Amendment 0003.pdf
PDF 600 KB Posted
- Attached to
- Calcasieu Lock east sector gate replacement Federal contract opportunity
- Solicitation number
- W912P823R0099
About this file
This document is an amendment to a solicitation for the Calcasieu Lock east sector gate replacement project for the Department of the Army Corps of Engineers Engineering District New Orleans. The amendment provides responses to 11 questions from potential offerors. Key details include that the scope of work involves furnishing, fabricating, and installing all components for new sector gates, including rack and cathodic protection systems, hinge bearings, pintles, and handrails. Patterns for castings must be provided by the contractor. Dimensional surveys are required at various stages. Composite timber must meet specified properties. The quote due date of September 1, 2023 remains unchanged.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 0002.pdf | ||
| Amendment 0001.pdf | ||
| Amendment(001).pdf | ||
| Solicitation-Synopsis .pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The subject solicitation for Calcasieu Lock East Sector Gate Replacement, Calcasieu Parish, Louisiana is hereby amended to provide Government responses to quoter questions on the attached Continuation pages.
The quote due date of 10:00am local time, 01 September 2023 remains unchanged.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 4
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 15-Aug-2023
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912P823R0099
X 9B. DATED (SEE ITEM 11)
02-Aug-2023
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
15-Aug-2023
CODE
USACE, CONTRACTING DIVISION
ATTN: CEMVN-CT, ROOM 172
7400 LEAKE AVE.
NEW ORLEANS LA 70118-3651
W912P8 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912P823R0099
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
QUESTIONS
1. We need clarification and a set of specifications for material supply, NDE requirements, and paint requirements.
In general, material and product requirements are in Section C1, NDE requirements are in Sections C2 and C3, and paint requirements are included in Section C4 of the advertised specifications. Note that there may be some cross over among the specification sections (e.g., Section C1 may include some inspection and NDE requirements).
2. We need to clarify if the supply of the rack and cathodic protection is actually part of the scope. There is a note on M501 that the 5/8" seal welded plate is to be machined to 1/2" in the field implying this may be supplied by others as weld. Again, on drawings CP100-103, there is a note about anodes systemed supplied by others. Are we supplying the anodes and other?
The rack and all of the components shown in Detail C5 on Drawing M-501 including welding of the 5/8” plate are part of the scope of work. The plate will be machined to the required thickness to achieve the gap specified in Detail A4 by the Government during installation. Please see Note 5.1 on sheet G-003.
Per Section C5, paragraph 1.2 GENERAL REQUIREMENTS:
For each sector gate, the Contractor shall furnish, fabricate, and install all anode supporting hardware and mounting techniques, connections, support steel channels, and assembly details in compliance with these contract plans/drawings and specifications, in accordance with the recommendations of the respective manufacturers, in accordance with standard construction practice, and as approved by the Contracting Officer's representative to conform with the minimum requirements of this contract.
Other paragraphs in Section C5 should also clarify what is required under this contract.
The Junction Box Support is also part of this contract.
Anodes, reference cells, conduit, wiring, and any other item that is stated as “NIC” (Not in Contract) are also not required to be purchased and installed by the Contractor.
The 5/8” steel band shown on Sht. M-501 is to be furnished and installed under this contract. The machining will be by others.
3. Please clarify the note on skin splice location being 8' from intercoastal members. At approximately 22' high, and having 3 intercoastal members, we are unsure of the intended location.
Intercostals are the vertical ribs located between the skin plate and the horizontal girders. Vertical splices in the skin plate shall be located at least 8” from the intercostals as stated on Note 4 on Drawing S-201. The contractor shall show the actual splice locations on the shop drawings for Government review and approval.
4.Need to confirm if a dimensional survey of the completed gate is a requirement.
Drawing G-005 states when the dimensional surveys are required (post fabrication/prior to painting, post painting/prior to delivery, and post delivery).
5. Confirm if handrails are installed or shipped loose upon shipment.
The Contractor has the option of installing the handrails prior to shipping or after shipping. If shipped loose, the handrails must be installed before the Contractor leaves the storage location.
6. Are there any splice restrictions on the composite timber lengths?
Splices in the composite timber fenders shall be kept to a minimum. Splice locations must be shown in the Contractor’s shop drawings.
7. On previous projects we have had trouble getting the exact seal detailed. Can you confirm that this will not be a problem if tail length is revised to facilitate the manufacturer's mold?
The slight lengthening or shortening of the seal should not be a problem. The final seal dimension though would have to be approved before acceptance by the Government.
8. On sheets M502-M504 - will the hinge bearing collar and bushing be part of the scope or will they reuse the existing one?
The hinge bearing collar (Sht. M-504) and hinge bushing (M-502) are part of the contract. The existing hinge anchorage plates shown on M-502 are embedded plates which are not in this contract.
9. The pintle on drawing M505 - is the pintle on the existing gate being reused?
The fabrication of the new pintles is part of the contract. See Sht. M-505.
10. Would you also possibly be able to provide the patterns and solid models for the project?
Per the spec, they have to make their own. See Section C3, para 3.2 below:
3.2 PATTERN
In the construction of patterns, care shall be taken to avoid sharp corners or abrupt changes in cross section, and ample fillets shall be used. The Contractor shall add such draft and increases in pattern thicknesses as will conform to his standard foundry practice and as may be necessary to insure that all metal thicknesses of the finished castings conform to the dimensions shown on the drawings, within the tolerances specified in paragraph "Dimensional Tolerances for Structural Work."
Patterns shall be furnished by the Contractor and shall be turned over to the Government Representative at the end of the contract. Patterns shall be delivered to Calcasieu Lock Facility.
11. I wanted to see if this project is to utilize Tangent Technologies’ 8 x12 SeaTimber (composite timber) for the gates?
“The supplier needs to submit a cut sheet showing the properties we specify in the paragraph below (Section C1, paragraph 2.1.15 as well as all of the subparagraphs) so we can compare the two before a determination can be made”.