This document is a Request for Proposal (RFP) Solicitation for the Design-Bid-Build construction of the 10th Flight Test Squadron Operations Building at Tinker Air Force Base, Oklahoma. The solicitation is for a Firm-Fixed-Price (FFP) contract with a total small business set-aside. The project is for the construction of a 15,200 square foot squadron operations building, including administrative offices, aircrew spaces, restrooms, lockers, storage, and conference/testing areas. The construction magnitude is anticipated to be between $10 million and $25 million. The contract duration is estimated at 480 calendar days. Interested offerors must be registered in the System for Award Management (SAM) database to be eligible for award. The point-of-contact for this procurement is Contract Specialist Ryan King.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GROUND LEVEL
100' - 0"
STANDING SEAM METAL ROOF
WITH GUTTERS AND DOWNSPOUTS
SLOPE: 3/12
PREFINISHED INSULATED METAL
WALL PANELS
ALUMINUM STOREFRONT
WINDOW - TYP
4" SPLIT FACE CMU119118
123B 124B 132A
W1W1W1W1W1W1W1
GUTTER AND DOWNSPOUT - TYP
CANOPY
CJ CJ CJ CJ
5 3.9 4710 89 311 3.75.45.5 212 113
EAVE HEIGHT 2
113' - 5"
GROUND LEVEL
100' - 0"
STANDING SEAM METAL ROOF
WITH GUTTERS AND DOWNSPOUTS
SLOPE: 3/12
PREFINISHED INSULATED METAL
WALL PANELS
ALUMINUM STOREFRONT
WINDOWS - TYP
4" SPLIT FACE CMU
W1W1W1W1W1W1W1W1W1W1W1
GUTTER AND DOWNSPOUT - TYP
CJCJCJCJCJ
53.94 7 108 93 113.7 5.4 5.52 121 13
EAVE HEIGHT 2
113' - 5"
EAVE HEIGHT 3
116' - 5" F5
A-742
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-201
E X
T E
R
IO
R B
U
IL
D
IN
G E
L E
V A
T
IO
N S
M O
W E
N S
B Y
M O
W E
N S
B Y
B M
A R
IN
O
J K
L
IN
G
SCALE: 1/8" = 1'-0"
A1
BUILDING ELEVATION - NORTH
SCALE: 1/8" = 1'-0"
D1
BUILDING ELEVATION - SOUTH
0 4' 8' 16'
0 4' 8' 16'
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
GUTTER 7"W x 7"D AND 5" DIA. ROUND
DOWNSPOUT W/ SPLASH BLOCK - TYP
53.94 7 108 93.7 5.4 5.5
E
1' - 0" 34' - 10" 1' - 0" 1' - 0" 38' - 7" 1' - 0"
36' - 10" 29' - 3" 40' - 7"
/4
/4
GUTTER 7"W x 7"D AND 5" DIA. ROUND
DOWNSPOUT W/ SPLASH BLOCK - TYP
GUTTER 7"W x 7"D AND 5" DIA. ROUND
DOWNSPOUT W/ SPLASH BLOCK - TYP
GROUND FLOOR
100' - 0"
EAVE HEIGHT 1
112' - 0"
PREFINISHED STANDING SEAM
METAL ROOF - DARK BRONZE
INSULATED METAL SOFFIT
PANELS - DARK BRONZE
PREFINISHED SHEET METAL GUTTER
AND DOWNSPOUT - TYP
STEEL TUBE COLUMN
RE: STRUCTURAL -
PAINT TO MATCH METAL WALL
PANEL FINISH
CONCRETE COLUMN BASE
RE: STRUCTURAL -
PAINT TO MATCH SPLIT FACE
BLOCK COLOR
SPLASH BLOCK
ROADWAY, CURB
AND SIDEWALK PER
CIVIL
A1
A-423 A4
A-423
DE
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-422
C A
N O
P Y
R O
O F
P L A
N A
N D
S E
C T
IO
N
M O
W E
N S
B Y
M O
W E
N S
B Y
B M
A R
IN
O
J K
L
IN
G
SCALE: 1/4" = 1'-0"
D1
CANOPY ROOF PLAN
SCALE: 3/8" = 1'-0"
A3
CANOPY SECTION
0 2' 4' 8'
0 2' 4' 6'
S L O
P E
:1
S L O
P E
:1
A
M E
N D
M E
N T
A
P R
IL
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
CONT. SEALANT
INSULATED METAL SOFFIT
PANELS - DARK BRONZE
METAL STUD LAYER
CONT. CLIP ANGLE EACH
SIDE OF SOFFIT PANEL
SELF ADHERED MEMBRANE
AIR BARRIER EXTEND TO
BENT PLATE
FLEXIBLE FOAM ROD (CONT).
EXTEND FOAM ROD AND AIR
BARRIER AROUND METAL
PANEL PENETRATION
DEFLECTION CONNECTION
WITH METAL PLATE AND
BENT PLATE WITH BATT
INSULATION FILL
RIGID INSULATION
STEEL PURLINS
RE: PEMB MFR
METAL DECK
1/2" GLASS-MAT
GYPSUM COVER
BOARD
PANEL CLIP
WEBBED MASTIC
(UNDER CLIP)
STEEL I-BEAMS
RE: PEMB MFR
METAL PANEL ON METAL
FURRING STUDS WITH GYP
BOARD INSIDE
ICE AND WATER
BARRIER BETWEEN
FLASHING GIRTS
PANEL CLIP
NON-CURLING
BUTYL SEALANT
WEBBED MASTIC
(UNDER CLIP)
EDGE STIFFENER
FASCIA FLASHING
PANEL END FLASHING
CONT. SEALANT
METAL DRIP EDGE
INSULATED METAL SOFFIT
PANELS - DARK BRONZE
1/4" SCREWS AT
EACH BRACKET
GUTTER
BRACKET
GUTTER
STRAP
METAL STUD LAYER
STEEL BEAM
RE: PEMB MFR
STEEL PURLINS
RE: PEMB MFR
CONT. SEALANT EACH
END OF SOFFIT
SHIM PER
FASTENER
ICE AND WATER
BARRIER BETWEEN
FLASHING GIRTS
1/2" GLASS-MAT
GYPSUM COVER
BOARD
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y U
.S A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K
A N
S A
S C
IT
Y
M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-423
C A
N O
P Y
D E
T A
IL
S
M O
W E
N S
B Y
M O
W E
N S
B Y
B M
A R
IN
O
J K
L
IN
G
SCALE: 1 1/2" = 1'-0"
A4
CANOPY CONNECTION DETAIL
SCALE: 1 1/2" = 1'-0"
A1
CANOPY EAVE DETAIL
0 1/2' 1' 1 1/2' 0 1/2' 1' 1 1/2'
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
C
C.3
5'
/2
5'
1'
/2
1' - 10" 8' - 10 1/2" 1' - 8 1/2"
A-431A1
MECHANICAL
EQUIPMENT,
REFER MECH
MECHANICAL
PLATFORM
ABOVE
PAINTED STEEL
LADDER
PAINTED STEEL
COLUMN, REFER
STRUCTURAL
A-431
A4
C
C.3
5'
/2
5'
1'
/2
1' - 6" 9' - 0" 1' - 6"
A-431A1
(2
E Q
R E
M O
V A
B
LE
R A
IL
IN
G S
4'
(1
R E
M O
V A
B
LE
R A
IL
IN
G
2'
2'
/2
1'
1/ 2"
MECHANICAL UNIT
REFER MECH.
STEEL GRATE FLOORING,
REFER STRUCTURAL
FIXED PAINTED
STEEL GUARDRAIL
A-431
A4
NOTE: PAINT LADDER, GUARDRAILS
AND EXPOSED STEEL AT MEZZANINE
COLOR PA-2.
GROUND LEVEL
100' - 0"
MECH PLATFORM
112' - 6"
C C.3
REMOVABLE STEEL
GUARDRAIL
FIXED STEEL
GUARDRAIL
REMOVABLE SAFETY
CHAIN
FIXED STEEL
LADDER
GROUND LEVEL
100' - 0"
MECH PLATFORM
112' - 6"
FIXED STEEL GUARDRAIL
FIXED STEEL
LADDER
E Q
E
Q
4" 4"
CONT. 1 1/2" DIA.
PAINTED STEEL PIPE
RAILING
GALV. STEEL GRATING
CONT. 1/4" STEEL
TOE PLATE WELD TO
POST & STEEL ANGLE
1 1/2" DIA STEEL PIPE
POST EQUALLY
SPACED 5'-0" O.C. MAX
NOTE:
PAINT ALL EXPOSED
SURFACES AT
RAILING
PLATFORM
RE: PLAN
PLATFORM
SUPPORT
FRAMING
3'
RAILING WELD TO
CHANNEL
E Q
E
Q
4" 4"
CONT. 1 1/2" DIA.
PAINTED STEEL PIPE
RAILING
CONT. 1/4" STEEL
TOE PLATE WELD TO
POST & STEEL ANGLE
1 1/2" DIA STEEL PIPE
POST EQUALLY
SPACED 5'-0" O.C. MAX
NOTE:
PAINT ALL EXPOSED
SURFACES AT
RAILING
PLATFORM
RE: PLAN
4" x 1/4" STEEL
PIPE RAIL INSERT
GALV. STEEL
GRATING
PLATFORM
SUPPORT
FRAMING
3'
N
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
A B
KEYPLAN
SCALE: NTS
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-431
M E
C H
A N
IC
A
L P
L A
T F
O R
M P
L A
N S
A N
D D
E T
A
IL
S
M O
W E
N S
B Y
M O
W E
N S
B Y
B M
A R
IN
O
J K
L
IN
G
0 2' 4' 6' 0 2' 4' 6'SCALE: 3/8" = 1'-0"
D1
GROUND FLOOR MECH PLATFORM PLAN
SCALE: 3/8" = 1'-0"
D4
MECH PLATFORM PLAN
SCALE: 1/2" = 1'-0"
A1
MECH. PLATFORM EAST ELEVATION
SCALE: 1/2" = 1'-0"
A4
MECH. PLATFORM SOUTH ELEVATION
0 1' 2' 4' 0 1' 2' 4'
SCALE: 1" = 1'-0"
D7
PLATFROM GUARDRAIL - FIXED
0 1/2' 1' 2'
SCALE: 1" = 1'-0"
B7
PLATFORM GUARDRAIL - REMOVABLE
0 1/2' 1' 2'
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
COL.
COL.
5/8" GYP BOARD
3 5/8" METAL
STUDS
BATT INSULATION
INSIDE FACE OF
GIRTS
4" CMU VENEER
1/2" FIBERGLASS MAT GYP BD
SHEATHING
SELF-ADHERING AIR BARRIER
RE: PLAN
COL.
COL.
4" CMU VENEER
5/8" GYP BOARD
3 5/8" METAL STUDS
BATT INSULATION 1/2" FIBERGLASS MAT GYP BD
SHEATHING
SELF-ADHERING AIR BARRIER
INSIDE FACE
OF GIRTS
1' - 0"
3 5/8" METAL STUDS,
INSTALL BETWEEN
HORIZONTAL GIRTS
R-5 RIGID INSULATION
COL.
COL.
4" CMU VENEER
5/8" GYP BOARD
3 5/8" METAL
STUDS
BATT INSULATION
1/2" FIBERGLASS MAT GYP BD
SHEATHING
WALL PER SCHEDULE
RE: PLAN
INSIDE FACE OF
GIRTS
SELF-ADHERING AIR BARRIER
COL.
COL.
5/8" GYP BOARD
3 5/8" METAL
STUDS
BATT INSULATION
INSIDE FACE
OF GIRTS
4" CMU VENEER
1/2" FIBERGLASS MAT GYP BD
SHEATHING
SELF-ADHERING AIR BARRIER
RE: PLAN
CMU WALL WITH FURRING
WALL AND 5/8" GYPSUM
BOARD EACH SIDE
3 - 5/8" METAL STUD WITH
ONE LAYER 5/8" GYPSUM
BOARD ON ONE SIDE,
TWO LAYERS OTHER SIDE
A
1/2" GYP
SHEATHING
3 5/8" METAL
STUDS
BATT INSULATION
4" CMU VENEER
PREFINISHED SHEET
METAL FLASHING
INSULATED METAL WALL
PANEL
3/8" BACKER ROD AND
SEALANT
2' - 0"
/4
6" METAL STUDS
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-451
P L A
N D
E T
A
IL
S
M O
W E
N S
B Y
M O
W E
N S
B Y
B M
A R
IN
O
J K
L
IN
G
SCALE: 1" = 1'-0"
C7
COLUMN FURRING
SCALE: 1" = 1'-0"
A5
CORNER COLUMN FURRING
0 1/2' 1' 2' 0 1/2' 1' 2'
SCALE: 1" = 1'-0"
A4
WALL ON COLUMN FURRING
SCALE: 1" = 1'-0"
E7
WALL ALIGNED TO COLUMN FURRING
SCALE: 1" = 1'-0"
A7
WALL ALIGNED TO CMU DETAIL
0 1/2' 1' 2'
0 1/2' 1' 2'
0 1/2' 1' 2'
SCALE: 1 1/2" = 1'-0"
E4
PLAN DETAIL
0 1/2' 1' 1 1/2'
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
1 1
W
2Q R
B0
3_
Pl an s-
FL
A
SCHEDULE
DOOR PER A
B
S C
H E
D U
L E
D O
O R
P E
R
A
SCHEDULE
DOOR PER
A
B
S C
H E
D U
L E
D O
O R
P E
R
D O
O R
P E
R S
C H
E D
U L E
D A
SCHEDULE
DOOR PER
D O
O R
P E
R S
C H
E D
U L E
SCHEDULE
DOOR PER
D
A
B
A
F
1 2
C
D O
O R
P E
R S
C H
E D
U L E
SCHEDULE
DOOR PER
A A
B C
D
L
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-601
D O
O R
S C
H E
D U
L E
M O
W E
N S
B Y
M O
W E
N S
B Y
B M
A R
IN
O
J K
L
IN
G
DOOR SCHEDULE
DOOR
NUMBER
DOOR FRAME
ASSEMBLY
RATING STC
DETAIL
HARDWARE
SET REMARKS
SIZE
TYPE MATERIAL FINISH TYPE MATERIAL FINISH HEAD JAMB SILL
PAIR
DOOR WIDTH HEIGHT
GROUND FLOOR
101B PR. 3' - 5 1/2" 8' - 9 1/2" FL ALUM DRK BRONZE 2.2 ALUM DRK BRONZE - - E1/A-621
SIM
C1/A-621
SIM
A1/A-621
SIM
101C PR. 3' - 0" 7' - 0" FL-IN ALUM DRK BRONZE 2.1 ALUM DRK BRONZE - - E7/A-621 C7/A-621 E7/A-623 01
102A PR. 3' - 0" 7' - 0" FL ALUM DRK BRONZE 2.2 ALUM DRK BRONZE - - E1/A-621
SIM
C1/A-621
SIM
A1/A-621
SIM
102B PR. 3' - 0" 7' - 0" FL-IN ALUM DRK BRONZE 2.1 ALUM DRK BRONZE - - E7/A-621 C7/A-621 E7/A-623 01
103 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
104 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
105 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 06
106 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
107 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
108 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
109 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
110 PR. 3' - 5 1/2" 8' - 9 1/2" FL-IN ALUM DRK BRONZE 2.1 ALUM DRK BRONZE - - E7/A-621 C7/A-621 E7/A-623 01
111 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
112 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
113 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
114 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 03
116 PR. 2' - 6" 7' - 0" F-IN HM PAINT 1.1 HM PAINT - - E3/A-621 C3/A-621 A3/A-621 12
117 PR. 3' - 0" 7' - 0" F-IN HM PAINT 1.1 HM PAINT - - E3/A-621 C3/A-621 A3/A-621 12
118 - 3' - 0" 7' - 0" F-IN HM PAINT 1.1 HM PAINT - - E3/A-621 C3/A-621 A3/A-621 11
119 PR. 3' - 0" 7' - 0" F-IN HM PAINT 1.1 HM PAINT - - E3/A-621 C3/A-621 A3/A-621 13
120 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - STC 45 E1/A-622 C1/A-622 A1/A-622 04
121 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 4.1
122A PR. 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - STC 50 E5/A-621 C5/A-621 A5/A-621 05
122B - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 06
122C - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - STC 50 E5/A-621 C5/A-621 A5/A-621 04
123A PR. 3' - 0" 7' - 0" FL ALUM DRK BRONZE 2.2 ALUM PAINT - - E1/A-621 C1/A-621 A1/A-621 02
123B PR. 3' - 0" 7' - 0" FL-IN ALUM DRK BRONZE 2.1 ALUM DRK BRONZE - - E7/A-621 C7/A-621 E7/A-623 01
124A PR. 3' - 0" 7' - 0" FL ALUM DRK BRONZE 2.2 ALUM DRK BRONZE - - E1/A-621
SIM
C1/A-621
SIM
A1/A-621
SIM
124B PR. 3' - 0" 7' - 0" FL-IN ALUM DRK BRONZE 2.1 ALUM DRK BRONZE - - E7/A-621 C7/A-621 E7/A-623 01
125A - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 08
125B - 3' - 0" 7' - 0" F HM PAINT 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 07
126 - 3' - 0" 7' - 0" F STEEL PAINT 1.2 HM PAINT 90 MIN - E5/A-622 C5/A-622 A5/A-622 10 3
126A - 2' - 6" 7' - 0" L WD STAIN 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 06
127 - 3' - 0" 7' - 0" L WD STAIN 1.2 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 6.1
128 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 09
129 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 09
129A - 2' - 0" 3' - 0" F STEEL PAINT 1.2 STEEL PAINT 90 MIN - A7/A-622 E7/A-622 A7/A-622 10 2, 3
130 - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 6.2
131A - 3' - 0" 7' - 0" F WD STAIN 1.1 HM PAINT - - E1/A-621 C1/A-621 A1/A-621 08 1
131B - 3' - 0" 7' - 0" F HM PAINT 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 07
132A PR. 3' - 0" 7' - 0" FL-IN ALUM DRK BRONZE 2.1 ALUM DRK BRONZE - - E7/A-621 C7/A-621 E7/A-623 01
134 - 3' - 0" 7' - 0" F HM PAINT 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 07
135 - 3' - 0" 7' - 0" F HM PAINT 1.1 HM PAINT - - E5/A-621 C5/A-621 A5/A-621 07
136 - 3' - 0" 7' - 0" FS HM PAINT 0 - - - - - - - - 4
DOOR AND FRAME LEGEND
FINISH
FF-1* FACTORY FINISHED
PE-4 PAINT-EPOXY
MATERIAL
AL ALUMINUM
HM HOLLOW METAL
WD WOOD
SIZE
- SINGLE DOOR
PR PAIR OF DOORS
UPR UNEQUAL PAIR
*REFERENCE DOOR OR FRAME SPECIFICATION
**FIELD APPLY PER PAINT SPECIFICATION FOR
APPLICABLE SUBSTRATE AND EXPOSURE. REFER TO
FINISH LEGEND ON SHEET A-701 FOR FINISH
INFORMATION.
(DOOR FRAME)
TYPE A B
0 2" 2"
1.1 2" 2"
1.2 2" 4"
(FRAME WITH TRANSOM)
TYPE A B D #
2.1 2" 2" 24" 2
2.2 2" 4" 24" 1
(FLUSH PANEL)
TYPE DESCRIPTION
FS FLUSH PANEL POCKET
F-IN FLUSH PANEL INSULATED
F FLUSH PANEL
(FULL LITE)
TYPE DESCRIPTION A B C D #
FL FULL LITE 6" 10" 66" 8" 1
FL-IN FULL LITE INSULATED 6" 10" 66" 8" 2
(DOOR W/ LOUVERS)
TYPE DESCRIPTION A B C D
L LOUVERS 4" 1' - 0" 1' - 0" 5' - 0"
REMARKS:
1. DOOR TO BE PROVIDED WITH X10 LOCK.
2. SILL TO BE 2' - 0" AFF
3. DOOR TO MEET ICC 500 AND FEMA P-361 REQUIREMENTS.
4. POCKET DOOR
NOTES:
1. HOLLOW METAL DOOR FRAMES TO BE FACTORY PRIMED.
2. EXTERIOR HOLLOW METAL DOORS AND FRAMES TO BE FACTORY FINISHED.
3. EXTERIOR DOORS TO MEET CURRENT ATFP STANDARDS.
A
M E
N D
M E
N T
A
P R
IL
W
2Q R
B0
3_
Pl an s-
METAL LOUVER
CONT. SEALANT
INSULATED METAL
WALL PANEL
CONTINUOUS SHEET
METAL FLASHING
L 4 x4 x 1/4
SUPPORT AT
PERIMETER OF
OPENINGSL
O U
V E
R H
E
IG
H T
S E
E S
C H
E D
U L E
BIRD SCREEN
FRAME WIDTH
STEEL
CHANNEL BEYOND
RE: STRUCTURAL
STEEL GIRT PER
PEMB MFR
EXTEND JAMB
CHANNEL TO
NEXT GIRT
ABOVE DOOR
HEAD
SEALANT TYP.
ALUMINUM WINDOW
RE: SCHEDULE
W
IN
D O
W
H E
IG
H
T S
E E
S C
H E
D U
L E
INSULATED
METAL WALL
PANEL
CONTINUOUS
METAL SILL
FLASHING
HEAD CHANNEL
METAL STUD
AND GYPSUM
BOARD FURRING
RE: FLOOR
PLANS FOR
LOCATIONS
MINI BLIND
1 1/2"
W
IN
D O
W H
E
IG
H T
S E
E S
C H
E D
U L E
5/8" GYP BD
MTL STUD AND
GYP BD FURRING
RE: FLOOR PLANS
FOR LOCATIONS
6" MTL STUD TRACK
ALUMINUM SLIDING
TRANSACTION WINDOW
FRAME
4"
SOLID SURFACE SILL
WOOD SHIM
SEALANT - TYP BOTH SIDES
WINDOW WIDTH
SEE SCHEDULE
ALUMINUM SLIDING
TRANSACTION WINDOW FRAME
5/8" GYP BD
W/ CORNER
TRIM
6" MTL STUD
/2
1"
SOLID SURFACE COUNTER TOP
WOOD SHIM
SEALANT - TYP
BOTH SIDES
5/8" GYP BD
MTL STUD AND GYP
BD FURRING
RE: FLOOR PLANS
FOR LOCATIONS
6" MTL STUD
ALUMINUM SLIDING
TRANSACTION WINDOW
FRAME
W
IN
D O
W H
E
IG
H T
S E
E S
C H
E D
U L E
WOOD SHIM
SEALANT - TYP BOTH SIDES
PRE-FINISHED SILL
FLASHING SET IN BED OF
SEALANT - COLOR TO
MATCH WINDOW FRAME
METAL STUD AND
GYPSUM BOARD
FURRING
RE: FLOOR
PLANS FOR
LOCATIONS
SOLID SURFACE
SILL
W
IN
D
W
H
IG
H
T S
E E
S C
H E
D U
L E
ALUMINUM WINDOW
GLAZING - SEE
WINDOW
SCHEDULE
4" CMU BLOCK
VENEER
RE: PEMB FOR
REINFORCEMENT
TREATED WOOD
BLOCKING (TYP)
NON-METALLIC SHIM
STEEL GIRT PER
PEMB MFR
SEALANT
SEALANT
5/8" GYPSUM
SHEATHING ON
METAL STUDS
ALUMINUM WINDOW
RE: SCHEDULE
METAL STUD AND
GYPSUM BOARD
FURRING
RE: FLOOR PLANS
FOR LOCATIONS
INSULATED METAL
WALL PANEL
CONTINUOUS METAL
SILL FLASHING
SEALANT
/2
METAL LOUVER
INSULATED
METAL
WALL
PANEL
CONTINUOUS
SHEET METAL
FLASHING
BIRD SCREEN
STEEL GIRT AND
ANGLE PER PEMB
MFR
FRAME WIDTH
STEELCHANNE
L BEYOND PER
PEMB MFR
EXTEND
JAMB
CHANNEL TO
NEXT GIRT
ABOVE DOOR
HEAD METAL
STUD AND
GYPSUM
BOARD
FURRING
RE: FLOOR
PLANS FOR
LOCATIONS
SEALANT
L 4 x4 x 1/4
ANGLE
SUPPORT AT
JAMBS
METAL LOUVER
CONT. SEALANT
METAL TRIM
CONTINUOUS SHEET
INSULATED WALL
PANEL
L O
U V
E R
W
ID
T H
S E
E S
C H
E D
U L
E BIRD SCREEN
STEEL GIRT PER
PEMB MFR
FRAME WIDTH
SILL FLASHING
BELOW
JAMB CHANNEL
BEYOND
ALUMINUM DOOR &
FRAME
RE: DOOR SCHEDULE
CONTINUOUS
METAL JAMB
FLASHING
BEYOND THRESHOLD SET IN
BED OF SEALANT
D O
O R
H E
IG
H
T S
E E
S C
H E
D U
L E
FINISH FLOOR RE:
ROOM FINISH SCHED.SLOPE
CONTINUOUS
METAL FLASHING
FINISHED WALL
RE: FINISH SCHEDULE
SERVICE WINDOW
REFERENCE SECTION 08 24 02
COUNTERTOP: 1/2" SOLID
SURFACE W/ TURNDOWN EDGE
FINISHED FLOOR
RE: FINISH SCHEDULE
RE: ELEC
1/2" RADIUSED EDGE
BASE
RE: FINISH SCHEDULE
3/4" PLYWOOD SUB-TOP
MAX
3"
7"
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y U
.S A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K
A N
S A
S C
IT
Y
M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-623
W
IN
D O
W A
N D
L O
U V
E R
D E
T A
IL
S
M O
W E
N S
B Y
M O
W E
N S
B Y
B M
A R
IN
O
J K
L
IN
G
SCALE: 3" = 1'-0"
C5
DETAIL SILL
SCALE: 3" = 1'-0"
E3
DETAIL HEAD
SCALE: 3" = 1'-0"
A5
DETAIL SILL
SCALE: 3" = 1'-0"
A7
DETAIL JAMB
SCALE: 3" = 1'-0"
E5
DETAIL HEAD
SCALE: 3" = 1'-0"
A3
DETAIL SILL
SCALE: 3" = 1'-0"
C3
DETAIL JAMB
SCALE: 3" = 1'-0"
A1
DETAIL HEAD
SCALE: 3" = 1'-0"
C7
DETAIL JAMB
SCALE: 1 1/2" = 1'-0"
E7
ALUM DOOR THRESHOLD
0 3" 6" 9" 0 3" 6" 9"
0 3" 6" 9"
0 3" 6" 9"
0 3" 6" 9"0 3" 6" 9"
0 3" 6" 9"0 3" 6" 9"0 3" 6" 9"
0 1/2' 1' 1 1/2'
SCALE: 1" = 1'-0"
C1
SERVICE WINDOW SECTION
0 1/2' 1' 2'
A
M E
N D
M E
N T
A
P R
IL
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
REFER TO INTERIOR ELEVATIONS, REFLECTED CEILING
DRAWINGS, FLOOR FINISH DRAWINGS, WALL FINISH
DRAWINGS, ENLARGED PLAN DRAWINGS AND INTERIOR
DETAIL DRAWINGS FOR ADDITIONAL FINISH PLACEMENT
INFORMATION.
REFER TO ELECTRICAL DRAWINGS, MECHANICAL
DRAWINGS, STRUCTURAL DRAWINGS AND COMMUNICATION
DRAWINGS FOR COORDINATION OF BUILDING FINISHES TO
BUILDING SYSTEMS.
REFER TO FLOOR FINISH DRAWINGS FOR PLACEMENT OF
FLOOR FINISHES, FLOOR PATTERNS AND FLOOR MATERIAL
CHANGES. REFER TO FLOORING TRANSITION DETAILS FOR
TRANSITIONS BETWEEN ADJOINING FLOORING MATERIALS.
REFER TO WALL FINISH DRAWINGS AND INTERIOR
ELEVATIONS FOR WALL FINISH EXTENTS, CORNER GUARD
LOCATIONS, SIGNAGE, ART AND SPECIALTY WALL FINISH
LOCATIONS.
REFER TO REFLECTED CEILING DRAWINGS FOR CEILING
HEIGHTS AND CEILING MATERIAL EXTENTS.
REFER TO ENLARGED TOILET DRAWINGS, WALL FINISH
PLANS AND INTERIOR ELEVATIONS FOR PLACEMENT OF
INTERIOR FINISHES IN TOILET/LOCKER ROOMS.
REFER TO MILLWORK DETAIL DRAWINGS AND INTERIOR
ELEVATIONS FOR ASSIGNMENT OF SOLID SURFACE AND
PLASTIC LAMINATE FINISHES AND ADDITIONAL
INFORMATION.
PROVIDE BLOCKING AS REQUIRED TO SECURE ALL WALL
MOUNTED ITEMS INCLUDING TOILET FIXTURES, TOILET
ACCESSORIES, TOILET PARTITIONS, MILLWORK, SHELVES,
COUNTERTOP SUPPORTS, MARKERBOARDS, TACKBOARDS,
FLAT PANEL DISPLAYS, CAMERAS, ACOUSTICAL WALL
PANELS, MURAL OR ART CABLE SYSTEMS, AND ANY OTHER
WALL MOUNTED OBJECT.
UNLESS NOTED OTHERWISE, ALL EXPOSED STRUCTURAL
STEEL TO BE PAINTED PA-1.
UNLESS NOTED OTHERWISE, ALL EXTERIOR / PERIMETER
WINDOWS TO RECEIVE WT-1.
ALL WINDOW SILLS TO BE SSF-1.
ALL DOOR FRAMES TO BE PE-4.
ALL METAL FABRICATIONS AND HANDRAILS TO BE PE-4.
INTERIOR CAULKING TO MATCH ADJACENT WALL FINISH
COLOR.
NO FINISHES REQUIRED ON CONCRETE WALLS OR
CONCRETE CEILINGS UNLESS NOTED OTHERWISE.
ALL EXPOSED CONCRETE FLOORS SHALL BE SEALED.
WALL CORNER GUARDS TO BE INSTALLED STARTING AT
THE TOP OF THE SCHEDULED WALL BASE.
AT GYPSUM BOARD SOFFITS AND BULKHEADS, PAINT ALL
EXPOSED SURFACES.
PAINT ALL EXPOSED STRUCTURAL STEEL ELEMENTS,
MISCELLANEOUS STEEL, PIPING, HANGERS, VALVES AND
CONDUITS EXCEPT PRE-FINISHED LINER PANELS AND FOAM
GENERATORS. THE PAINT COLOR SHALL BE AS INDICATED
ON SCHEDULE. ALL FIRE PROTECTION PIPING COLOR SHALL
BE SAFETY RED.
ALL EXPOSED MECHANICAL AND ELECTRICAL EQUIPMENT
AND ASSOCIATED SUPPORTING EQUIPMENT TO BE PAINTED
PA-3 UNLESS OTHERWISE REQUIRED BY CODE.
COORDINATE WITH MECHANICAL / ELECTRICAL FOR
FINISHES ON MECHANICAL OR ELECTRICAL EQUIPMENT.
DO NOT PAINT PRE-FINISHED ITEMS, FINISHED METAL
SURFACES, OPERATING PARTS, LABELS OR WARNINGS.
REFER TO AND COORDINATE WITH FURNITURE DRAWINGS
AND TYPICAL MOUNTING HEIGHTS DRAWING FOR WALL
MOUNTING HEIGHTS OF FF&E, VISUAL DISPLAYS AND AUDIO
VISUAL EQUIPMENT.
REFER TO SPECIFICATION 09 06 00 SCHEDULE FOR
FINISHES FOR EXTERIOR AND INTERIOR FINISH MATERIALS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
GENERAL SHEET NOTES
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-701
R O
O M
F
IN
IS
H
S C
H E
D U
L E
N H
O R
Y N
A
N H
O R
N Y
A
R L
A S
T E
R
J K
L
IN
G
ROOM FINISH SCHEDULE
ROOM
NUMBER ROOM NAME FLOOR
BASE WALLS
CEILING REMARKSMATERIAL NORTH EAST SOUTH WEST
GROUND FLOOR
101 CORRIDOR RF-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
102 VEST WOM-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
103 KC-46 CPT-1 / CPT-2 RB-1 PA-1 PA-2 PA-1 PA-1 ACT-1 1
104 B-52 CPT-1 / CPT-2 RB-1 PA-1 PA-1 PA-1 PA-1 / PA-2 ACT-1 1
105 STORAGE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 -
106 E-3 CPT-1 / CPT-2 RB-1 PA-1 PA-2 PA-1 PA-1 ACT-1 1
107 B-1 CPT-1 / CPT-2 RB-1 PA-1 PA-1 PA-1 PA-1 / PA-2 ACT-1 1
108 ADMIN/AVIATION CPT-1 / CPT-2 RB-1 PA-1 PA-1 PA-2 PA-1 ACT-1 1
109 D.O. CPT-1 / CPT-2 RB-1 PA-1 PA-1 PA-1 / PA-2 PA-1 ACT-1 1
110 VEST WOM-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
111 ADMIN CPT-1 / CPT-2 RB-1 PA-1 PA-1 PA-2 PA-1 ACT-1 1
112 COMMAND CPT-1 / CPT-2 RB-1 PA-1 PA-1 PA-1 / PA-2 PA-1 ACT-1 1
113 B-21 CPT-1 / CPT-2 RB-1 PA-1 PA-1 / PA-2 PA-1 PA-1 ACT-1 1
114 KC-135 CPT-1 / CPT-2 RB-1 PA-1 PA-1 PA-1 PA-1 / PA-2 ACT-1 1
116 MECH CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 -
117 FIRE PUMP CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 -
118 COMM CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 -
119 ELEC CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 -
120 BRIEFING ROOM CPT-1 / CPT-2 RB-1 PA-2 PA-1 PA-1 PA-1 ACT-1 1
121 STORAGE CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
122 MAIN BRIEFING ROOM CPT-1 / CPT-2 / RF-2 RB-1 PA-2 / WDP-1 PA-1 PA-1 PA-1 ACT-1 / PA-3 1
122A AV / STOR CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 -
123 HERITAGE ROOM RF-2 RB-1 PA-1 PA-1 PA-2 PA-1 ACT-1
124 VEST WOM-1 RB-1 PA-1 PA-1 / TLP-3 PA-1 PA-1 ACT-1
125 AFE LOCKERS CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
126 FEMA ENTRY RF-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
126A UTILITY CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 PA-3
127 JAN RF-1 RB-1 PE-1 PE-1/ TLP-2 PE-1/ TLP-2 PE-1 PA-3
128 WOMEN TLP-1 TBP-1 TLP-2 / PA-1 TLP-2 / PA-1 TLP-2 / PA-1 TLP-2 / PA-1 PA-3
129 MEN TLP-1 TBP-1 TLP-2 / PA-1 TLP-2 / PA-1 TLP-2 / PA-1 TLP-2 / PA-1 PA-3
130 MOTHER CPT-1 RB-1 PA-1 PA-1 PA-1 PA-1 PA-3
131 AFE ADMIN CPT-1 / CPT-2 RB-1 PA-1 PA-2 PA-1 PA-1 ACT-1 1
132 AFE WORKSPACE CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
134 LAUNDRY CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
135 AFE SPACE SAVER CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 ACT-1
136 AFE CLOSET CS-1 RB-1 PA-1 PA-1 PA-1 PA-1 -
FINISH LEGEND
MATERIAL DESCRIPTION MANUF.
MODEL
NUMBER PRODUCT NUMBER COLOR REMARKS
ACOUSTICAL CEILING TILE
ACT-1 24" X 24" ACOUSTICAL CEILING TILE ARMSTRONG - FINE FISSURED, 1732 WHITE
CONCRETE
CS-1 CONCRETE - SEALED - - - -
CORNER GUARD
CG-1 2" CORNER GUARD - VINYL CONSTRUCTION SPECIALTIES - ACROVYN, SFS-20N 927 FOLKSTONE, SUEDE TEXTURE
FLOORING
CPT-1 CARPET TILE, 25CM X 1M INTERFACE - DRIFTWOOD 104856 LINDEN ASHLAR INSTALLATION
CPT-2 CARPET TILE, 25CM X 1M INTERFACE - DRIFTWOOD 104859 SWEETGUM ASHLAR INSTALLATION
RF-1 LUXURY VINYL TILE INTERFACE - DRAWN LINES A00908 SILVER
RF-2 LUXURY VINYL TILE INTERFACE - STEADY STRIDE WOODGRAINS B001 B00109 ELM
WOM-1 WALK-OFF MAT INTERFACE - STEP REPEAT SR699 104931 GRANITE QUARTER TURN INSTALLATION
GROUT
GR-1 GROUT TEC SPECIALTIES - ACCUCOLOR 909 STERLING
MISC
TP-1 TOILET PARTITIONS SCRANTON PRODUCTS - HINY HIDERS CHARCOAL GREY ORANGE PEEL TEXTURE
WT-1 WINDOW TREATMENT LEVOLOR - RIVIERA COMMERCIAL 1" 885 DARK BRONZE
PAINT
PA-1 LATEX, EGGSHELL SHERWIN WILLIAMS - SW7015 REPOSE GRAY TYPICAL
PA-2 LATEX, EGGSHELL SHERWIN WILLIAMS - SW7017 DORIAN GRAY ACCENT
PA-3 LATEX, MATTE SHERWIN WILLIAMS - SW7007 CEILING BRIGHT WHITE CEILING
PE-1 EPOXY, SATIN SHERWIN WILLIAMS - SW7015 REPOSE GRAY
PE-4 EPOXY, SEMI-GLOSS SHERWIN WILLIAMS - SW7019 GAUNTLET GRAY TRIM
PLASTIC LAMINATE
PLAM-1 CASEWORK FORMICA - - 3505-58 STORM SOLIDZ
RESILIENT BASE
RB-1 4" COVE BASE JOHNSONITE - - 48 GREY
SOLID SURFACE FABRICATION
SSF-1 SOLID SURFACE FABRICATION DUPONT - CORIAN DOVE
TILE
TBP-1 PORCELAIN TILE BASE CROSSVILLE - GOTHAM MAINLINE 6" COVE BASE
TLP-1 PORCELAIN TILE, 12X24 CROSSVILLE - GOTHAM MAINLINE RUNNING BOND INSTALLATION
TLP-2 PORCELAIN TILE, 2X6 CROSSVILLE - GOTHAM CLOCK TOWER RUNNING BOND INSTALLATION
TLP-3 MOSAIC PORCELAIN TILE, 2X4 DALTILE - KEYSTONES BERRY BLEND DK24
WALLS
WDP-1 LAMINATE-FACED PANEL PIONITE - - KINGSLEY WW011-SD
REMARKS:
1. CARPET TO BE 70% CPT-1, 30% CPT-2, INSTALLED IN RANDOM ASHLAR PATTERN.
GENERAL SHEET NOTES
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
UP
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
REFER TO ROOM FINISH SCHEDULE GENERAL NOTES.
REFER TO ROOM FINISH SCHEDULE AND INTERIOR
ELEVATIONS FOR ADDITIONAL INTERIOR FINISH
PLACEMENTS.
FOR FLOORING MATERIAL TRANSITIONS WHICH OCCUR
AT DOORWAYS, TERMINATE FINISH TRANSITION AND
TRANSITION STRIP UNDER THE DOOR AT THE DOOR STOP
OR CENTER UNDER THE CLOSED DOOR.
CENTER ALL FLOOR TILE SO THAT PERIMETER CUTS ARE
EQUAL UNLESS NOTED OTHERWISE.
REFER TO SHEET A-771 FOR FLOORING TRANSITION AND
TILE DETAILS.
REFER TO SIGNAGE SCHEDULE GENERAL NOTES.
REFER TO SIGNAGE SCHEDULE AND DETAIL DRAWINGS
FOR ADDITIONAL INFORMATION
REFER TO SIGNAGE SCHEDULE FOR SIGN LOCATION TAG,
DOOR LOCATION, SIGN TYPE, SIGN TEXT NUMBER, AND
PLACEHOLDER MESSAGE TEXT.
REFER TO SIGNAGE MOUNTING HEIGHTS ON SIGNAGE
DETAIL DRAWINGS. SIGNS TO BE WALL-MOUNTED ON THE
LATCH SIDE OF DOOR OR AS INDICATED. HEIGHTS,
CLEARANCES, AND CONFIGURATIONS SHOWN ARE
TYPICAL AND SHALL APPLY IN ALL INSTANCES UNLESS
NOTED OTHERWISE.
EXTERIOR AND INTERIOR SIGNAGE MUST COMPLY WITH
UFGS REQUIREMENTS, GUIDANCE FOR AIR FORCE
SIGNAGE AS FOUND IN UFC 3-120-01 "DESIGN: SIGN
STANDARDS, WITH CHANGE 3" AND BASE STANDARDS.
ELEC
FIRE PUMP
MECH
COMM
BRIEFING ROOM
STORAGE
KC-135
B-21
HERITAGE ROOM
AV / STOR
122A
MAIN BRIEFING
ROOM
VEST
CORRIDOR
COMMAND
ADMIN
S111
S120
S121
S116
S117
S119 S118
S122B
S122A
S110B
S123B
S139
S140
PA-2
PA-2
PA-2
CG-1
CG-1CG-1
CG-1 CG-1
CG-1
CG-1
CG-1 CG-1 CG-1 CG-1 CG-1
S108
PA-2 PA-2WDP-1
PA-2
PA-2
S113 S114
CG-1
CG-1
CG-1
CG-1
CG-1
S112
S142
B
C
C.3
PA-2
CG-1 CG-1 CG-1
CG-1
CG-1
7 108 9
C.5
B.9
B.3
D
A
E
CG-1
S123A
RF-1CPT-1/CPT-2 CPT-1/CPT-2
RF-1
CPT-1/CPT-2
RF-1
CPT-1/CPT-2
CPT-1/CPT-2RF-1
RF-2
RF-1
RF-1
CPT-1/CPT-2
RF-1
CPT-1/CPT-2
R F
-1 W
O M
-1
A R
E A
A
A R
E A
B
S110A
N
GENERAL SHEET NOTES
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K A
N S
A S
C
IT
Y M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
A B
KEYPLAN
SCALE: NTS
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-712
G R
O U
N D
F L O
O R
F
IN
IS
H
S
IG
N
A G
E P
L A
N
A R
E A
B
N H
O R
Y N
A
N H
O R
N Y
A
R L
A S
T E
R
J K
L
IN
G
SCALE: 1/8" = 1'-0"
A3
GROUND FLOOR WALL FINISH & SIGNAGE PLAN AREA - B
0 4' 8' 16'
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
REFER TO SIGNAGE PLACEMENT DRAWINGS FOR LOCATION
OF INTERIOR SIGNS.
REFER TO EXTERIOR BUILDING ELEVATIONS, SIGNAGE
SCHEDULE AND SIGNAGE DRAWINGS FOR LOCATION OF ALL
EXTERIOR SIGNAGE.
REFER TO SIGNAGE DETAILS FOR SIGNAGE CONSTRUCTION
AND MOUNTING ELEVATION.
REFER TO ARCHITECTURAL DRAWINGS FOR COORDINATION
OF SIGNAGE INSTALLATION TO WALL CONSTRUCTION.
SIGNAGE MUST BE ANCHORED THRU THE SURFACE APPLIED
WALL FINISHES TO THE SUBSTRATE WALL.
ALL HARDWARE/MOUNTING ATTACHMENTS TO BE
CONCEALED AND APPROPRIATE FOR THE RECEIVING
BUILDING SURFACE.
ALL SIGNAGE SHALL COMPLY WITH THE MOST CURRENT
VERSION OF THE ARCHITECTURAL BARRIER ACT (ABA).
CONSTRUCT EXTERIOR GRADE SIGNAGE WITH MATERIAL
APPROPRIATE FOR EXTERIOR USAGE.
GENERAL CONTRACTOR IS RESPONSIBLE FOR
COORDINATING WITH SIGNAGE MANUFACTURER(S) TO
PROVIDE ANY ADDITIONAL SIGNAGE AS REQUIRED BY
GOVERNING MUNICIPALITY AT THE SITE LOCATION.
ALL MESSAGE TEXT AS SHOWN ON THE SIGN SCHEDULE IS A
PLACE HOLDER ONLY AND IS NOT THE FINAL TEXT MESSAGE.
ALL MESSAGE TEXT MUST BE CONFIRMED BY GOVERNMENT
END USER PRIOR TO SIGNAGE SHOP DRAWINGS. ALLOW FOR
MAXIMUM 4 DIGIT ROOM NUMBERS AND MINIMUM 25
CHARACTER ROOM NAMES TYPICAL FOR ALL SIGNS.
PROVIDE EXTERIOR BUILDING NUMBER SIGN PER BASE
STANDARDS AND IN ACCORDANCE WITH AIR FORCE SIGN
STANDARDS UFC 3-120-01.
REFER TO 09 06 00 SCHEDULE OF FINISHES FOR BASIS OF
DESIGN OR EQUIVALENT MANUFACTURER, PRODUCT STYLE,
MATERIALS AND COLOR.
GENERAL CONTRACTOR IS RESPONSIBLE FOR OBTAINING
LOGO IMAGES FROM APPROVED GOVERNMENT
REPRESENTATIVE AND PROVIDING TO SIGNAGE
MANUFACTURER(S). SIGNAGE MANUFACTURER(S) IS
RESPONSIBLE FOR CREATING VECTOR IMAGES FOR
INCORPORATION INTO SIGNAGE BACKGROUND INSERTS AND
LOGO MEDALLION SIGNAGE.
PROVIDE MESSAGE INSERTS FOR WINDOW SIGNS WHERE
INDICATED IN THE SIGNAGE DRAWINGS OR SPECIFICATIONS.
Updateable Insert Verify Text w/
User
9"
PERMANENT RAISED TEXT 1
1/2" HIGH WITH BRAILLE
BELOW HELVETICA NEUE 55
ROMAN
3/8" THICK MATTE ACRYLIC
INSERT AREA -
UPDATEABLE TEXT 3/4"
HIGH
HELVETICA NEUE 55 ROMAN
/4
8"
Mechanical Room
9"
PERMANENT RAISED
TEXT 1 1/2" HIGH
3/8" THICK MATTE
ACRYLIC
/2
/4
8"
PERMANENT RAISED
TEXT, 1/2" HIGH WITH
GRADE II BRAILLE
BELOW
FOR SIGNS USED ON EXTERIOR OF BUILDING
BRAILLE IS NOT REQUIRED
9"
1" HIGH PERMANENT RAISED
TEXT AND BRAILLE
HELVETICA NEUE 55 ROMAN
3/8" THICK MATTE ACRYLIC
BACKGROUND
6" PICTOGRAM BASED ON SIGN
LOCATION. WHITE PICTOGRAM.
9"
7" 2"
TORNADO
DESIGN WIND SPEED: 250 MPH
PER ICC500, 2014 EDITION
BUILDER: XXXXXXXXXXXXXXXX
SHELTER
8 1/2"
5" PICTOGRAM. WHITE PICTOGRAM.
3/8" THICK MATTE ACRYLIC BACKGROUND
1" HIGH PERMANENT RAISED TEXT,
HELVETICA NEUE 75 BOLD
1/4" HIGH RAISED TEXT, HELVETICA
DESIGN OCCUPANT CAPACITY: 80
1' - 0"
3/8" THICK MATTE ACRYLIC
NOTE: DUAL SIDED SIGN - SAME
TEXT ON OPPOSITE SIDE,
CENTER TEXT AS SHOWN,
CENTER SIGN ABOVE DOOR
BELOW
WALL FACE
9.5" HIGH PICTOGRAM
STORM SHELTER
PERMANENT RAISED TEXT 1"
HIGH HELVETICA NEUE 55
ROMAN
GENERAL SHEET NOTES
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y U
.S A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K
A N
S A
S C
IT
Y
M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-741
S
IG
N A
G E
S C
H E
D U
L E
A N
D D
E T
A
IL
S
N H
O R
Y N
A
N H
O R
N Y
A
R L
A S
T E
R
J K
L
IN
G
SIGN TAG
SIGN
TYPE
MESSAGE TEXT
REMARKSNUMBER WORDING
S103 A 103 KC-46
S104 A 104 B-52
S105 B 105 STORAGE
S106 A 106 E-3
S107 A 107 B-1
S108 A 108 ADMIN / AVIATION
S109 A 109 D.O.
S110A EXT3 - 'BUILDING NAME'
S110B EXT1 - 'BUILDING NAME AND NUMBER'
S111 A 111 ADMIN
S112 A 112 COMMAND
S113 A 113 B-21
S114 A 114 KC-135
S116 B 116 MECHANICAL ROOM
S117 B 117 FIRE PUMP ROOM
S118 B 118 COMMUNICATIONS ROOM
S119 B 119 ELECTRICAL ROOM
S120 A 120 BRIEFING ROOM
S121 B 121 STORAGE
S122A A 122 MAIN BRIEFING ROOM
S122B A 122 MAIN BRIEFING ROOM
S123A A 123 HERITAGE ROOM
S123B B 123 HERITAGE ROOM
S125A A 125 AFE LOCKERS
S125B A 125 AFE LOCKERS
S126 D - 'TORNADO SHELTER'
S126A B 126A UTILITY
S126B F - 'PICTOGRAM'
S126C J - STORM SHELTER EXIT; DO NOT BLOCK DOOR
S126D G - 'PICTOGRAM'
S127 B 127 JANITOR
S128 C - WOMEN
S129 C - MEN
S130 A 130 MOTHER'S ROOM
S131A A 131 AFE ADMIN
S131B A 131 AFE ADMIN
S133A A 132 AFE WORKSPACE
S133B A 132 AFE WORKSPACE
S133D B 132 AFE WORKSPACE
S134 B 134 LAUNDRY
S135 A 135 AFE SPACE SAVER
S136 A 136 AFE CLOSET
S137 EXT2 - 'BUILDING NUMBER'
S138 EXT2 - 'BUILDING NUMBER'
S139 EXT2 - 'BUILDING NUMBER'
S140 EXT2 - 'BUILDING NUMBER'
S142 H - 'SQUADRON PATCH'
SCALE: 3" = 1'-0"
E5
SIGN TYPE A
SCALE: 6" = 1'-0"
D5
SIGN TYPE B
SCALE: 3" = 1'-0"
A1
SIGN TYPE C
0 3" 6" 9"
0 1" 2" 4"3"
0 1" 2" 4"3"
0 1" 2" 4"3"
SCALE: 3" = 1'-0"
B5
SIGN TYPE F
0 1" 2" 4"3"
SCALE: 3" = 1'-0"
A3
SIGN TYPE D
NOTE: DUAL-SIDED
SIGN - SAME SYMBOLS
ON OPPOSITE SIDE
3/8" THICK MATTE ACRYLIC
WALL FACE
SCALE: 3" = 1'-0"
A5
SIGN TYPE G
0 1" 2" 4"3"
A
M E
N D
M E
N T
A
P R
IL
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
T O
3"
BASE LINE OF HIGHEST COPY MOUNTED
NO HIGHER THAN 60" AFF
BASELINE OF LOWEST COPY MOUNTED
NO LOWER THAN 48" AFF
MOUNT SIGN ON LATCH SIDE OF DOOR
1' - 6"
PERMANENT TEXT 1 1/4" HIGH
HELVETICA NEUE 75 BOLD
PERMANENT TEXT 3" HIGH
HELVETICA NEUE 85 HEAVY
10th Flight Test
Squadron
3/8" THICK SOLID LINE
Operations Facility PERMANENT TEXT 1 1/4" HIGH
HELVETICA NEUE 65 MEDIUM
3/8" THICK MATTE ACRYLIC
1' - 6"
6" HIGH BUILDING NUMBERS,
3M REFLECTIVE WHITE.
VERIFY BUILDING NUMBER.
EXTERIOR GRADE PAINTED
STEEL SIGN SUBSTRATE
A F
F T
C
N T
E R
L
IN
E O
F S
IG
N
G R
E A
T E
R T
H A
N
2' - 5 1/4"
SQUADRON GRAPHIC (USER PROVIDED),
PRINTED IN COLOR ON 1/2" THICK MATTE
ACRYLIC. SURFACE MOUNT TO WALL
FACE.
S-13
10"
/2
/4
/4
/2
/2
STORM SHELTER
EXIT
DO NOT BLOCK DOOR
1/4"
3/8" THICK MATTE
ACRYLIC
PERMANENT RAISED
TEXT 3/4" HIGH
PERMANENT RAISED
TEXT 1/2" HIGH
24” HIGH CAST ALUMINUM LETTERS
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C E
R T
IF
IE
D F
IN
A
L D
E S
IG
N
T
IN
K E
R A
IR
F
O R
C E
B A
S E
O
K L A
H O
M A
T
H F
L
IG
H T
T E
S T
S Q
U A
D R
O N
O P
E R
A T
IO
N
S F
A C
IL
IT
Y
P R
O J E
C T
N O
W
W Y
K
F
Y
D E
P A
R T
M E
N T
O F
T H
E A
R M
Y U
.S A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
K E
N T
U C
K Y
B U
R N
S A
N D
M c D
O N
N E
L L
W
A R
D P
A R
K W
A Y
K
A N
S A
S C
IT
Y
M
O
F
IL
E N
A M
E
US Army Corps of Engineers ®
J A
N
D
2 3
C
A
B
6 7 8 9
E
F
A-742
S
IG
N A
G E
D E
T A
IL
S
N H
O R
Y N
A
N H
O R
N Y
A
R L
A S
T E
R
J K
L
IN
G
SCALE: 3/4" = 1'-0"
A1
TYPICAL INTERIOR SIGN INSTALLATION - WALL
SCALE: 3" = 1'-0"
D7
SIGN TYPE EXT1
SCALE: 3" = 1'-0"
A7
SIGN TYPE EXT2
0 1' 2' 3' 0 3" 6" 9"
0 3" 6" 9"
SCALE: 3/4" = 1'-0"
A4
FLAG-MOUNTED SIGNS ELEVATION
0 1' 2' 3'
SCALE: 1 1/2" = 1'-0"
D1
SIGN TYPE H
SCALE: 6" = 1'-0"
D4
SIGN TYPE J
0 1" 2" 4"3"0 1/2' 1' 1 1/2'
A
M E
N D
M E
N T
A
P R
IL
A
M E
N D
M E
N T
A
P R
IL
SCALE: 1/2" = 1'-0"
F5
SIGN TYPE EXT3
0 1' 2' 3'
MICHAEL R.
OWENSBY
a5814
L
IC
E N S E D A R C H IT
E C
T
S T
A T
E
O F O K LA
H
O M
A
04/17/2024
W
2Q R
B0
3_
Pl an s-
| A-201 - EXTERIOR BUILDING ELEVATIONS |
| A-422 - CANOPY ROOF PLAN AND SECTION |
| A-423 - CANOPY DETAILS |
| A-431 - MECHANICAL PLATFORM PLANS AND DETAILS |
| A-451 - PLAN DETAILS |
| A-601 - DOOR SCHEDULE |
| A-623 - WINDOW AND LOUVER DETAILS |
| A-701 - ROOM FINISH SCHEDULE |
| A-712 - GROUND FLOOR FINISH & SIGNAGE PLAN - AREA B |
| A-741 - SIGNAGE SCHEDULE AND DETAILS |
| A-742 - SIGNAGE DETAILS |