This solicitation is for a full facility restoration project of Building 295 located at Fort Hunter Liggett in California. The project cost is estimated between $10 million to $25 million. It is a full and open competitive procurement conducted in accordance with FAR 19.1307, which requires a 10% price evaluation preference for HUBZone small businesses. The NAICS code for this project is 236220. Offerors must register in the System for Award Management, which combines the former Central Contractor Registration, Online Representations and Certifications Application, and Exclusions records into a single location. Technical inquiries should be submitted through Bidder Inquiry in ProjNet. No contract award will be made until appropriated funds are available for the acquisition. The solicitation does not specify a response deadline or anticipated award date.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
HVAC & PLUMBING UPGRADES IN BARRACKS
BUILDING 295 - ISSUE FOR CONSTRUCTION
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
BUILDING 295
G-0-001
BUILDING 295 - COVER SHEET
01 OF 28N.T.S.
SHEET NUMBER SHEET TITLE
BUILDING 295: GENERAL
G-0-001 BUILDING 295 - COVER SHEET
BUILDING 295: ARCHITECTURAL
A-0-001 BUILDING 295 - ARCHITECTURAL LEGEND & ABBREVIATIONS
A-1-101 BUILDING 295 - WINDOW LAYOUT AND DETAILS
A-1-102 BUILDING 295 - NORTH CURTAIN WALL
A-1-103 BUILDING 295 - WEST CURTAIN WALL
A-1-104 BUILDING 295 - EAST CURTAIN WALL
BUILDING 295: MECHANICAL
M-0-001 BUILDING 295 - MECHANICAL LEGEND & SYMBOLS
M-1-101 BUILDING 295 - FIRST FLOOR HVAC PLAN
M-1-201 BUILDING 295 - SECOND FLOOR HVAC PLAN
M-1-301 BUILDING 295 - THIRD FLOOR HVAC PLAN
M-4-101 BUILDING 295 - ENLARGED MECH ROOM PLAN - DEMO
M-4-102 BUILDING 295 - ENLARGED MECH ROOM PLAN - NEW WORK
M-5-001 BUILDING 295 - MECHANICAL DETAILS
M-6-001 BUILDING 295 - MECHANICAL SCHEDULES
M-6-002 BUILDING 295 - MECHANICAL SCHEDULES
M-6-003 BUILDING 295 - MECHANICAL SCHEDULES
M-6-004 BUILDING 295 - OVERALL DUAL TEMPERATURE WATER FLOW DIAGRAM
M-6-005 BUILDING 295 - DOMESTIC WATER SOURCE HEATING PLANT FLOW DIAGRAM
M-6-006 BUILDING 295 - SOURCE WATER FLOW DIAGRAM
M-6-007 BUILDING 295 - DUAL TEMP WATER SYSTEM FLOW DIAGRAM
BUILDING 295: ELECTRICAL
E-1-101 BUILDING 295 - FIRST FLOOR MECHANICAL POWER PLAN
E-1-201 BUILDING 295 - SECOND FLOOR MECHANICAL POWER PLAN
E-1-301 BUILDING 295 - THIRD FLOOR MECHANICAL POWER PLAN
E-6-001 BUILDING 295 - DETAILS, SCHEDULES, AND ENLARGED PLANS
E-2-101 BUILDING 295 - ENLARGED FLOOR - LIGHTING PLANS
BUILDING 295: PLUMBING
P-0-001 BUILDING 295 - PLUMBING LEGEND & SYMBOLS
P-4-101 BUILDING 295 - ENLARGED PLUMBING PLAN - NEW WORK
P-6-001 P-6-001 BUILDING 295 - PLUMBING SCHEDULES
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
WIDTH, WINDOW
DIMENSION, WOOD
VINYL BASE, VAPOR
BARRIER
W/O WITHOUT
QUARRY TILEQT
CLG CEILING
ELEV ELEVATION
EYE WASH
EMERGENCY SHOWER
EXPANSION JOINT
EXPANSION, EXPOSED
EQUIPMENT
AND SO FORTH
ELECTRIC WATER COOLER
EQUAL
EXISTING
EXTERIOREXT
EW
EXP JT, EJ
EXIST
EXP
EWC
ETC
ES
EQPT
EQ
DOOR
DETAIL
DRINKING FOUNTAIN
DEMOLITION, DEMOLISH
DOWN
DAMPPROOFING
DOWNSPOUT
DRAWING
DRAWER
EACH
ELECTRICAL
EXHAUST FAN
ELEC
EA
EF
E
DR
DWG
DWR
DTL
DS
DN, DWN
DP
DEMO
DF
CERAMIC TILE
CONTRACTOR ROUGH-IN
CARPET
CONCRETE
CLEAR
CONCRETE MASONRY UNIT
CLEANOUT
COLUMN
CONTINUOUS
DOUBLE
DIAGONAL
DIMENSION
DIAMETER
CT
D
DIA
DIAG
DIM
DBL
CPT
CR
CONC
CONT
CMU
COL
CO
CLR
SQ SQUARE
MC MEDICINE CABINET
STANDARD
STAINLESS STEEL
STORAGE
STRUCTURAL
SUSPENDED
MANUFACTURE,
MANUFACTURER
MASONRY OPENING
MEMBRANE
WATERPROOFING
METAL THRESHOLD
MASONRY
METAL SPLASH PAN
MOUNTED
MOVABLE
MTL METAL
MVBL
MWP
MT
MTD
MSNRY
MSP
MECHANICAL
MEZZANINE
MANHOLE
MINIMUM
MISCELLANEOUS
MOLDING
MIN
MK
MLDG
MO
MISC
MARK
MFR
MH
MECH
MEZZ
STRUCT
SUSP
STL
STOR
STD
SS
STEEL
RADIUS, RISER
SOAP DISPENSER
SPLASH BLOCK
SOLID CORE
ROBE HOOK
RUBBER BASE
RETURN AIR
ROAD, ROOF DRAIN
REINFORCE, REINFORCED
REFER, REFERENCE
REPRESENTATIVE
ROOFING
SCHEDULE
SECTION
SEQUENCE
SIMILAR
STUCCO JOINT, SAWN
JOINT
CONTRACT SPECIFICATIONS
SANITARY NAPKIN
DISPENSER
REQUIRED
RECTANGULAR
L
MACHINE
MAINTENANCE
MATERIAL
MAXIMUM
MEMBER
MAX
MBR
MAINT
MATL
MACH
M
LAMINATE
LIGHTWEIGHT
LAVATORY
LINEAL FEET
LOUVER
LBL LABEL
LWT
LF
LVR
LAV
LB
LAM
POUND
SCHED
SND
SPECS
SIM
SJ
SECT
SEQ
SHT
SD
SHEET
SB
SC
S
RND ROUND
JOISTJST
J
JT JOINT
INSIDE DIAMETER
INSULATION
INTERI0RINT
INSUL
IN INCH
I
ID
RB
REQD
RFG
RH
RM
REP
ROOM
REINF
REF, RE
RECT
RD
R
RA
R
BOT, BTM BOTTOM
CEMENTITIOUS BACKER
BOARD
CORNER GUARD
CONTRACTOR CONNECT
BASEMENT
BEARING
BRICK
CENTER TO CENTER
CABINET
CONTRACTOR FURNISHED
COLD FORMED METAL
FRAMING
CONTRACTOR INSTALLED
CONSTRUCTION CONTROL
JOINT
CENTER LINE
CG
CJ
CL
CFMF
CI
CC
CF
CBB
CAB
C TO C
C
BSMT
BRG
BRK
BASE BID
AGGREGATE
APPROVED
APPROXIMATE
AS SOON AS POSSIBLE
ALUMINUM
ARCHITECT,
BOARD
BITUMINOUS
BUILDING
BLOCKING
BEAM, BENCH MARK
ALTERNATE
BLKG
BM
BITUM
BLDG
BB
BD
B
APVD
ASAP
ARCH
ALUM/AL
APPROX
AGGR
ALT
ADDITIVE BID ITEM
AIR CONDITIONING
ANCHOR BOLT
ADJACENT, ADJUSTABLE
ACOUSTICAL
ACOUSTICAL CEILING TILE
ABOVE FINISH FLOOR
A/C
ACT
ADJ
AFF
ACOUST
ABI
AB
A
@ AT
PLASTIC
PREFINISHED
PAINTED
PARTITION
OVERHEAD
OVER-ALL, OUTSIDE AIR
ON CENTER
OUTSIDE DIAMETER
OPPOSITE
OPENING
PROJECTION
PLYWOOD
PREFABRICATED
PROPERTY
PLUMBING
POUNDS PER SQ IN
PARTIAL
PLATE, PLASTIC
PANEL, PANELBOARD
POLYVINYL CHLORIDE
PLAS
GL GLASS, GLAZING
AND AIR CONDITIONING
HOLLOW METAL
HEIGHT
HARDWOOD
HEATING, VENTILATING
HANDICAPPED
HARDWARE
HEATER
HORIZONTALHORIZ
HVAC
HT
HTR
HDWD
HM
HCPD, HC
HDW
GYPSUM WALLBOARD
HOLLOW CORE
GYPSUM
HOSE BIB
HC
HB
H
GWB
GYP
Q
PVC
PTDD
PTN
PREFIN
PROP
PTD
PSI
PRJ
PREFAB
PNL
PLYWD
PLBG
GALVANIZED
GRAB BARGB
GALV
GA
G
GAUGE
FURRED, FURRING
FOOT, FEET
FINISHED
FIREPROOF
FOOTINGFTG
FURR
FPRF
FT
FIN
FLR FLOOR
OZ OUNCE
PART
PL
P
OC
OVHD
OPP
OPNG
OD
O
OA
W
WASTE RECEPTACLE
WEATHER STRIPPING
WITH (COMB. FORM)
WINDOW
WATER CLOSET
WATER HEATER
WATERPROOF
WS
W/
WR
WP
WD
WDW
WH
WC
VINYL WALL COVERING
VENT THRU ROOF
VENT PIPE
VERTICAL
VWC
VTR
VERT
VP
UNO UNLESS NOTED OTHERWISE
VINYL COMPOSITION TILE
URINAL
V
VCT
VB
UR
UNDERGROUND
TOILET TISSUE DISPENSER
TYPICAL
U
UGND
TTD
TYP
NOT IN CONTRACT
NUMBER
NOMINAL
NEOPRENE
NOT TO SCALE
FIRE EXTINGUISHER
CABINET
FOUNDATION
FIRE EXTINGUISHER
FINISH FLOOR
FIRE HOSE STATION
FLOOR DRAIN
FIRE HOSE CABINET
FIRE HYDRANT
FEC
FH
FHS
FHC
FF
FDN
FE
F
FD
NPRN
NTS
NO
NOM
N
NIC
TOP OF WALL
TOP OF CONCRETE
TOP OF MASONRY
TRANSFORMER
THROUGH
TOP OF STEEL
THRU
TOM
TOW
TOS
TOC
THK
TFMR
T T
THICK
TREAD
TD TOWEL DISPENSER
ATTEN ATTENUATOR,
ATTENUATION
ST SOILED TOWEL RECEPTACLE
ABBREVIATIONS
ARCHITECTURAL
PAPER TOWEL
DISPENSER/DISPOSAL
R
SINGLE-DEGREE-OF-FREEDOM
BLAST EFFECTS DESIGN
SPREADSHEETS FOR WINDOWS
SBEDS-W
ANTI-TERRORISM FORCE
PROTECTION
ATFP
G
ROOM NAME
150 SF
G012
A
NAME
ELEVATION
A-101
DIRECTION OF VIEW FOR SECTION
SECTION NUMBER
SHEET ON WHICH SECTION
APPEARS
DETAIL NUMBER
SHEET ON WHICH DETAIL APPEARS
VIEW NUMBER
NUMBER DESIGNATION
LETTER DESIGNATION
NUMBER DESIGNATION
LETTER/NUMBER DESIGNATION
LETTER DESIGNATIONA
A-101
A-101
DIRECTION OF VIEW FOR
ELEVATION
SHEET ON WHICH ELEVATION
APPEARS
ELEVATION NUMBER
DIRECTION OF VIEW FOR
ELEVATION
SHEET ON WHICH ELEVATION
APPEARS
ELEVATION NUMBER
HEIGHT DESIGNATION10'-0"
NUMBER DESIGNATION
HEIGHT DESIGNATION
LETTER/NUMBER DESIGNATION
ELEVATION DESIGNATION
ROOM NAME/NUMBER SYMBOL
WINDOW/STOREFRONT SYMBOL
EQUIPMENT/FURNITURE SYMBOL
PARTITION TYPE SYMBOL
TOILET ACCESSORY SYMBOL
SPOT/CEILING ELEVATION SYMBOL
DOOR SYMBOL
ELEVATION SYMBOL
GRID SYMBOL
ARCHITECTURAL DRAFTING CONVENTIONS
VIEW TITLE
EXTERIOR ELEVATION MARKER
INTERIOR ELEVATION MARKER
SECTION MARKER
DETAIL MARKER
A-101
SCALE:
VIEW NAME
SCALE
1. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER IMMEDIATELY OF DISCREPANCIES IN THE DRAWINGS BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, AND/OR BETWEEN THE CONSTRUCTION DOCUMENTS AND ACTUAL JOB CONDITIONS WHICH AFFECT THE EXECUTION OF THE WORK
AS INDICATED.
2. CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL CONSTRUCTION WORK PERFORMED BY SUBCONTRACTORS UNLESS NOTED OR
INDICATED OTHERWISE.
3. CONTRACTOR SHALL LOCATE AND LAYOUT WALLS AND PARTITIONS AS THEY RELATE TO THE STRUCTURE AND OTHER BUILDING ELEMENTS AS SHOWN IN THE CONSTRUCTION DOCUMENTS. CONFLICTS OR AREAS OF INTERPRETATION SHALL BE RESOLVED BY THE CONTRACTING OFFICER.
4. THE CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE FIRESTOPPING AND THE FIRE RESISTANT ASSEMBLIES OF MATERIALS IN COMPLIANCE WITH THE CONSTRUCTION DOCUMENTS AND THE REQUIREMENTS OF THE REFERENCED UL ASSEMBLIES. THESE MATERIALS SHALL BE REAPPLIED OR REPAIRED TO MAINTAIN THE REQUIRED BARRIER AT NO ADDITIONAL COST TO THE GOVERNMENT.
5. THE CONTRACTOR SHALL SCRIBE GYPSUM BOARD ON FIRE RESISTANT PARTITIONS TO THE IRREGULARITIES OF THE STRUCTURE AS DETAILED ON THE
DRAWINGS UNLESS NOTED OR INDICATED OTHERWISE.
6. THE CONTRACTOR SHALL COORDINATE REQUIRED PENETRATIONS THROUGH FIRE RESISTANT PARTITIONS AND SEAL TIGHTLY AROUND THE
PENETRATION UNLESS NOTED OR INDICATED OTHERWISE.
7. THE CONTRACTOR SHALL FILL ANY OTHER IRREGULAR OPENINGS OR GAPS IN FIRE RESISTANT PARTITIONS AND SEAL TIGHTLY AROUND THE PENETRATION WITH THE SPECIFIED INERT NONCOMBUSTIBLE FIRESAFING MATERIAL UNLESS NOTED OR INDICATED OTHERWISE.
8. ALL PARTITIONS SHALL EXTEND A MINIMUM OF 6" ABOVE THE CEILING HEIGHT AND BE BRACED TO THE STRUCTURE AT 4'-0" O.C. UNLESS NOTED OR
INDICATED OTHERWISE.
9. THE CONTRACTOR SHALL PROVIDE CONCEALED FIRE-TREATED WOOD BLOCKING WHERE REQUIRED IN METAL STUD PARTITIONS FOR THE PROPER ANCHORAGE OF WALL ATTACHED ITEMS SUCH AS GRAB BARS, TOILET ACCESSORIES, TACKBOARDS, MARKERBOARDS, SHELF BRACKETS AND SHELVING, MILLWORK, AND ALL OTHER WALL ATTACHED MATERIALS UNLESS NOTED OR OTHERWISE INDICATED.
10. THE CONTRACTOR SHALL MAKE ALL EXTERIOR WALL/ROOF OR WALL/WALL TRANSITIONS WATERTIGHT AND AIRTIGHT WITH SEALANT, FLASHING, EXPANDABLE FOAM, AIR INFILTRATION BARRIER, ETC. TO MAINTAIN REQUIRED INSULATION VALUES AND MECHANICAL SYSTEM PERFORMANCE IN THE FACILITY UNLESS NOTED OR INDICATED OTHERWISE. NO GAPS, OPENINGS, OR PENETRATIONS IN THE EXTERIOR WALL OR ROOF ASSEMBLIES SHALL BE
LEFT EXPOSED TO THE ELEMENTS.
11. THE EXTERIOR FINISH SYSTEM (EIFS) SHALL BE A VERTICAL CHANNELED ADHESIVE DESIGN WHICH INCORPORATES VERTICAL DRAINAGE CHANNELS AND
AN AIR/WEATHER BARRIER DESIGN. GENERAL NOTES ARE ON EXTERIOR ELEVATIONS SHEETS.
12. CONTRACTOR SHALL VERIFY AND CORRELATE ALL DIMENSIONS DURING THE CONSTRUCTION LAYOUT OF THE WORK. THE FOLLOWING GUIDANCE
APPLIES TO DIMENSIONS USED ON THE ARCHITECTURAL DRAWINGS:
A. THE CONTRACTOR SHALL USE DIMENSIONS INDICATED ON THE DRAWINGS.
B. THE CONTRACTOR SHALL NOT SCALE FROM THE DRAWINGS.
C. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF DISCREPANCIES IN DIMENSIONS SHOWN ON THE DRAWINGS IMMEDIATELY.
D. ALL PLAN DIMENSIONS ARE TO THE STRUCTURAL GRID LINES OR TO THE CENTERLINE OF COLUMNS AND BEAMS, TO THE CENTER OF METAL STUD
WALLS, OR TO THE NOMINAL FACE OF MASONRY UNITS UNLESS NOTED OR INDICATED OTHERWISE.
E. ALL PLAN DIMENSIONS ON EXTERIOR WALL ASSEMBLIES ARE FROM THE ACTUAL OUTSIDE FACE OF WALL TO THE ACTUAL INSIDE FACE OF METAL
STUD UNLESS NOTED OR INDICATED OTHERWISE.
F. ALL OTHER MASONRY DIMENSIONS ARE INDICATED AS NOMINAL DIMENSIONS WHICH INCLUDE AN ALLOWANCE FOR + OR - 3/8" MORTAR JOINT
UNLESS NOTED OR INDICATED OTHERWISE.
G. ALL MASONRY OPENING DIMENSIONS ARE INDICATED AS NOMINAL DIMENSIONS WHICH INCLUDE AN ALLOWANCE FOR + OR - 3/8" MORTAR
JOINT UNLESS NOTED OR INDICATED OTHERWISE.
GENERAL ARCHITECTURAL NOTES
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
AA-0-001
BUILDING 295 - ARCHITECTURAL
LEGEND & ABBREVIATIONS
02 OF 28NO SCALE
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
LAUNDRY
160 JAN
STORAGE
ORDERLY
DORM
DORM
LOBBY
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
BATH TYPE 1
BATH TYPE 1
BATH TYPE 1
DORM
DORM
DORM
DORM
DORM
DORM
DORM
107 DORM
MECH
LOUNGE
STORAGE
STORAGE
STORAGE
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
BATH TYPE 1
BATH TYPE 1
BATH TYPE 1
STORAGE
STORAGE
STORAGE
LOUNGE
BATH
TYPE 3
BATH
TYPE 3
BATH
TYPE 2
BATH
TYPE 2
BATH
TYPE 2
6'-0"
5' -4
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
1. CONTRACTOR SHALL FIELD VERIFY ALL
WINDOW/ STOREFRONT/ CURTAIN WALL
QUANTITIES AND OPENING SIZES.
2. ALL EXTERIOR STOREFRONT AND CURTAIN
WALL SHALL BE THERMALLY BROKEN.
3. THE CURTAIN WALL SUPPLIER IS TO DESIGN
THE GLAZING, INSULATED PANELS,
MULLIONS, FRAMES, ANCHORAGE, ETC. TO
BE A COMPLETE SYSTEM COMPLIANT UFC
4-010-01 (OCTOBER, 2013). THE AT/FP
CRITERIA FOR DESIGN IS AS FOLLOWS:
· ACTUAL STANDOFF DISTANCE = 46FT
· APPLICABLE EXPLOSIVE WEIGHT = 11
· BUILDING CLASSIFICATION = BILLETING
· APPLICABLE LEVEL OF PROTECTION =
LOW
· FACILITY IS LOCATED WITHIN A
CONTROLLED PERIMETER
· MINIMUM GLAZING PERIMETER = 1/4"
FULLY TEMPERED GLASS + 1/2" AIR +
1/8" ANNEALED GLASS + 0.03"
POLYVINYL-BUTYRAL + 1/8" ANNEALED
GLASS
· GLAZING DESIGN BLAST INFORMATION
AS DETERMINED BY SBEDS-W:
·· PEAK PRESSURE = 15.8 PSI
·· IMPULSE = 56PSI-MS
GENERAL NOTES
A-1-101
SCALE:
FIRST FLOOR PLAN
1/16"=1'-0"
VARIES
BUILDING 295 - WINDOW LAYOUT AND
DETAILS
SCALE:
TYPICAL WINDOW DETAIL
1/2"=1'-0"
NEW MECHANICAL TANK TO BE
INSTALLED THROUGH EXISTING DOORS.
1/2"=1'-0"
2' 4'0 2'
16' 8'
1/16"=1'-0"
0 16' 32'
REFINISH ALL BATHROOMS (TYPES 1,2, AND
3) WALL AND CEILING AREAS TO INCLUDE
PRIMER AND PAINT TREATMENT WITH KILZ
OR EQUAL TYPE PRIMER/PAINT.
TYPICAL EXISTING WINDOWS TO BE REPLACED
WITH NEW OPERABLE WINDOWS IN ACCORDANCE
WITH UFC 4-010-01 STANDARD 10. SEE GENERAL NOTES
BATHROOM TYPE 1 = 18
(6 PER FLOOR)
BATHROOM TYPE 2 = 9
(3 PER FLOOR)
BATHROOM TYPE 3 = 3
(1 PER FLOOR)
N
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
16'-0"±
'-8
3/
4"
3' -0
5'
-0
3' -0
5'
-6
3' -0
5'
-6
9' -1
/8
9'
-1
/8
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
5'-1" 5'-0" 5'-1"
IP
G1
IPIP
G1 G1
IP IPIP
G1G1 G1
IP IPIP
IP IPIP
G1G1 G1
A-1-104
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
G1 MINIMUM GLAZING ASSEMBLY =
1/4" FULLY TEMPERED GLASS + 1/2"
AIR + 1/8" ANNEALED GLASS + 0.03"
POLYVINYL-BUTYRAL + 1/8"
ANNEALED GLASS.
IP INSULATED PANEL
GLAZING SCHEDULE:
A-1-102
SCALE:
NORTH CURTAIN WALL
1/16"=1'-0"
1/16"=1'-0"
BUILDING 295 - NORTH CURTAIN WALL
SCALE:
NORTH ELEVATION
N.T.S.
EXISTING ELEVATION DRAWING FOR REFERENCE ONLY
16' 8'
1/16"=1'-0"
0 16' 32'
1. CONTRACTOR SHALL FIELD VERIFY ALL
WINDOW/ STOREFRONT/ CURTAIN WALL
QUANTITIES AND OPENING SIZES.
2. ALL EXTERIOR STOREFRONT AND CURTAIN
WALL SHALL BE THERMALLY BROKEN.
3. THE CURTAIN WALL SUPPLIER IS TO DESIGN
THE GLAZING, INSULATED PANELS,
MULLIONS, FRAMES, ANCHORAGE, ETC. TO
BE A COMPLETE SYSTEM COMPLIANT UFC
4-010-01 (OCTOBER, 2013). THE AT/FP
CRITERIA FOR DESIGN IS AS FOLLOWS:
· ACTUAL STANDOFF DISTANCE = 46FT
· APPLICABLE EXPLOSIVE WEIGHT = 11
· BUILDING CLASSIFICATION = BILLETING
· APPLICABLE LEVEL OF PROTECTION =
LOW
· FACILITY IS LOCATED WITHIN A
CONTROLLED PERIMETER
· MINIMUM GLAZING PERIMETER = 1/4"
FULLY TEMPERED GLASS + 1/2" AIR +
1/8" ANNEALED GLASS + 0.03"
POLYVINYL-BUTYRAL + 1/8" ANNEALED
GLASS
· GLAZING DESIGN BLAST INFORMATION
AS DETERMINED BY SBEDS-W:
·· PEAK PRESSURE = 15.8 PSI
·· IMPULSE = 56PSI-MS
GENERAL NOTES
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
24'-2"±
10'-2"± 1'-0"± 13'-0"±
5' -0
4'
-0
5' -0
3'
-0
5' -0
3'
-3
/2
9' -1
/8
9'
-1
/8
FIRST FLOOR
SECOND FLOOR
THIRD FLOOR
1' -9
/2
1'-8"± 6'-0"± 1'-8"± 1'-11 3/4"± 4'-0"± 4'-0"± 1'-11 3/4"±
7' -0
6'-0"±
'-4
IP
G1
IP IP IP IP IP IP
G1 G1 G1 G1 G1 G1
IPIP IP IP IP IP IP
IPIP IP IP IP IP IP
IPIP IP IP IP IP IP
G1G1 G1 G1 G1 G1 G1
G1 G1 G1 G1 G1 G1
A-1-103
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
G1 MINIMUM GLAZING ASSEMBLY =
1/4" FULLY TEMPERED GLASS + 1/2"
AIR + 1/8" ANNEALED GLASS + 0.03"
POLYVINYL-BUTYRAL + 1/8"
ANNEALED GLASS.
IP INSULATED PANEL
GLAZING SCHEDULE:
A-1-103
SCALE:
NEW WEST CURTAIN WALL
1/4"=1'-0"
1/4"=1'-0"
BUILDING 295 - WEST CURTAIN WALL
EXISTING ELEVATION DRAWING FOR REFERENCE ONLY
NEW DOORS TO BE PAIRED 3'-0" X 7'-0" INSULATED
HOLLOW METAL WITH VISION LIGHTS TO MATCH
EXISTING, PAINT TO MATCH EXISTING, HARDWARE
CONFIGURATION TO MATCH EXISTING. SEE GENERAL
NOTES FOR ATFP CRITERIA.
DEMO EXISTING CURTAIN WALL AND REPLACE WITH NEW
CURTAIN WALL. SEE 1/A-1-103 FOR NEW CURTAIN WALL
CONFIGURATION AND GENERAL NOTES FOR CRITERIA.
SCALE:
EXISTING WEST ELEVATION
NO SCALE
4'
1/4"=1'-0"
0 4' 8'
1. CONTRACTOR SHALL FIELD VERIFY ALL
WINDOW/ STOREFRONT/ CURTAIN WALL
QUANTITIES AND OPENING SIZES.
2. ALL EXTERIOR STOREFRONT AND CURTAIN
WALL SHALL BE THERMALLY BROKEN.
3. THE CURTAIN WALL SUPPLIER IS TO DESIGN
THE GLAZING, INSULATED PANELS,
MULLIONS, FRAMES, ANCHORAGE, ETC. TO
BE A COMPLETE SYSTEM COMPLIANT UFC
4-010-01 (OCTOBER, 2013). THE AT/FP
CRITERIA FOR DESIGN IS AS FOLLOWS:
· ACTUAL STANDOFF DISTANCE = 46FT
· APPLICABLE EXPLOSIVE WEIGHT = 11
· BUILDING CLASSIFICATION = BILLETING
· APPLICABLE LEVEL OF PROTECTION =
LOW
· FACILITY IS LOCATED WITHIN A
CONTROLLED PERIMETER
· MINIMUM GLAZING PERIMETER = 1/4"
FULLY TEMPERED GLASS + 1/2" AIR +
1/8" ANNEALED GLASS + 0.03"
POLYVINYL-BUTYRAL + 1/8" ANNEALED
GLASS
· GLAZING DESIGN BLAST INFORMATION
AS DETERMINED BY SBEDS-W:
·· PEAK PRESSURE = 15.8 PSI
·· IMPULSE = 56PSI-MS
GENERAL NOTES
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
A-1-104
10'-0"±
5' -0
9' -1
/8
FIRST FLOOR
SECOND FLOOR
1' -9
/2
8' -0
1/
2"
IP
G1
IPIP
IP IP
G1
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
G1 MINIMUM GLAZING ASSEMBLY =
1/4" FULLY TEMPERED GLASS + 1/2"
AIR + 1/8" ANNEALED GLASS + 0.03"
POLYVINYL-BUTYRAL + 1/8"
ANNEALED GLASS.
IP INSULATED PANEL
GLAZING SCHEDULE:
A-1-104
1/4"=1'-0"
BUILDING 295 - EAST CURTAIN WALL
SCALE:
NEW EAST CURTAIN WALL
1/4"=1'-0"
NEW DOORS TO BE PAIRED 3'-0" X 7'-0" INSULATED
HOLLOW METAL WITH VISION LIGHTS TO MATCH
EXISTING, PAINTED TO MATCH EXISTING, HARDWARE
CONFIGURATION TO MATCH EXISTING. SEE GENERAL
NOTES FOR ATFP CITERIA.
4'
1/4"=1'-0"
0 4' 8'
EXISTING ELEVATION DRAWING FOR REFERENCE ONLY
SCALE:
EXISTING EAST ELEVATION
NO SCALE
1. CONTRACTOR SHALL FIELD VERIFY ALL
WINDOW/ STOREFRONT/ CURTAIN WALL
QUANTITIES AND OPENING SIZES.
2. ALL EXTERIOR STOREFRONT AND CURTAIN
WALL SHALL BE THERMALLY BROKEN.
3. THE CURTAIN WALL SUPPLIER IS TO DESIGN
THE GLAZING, INSULATED PANELS,
MULLIONS, FRAMES, ANCHORAGE, ETC. TO
BE A COMPLETE SYSTEM COMPLIANT UFC
4-010-01 (OCTOBER, 2013). THE AT/FP
CRITERIA FOR DESIGN IS AS FOLLOWS:
· ACTUAL STANDOFF DISTANCE = 46FT
· APPLICABLE EXPLOSIVE WEIGHT = 11
· BUILDING CLASSIFICATION = BILLETING
· APPLICABLE LEVEL OF PROTECTION =
LOW
· FACILITY IS LOCATED WITHIN A
CONTROLLED PERIMETER
· MINIMUM GLAZING PERIMETER = 1/4"
FULLY TEMPERED GLASS + 1/2" AIR +
1/8" ANNEALED GLASS + 0.03"
POLYVINYL-BUTYRAL + 1/8" ANNEALED
GLASS
· GLAZING DESIGN BLAST INFORMATION
AS DETERMINED BY SBEDS-W:
·· PEAK PRESSURE = 15.8 PSI
·· IMPULSE = 56PSI-MS
GENERAL NOTES
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
FLOW SWITCH
STRAINER
CALIBRATED BALANCING VALVE
NEW CONNECTION INTO EXISTING
PLUG VALVE / COCK VALVE
CHECK VALVE
PIPE ANCHOR, PIPE DEMOLITION
TEE OUT OF BOTTOM OF PIPE
TEE OUT OF TOP OF PIPE
END DROP (90° ELL)
CAP ON END OF PIPE
END RISE (90° ELL)
RISE OR DROP
VALVE IN RISER
SHUT-OFF / ISOLATION VALVE
REFER TO
DRAWING/DETAIL NUMBER
SHEET NUMBER
X-X-XXX
DRAWING NOTE REFERENCE (I.E., NOTES BY SYMBOL)1
NOTE: ALL SYMBOLS AND ABBREVIATIONS SHOWN
ARE NOT NECESSARILY USED ON THE DRAWINGS
BALL VALVE
BUTTERFLY VALVE
GLOBE VALVE
UNION (DIELECTRIC)
2-WAY CONTROL VALVE
3-WAY CONTROL VALVE
SOLENOID VALVES
ALIGNMENT GUIDEAG
ELEVATION NUMBER1
SHEET NUMBER
AD
AD
20/20 16/20
20/20 16"Ø
DESCRIPTION
18"Ø
FD
M
T TS
D
R=3D/2
W
R=3W/2
20/20 ACOUSTICAL DUCT LINING (FIGURES SHOWN ARE
INSIDE DUCT DIMENSIONS
SUPPLY AIR DUCT UP (POSITIVE PRESSURE)
RETURN, EXHAUST OR OUTSIDE AIR INTAKE DUCT
UP (NEGATIVE PRESSURE)
SUPPLY AIR DUCT DOWN (POSITIVE PRESSURE)
RETURN, EXHAUST OR OUTSIDE AIR INTAKE DUCT
DOWN (NEGATIVE PRESSURE)
ROUND DUCT UP
TRANSITION CONCENTRIC UNLESS TOP LEVEL(TOP
LVL) OR BOTTOM LEVEL(BOT LVL) IS NOTED
TRANSITION, RECTANGULAR TO ROUND CONCENTRIC UNLESS
TOP LEVEL (TOP LVL) OR BOTTOM LEVEL (BOT LVL) IS NOTED
ROUND DUCT RADIUS ELBOW
RECTANGULAR DUCT RADIUS ELBOW
RECTANGULAR DUCT SQUARE ELBOW WITH
TURNING VANES
ACCESS DOOR, SIDE, SIZE AS NOTED OR SPECIFIED
ACCESS DOOR, BOTTOM (UNLESS OTHERWISE NOTED)
SIZE AS NOTED OR SPECIFIED
ARROW INDICATES DIRECTION OF AIR FLOW
ROUND DUCT DOWN
UP
CHANGE OF ELEVATION, RISE(UP) OR DROP (DN) IN
DIRECTION OF ARROW
DIFFUSER, GRILLE DESIGNATION
AMOUNT OF AIR
NECK SIZE OR WIDTH X HEIGHT
(FOR LOUVERS)
SYMBOLS, AND ABBREVIATIONS
ABBREVIATIONS
DRAWING/DETAIL REFERENCE
MISCELLANEOUS
SYMBOLS
SYMBOL
DUCT FLEXIBLE CONNECTION
SOUND ATTENUATER
SQUARE CEILING DIFFUSER (SUPPLY)
(4-WAY UNLESS OTHERWISE INDICATED)
SQUARE CEILING GRILLE (RETURN OR EXHAUST)
THERMOSTAT (OR) TEMP SENSOR
MOTORIZED DAMPER
MANUAL VOLUME DAMPER
FIRE DAMPER
20/20
20/20
20/20
20/20
18"Ø
AD ACCESS DOOR
A/C AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
AFS AIR FLOW SWITCH
AHU AIR HANDLING UNIT
APPROX APPROXIMATE
AS AIR SEPARATOR
BAS BUILDING AUTOMATION SYSTEM
BHP BRAKE HORSE POWER
BTU BRITISH THERMAL UNIT PER HOUR
C CONSTANT
CAP CAPACITY
C/A COMBUSTION AIR
CC COOLING COIL
CD CONDENSATE
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CH CHILLER
CLG CEILING
CP CIRCULATION PUMP
CU CONDENSING UNIT
D EQUIPMENT DRAIN
DDC DIRECT DIGITAL CONTROL
DEG DEGREES
DB DRY BULB
DCW DOMESTIC COLD WATER
DEG DEGREES
DHW DOMESTIC HOT WATER
DHWR DOMESTIC HOT WATER RETURN
DHWS DOMESTIC HOT WATER SUPPLY
DIA DIAMETER
DN DOWN
DP DIFFERENTIAL PRESSURE
DPR DAMPER
DWG DRAWING
DWS DOMESTIC WATER SOURCE
(E) EXISTING
EAT ENTERING AIR TEMPERATURE
E/A EXHAUST AIR
ECM ELECTRONICALLY COMMUNICATED
MOTOR
EDH ELECTRIC DUCT HEATER
EF EXHAUST FAN
EQUIP EQUIPMENT
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EXT EXTERNAL
°F/DEG F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
FD FIRE DAMPER
FLA FULL LOAD AMPS
FLR FLOOR
FPVAV FAN POWERED VAV
FSD FIRE SMOKE DAMPER
FT. FOOT, FEET
FT. WG FEET WATER GAUGE
G NATURAL GAS
GA U.S. GAUGE
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GPM GALLONS PER MINUTE
H HEIGHT
HB HEAVY BARREL
HP HORSEPOWER
HWP HOT WATER PUMP
HX HEAT EXCHANGER
HZ HERTZ
IN. INCH, INCHES
IN.WG INCHES WATER GAUGE
J-BOX JUNCTION BOX
kW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LPC LOW PRESSURE CONDENSATE
LPS LOW PRESSURE STEAM
LB POUNDS
LRA LOCKED ROTOR AMPS
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MAU MAKE UP AIR UNIT
MBH 1000 BRITISH THERMAL UNITS / HOUR
MCA MINIMUM CIRCUIT AMPACITY
MFR MANUFACTURER
MIN MINIMUM
MTD MOUNTED
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NO NORMALLY OPEN
O/A OUTSIDE AIR/FRESH AIR
OBD OPPOSED BLADE DAMPER
O/C ON CENTER
PD PRESSURE DROP
PDTW PRIMARY DUAL TEMP WATER
PEF PURGE EXHAUST FAN
PH PHASE
PROVIDE FURNISH AND INSTALL
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSW PRIMARY SOURCE WATER
R/A RETURN AIR
RE: REFERENCE, REFER
REQ'D REQUIRED
REV REVISION
RH RELIEF HOOD
RL REFRIGERANT LIQUID
RLA RUNNING LOAD AMPS
RLF RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
S/A SUPPLY AIR
SD SMOKE DETECTOR
SDTW SECONDARY DUAL TEMP WATER
SF SQUARE FOOT, SUPPLY FAN
S.O. SHUT OFF
SPECS SPECIFICATIONS
SSW SECONDARY SOURCE WATER
ST STORAGE TANK
T, TSTAT THERMOSTAT, ROOM SENSOR
T/A TRANSFER AIR
THRU THROUGH
TMV THERMOSTATIC MIXING VALVE
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT OR ROOM SENSOR
TYP TYPICAL
UL UNDERWRITERS LABORATORIES, INC.
UH UNIT HEATER
V VOLTS
VAV VARIABLE AIR VOLUME
VEL VELOCITY
VF VENTILATION FAN
VFD VARIABLE FREQUENCY DRIVE
W/ WITH
WB WET BULB
W/O WITHOUT
10x10A
DESCRIPTION
SYMBOLS
SYMBOLDESCRIPTIONSYMBOL
VALVES AND FITTINGS
EQUIPMENT/DUCT WORK TO BE DEMOLISHED
EXISTING EQUIPMENT/DUCT WORK TO REMAIN
M-X-XXX
M-X-XXX
SHEET NUMBER
DETAIL NUMBER
GAUGE
1 CROSS SHEET REFERENCE (BY NUMBER)
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
AM-0-001
BUILDING 295 - MECHANICAL
LEGEND & SYMBOLS
N.T.S. 07 OF 28
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
STORAGE
ORDERLY
DORM
DORM
LOBBY
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
BATH TYPE 1
BATH TYPE 1
BATH TYPE 1
DORM
DORM
DORM
DORM
DORM
DORM
DORM
107 DORM
MECH
LOUNGE
STORAGE
STORAGE
STORAGE
DORM
BATH TYPE 1
LOUNGE
BATH
TYPE 3
BATH
TYPE 3
BATH
TYPE 2
BATH
TYPE 2
BATH
TYPE 2
M-4-102
FCU-B-1-01
FCU-B-1-02
FCU-B-1-05
FCU-B-1-43 FCU-B-1-42
FCU-B-1-25
FCU-A-1-22
FCU-B-1-19 FCU-B-1-21
FCU-B-1-03
FCU-B-1-04 FCU-B-1-06
FCU-B-1-07
FCU-B-1-08
FCU-B-1-11FCU-B-1-09
FCU-B-1-10 FCU-B-1-12
FCU-B-1-13
FCU-B-1-14
FCU-B-1-17FCU-B-1-15
FCU-B-1-16 FCU-B-1-18 FCU-B-1-20
FCU-B-1-23
FCU-B-1-24
FCU-B-1-45 FCU-B-1-44
FCU-B-1-47 FCU-B-1-46
FCU-B-1-49 FCU-B-1-48
T T T T T T T T T
T T
T
TTTT
TTT
TTTT
T
T
T
T
T
T
T
T
T
T
FCU-B-1-26
FCU-B-1-27
T
FCU-B-1-52
FCU-B-1-50
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
BATH TYPE 1
BATH TYPE 1
BATH TYPE 1
STORAGE
STORAGE
STORAGE
FCU-B-1-26
FCU-B-1-27 FCU-B-1-29
FCU-B-1-28
FCU-B-1-31
FCU-B-1-30 FCU-B-1-32
FCU-B-1-33 FCU-B-1-35
FCU-B-1-34
FCU-B-1-37
FCU-B-1-36 FCU-B-1-38
FCU-B-1-39 FCU-B-1-41
FCU-B-1-40
T T T T T T T T
TTTT
T
TT
T
FCU-B-1-51
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
SCALE:
FIRST FLOOR HVAC PLAN AREA B - BLDG 295
1/8"=1'-0"
SCALE:
FIRST FLOOR HVAC PLAN AREA A - BLDG 295
1/8"=1'-0" 1N
N
1. BALANCE ALL ROOM MOUNTED
FCU'S FOR 35 CFM OUTSIDE AIR.
2. ALL EXISTING FCU'S AND
ASSOCIATED THERMOSTATS,
CONTROL, BALANCING AND
ISOLATION VALVES, STRAINER, ETC.
TO BE REMOVED. INSTALL NEW
FCU'S, THERMOSTATS, CONTROL
AND BALANCING VALVES,
STRAINERS.
3. REMOVE EXISTING EXHAUST GRILLES
AND PROVIDE/INSTALL NEW
REGISTERS AND BALANCE AS
SHOWN. (TYPICAL)
GENERAL NOTES
KEYED" "NOTESX
8'
1/8"=1'-0"
0 8' 16'
EXIST. 36x12 LOUVER
MTZ
DMPR
EXIST. 36x12 LOUVER
MTZ
DMPR
TYPICAL EXIST.
EXHAUST RISER
EXIST. EXHAUST DUCT
EXIST. 36x12 LOUVER
MTZ
DMPRTYPICAL EXIST.
EXHAUST RISER
M-1-101
BUILDING 295 - FIRST FLOOR
HVAC PLAN
08 OF 281/8"=1'-0"
M
AT
CH
LI
N E
M
AT
CH
LI
N E
B B
B B
B B
B B
B B
B B
A
A
A
A
A
A
A A
C
A 25
NEW THERMOSTAT
(TYP. ALL)
1 1 1
1 1 1
4" 1 12" 2"
1"
1 12"
1"
4"
4"
1" 1 12"
2"
M
AT
CH
LI
N E
M
AT
CH
LI
N E
PROVIDE ACCESS THRU WALL
FOR CONDENSATE DRAIN PIPING.
TYPICAL ALL BATH TYPE 1 FCU'S.
REMOVE EXISTING FIN TUBE
HEATER AND DTS PIPING.
REROUTE EXISTING DTS AND
CONDENSATE PIPING IN THIS AREA
TO ACCOMMODATE NEW
OUTSIDE AIR SYSTEM
INSTALLATION.
PROVIDE ACCESS THRU WALL
(8 IN X6 IN) FOR OUTSIDE AIR
INTAKE, HVAC AND CONDENSATE
DRAIN PIPING. TYPICAL ALL
BEDROOM FCU'S.
EXISTING CONDENSATE DRAIN
PIPING.
EXISTING SDTWS & R PIPES.
RELOCATE EXISTING PIPES TO
ACCOMMODATE NEW FCU.
RELOCATE LIGHT FIXTURE AND EXIT
SIGN TO ACCOMMODATE NEW
FCU.
3/4" SDTWS&R FOR NEW FCU.
BRANCH OFF EXISTING SDTWS&R
MAIN. PROVIDE NEW 3 4"
CONDENSATE DRAIN PIPING.
KEYED" "NOTESX
OA SYSTEM, REFER TO 3/M-5-001
BATHROOM FCU RIGHT SIDE PIPE
FCU 1/2" PIPE CONN, 1" EXT
TYPICAL FOR BATH TYPE 1 ON ALL
WINGS.
EXISTING TRANSFORMERS IN
MECHANICAL YARD TO REMAIN.
DEMOLISH EXISTING 80 TON AIR
COOLED CHILLER, CHILLED WATER
LINES, CONTROLS, ELECTRICAL,
AND ASSOCIATED
APPURTENANCES IN MECHANICAL
YARD.
111111
111111
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
JAN
210 STORAGE
ORDERLY
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
TOILET
TOILET
TOILET
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
LOUNGE
STORAGE
STORAGE
STORAGE
LOUNGE
STAIRS
SUPPLY
ROOM
BATH
TYPE 3
BATH
TYPE 3
BATH
TYPE 2
BATH
TYPE 2
BATH
TYPE 2
FCU-B-2-01
FCU-B-2-02
FCU-B-2-03
FCU-B-2-04
FCU-B-2-05
FCU-B-2-06
FCU-B-2-07
FCU-B-2-08
FCU-B-2-09
FCU-B-2-10
FCU-B-2-11
FCU-B-2-12
FCU-B-2-13
FCU-B-2-14
FCU-B-2-15
FCU-B-2-16
FCU-B-2-17
FCU-B-2-18
FCU-B-2-22
FCU-B-2-19 FCU-B-2-21
FCU-B-2-20
FCU-B-2-23
FCU-B-2-24
FCU-B-2-43 FCU-B-2-42
FCU-B-2-45 FCU-B-2-44
FCU-B-2-47 FCU-B-2-46
FCU-B-2-49 FCU-B-2-48
T T
T T
T T
T T
T T T T T T T T T T T
T
TTTT
TTT
TTTT
T
T T
T T
T T
T T
FCU-B-2-52
FCU-B-2-50
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
TOILET
TOILET
TOILET
STORAGE
STORAGE
STORAGE
FCU-B-2-27
FCU-B-2-26
FCU-B-2-29
FCU-B-2-28
FCU-B-2-31
FCU-B-2-30
FCU-B-2-33
FCU-B-2-32
FCU-B-2-35
FCU-B-2-34
FCU-B-2-37
FCU-B-2-36
FCU-B-2-39
FCU-B-2-38
FCU-B-2-41
FCU-B-2-40
T T T T T T T T
TTTT
T
TT
T
FCU-B-2-51
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
SCALE:
SECOND FLOOR HVAC PLAN AREA B - BLDG 295
1/8"=1'-0"
SCALE:
SECOND FLOOR HVAC PLAN AREA A - BLDG 295
1/8"=1'-0" 1N
N
1. BALANCE ALL ROOM MOUNTED
FCU'S FOR 35 CFM OUTSIDE AIR.
2. ALL EXISTING FCU'S AND ASSOCIATED
THERMOSTATS, CONTROL,
BALANCING AND ISOLATION VALVES,
STRAINER, ETC. TO BE REMOVED.
INSTALL NEW FCU'S, THERMOSTATS,
CONTROL AND BALANCING VALVES,
STRAINERS.
3. REMOVE EXISTING EXHAUST GRILLES
AND PROVIDE/INSTALL NEW
REGISTERS AND BALANCE AS
SHOWN. (TYPICAL)
GENERAL NOTES
KEYED" "NOTESX
TYPICAL EXIST.
EXHAUST RISER
NEW THERMOSTAT
(TYP. ALL)
EXIST. EXHAUST DUCT
NEW THERMOSTAT
(TYP. ALL)
EXIST. 36x12
LOUVER
MTZ DMPR
EXIST. 36x12
LOUVER
MTZ DMPR
EXIST. 36x12
LOUVER
MTZ
DMPR
8'
1/8"=1'-0"
0 8' 16' M-1-201
BUILDING 295 - SECOND FLOOR
HVAC PLAN
09 OF 281/8"=1'-0"
TYPICAL EXIST.
EXHAUST RISERM
AT
CH
LI
N
E M
AT
CH
LI
N
E
B B
B B
B B
B B
B B
B B
A
A
A
A
A
A
A
A
C A 2580
1 1
4" 1 12" 2"1"
4"
1"
1 12"
2"
1 12"
1"
4"
M
AT
CH
LI
N E
M
AT
CH
LI
N E
PROVIDE ACCESS THRU WALL
FOR CONDENSATE DRAIN PIPING.
TYPICAL ALL BATH TYPE 1 FCU'S.
REMOVE EXISTING FIN TUBE
HEATER AND DTS PIPING.
REROUTE EXISTING DTS AND
CONDENSATE PIPING IN THIS AREA
TO ACCOMMODATE NEW
OUTSIDE AIR SYSTEM
INSTALLATION.
PROVIDE ACCESS THRU WALL
(8 IN X6 IN) FOR OUTSIDE AIR
INTAKE, HVAC AND CONDENSATE
DRAIN PIPING. TYPICAL ALL
BEDROOM FCU'S.
EXISTING CONDENSATE DRAIN
PIPING.
EXISTING SDTWS & R PIPES.
RELOCATE EXISTING PIPES TO
ACCOMMODATE NEW FCU.
RELOCATE LIGHT FIXTURE AND EXIT
SIGN TO ACCOMMODATE NEW
FCU.
3/4" SDTWS&R FOR NEW FCU.
BRANCH OFF EXISTING SDTWS&R
MAIN. PROVIDE NEW 3 4"
CONDENSATE DRAIN PIPING.
91111
111111
112 2 2
KEYED" "NOTESX
OA SYSTEM, REFER TO 3/M-5-001
BATHROOM FCU RIGHT SIDE PIPE
FCU 1/2" PIPE CONN, 1" EXT
TYPICAL FOR BATH TYPE 1 ON ALL
WINGS.
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
JAN
361 STORAGE
OPEN
AREA
DORM
DORM
LOBBY
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
TOILET
TOILET
TOILET
DORM
DORM
DORM
DORM
DORM
DORM
DORM
307 DORM
MECH
LOUNGE
STORAGE
STORAGE
354STORAGE
LOUNGE
STAIRS
BATH
TYPE 3
BATH
TYPE 3
BATH
TYPE 2
BATH
TYPE 2
BATH
TYPE 2
FCU-B-3-01
FCU-B-3-02
FCU-B-3-05FCU-B-3-03
FCU-B-3-04 FCU-B-3-06
FCU-B-3-07
FCU-B-3-08
FCU-B-3-11FCU-B-3-09
FCU-B-3-10 FCU-B-3-12
FCU-B-3-13
FCU-B-3-14
FCU-B-3-17FCU-B-3-15
FCU-B-3-16 FCU-B-3-18
FCU-B-3-43 FCU-B-3-42
FCU-B-3-45 FCU-B-3-44
FCU-B-3-47 FCU-B-3-46
FCU-B-3-49 FCU-B-3-48
FCU-B-3-22
FCU-B-3-19 FCU-B-3-21
FCU-B-3-20
FCU-B-3-23
FCU-B-3-24
FCU-B-3-25
EF-B1 EF-B2 EF-B3
EF-B9 EF-B8
EF-B10EF-B11
EF-B7
T
T
T
T
T T T T T T T T T
T T
T
TTTT
TTT
TTTT
T
T
T
T
T
T
T
T
T
T
FCU-B-3-50
FCU-B-3-52
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
DORM
TOILET
TOILET
TOILET
STORAGE
STORAGE
STORAGE
FCU-B-3-29FCU-B-3-27
FCU-B-3-26 FCU-B-3-28
FCU-B-3-31
FCU-B-3-30
FCU-B-3-35FCU-B-3-33
FCU-B-3-32 FCU-B-3-34
FCU-B-3-37
FCU-B-3-36
FCU-B-3-41FCU-B-3-39
FCU-B-3-38 FCU-B-3-40
EF-B4 EF-B6EF-B5
T T T T T T T T
TTTT
T
TT
T
FCU-B-3-51
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
SCALE:
THIRD FLOOR HVAC PLAN AREA B - BLDG 295
1/8"=1'-0"
SCALE:
THIRD FLOOR HVAC PLAN AREA A - BLDG 295
1/8"=1'-0" 1N
N
1. BALANCE ALL ROOM MOUNTED
FCU'S FOR 35 CFM OUTSIDE AIR.
2. ALL EXISTING FCU'S AND
ASSOCIATED THERMOSTATS,
CONTROL, BALANCING AND
ISOLATION VALVES, STRAINER, ETC.
TO BE REMOVED. INSTALL NEW
FCU'S, THERMOSTATS, CONTROL
AND BALANCING VALVES,
STRAINERS.
3. REMOVE EXISTING EXHAUST GRILLES
AND PROVIDE/INSTALL NEW
REGISTERS AND BALANCE AS
SHOWN. (TYPICAL)
GENERAL NOTES
KEYED" "NOTESX
NEW THERMOSTAT
(TYP. ALL)
MTZ
DMPR
EXIST. 36x12
LOUVER
NEW THERMOSTAT
(TYP. ALL)
EXIST. EXHAUST DUCT
MTZ DMPR
EXIST. 36x12
LOUVER
LOCATION FOR
ANTENNA
FOR RADIO
CONTROLLED
VALVE
EXIST. 36x12
LOUVER MTZ DMPR
TYPICAL EXIST.
EXHAUST RISER
8'
1/8"=1'-0"
0 8' 16' M-1-301
BUILDING 295 - THIRD FLOOR
HVAC PLAN
10 OF 281/8"=1'-0"
TYPICAL EXIST.
EXHAUST RISERM
AT
CH
LI
N
E M
AT
CH
LI
N
E
B B
B B
B B
B B
B B
B B
A
A
A
A
A
A
A
A
C A 2580
4" 1 12" 2"1"
1 12"
1"
4"
4"
1" 1 12"
2"4
M
AT
CH
LI
N E
M
AT
CH
LI
N E
111111
11 11
11 11
111111
121212
121212
2 2
6 5
KEYED" "NOTESX
OA SYSTEM, REFER TO 3/M-5-001
REPLACE EXISTING FAN ON ROOF.
SEE SCHEDULES.
BATHROOM FCU RIGHT SIDE PIPE
FCU 1/2" PIPE CONN, 1" EXT
TYPICAL FOR BATH TYPE 1 ON ALL
WINGS.
PROVIDE ACCESS THRU WALL
FOR CONDENSATE DRAIN PIPING.
TYPICAL ALL BATH TYPE 1 FCU'S.
REMOVE EXISTING FIN TUBE
HEATER AND DTS PIPING.
REROUTE EXISTING DTS AND
CONDENSATE PIPING IN THIS AREA
TO ACCOMMODATE NEW
OUTSIDE AIR SYSTEM
INSTALLATION.
PROVIDE ACCESS THRU WALL
(8 IN X6 IN) FOR OUTSIDE AIR
INTAKE, HVAC AND CONDENSATE
DRAIN PIPING. TYPICAL ALL
BEDROOM FCU'S.
EXISTING CONDENSATE DRAIN
PIPING.
EXISTING SDTWS & R PIPES.
RELOCATE EXISTING PIPES TO
ACCOMMODATE NEW FCU.
RELOCATE LIGHT FIXTURE AND EXIT
SIGN TO ACCOMMODATE NEW
FCU.
3/4" SDTWS&R FOR NEW FCU.
BRANCH OFF EXISTING SDTWS&R
MAIN. PROVIDE NEW 3 4"
CONDENSATE DRAIN PIPING.
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
SCALE:
ENLARGED FIRST FLOOR MECH ROOM DEMO PLAN
1/2"=1'-0"
REMOVE EXISTING PROPANE PIPING
TO BELOW GRADE. DISCONNECT AT
TANK AND REMOVE TO BELOW
GRADE. OUTSIDE FUEL PIPING TO
REMAIN IN PLACE. DRAIN AND CAP
FUEL PIPING LEFT IN PLACE.
4" DCW ENTRY TO REMAIN. 4" DCW
ISOLATION VALVE TO BE REPLACED.
DHWR PUMP AND ALL ASSOCIATED
PIPING TO BE REMOVED. NEW
DHWR LINES WILL CONNECT TO
EXISTING PIPING
CAP EXISTING DHW SUPPLY PIPE. TO
BE CONNECTED TO NEW DHW PIPE.
REMOVE EXISTING CHILLED WATER
PIPING ENTRY TO BELOW SLAB. NEW
DUAL TEMP TO BE INSTALLED IN IT'S
PLACE.
DEMOLISH EXISTING DTS PIPING AS
SHOWN IN THE HATCH AREA TO
ACCOMMODATE NEW TANK
INSTALLATION.
EXISTING BOILER, PAD, FLUE STACK,
ASSOCIATED PIPING AND
APPURTENANCES TO BE REMOVED.
CAP AND REPAIR FLUE STACK ROOF
PENETRATION.
EXISTING UNDERFLOOR WASTE TO
BE ABANDONED IN PLACE.
EXISTING DHW STORAGE TANK AND
ALL ASSOCIATED PIPING AND PUMPS
TO BE REMOVED.
EXISTING WASTE FROM DRAIN TO BE
REMOVED.
EXISTING HWP AND ASSOCIATED
PIPING TO BE REMOVED.
KEYED" "NOTESX
KEY PLAN
1/2"=1'-0"
2' 4'0 2' N
M-4-101
BUILDING 295 - ENLARGED MECH
ROOM PLAN - DEMO
11 OF 281/2" = 1'-0"
5 6
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
SCALE:
ENLARGED FIRST FLOOR MECHANICAL PLAN - NEW WORK
1/2"=1'-0" 1N
EXISTING SECONDARY
DUAL TEMPERATURE
SUPPLY AND RETURN
SECONDARY SOURCE
WATER. REFER TO CIVIL
FOR CONTINUATION.
SECONDARY DUAL TEMPERATURE
WATER. REFER TO CIVIL
FOR CONTINUATION.
ELECTRICAL
PANELS
4"
2" 2-1/2"
KEY PLAN
1/2"=1'-0"
2' 4'0 2' N
M-4-102
BUILDING 295 - ENLARGED MECH
ROOM PLAN - NEW WORK
12 OF 281/2" = 1'-0"
DHWHP-3 DHWHP-4
GENERAL NOTES
KEYED" "NOTESX
SECONDARY SOURCE WATER
HEATER. REFER TO PLUMBING.
DOMESTIC HOT WATER STORAGE.
REFER TO PLUMBING.
INSTALL ISOLATION VALVE IN RISE.
INSTALL PIPING 14' AFF.
REROUTE 3" DTS PIPING TO FIRST
AND THIRD FLOOR AS SHOWN TO
ACCOMMODATE NEW HOT WATER
TANKS INSTALLATION.
REROUTE 3" DTS PIPING TO
SECOND FLOOR AS SHOWN TO
ACCOMMODATE NEW HOT WATER
TANKS INSTALLATION.
DOMESTIC HOT WATER EXPANSION
TANK. REFER TO PLUMBING.
EXISTING SECONDARY
DUAL TEMPERATURE
SUPPLY AND RETURN
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
DPenney Rectangle
COIL
3/4" CD (MIN) FROM
UNIT THRU 6" DEEP
RUNNING TRAP
PROVIDE REQUIRED
CLEARANCE AROUND
AND MAINTENANCE
UNIT FOR SERVICE
CDSDTWSSDTWR
FAN
O/A
SUSPEND UNIT FROM
STRUCTURE WITH THREADED
ROD PER MFR RECMDS
TYPICAL HORIZONTAL
FAN COIL UNIT
R/A
S/A
CONNECT TO EXISTING
HYDRONIC AND
CONDENSATE PIPING
REFER 6/M-501
UNIT MOUNTED AGAINST CORRIDOR
WALL. OUTSIDE AIR ENTERS ABOVE
CEILING VIA SUPPLY PLENUM
FILTER
STEEL SUPPORTS AT OR
NEAR PENETRATION TO
SUSTAIN CURB AND ROOF
DESIGN LOADS, RE:
ARCHITECTURAL
SET EQUIPMENT LEVEL.
SUPPORT ROOF CURB ON ROOF STRUCTURE NOT ROOF INSULATION.
1.
2.
NOTES:
VARIES
PRE-MANUFACTURED
14" ROOF CURB
FL
AS
HI
N
G
HE
IG
HT
" N
O M
IN
AL
RIGID INSULATION
ROOF EQUIPMENT
BIRDSCREEN
ROOF STRUCTURE
ROOF MEMBRANE
MEMBRANE BASE
FLASHING
EXTEND FIELD PLIES
8" MIN ABOVE ROOF
HIGH-DOMED, CAPPED, GASKETED
FASTENERS 18" OC (MINIMUM
TWO FASTENERS PER SIDE)
SHEET METAL
FLASHING RECEIVER
SEALING MATERIAL
COVERBOARD
WOOD NAILER
6"
EQUIPMENT BASE
6"
FLOOR
4" U
N
LE
SS
O
TH
ER
W
IS
E
*1 -1
/2
STEEL PIPE
(WHEN USED)
COPPER PIPE
COPPER PIPE
REF: NOTE
INDICATED ON THE EQUIPMENT SCHEDULES. PROVIDE
UNIONS ON COIL SIDE OF S.O. VALVES IF ALL SWEAT
CONNECTIONS ARE USED.
PROVIDE 2-WAY OR 3-WAY CONTROL VALVES AS
NOTE:
1/2" UNLESS OTHERWISE
SHOWN
ISOLATING UNION
GATE VALVE
FLOW CONTROL VALVE
MODULATING CONTROL VALVE
TEST PLUG
UNION
ISOLATING UNION
GATE VALVE
STRAINER
TEST PLUG
UNION
COIL
WATER
TEMP
DUAL
EXISTING 12x36 LOUVER
FLOOR DECK
MOTORIZED DAMPER
FROM
12 TO
30IN.
1. REFER TO DETAIL 5/M-5-001 FOR PIPING
CONNECTION
2. REFER TO DETAIL 1/M-5-001 FOR MOUNTING
3. ABOVE CEILING IN CORRIDOR
NOTE:
CEILING
SCALE:
FAN COIL MOUNTING DETAIL
N.T.S.
1200 Summit Ave, Suite 650 Fort Worth, Texas 76102 Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
SCALE:
SECTION AT EXHAUST FAN
N.T.S.
SCALE:
TYPICAL EQUIPMENT PAD DETAIL
N.T.S.
SCALE:
SDTW PIPING AT FAN COIL UNITS
N.T.S.
GENERAL NOTES
M-5-001
BUILDING 295 - MECHANICAL
DETAILS
N.T.S. 13 OF 28
SCALE:
OUTSIDE AIR SYSTEM DETAIL
N.T.S.
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
1. FURNISH APPROPRIATE MOTOR
STARTER FOR ALL MOTORS.
2. FOR ALL MOTORS - MOTOR BRAKE
HORSEPOWER SHALL NOT EXCEED
85% OF NORMAL NAMEPLATE
HORSEPOWER (WITHOUT
CONSIDERATION OF THE SERVICE
FACTOR).
3. FAN RPM AT DESIGN CONDITIONS
SHALL NOT EXCEED 85% OF
MANUFACTURER'S MAXIMUM FOR
THE CLASS OF CONSTRUCTION.
4. EQUIPMENT CAPACITIES SHALL BE
BASED ON AN ELEVATION OF 1467
ABOVE SEA LEVEL.
GENERAL NOTES
M-6-001
BUILDING 295 - MECHANICAL
SCHEDULES
N.T.S. 14 OF 28
FAN COIL UNIT SCHEDULE
MARK DESCRIPTION ROOM NO
FAN DATA COIL DATA COOLING DATA HEATING DATA
3-WAY
VALVE BASIS OF DESIGN
TOTAL
CFM
MAX.
EXT. S.P.
IN.W.C. FAN SPEED
MIN. FAN
H.P. GPM
MAX
WATER
P.D. FEET
TOTAL
MBH
SENSIBLE
MBH
ENT. AIR
D.B.
DEG F
ENT. AIR
W.B.
DEG F
ENT. WTR.
TEMP
DEG F
TOTAL
MBH
ENT. AIR
TEMP.
DEG F
ENT. WTR.
TEMP
DEG F
FCU-B-1-01 HORIZONTAL CABINET 475 0.1 MEDIUM 1/12 1.5 5 8.8 8.3 78.0 64.0 44 12.3 69 140 YES DAIKIN FCHC-206 FCU-B-1-02 HORIZONTAL CABINET 500 0.1 MEDIUM 1/12 1.5 5 9.9 9.3 78.0 64.0 44 12.3 69 140 YES DAIKIN FCHC-206 FCU-B-1-03 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 YES DAIKIN FCHC-203 FCU-B-1-04 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-05 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-06 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-07 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-08 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-09 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-10 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-11 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-12 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-13 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-14 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-15 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-16 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-17 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-18 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-19 HORIZONTAL CABINET 400 0.1 MEDIUM 1/12 1.5 5 7.6 7.2 78.0 64.0 44 9.0 69 140 DAIKIN FCHC-206 FCU-B-1-20 HORIZONTAL CABINET 400 0.1 MEDIUM 1/12 1.5 5 7.9 7.4 78.0 64.0 44 - 69 140 DAIKIN FCHC-206 FCU-B-1-21 HORIZONTAL CABINET 400 0.1 MEDIUM 1/12 1.5 5 7.6 7.2 78.0 64.0 44 9.0 69 140 DAIKIN FCHC-206 FCU-B-1-22 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-23 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-24 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-25 HORIZONTAL RECESSED 350 0.3 MEDIUM 1/8 1.1 5 6.4 6.0 78.0 64.0 44 8.4 69 140 DAIKIN FCHR-203 FCU-B-1-26 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-27 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-28 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-29 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-30 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-31 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-32 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-33 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-34 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-35 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-36 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-37 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-38 HORIZONTAL CABINET 300 0.1 MEDIUM 1/20 1.0 5 6.0 5.6 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-39 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 4.7 4.4 78.0 64.0 44 5.5 69 140 YES DAIKIN FCHC-203 FCU-B-1-40 HORIZONTAL CABINET 500 0.1 MEDIUM 1/12 1.5 5 9.9 9.3 78.0 64.0 44 12.3 69 140 YES DAIKIN FCHC-206 FCU-B-1-41 HORIZONTAL CABINET 475 0.1 MEDIUM 1/12 1.5 5 8.6 8.1 78.0 64.0 44 12.3 69 140 YES DAIKIN FCHC-206 FCU-B-1-42 HORIZONTAL CABINET 350 0.1 MEDIUM 1/20 1.0 5 6.4 6.0 78.0 64.0 44 8.4 69 140 DAIKIN FCHC-203 FCU-B-1-43 HORIZONTAL CABINET 475 0.1 MEDIUM 1/12 1.5 5 8.8 8.3 78.0 64.0 44 12.3 69 140 DAIKIN FCHC-206 FCU-B-1-44 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 5.1 4.8 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-45 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 1.0 5 5.3 5.0 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-46 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 0.8 5 5.1 4.8 78.0 64.0 44 5.5 69 140 DAIKIN FCHC-203 FCU-B-1-47 HORIZONTAL CABINET 230 0.1 MEDIUM 1/20 1.0 5 5.3 5.0 78.0 64.0 44 5.5 69 140 YES DAIKIN FCHC-203 FCU-B-1-48 HORIZONTAL CABINET 500 0.1 MEDIUM 1/12 1.5 5 10.1 9.5 78.0 64.0 44 12.1 69 140 YES DAIKIN FCHC-206 FCU-B-1-49 HORIZONTAL CABINET 500 0.1 MEDIUM 1/12 1.5 5 10.1 9.6 78.0 64.0 44 12.1 69 140 YES DAIKIN FCHC-206 FCU-B-1-50 HORIZONTAL RECESSED CORRIDOR 550 0.5 MEDIUM 1/8 3.7 5 18.0 18.0 102.0 71.0 44 24 140 YES DAIKIN FCHR-204
FCU-B-1-51 CORRIDOR 550 0.5 MEDIUM 1/8 3.7 5 44 140 YES DAIKIN FCHR-204
FCU-B-1-52 CORRIDOR 550 0.5 MEDIUM 1/8 3.7 5 44 28.0 140 YES DAIKIN FCHR-204
HORIZONTAL RECESSED
HORIZONTAL RECESSED
18.0 18.0
18.0 18.0
28.0 28.0
102.0 71.0
102.0 71.0
1. SENSIBLE COOLING MUST BE MET EVEN IF TOTAL CAPACITY EXCEEDS TOTAL LOAD.
2. FAN COILS TO BE SELECTED AT MEDIUM SPEED.
3. CONTROL VALVES FOR RECESSED OR CONCEALED UNITS MAY BE EXTERNAL TO THE FCU. CONTROL VALVES FOR
CABINET MODELS SHALL BE INTERNAL.
4. COIL CONNECTION ARE SWEAT.
5. CORRIDOR UNITS ARE 100% OA, OUTSIDE AIR INTAKE ON BACK WITH AUTOMATIC DAMPER, AND RIGHT HAND
PIPING.
6. ALL UNITS TO BE BOTTOM RETURN.
7. DORM ROOM UNITS TO BE LEFT HAND PIPING AND OA INTAKE ON BACK.
8. RESTROOM AND LAUNDRY UNITS TO BE RIGHT HAND PIPING, WITHOUT OA INTAKE.
ARIMS: 200A Disposition: Maintain for 15yrs after construction
W
2Q R
R
-0
Phone: 817-632-6100
TBPE FIRM: TX F-13289
PROJECT
DRAWING NAME
P17018 FORT HUNTER LIGGETT
HVAC & PLUMBING UPGRADES
FORT HUNTER LIGGETT
JOLON, CALIFORNIA
A XX/XX/18
8600 N. Royal Lane, Suite 100
Irving, TX 75063 U.S.A
Phone: 972-550-8488
Fax: 972-751-1194
REV DESCRIPTION DATE
REVISIONS
TH
AM
ISSUE FOR CONSTRUCTION
CHECKED BY
DESIGNED BY
SHEETSCALE SIZE
DWG NO. REV
D
A
1. FURNISH APPROPRIATE MOTOR
STARTER FOR ALL MOTORS.
2. FOR ALL MOTORS - MOTOR BRAKE
HORSEPOWER SHALL NOT EXCEED
85% OF NORMAL NAMEPLATE
HORSEPOWER (WITHOUT
CONSIDERATION OF THE SERVICE
FACTOR).
3. FAN RPM AT DESIGN CONDITIONS
SHALL NOT EXCEED 85% OF
MANUFACTURER'S MAXIMUM FOR
THE CLASS OF CONSTRUCTION.
4. EQUIPMENT CAPACITIES SHALL BE
BASED ON AN ELEVATION OF 1467
ABOVE SEA LEVEL.
GENERAL NOTES
M-6-002
BUILDING 295 - MECHANICAL
SCHEDULES
N.T.S. 15 OF 28
FAN COIL UNIT SCHEDULE (CONT)
MARK DESCRIPTION ROOM NO
FAN DATA COIL DATA COOLING DATA HEATING DATA
3-WAY
VALVE BASIS OF DESIGN
TOTAL
CFM
MAX.
EXT. S.P.
IN.W.C FAN SPEED
MIN. FAN
H.P. GPM
MAX
WATER
P.D. FEET
TOTAL
MBH
SENSIBLE
MBH
ENT. AIR
D.B.
DEG F
ENT. AIR
W.B.
DEG F
ENT. WTR.
TEMP
DEG F
TOTAL
MBH
ENT. AIR
TEMP.
DEG F
ENT. WTR.
TEMP
DEG F
FCU-B-2-01 HORIZONTAL CABINET 247 475 0.1 MEDIUM 5 8.8 8.3 78.0 64.0 44 12.3 69 140 YES FCU-B-2-02 HORIZONTAL CABINET 248 500 0.1 MEDIUM 5 9.9 9.3 78.0 64.0 44 12.3 69 140 YES FCU-B-2-03 HORIZONTAL CABINET 246 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 YES FCU-B-2-04 HORIZONTAL CABINET 249 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-05 HORIZONTAL CABINET 245 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-06 HORIZONTAL CABINET 251 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-07 HORIZONTAL CABINET 244 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-08 HORIZONTAL CABINET 252 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-09 HORIZONTAL CABINET 243 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-10 HORIZONTAL CABINET 253 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-11 HORIZONTAL CABINET 242 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-12 HORIZONTAL CABINET 255 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-13 HORIZONTAL CABINET 241 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-14 HORIZONTAL CABINET 256 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-15 HORIZONTAL CABINET 240 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-16 HORIZONTAL CABINET 257 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-17 HORIZONTAL CABINET 239 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-18 HORIZONTAL CABINET 259 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140 FCU-B-2-19 HORIZONTAL CABINET 238 400 0.1 MEDIUM 5 7.6 7.2 78.0 64.0 44 9.0 69 140
FCU-B-2-20 HORIZONTAL CABINET 209 400 0.1 MEDIUM 5 7.6 7.2 78.0 64.0 44 - 69 140
FCU-B-2-21 HORIZONTAL CABINET 237 400 0.1 MEDIUM 5 7.6 7.2 78.0 64.0 44 9.0 69 140 FCU-B-2-22 HORIZONTAL CABINET 212 230 0.1 MEDIUM 5 5.0 4.7 78.0 64.0 44 5.4 69 140 FCU-B-2-23 HORIZONTAL CABINET 236 230 0.1 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140 FCU-B-2-24 HORIZONTAL CABINET 216 300 0.1 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140
FCU-B-2-25 NOT USED
FCU-B-2-26 HORIZONTAL CABINET 217 300 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140
FCU-B-2-27 HORIZONTAL CABINET 226 230 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140
FCU-B-2-28 HORIZONTAL CABINET 219 300 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140
FCU-B-2-29 HORIZONTAL CABINET 234 230 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140
FCU-B-2-30 HORIZONTAL CABINET 220 300 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140
FCU-B-2-31 HORIZONTAL CABINET 223 230 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140
FCU-B-2-32 HORIZONTAL CABINET 221 300 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140
FCU-B-2-33 HORIZONTAL CABINET 232 230 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140
FCU-B-2-34 HORIZONTAL CABINET 223 300 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69 140
FCU-B-2-35 HORIZONTAL CABINET 231 230 MEDIUM 5 4.7 4.4 78.0 64.0 44 5.5 69 140
FCU-B-2-36 HORIZONTAL CABINET 224 300 MEDIUM 5 6.0 5.6 78.0 64.0 44 5.5 69…