy; all other operators of mechanical tools, including vibrators egardless of type of power.

GROUP 8: The handling, loading, unloading, stacking, distribution, erection and dismantling of any and all types of scaffolding and/or work platforms used in the removal of insulating material regardless of the composition of said material. The removal of all insulation materials whether they contain asbestos or not from mechanical systems, (pipes, boilers,ducts, flues, breechings, etc.) on all mechanical systems (pipes, boilers, ducts, flues, breeching, etc.) that are going to be scrapped. The removal of all insulating materials whether they contain asbestos or not. The removal of all asbestos containing materials from walls, ceilings, floors, columns and all other non-mechanical structures and surfaces, etc;

GROUP 9: Use of supplied air respirators

FOOTNOTE:

a. PAID HOLIDAYS: Memorial Day, Labor Day, Thanksgiving Day

PAIN0004-009 05/01/2024

TOWNSHIPS OF HARTLAND, LOCKPORT NORTH TONAWANDA, NEWFANE,

PENDLETON, ROYALTON, SOMERSET and the eastern halves of CAMBRIA and WILSON

Rates Fringes

Painters:

BRUSH & ROLLER..............$ 31.37 27.91

DRYWALL/TAPING..............$ 32.86 27.52

PAIN0004-010 05/01/2017

TOWNSHIPS OF LEWISTON, NIAGARA FALLS, PORTER, WHEATFIELD and the western halves of CAMBRIA and WILSON

Rates Fringes

Painters:

Painters....................$ 25.95 23.69 Tapers/Dry Wall.............$ 26.45 23.69

PAIN0004-012 05/01/2023

Rates Fringes

GLAZIER..........................$ 30.48 26.34

PLAS0111-003 07/01/2023

Rates Fringes

CEMENT FINISHER..................$ 32.45 34.17

PLASTERER........................$ 30.15 20.49

PLUM0022-005 04/29/2024

Rates Fringes

Plumber and Steamfitter

ZONE 1......................$ 42.20 29.80

ROOF0074-002 06/01/2024

Rates Fringes

Roofers:

Composition.................$ 34.96 26.03 Slate & Tile................$ 35.11 26.03

SHEE0071-002 05/27/2024

Rates Fringes

Sheet metal worker...............$ 39.50 29.18

WELDERS - Receive rate prescribed for craft performing operation to which welding is incidental.

Note: Executive Order (EO) 13706, Establishing Paid Sick Leave for Federal Contractors applies to all contracts subject to the Davis-Bacon Act for which the contract is awarded (and any solicitation was issued) on or after January 1, 2017. If this contract is covered by the EO, the contractor must provide employees with 1 hour of paid sick leave for every 30 hours they work, up to 56 hours of paid sick leave each year.

Employees must be permitted to use paid sick leave for their own illness, injury or other health-related needs, including preventive care; to assist a family member (or person who is like family to the employee) who is ill, injured, or has other health-related needs, including preventive care; or for reasons resulting from, or to assist a family member (or person who is like family to the employee) who is a victim of, domestic violence, sexual assault, or stalking. Additional information on contractor requirements and worker protections under the EO is available at https://www.dol.gov/agencies/whd/government-contracts.

Unlisted classifications needed for work not included within the scope of the classifications listed may be added after award only as provided in the labor standards contract clauses (29CFR 5.5 (a) (1) (iii)).

The body of each wage determination lists the classifications and wage rates that have been found to be prevailing for the type(s) of construction and geographic area covered by the wage determination. The classifications are listed in alphabetical order under rate identifiers indicating whether the particular rate is a union rate (current union negotiated rate), a survey rate, a weighted union average rate, a state adopted rate, or a supplemental classification rate.

Union Rate Identifiers

A four-letter identifier beginning with characters other than ""SU"", ""UAVG"", ?SA?, or ?SC? denotes that a union rate was prevailing for that classification in the survey. Example:

PLUM0198-005 07/01/2024. PLUM is an identifier of the union whose collectively bargained rate prevailed in the survey for this classification, which in this example would be Plumbers.

0198 indicates the local union number or district council number where applicable, i.e., Plumbers Local 0198. The next number, 005 in the example, is an internal number used in processing the wage determination. The date, 07/01/2024 in the example, is the effective date of the most current negotiated rate.

Union prevailing wage rates are updated to reflect all changes over time that are reported to WHD in the rates in the collective bargaining agreement (CBA) governing the classification.

Union Average Rate Identifiers

The UAVG identifier indicates that no single rate prevailed for those classifications, but that 100% of the data reported for the classifications reflected union rates. EXAMPLE:

UAVG-OH-0010 01/01/2024. UAVG indicates that the rate is a weighted union average rate. OH indicates the State of Ohio.

The next number, 0010 in the example, is an internal number used in producing the wage determination. The date, 01/01/2024 in the example, indicates the date the wage determination was updated to reflect the most current union average rate.

A UAVG rate will be updated once a year, usually in January, to reflect a weighted average of the current rates in the collective bargaining agreements on which the rate is based.

Survey Rate Identifiers

The ""SU"" identifier indicates that either a single non-union rate prevailed (as defined in 29 CFR 1.2) for this classification in the survey or that the rate was derived by computing a weighted average rate based on all the rates reported in the survey for that classification. As a weighted average rate includes all rates reported in the survey, it may include both union and non-union rates. Example: SUFL2022-007 6/27/2024. SU indicates the rate is a single non-union prevailing rate or a weighted average of survey data for that classification. FL indicates the State of Florida. 2022 is the year of the survey on which these classifications and rates are based. The next number, 007 in the example, is an internal number used in producing the wage determination. The date, 6/27/2024 in the example, indicates the survey completion date for the classifications and rates under that identifier.

?SU? wage rates typically remain in effect until a new survey is conducted. However, the Wage and Hour Division (WHD) has the discretion to update such rates under 29 CFR 1.6(c)(1).

State Adopted Rate Identifiers

The ""SA"" identifier indicates that the classifications and prevailing wage rates set by a state (or local) government were adopted under 29 C.F.R 1.3(g)-(h). Example: SAME2023-007 01/03/2024. SA reflects that the rates are state adopted. ME refers to the State of Maine. 2023 is the year during which the state completed the survey on which the listed classifications and rates are based. The next number, 007 in the example, is an internal number used in producing the wage determination.

The date, 01/03/2024 in the example, reflects the date on which the classifications and rates under the ?SA? identifier took effect under state law in the state from which the rates were adopted.

WAGE DETERMINATION APPEALS PROCESS

1) Has there been an initial decision in the matter? This can be:

a) a survey underlying a wage determination

b) an existing published wage determination

c) an initial WHD letter setting forth a position on a wage determination matter

d) an initial conformance (additional classification and rate) determination

On survey related matters, initial contact, including requests for summaries of surveys, should be directed to the WHD Branch of Wage Surveys. Requests can be submitted via email to davisbaconinfo@dol.gov or by mail to:

Branch of Wage Surveys Wage and Hour Division U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210

Regarding any other wage determination matter such as conformance decisions, requests for initial decisions should be directed to the WHD Branch of Construction Wage Determinations.

Requests can be submitted via email to BCWD-Office@dol.gov or by mail to:

Branch of Construction Wage Determinations Wage and Hour Division U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210

2) If an initial decision has been issued, then any interested party (those affected by the action) that disagrees with the decision can request review and reconsideration from the Wage and Hour Administrator (See 29 CFR Part 1.8 and 29 CFR Part 7).

Requests for review and reconsideration can be submitted via email to dba.reconsideration@dol.gov or by mail to:

Wage and Hour Administrator U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210

The request should be accompanied by a full statement of the interested party's position and any information (wage payment data, project description, area practice material, etc.) that the requestor considers relevant to the issue.

3) If the decision of the Administrator is not favorable, an interested party may appeal directly to the Administrative Review Board (formerly the Wage Appeals Board). Write to:

Administrative Review Board U.S. Department of Labor 200 Constitution Avenue, N.W.

Washington, DC 20210.

END OF GENERAL DECISION"

SECTION 07 92 00

JOINT SEALANTS

AMDT 0002

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C509 (2006; R 2021) Standard Specification for Elastomeric Cellular Preformed Gasket and Sealing Material

ASTM C734 (2015; R 2019) Standard Test Method for Low-Temperature Flexibility of Latex Sealants After Artificial Weathering

ASTM C919 (2022) Standard Practice for Use of Sealants in Acoustical Applications

ASTM C920 (2018) Standard Specification for Elastomeric Joint Sealants

ASTM C1193 (2016) Standard Guide for Use of Joint Sealants

ASTM C1311 (2022) Standard Specification for Solvent Release Sealants

ASTM C1521 (2019; R 2020) Standard Practice for Evaluating Adhesion of Installed Weatherproofing Sealant Joints

ASTM D217 (2021a) Standard Test Methods for Cone Penetration of Lubricating Grease

ASTM D1056 (2020) Standard Specification for Flexible Cellular Materials - Sponge or Expanded Rubber

ASTM D1667 (2022) Standard Specification for Flexible Cellular Materials - Poly (Vinyl Chloride) Foam (Closed-Cell)

ASTM E84 (2023) Standard Test Method for Surface Burning Characteristics of Building Materials

ASTM E90 (2023) Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements

SECTION 07 92 00 Page 1

CERTIFIED FINAL - AMDT 0002

CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)

CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS SCS Global Services (SCS) Indoor Advantage

SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)

SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications

UNDERWRITERS LABORATORIES (UL)

UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

1.2 SUBMITTALS

Government approval is required for submittals with a "G" classification.

Submittals not having a "G" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-03 Product Data

Sealants; G

Primers; G

Bond Breakers; G

Backstops; G

Caulking; G

Cleaning Solvents; G

SD-06 Test Reports

Field Adhesion; G

SD-04 Samples

Color Charts; G

1.3 PRODUCT DATA

Include storage requirements, shelf life, curing time, instructions for mixing and application, and accessories. Provide manufacturer's Safety Data Sheets (SDS) for each solvent, primer and sealant material proposed.

SECTION 07 92 00 Page 2

1.4 CERTIFICATIONS

1.4.1 Indoor Air Quality Certifications

Submit required indoor air quality certifications in one submittal package.

1.4.1.1 Adhesives and Sealants

Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.

1.5 ENVIRONMENTAL CONDITIONS

Apply sealant when the ambient temperature is between 40 and 90 degrees F.

1.6 DELIVERY AND STORAGE

Deliver materials to the jobsite in unopened manufacturers' sealed shipping containers, with brand name, date of manufacture, color, and material designation clearly marked thereon. Label elastomeric sealant containers to identify type, class, grade, and use. Handle and store materials in accordance with manufacturer's printed instructions. Prevent exposure to foreign materials or subjection to sustained temperatures exceeding 90 degrees F or lower than 0 degrees F. Keep materials and containers closed and separated from absorptive materials such as wood and insulation.

1.7 QUALITY ASSURANCE

1.7.1 Compatibility with Substrate

Verify that each sealant is compatible for use with each joint substrate in accordance with sealant manufacturer's printed recommendations for each application.

1.7.2 Joint Tolerance

Provide joint tolerances in accordance with manufacturer's printed instructions.

1.7.3 Mock-Up

Provide a mock-up of each type of sealant using materials, colors, and techniques approved for use on the project. Approved mock-ups may be incorporated into the Work.

1.7.4 Adhesion

Provide in accordance with ASTM C1193 or ASTM C1521.

SECTION 07 92 00 Page 3

PART 2 PRODUCTS

2.1 SEALANTS

Provide sealant products that have been tested, found suitable, and documented as such by the manufacturer for the particular substrates to which they will be applied.

2.1.1 Interior Sealants

Provide ASTM C920, Type S or M, Grade NS, Class 12.5, Use NT. Provide sealant products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Location(s) and color(s) of sealant for the following (Note, color "as selected" refers to Government selection of color from manufacturer's full range of color options):

LOCATION COLOR

a. Small voids between walls or partitions and adjacent lockers, casework, shelving, door frames, built-in or surface mounted equipment and fixtures, and similar items.

As selected

b. Perimeter of frames at doors, windows, and access panels which adjoin exposed interior concrete and masonry surfaces.

As selected

c. Joints of interior masonry walls and partitions which adjoin columns, pilasters, concrete walls, and exterior walls unless otherwise detailed.

As selected

d. Joints between edge members for acoustical tile and adjoining vertical surfaces.

As selected

e. Interior locations, not otherwise indicated or specified, where small voids exist between materials specified to be painted.

As selected

2.1.2 Exterior Sealants

For joints in vertical surfaces, provide ASTM C920, Type S or M, Grade NS, Class 25, Use NT. For joints in horizontal surfaces, provide ASTM C920, Type S or M, Grade P, Class 25, Use T. Provide location(s) and color(s) of sealant as follows (Note, color "as selected" refers to Government selection of color from manufacturer's full range of color options):

SECTION 07 92 00 Page 4

LOCATION COLOR

a. Joints and recesses formed where frames and subsills of windows, doors, louvers, and vents adjoin masonry, concrete, or metal frames. Use sealant at both exterior and interior surfaces of exterior wall penetrations.

As selected

b. Joints between new and existing exterior masonry walls.

Match adjacent mortar color

c. Masonry joints where shelf angles occur. As selected

e. Expansion and control joints. As selected

f. Interior face of expansion joints in exterior concrete or masonry walls where metal expansion joint covers are not required.

As selected

g. Voids where items pass through exterior walls.

As selected

h. Metal reglets, where flashing is inserted into masonry joints, and where flashing is penetrated by coping dowels.

As selected

i. Metal-to-metal joints where sealant is indicated or specified.

As selected

j. Joints between ends of gravel stops, fascia, copings, and adjacent walls.

As selected

2.1.3 Floor Joint Sealants

ASTM C920, Type S or M, Grade P, Class 25, Use T. Provide sealant products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Provide location(s) and color(s) of sealant as follows (Note, color "as selected" refers to Government selection of color from manufacturer's full range of color options):

LOCATION COLOR

a. Seats of metal thresholds for exterior doors.

Gray

SECTION 07 92 00 Page 5

LOCATION COLOR

b. Control and expansion joints in floors, slabs, ceramic tile, and walkways.

Match adjacent floor finish color

2.1.4 Acoustical Sealants

Rubber or polymer based acoustical sealant in accordance with ASTM C919 to have a flame spread of 25 or less and a smoke developed rating of 50 or less when tested in accordance with ASTM E84. Provide non-staining acoustical sealant with a consistency of 250 to 310 when tested in accordance with ASTM D217. Acoustical sealant must remain flexible and adhesive after 500 hours of accelerated weathering as specified in ASTM C734. Provide sealant products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 .

2.1.5 Preformed Foam Expansion Joints

Joints shall be silicone pre-coated, preformed, pre-compressed, self-expanding, sealant system. Expanding foam to be cellular foam impregnated with a water-based, non-drying, 100% acrylic dispersion. Seal shall combine factory-applied, low-modulus silicone and a backing of acrylic-impregnated expanding foam into a unified hybrid sealant system.

Color to be selected by the Contracting Officer from the manufacturer's full range of colors for exposed locations.

Joints shall be capable of 50% expansion and 50% contraction of the joint width indicated. Products shall be certified of withstanding 150°F (65°C) for 3 hours while compressed down to the minimum of movement capability dimension of the product (-50% of nominal material size) without evidence of any bleeding of impregnation medium from the material; and that the same material after the heat stability test and after first being cooled to room temperature will subsequently self-expand to the maximum of movement capability dimension of the product (+50% of nominal material size) within 24 hours at room temperature 68°F (20°C).

2.1.6 Spray-Applied Acoustical Sealant

Spray-applied sealant must be a water-based acrylic capable of +/- 12.5% movement that forms a flexible membrane. It must be tested in accordance with ASTM E90 to achieve a sound transmission classification (STC) of 56 (per tested construction type.) It must have a flame spread of 10 or less and smoke spread of 5 or less when tested per ASTM E84 for surface burning characteristics.

*********************************************************************** *****Amdt. #0002

2.2 PRIMERS

Non-staining, quick drying type and consistency as recommended by the

SECTION 07 92 00 Page 6

CERTIFIED FINAL - AMDT 0002

Amdt. #0002**************************************************************************** sealant manufacturer for the particular application. Provide primers for interior applications that meet the indoor air quality requirements of the paragraph INTERIOR SEALANTS above.

2.3 BOND BREAKERS

Type and consistency as recommended by the sealant manufacturer to prevent adhesion of the sealant to the backing or to the bottom of the joint.

Provide bond breakers for interior applications that meet the indoor air quality requirements of the paragraph INTERIOR SEALANTS above.

2.4 BACKSTOPS

Provide glass fiber roving, neoprene, butyl, polyurethane, or polyethylene foams free from oil or other staining elements as recommended by sealant manufacturer. Provide 25 to 33 percent oversized backing for closed cell and 40 to 50 percent oversized backing for open cell material, unless otherwise indicated. Provide backstop material that is compatible with sealant. Do not use oakum or other types of absorptive materials as backstops.

2.4.1 Rubber

Provide in accordance with ASTM D1056, Type 2, closed cell, Class A, Grade 1, round cross section for cellular rubber sponge backing.

2.4.2 PVC

Provide in accordance with ASTM D1667, Grade VO 12, open-cell foam, round cross section for polyvinyl chloride (PVC) backing.

2.4.3 Synthetic Rubber

Provide in accordance with ASTM C509, Option I, Type I preformed rods or tubes for synthetic rubber backing.

2.4.4 Neoprene

Provide in accordance with ASTM D1056, closed cell expanded neoprene cord Type 2, Class C, Grade 2C2 for neoprene backing.

2.4.5 Butyl Rubber Based

Provide in accordance with ASTM C1311, from a single component, with solvent release. Color as selected from manufacturer's full range of color choices.

2.4.6 Silicone Rubber Base

Provide in accordance with ASTM C920, from a single component, with solvent release, Non-sag, Class 25. Color as selected from manufacturer's full range of color choices.

2.5 CLEANING SOLVENTS

Provide type(s) recommended by the sealant manufacturer and in accordance with environmental requirements herein.. Provide solvents for interior applications that meet the indoor air quality requirements of the paragraph INTERIOR SEALANTS above.

SECTION 07 92 00 Page 7

PART 3 EXECUTION

3.1 FIELD QUALITY CONTROL

Perform a field adhesion test in accordance with manufacturer's instructions and ASTM C1193, Method A or ASTM C1521, Method A, Tail Procedure. Remove sealants that fail adhesion testing; clean substrates, reapply sealants, and re-test. Test sealants adjacent to failed sealants.

Submit field adhesion test report indicating tests, locations, dates, results, and remedial actions taken.

3.2 SURFACE PREPARATION

Prepare surfaces according to manufacturer's printed installation instructions. Clean surfaces from dirt, frost, moisture, grease, oil, wax, lacquer, paint, or other foreign matter that would destroy or impair adhesion. Remove oil and grease with solvent; thoroughly remove solvents prior to sealant installation. Wipe surfaces dry with clean cloths. When resealing an existing joint, remove existing caulk or sealant prior to applying new sealant. For surface types not listed below, provide in accordance with sealant manufacturer's printed instructions for each specific surface.

3.2.1 Steel Surfaces

Remove loose mill scale by sandblasting or, if sandblasting is impractical or would damage finished work, scraping and wire brushing. Remove protective coatings by sandblasting or using a residue free solvent.

Remove resulting debris and solvent residue prior to sealant installation.

3.2.2 Aluminum or Bronze Surfaces

Remove temporary protective coatings from surfaces that will be in contact with sealant. When masking tape is used as a protective coating, remove tape and residual adhesive prior to sealant application. For removing protective coatings and final cleaning, use non-staining solvents recommended by the manufacturer of the item(s) containing aluminum or bronze surfaces.

3.2.3 Concrete and Masonry Surfaces

Where surfaces have been treated with curing compounds, oil, or other such materials, remove materials by sandblasting or wire brushing. Remove laitance, efflorescence and loose mortar from the joint cavity. Remove resulting debris prior to sealant installation.

3.2.4 Wood Surfaces

Ensure wood surfaces that will be in contact with sealants are free of splinters, sawdust and other loose particles.

3.3 SEALANT PREPARATION

Do not add liquids, solvents, or powders to sealants. Mix multicomponent elastomeric sealants in accordance with manufacturer's printed instructions.

SECTION 07 92 00 Page 8

3.4 APPLICATION

3.4.1 Joint Width-To-Depth Ratios

Acceptable Ratios:

JOINT WIDTH JOINT DEPTH

Minimum Maximum

For metal, glass, or other nonporous surfaces:

1/4 inch (minimum) 1/4 inch 1/4 inch over 1/4 inch 1/2 of width Equal to width

For wood, concrete, masonry:

1/4 inch (minimum) 1/4 inch 1/4 inch over 1/4 inch to 1/2 inch 1/4 inch Equal to width over 1/2 inch to 1 inch 1/2 inch 5/8 inch

Over 1 inch prohibited

Unacceptable Ratios: Where joints of acceptable width-to-depth ratios have not been provided, clean out joints to acceptable depths and grind or cut to acceptable widths without damage to the adjoining work. Grinding is prohibited at metal surfaces.

3.4.2 Unacceptable Sealant Use

Do not install sealants in lieu of other required building enclosure weatherproofing components such as flashing, drainage components, and joint closure accessories, or to close gaps between walls, floors, roofs, windows, and doors, that exceed acceptable installation tolerances.

Remove sealants that have been used in an unacceptable manner and correct building enclosure deficiencies to comply with contract documents requirements.

3.4.3 Masking Tape

Place masking tape on the finished surface on one or both sides of joint cavities to protect adjacent finished surfaces from primer or sealant smears. Remove masking tape within 10 minutes of joint filling and tooling.

3.4.4 Backstops

Provide backstops dry and free of tears or holes. Tightly pack the back or bottom of joint cavities with backstop material to provide joints in specified depths. Provide backstops where indicated and where backstops are not indicated but joint cavities exceed the acceptable maximum depths specified in JOINT WIDTH-TO-DEPTH RATIOS Table.

SECTION 07 92 00 Page 9

3.4.5 Primer

Clean out loose particles from joints immediately prior to application

of. Apply primer to joints in concrete masonry units, wood, and other porous surfaces in accordance with sealant manufacturer's printed instructions. Do not apply primer to exposed finished surfaces.

3.4.6 Bond Breaker

Provide bond breakers to surfaces not intended to bond in accordance with, sealant manufacturer's printed instructions for each type of surface and sealant combination specified.

3.4.7 Sealants

Provide sealants compatible with the material(s) to which they are applied. Do not use a sealant that has exceeded its shelf life or has jelled and cannot be discharged in a continuous flow from the sealant gun. Apply sealants in accordance with the manufacturer's printed instructions with a gun having a nozzle that fits the joint width. Work sealant into joints so as to fill the joints solidly without air pockets.

Tool sealant after application to ensure adhesion. Apply sealant uniformly smooth and free of wrinkles. Upon completion of sealant application, roughen partially filled or unfilled joints, apply additional sealant, and tool smooth as specified. Apply sealer over sealants in accordance with the sealant manufacturer's printed instructions.

Amdt. #0002****************************************************************************

3.5 SPRAY-APPLIED ACOUSTICAL SEALANTS

Comply with manufacturer's instructions for installation of spray-applied acoustical sealant at top-of-wall and other joints as indicated. Seal holes and voids to ensure an air and sound-resistant seal. Thickness of cured spray-applied membrane must match manufacturer's tested assembly.

************************************************************************* *** Amdt. #0002

3.6 PROTECTION AND CLEANING

3.6.1 Protection

Protect areas adjacent to joints from sealant smears. Masking tape may be used for this purpose if removed 5 to 10 minutes after the joint is filled and no residual tape marks remain.

3.6.2 Final Cleaning

Upon completion of sealant application, remove remaining smears and stains and leave the work in a clean and neat condition.

a. Masonry and Other Porous Surfaces: Immediately remove fresh sealant that has been smeared on adjacent masonry, rub clean with a solvent, and remove solvent residue, in accordance with sealant manufacturer's printed instructions. Allow excess sealant to cure for 24 hours then

SECTION 07 92 00 Page 10 remove by wire brushing or sanding. Remove resulting debris.

b. Metal and Other Non-Porous Surfaces: Remove excess sealant with a solvent moistened cloth. Remove solvent residue in accordance with solvent manufacturer's printed instructions.

-- End of Section --

SECTION 07 92 00 Page 11

THIS PAGE INTENTIONALLY LEFT BLANK

SECTION 07 92 00 Page 12

SECTION 23 09 00

INSTRUMENTATION AND CONTROL FOR HVAC

AMDT 0002

PART 1 GENERAL

1.1 SUMMARY

Amdt. #0002***************************************************************

Provide a complete Direct Digital Control (DDC) system, suitable for the control of the heating, ventilating and air conditioning (HVAC) and other building-level systems as indicated and shown and in accordance with Section 23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC, Section 23 09 93 SEQUENCES OF OPERATION FOR HVAC CONTROL, and Section 23 09 23.02

BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL SYSTEMS

for BACnet systems, and other referenced Sections.

************************************************************** ** Amdt. #0002

1.1.1 Proprietary Systems

1.1.1.1 Proprietary Systems Exempted From Open Protocol Requirements

The following systems are specifically exempted from the open protocol requirements of Section 23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC

AND OTHER BUILDING CONTROL SYSTEMS:

a. A simple split (DX) system consisting of a single indoor unit and a single outdoor unit from the same manufacturer.

b. Systems in Table I (previously approved by the designer in accordance with UFC 3-410-02).

TABLE I: Systems Approved to Use Proprietary Communications

System Type (Multi-Split/VRF or Chiller/Boiler Plant)

Proprietary Multi-Split Engineering Tool Software Required (for Multi-Split/VRF only)

c. A system (not already shown Table I) of multiple boilers or multiple chillers communicating with a proprietary network for which an approved request has been obtained and for which: all units are from the same manufacturer, they are all co-located in the same room, the network connecting them is fully contained in that room, and the units are operating using a common "plant" sequence of operation which stages the units in a manner that requires operational parameters be shared between them and which cannot be accomplished with a single lead-lag command from a third-party controller.

SECTION 23 09 00 Page 1

1.1.1.2 Implementation of Proprietary Systems

For proprietary systems exempted from open protocol requirements, a proprietary network and DDC hardware communicating via proprietary protocol are permitted. For these systems a building control network meeting the requirements of Section 23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL SYSTEMS must also be provided, along with a gateway or interface to connect the proprietary system to the open building control network.

The proprietary system gateway or interface must provide the required functionaliality as shown on the points schedule. Scheduling, alarming, trending, overrides, network inputs, network outputs and other protocol related requirements must be met on the open protocol control system as specified in Section 23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC

AND OTHER BUILDING CONTROL SYSTEMS.

1.1.1.3 Proprietary Multi-Split Engineering…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .