QUESTIONS AND ANSWERS COMBINED SYNOPSIS SOL W912PF‐19‐Q‐0069

Q ‐ Do you accept a digital instrument panel, incorporated in the electronic control unit (engine and alternator protection), with readings shown on a single display (DEEP SEA, COMAP etc.)?

A ‐ Yes

Q – Do you accept engines with different displacements but with power characteristics equal to or greater than those required by the specifications allowed?

A – Please refer to technical specifications

Q ‐ Please specify the level of exhaust gas emissions, considering that, being a mobile unit, the level of gaseous emissions in the EU must be equal to STAGE V

A – The gas emission level must be in accordance with local regulations

Q ‐ Do you want the preheating of the cooling fluid?

A – Yes

Q ‐ Does the soundproof canopy have to be supplied with a separate price (optional)?

A – We have listed the soundproof canopy as optional in the specifications but should be required and therefore included

Q ‐ What kind of soundproofing material is required (mineral wool, polyester fiber etc.)?

A – No preference for the material provided

Q ‐ Does the general equipment switch have to be equipped with selective differential protection?

A – As stated by the law and regulation

Q ‐ Does the engine electrical system have to be 24 V or is it also 12 V accepted?

A – It can be 12V or 24V

Q – You are asking “Rated voltage 400 / 230V (adjustable)”, is the regulation of the voltage (+/‐ 15‐20V) by potentiometer placed on the control panel?

A – The generator should be made to provide both voltages 400V and 230V tri‐phases

Q ‐ Are the dimensions (2750 * 850 * 1150) and weight (1250 kg) referred to the generator only without a soundproof canopy?

A – No they are referred to the whole generator

Q ‐ Does the generator set complete with trailer have a maximum weight not to exceed?

A – Indicative weight is 1250 Kg

Q ‐ Does the generator set complete with trailer have to be of a maximum size not to exceed?

A – Indicative sizes (2750*850*1150)

Q ‐ What capacity should have the fuel tank?

A – The fuel tank should have a daily capacity

Q ‐ Does the generator set have to be equipped with a distribution panel with sockets, switches, etc.?

A – Yes, it is specified in the detail below:

A. the number of sockets, the amperage and the type (CEE or other types) = 5 sockets CEE, 1 each 200A

3P+N+T, 1 each 63A 3P+N+T, 1 each 32A 3P+N+T, 1 each 32A 3P+T, 1 each 16A 2P

B. if each socket must be equipped with a magnetic thermic switch = Yes

C. if each socket must be equipped with differential protection = Yes

D. if powerlock (CAM‐LOCK) must be provided for the taking of the total power of the generating set = Yes with panel

E. If the power locks are to be provided, are the panel ones (PANEL SOURCE CONNECTOR) sufficient or the flying males (LINE DRAINE CONNECTOR) also provided? = Panel are sufficient

Q ‐ Does the trailer has to be for fast road towing or for slow construction towing?

A – Road towing

Q ‐ If it must be for fast road towing, specify if:

A. it must be equipped with a height‐adjustable tiller or fixed tiller = adjustable

B. the approval must be of the type "for special use for transporting the generator" = Yes

C. Is registration required with the corresponding number plate? = No

D. if only one axis is sufficient or the two tandem axles are required = Double axle

E. Does it have to be fitted with a ball joint, a NATO eye or both with a removable and replaceable system?

= It should be equipped with both interchangeable system

Q – The price of the generator has to include shipping charges to your location?

A ‐ Yes

If you need to include the transport, please specify:

A. the destination = Address is listed on the combined/synopsis solicitation W912PF‐19‐Q‐0069

B. is the price including also the unloading on the ground on a square by crane? = Yes

C. please specify if there are obstacles to the access of a truck, and/or a crane, reference the maneuvering spaces, plants, flower beds, urban underground services, pipes, cable ducts, tunnels, overhead lines, underground rooms, transit permits of trucks, restrictions on the capacity of access routes, etc. = the details of the delivery of the generator will have to be planned upon delivery date