W912P522B0003 TPlans_CEN RCC Berm Electrical 01.20.2022.pdf
PDF 9 MB Posted
- Attached to
- RCC BERM ELECTRICAL REWORK Federal contract opportunity
- Solicitation number
- W912P522B0003
About this file
This federal contract opportunity notice solicits proposals for electrical rework work at the Center Hill RCC dam near Lancaster, Tennessee. The work includes removing some electrical equipment from the roller-compacted concrete berm and installing new electrical and mechanical equipment in a new building above the berm. Some existing electrical equipment in the berm gallery will be abandoned in place. New equipment will include lighting, controls, switches, a dehumidifier, and HVAC system. A pre-bid site visit is scheduled for March 2nd and proposals are due by March 28th. The contract will have a performance period of 329 calendar days. The U.S. Army Corps of Engineers Nashville District will administer the contract and designed the construction documents.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W912P522B0003 - RCC Berm Electrical Rework Solicitation.pdf | ||
| Wage Determinations TN20220122.pdf | ||
| W912P522B0003 TSpecs_CEN RCC Berm Electrical 02.17.2022.pdf | ||
| W912P522B0003 Bid Schedule CEN RCC Electrica 12.03.2021.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
D E
S C
R
IP
T
IO
N M
A
K
U
B
L
IV
W
H
P
-2
-B -0
V
IL
IS
IC
-X
X
-3
O
T-502 lo t im e a te
F il m
:3
:1
/2 c u s rs
\h x d k
\d o n ts \p w rk \c lr
\Q
-R
-T -5
.d g
G
J
13121110987654321
A SHEET ID
®of Engineers
US Army Corps
.S
Y
IN
IG
IT
I Z
CERTIFIED FINAL DOCUMENTS - RTA
Q4
IR
IA
.E
JB
SHEET ID
ALARM HORN
HINGES, TYP
DOOR SWITCH
BALANCED MAGNETIC
(SEE NOTE 8)
LOCATE AS REQUIRED,
HARDWARE
DOOR
DETAIL A
SEE NOTES 7 AND 8, TYP
QUANTITY AS REQUIRED)
JUNCTION BOX (SIZE AND
HARDWARE
WITH REQUIRED MOUNTING
GARAGE DOOR 'L' BRACKET
MOUNTING HARDWARE
WITH TAMPER RESISTANT
OVERHEAD DOOR TRACK BRACKET
OVERHEAD DOOR
SECURE SIDE
CHANNEL TRACK
OVERHEAD DOOR
ROLLER (TYP)
HINGE AND
FLOOR
FINISHED
REQUIRED)
CABLE (LENGTH AS
STEEL ARMORED FLEX
PREWIRED STAINLESS
WITH REDUCER (SIZE AS REQUIRED)
ARMORED FLEX CONDUIT FITTING
SEE NOTE 7 AND 8, TYP
FINISHED FLOOR
SECURE SIDE
ROUTE CONDUIT TO SECURITY CABINET SEC RCC-1.
" RGS CONDUIT WITH CIRCUIT S-BMS-L3.4
INTERIOR WALL
SEE NOTE 2
AND CONNECTORS
ARMORED FLEX CABLE
STAINLESS STEEL
MOUNTING HARDWARE
DOOR SWITCH AND
DOOR HEAD FRAME
DOOR STOP
SECURE SIDE (TYP)
MOUNTING AS REQUIRED
USE SPACERS OR BRACKETS FOR
MAGNET
" MAX2
SWITCH
MAGNET MAGNET
SIDE
SECURE
HARDWARE AS REQUIRED(SEE NOTES 3, 4, AND 8 )
JUNCTION BOX SURFACE MOUNTED WITH
HANDED DOORS )
NON-HINGED SIDE OF DOOR(TYPICAL FOR RIGHT OR LEFT
DOOR FRAME
DOOR EDGE
4"
1"(TYP )
MAX FROM DOOR EDGE
INTERIOR FRONT VIEW ELEVATION
(LEFT BANK SIDE SHOWN, RIGHT SIDE SIMILAR )
TYPICAL PERSONNEL DOOR WITH SECURITY DEVICES
INTERIOR VIEW
MAGNETIC SWITCH SENSOR MOUNTING DETAIL
TYPICAL OVERHEAD DOOR BALANCED
(LEFT BANK SIDE SHOWN, RIGHT SIDE SIMILAR )
SIDE VIEW
FRONT VIEW
SURFACE MOUNT DETAIL
TYPICAL SINGLE DOOR SWITCH
CL
Q
CABINET LOCATION
CONDUIT TO NEW SECURITY
S-AH-L1,S-BMS-L1,S-BMS-L2. ROUTE
2" RGS CONDUIT WITH CIRCUITS:
(SEE NOTE 10 )
BRACKET AND HARDWARE, TYP
WITH REQUIRED MOUNTING
" MAX GAP2
1" MIN TO 2 4
BALANCED MAGNETIC SWITCH
J.
TYP.
2, 3,4, AND 6),
CABLE(SEE NOTES
SST ARMORED FLEX
OF OVERHEAD DOOR. TWO SWITCHES TOTAL PER DOOR.
10. PROVIDE A BALANCED MAGNETIC SWITCH ON EACH SIDE
TO LOCATING SWITCHES INSIDE OF DOORS.
9. CONTRACTOR SHALL VERIFY DOOR HARDWARE PRIOR
OUT OF REACH FROM FINISHED FLOOR.
BE LOCATED IN PROXIMITY OF DOOR LOCATIONS AND BE
8. JUNCTION BOX AND POWER SUPPLY ENCLOSURES SHALL
ENCLOSURE.
AND CONDUITS FROM DEVICES TO THE INTENDED
7. USE 4" SQUARE JUNCTION BOX WITH COVER FOR CABLES
BUT SHALL BE WRAPPED AND TAPED TO THE CABLE.
AT THE ENCLOSURE. SHIELDS SHALL NOT BE TERMINATED AT DEVICE,
6. CABLES WITH SHIELDS SHALL HAVE SHIELDS GROUNDED ONLY
SEE CABLE SCHEDULE ON DRAWING Q4-T-605.
5. SEE GALLERY LAYOUT DRAWINGS FOR LOCATION OF DEVICES.
FINISHED WALLS AND CEILINGS WHERE APPLICABLE.
4. RGS CONDUITS SHALL BE CONCEALED BEHIND
BOX ENCLOSURE.
ONLY BE INSIDE THE DEVICE ENCLOSURE OR ASSIGNED
3. WIRE TERMINATIONS FOR SECURITY DEVICES SHALL
SPECIFICATIONS.
SUPPORT HARDWARE PER NEC AND PROJECT
AND CONDUITS SHALL BE INSTALLED WITH REQUIRED
2. ALL EXPOSED SECURITY DEVICES, ARMORED CABLES,
SEE DGN. Q4-G-002.
1. FOR GENERAL NOTES, LEGEND AND ABBREVIATIONS,
NOTES:
:4
-6
CCTV-L1
FO-CAM-L1
CABLE NUMBER (TYPICAL)
EP-102
S-TS-L1
360°
HORN-L1
ALARM
S-AH-L1
S-BMS-L2
S-BMS-L1
S-BMS-L4
JBS-BMS-L3
T-L1
BMS-L1 BMS-L2
BMS-L4BMS-L3
PHONE L1
FO-RCC-1
POWERHOUSE
TO
P-100
P-101
FO-PP-L
TERMINAL PANEL
WIRING
PATCH PANEL
COPPER
CONVERTER
MEDIA
CONTROLLER
SECURITY
POWER SUPPLY
24 VDC
EP-100
UPS-L
OUTPUT INPUT
SEE NOTE 5
GENERAL BLOCK DIAGRAM
FO-CAM-R1
EP-202
CCTV-R1
S-TS-R1
S-AH-R1
T-R1
S-BMS-R1
S-BMS-R2
S-BMS-R3
S-BMS-R4
R1
PHONE
BMS-
R2
BMS- HORN-R1
R4
R3
(CKT. 19)
LP-RCC-1
XFMR
NEW ESSENTIAL POWER
120V PANEL - EP-L1
SEC RCC-1
NEW CABINET -
SEE NOTE 6 SEE NOTE 4
T-601
SEE NOTE 7
NEW PANEL LP-RCC-2
POWER ZONE UNIT SUBSTATION.
SIMILAR AND EQUAL TO SQUARE D SEALED, MINI-
7. PROVIDE PANEL WITH INTEGRAL TRANSFORMER
6. REROUTE LINES TO NEW SECURITY CABINET RCC-1.
INSTALLED EQUIPMENT.
FOR GOVERNMENT FURNISHED GOVERNMENT
SEE SPECIFICATIONS INCLUDE 4RU SPARE SPACE
5. PROVIDE 19-INCH RACK CABINET RATED NEMA 3R.
SECURITY CABINET RCC-1.
SHEET E-201. GO THRU GALLERY AND UP TO NEW
4. ROUTE LINES THRU EMBEDDED CONDUIT SHOWN ON
SERVING THE LOCATION.
AND DEVICES SHALL BE FED FROM THE UPS PANEL
3. POWER SUPPLIES FOR ALL CONVERTERS, EQUIPMENT,
Q4-T-605.
2. SEE ASSOCIATED CABLE SCHEDULE ON DRAWING
Q4-G-002.
1. FOR LEGEND AND ABBREVIATIONS, SEE DRAWING
NEW WORK
0S
CENTER HILL
(SEE NOTE 1)
SCADA SYSTEM
EXISTING
FO-PH-S1
(SEE NOTE 1) NEW
FO-PP-PH
(TYPICAL)
FIBER OPTIC
CABLE NUMBER
(LEFT SIDE ONLY) FO-PP-L
(UPS-R)
TB
(SEC RCC-2)
CABINET - SEC RCC-1
FO TO ETHERNET
MEDIA CONVERTER
POWER SUPPLIES
PANEL LP-RCC-2
CABLE
ETHERNET
(SEE NOTE 3)
CUT-OFF
SEE NOTE 6
S-BMS-L2 S-BMS-L3 S-BMS-L4
ON CCTV CABINET
TAMPER SWITCH
BMS
HORN
PANEL
ESSENTIAL
120 VOLT
SECURITY BLOCK DIAGRAM
RCC REINFORCING BERM LEFT BANK
(SEE NOTE 1)
CCTV SYSTEM
FO-PH-TV1 FO-RCC-1
INPUT TO
EP-L1
NEW
(CCTV-R1)
PARENTHESIS ().
SIDE AS SHOWN RIGHT BANK IN
RCC REINFORCING BERM LEFT BANK
CCTV BLOCK DIAGRAM
EP-101
T-602
4. ROUTE CONDUIT FOR POWER SYSTEMS EXPOSED ON GALLERY WALLS.
3. ROUTE CONDUIT FOR SECURITY COMPONENTS EMBEDDED/CONCEALED IN GALLERY WALLS.
MODEL TS-7558-BOX. SEE SPECIFICATIONS.
WITH OPTO-ISOLATED INPUT/OUTPUT CHANNELS SIMILAR AND EQUAL TO TECHNOLOGIC SYSTEMS
2. THE SECURITY CONTROLLER SHALL BE A MULTI-FUNCTIONAL INDUSTRIAL CONTROLLER
THERE.
FROM THE PATCH PANEL TO THE EXISTING POWER-HOUSE EQUIPMENT AND MAKE FINAL CONNECTIONS
INDICATED BY THE GOVERNMENT. THE GOVERNMENT WILL INSTALL CABLES FO-PH-S1 AND FO-PH-TV1
NEW PATCH PANEL FO-PP-PH IN THE POWER-HOUSE TELEPHONE OR SPREAD ROOM IN LOCATION
1. CONTRACTOR SHALL INSTALL NEW FIBER OPTIC CABLE FO-RCC-1 FROM THE RCC STRUCTURE AND
SEE NOTE 4
AT RCC REINFORCING BERM
P-102
SEE NOTE 1
CHARGER
INVERTER
BYPASS
BATTERY
130 VDC
SEE NOTE 3.
RCC REINFORCING BERM LEFT SIDE
LP-RCC-1, CIRCUIT NO. 19
277/480 V PANEL
10 KVA, 480-120V, 1-PHASE
PANELBOARD WITH INTEGRAL
TRANSFORMER (MINI-POWER CENTER).
SUPPLY. SEE NOTE 4.
UNINTERRUPTIBLE POWER
1000VA, 120V,1-PHASE
T-603
FO-PH-T1 NEW
SEE NOTE 8
(FO-PP-R)
(UPS-R)
POWER SUPPLIES
GROUND BUS
MEDIA CONVERTER
POE SWITCH
OUTLETS
NEMA 5-20R
20A, 120V
FURNISHED GOVERNMENT INSTALLED EQUIPMENT.
PROVIDE 4RU SPARE SPACE FOR GOVERNMENT
EP-103 T-L1
120/208 VOLT
LIGHTING PANEL
LP-RCC-2
(SEE NOTE 9)
RJ45 JACK
CAT6 OUTLET
TO PANELBOARD
P-103
P-104EP-100
TELEPHONE BLOCK DIAGRAM
BERM LEFT BANK SIDE IS AS SHOWN.
EQUIPMENT ON RCC REINFORCING
UPS BLOCK DIAGRAM
(SEE NOTE 6)
TELEPHONE SYSTEM
SEE NOTE 7
EXCEPT THAT PHONE UNITS WILL BE FURNISHED BY OTHERS.
9. THE CONTRACTOR SHALL PROVIDE ALL TELEPHONE EQUIPMENT AND WIRING SHOWN INCLUDING JACKS
GOVERNMENT FURNISHED GOVERNMENT INSTALLED EQUIPMENT.
ONLY EQUIPMENT RELATED TO THE INDICATED SYSTEMS. PROVIDE 4RU SPARE SPACE FOR
8. THE SEC-RCC CABINETS ALSO CONTAIN EQUIPMENT OF OTHER SYSTEMS. THESE BLOCK DIAGRAMS SHOW
7. CONNECT NO. 4/0 AWG GROUND TO RCC GROUND BUS IN THE GALLERY.
PANELTO THE EXISTING POWER HOUSE EQUIPMENT AND MAKE FINAL CONNECTIONS THERE.
INDICATED BY THE GOVERNMENT. THE GOVERNMENT WILL INSTALL CABLE FO-PH-T1 FROM THE PATCH
NEW PATCH PANEL FO-PP-PH IN THE POWERHOUSE TELEPHONE OR SPREAD ROOM IN LOCATION
6. CONTRACTOR SHALL INSTALL NEW FIBER OPTIC CABLE FO-RCC-1 FROM THE RCC STRUCTURE AND
5. ROUTE CONDUIT FOR POWER SYSTEMS EXPOSED ON GALLERY WALLS.
APPROVED UPS SYSTEM.
AND SUPPLY EQUIPMENT INCLUDING WIRING AND OVER- CURRENT PROTECTION BASED ON
CONTRACTOR SHALL ALSO BE RESPONSIBLE TO SIZE THE ASSOCIATED UPS FEEDER
UPS BACK-UP REQUIREMENT AND AS APPROVED BY THE COR. SEE SPECIFICATIONS. THE
4. THE CONTRACTOR SHALL DETERMINE UPS RATING BASED ON ACTUAL LOADS AND 2-HOUR
3. FOR PANEL SCHEDULES FOR EP-L1, SEE DGN.Q4-T-604.
SEE SPECIFICATIONS.
2. PROVIDE BATTERY MODULES TO OPERATE LOADS FOR A MINIMUM OF 2 HOURS.
1. UPS SYSTEM EQUIPMENT IS RACK MOUNTED IN CABINETS SEC RCC-1.
T-604
AREA
GALLERY
CABINET
LOAD SERVED
SPACE
VA
LOAD LP-RCC-2
�A �B
�A
LOAD
SUB TOTALS: 3680
TOTAL LOAD: 8520 VA
SUB TOTALS:4,840
LOAD SERVED AREA
RECEPTACLE HIGH MAST POLE
SYSTEM RECEPTACLE
DEDICATED PHONE
SYSTEM RECEPTACLE
DEDICATED PHONE
SPARE
1,440
1,200
1,200
1 2
3 4
5 6
RECEPTACLES
CIRCUIT
ENCLOSURE: NEMA 1
NUMBER OF POLES: 12
MAIN BUS:60A
VOLTAGE: 240V, 1PH, 3W
CHARACTERISTICS:
MOUNTING: SURFACE MOUNTED
BRANCH CIRCUIT BREAKERS: 1P-20A, UNLESS NOTED OTHERWISE
MAIN CIRCUIT BREAKER: 2P-60A
SHORT CIRCUIT RATING: 10,00 SYM AMPS.
SITE
CAMERA CCTV-L1
& PWR SUPPLIES
PHONE-MEDIA CONVERTERS
LOAD EP-L1
CIRCUIT �B
MEDIA CONV & PWR SUPPLY
SECURITY CONTROLLER,
NUMBER OF POLES: 12
MAIN BUS:100A
VOLTAGE: 120V, 1PH, 3W
ALL BREAKERS TO BE GFCI TYPE
MOUNTING: SURFACE MOUNTED
BRANCH CIRCUIT BREAKERS: 1P-20A, UNLESS NOTED OTHERWISE
MAIN CIRCUIT BREAKER: 1P-100A
SUB TOTALS: 420 112 SUB TOTALS:
TOTAL LOAD: 532 VA
3 4
11 12
SPARE (SEE NOTE 2 )
SPARE (SEE NOTE 2 )
110SITE CAMERA CCTV-R1
2000ELEC ROOM HVAC
ELEC ROOM HVAC 2000 RECEPTACLE ELEC ROOM
�B
�B
ACTUAL EQUIPMENT LOADS WHEN SIZING THE UPS AND BATTERY SYSTEM.
2. THE CONTRACTOR SHALL INCLUDE THE INDICATED SPARE CAPACITY AND
1. SEE DRAWING Q4-T-603 FOR UPS SYSTEM BLOCK DIAGRAM.
T-605
SECURITY SYSTEMS CABLE SCHEDULE
CABLE NO. CABLE SIZE
1-48 FIBER
FO-RCC-2
FO-CAM-L1A
FO-CAM-R1A
FO-PH-S1
FO-PH-TV1
FO-PH-T1
1-24 FIBER
1-4 FIBER
1-1 FIBER
1-4 FIBER
1-1 FIBER
SEE REMARKS
S-BMS-L3
CAT6 UTP
CAT6 UTP
1-2/C #16
EP-101
EP-103
P-102
P-103
P-104
1-1/C #12 GND
2-1/C #12;
1-1/C #10 GND
2-1/C #10;
NEW FO-PP-PH (CENTER HILL POWER HOUSE)
FO-PP-L (RCC BERM SECURITY CABINET-1)
CCTV-L1 CAMERA TOWER FO BREAKOUT BOX
FO-PP-R (RCC BERM SECURITY CABINET-2)
CCTV-R1 CAMERA TOWER FO BREAKOUT BOX
FROM
SECURITY CABINET-1, SECURITY CONTROLLER
SECURITY CABINET-2, SECURITY CONTROLLER
120V ESSENTIAL POWER PANEL EP-L1
480V PANEL LP-RCC-1
120V PANEL LP-RCC-2
TO VIA REMARKS
CCTV-L1 CAMERA TOWER FO BREAKOUT BOX
CCTV-L1 CAMERA
CCTV-R1 CAMERA TOWER FO BREAKOUT BOX
CCTV-R1 CAMERA
EXISTING POWERHOUSE SCADA SYSTEM CABINET
EX POWERHOUSE CCTV FO PATCH PANEL
EX POWERHOUSE FO CABINET IN TELEPHONE ROOM
TELEPHONE L1 RJ45 OUTLET
TELEPHONE R1 RJ45 OUTLET
DOOR BALANCED MAGNET SWITCH L1
DOOR BALANCED MAGNET SWITCH L2
DOOR BALANCED MAGNET SWITCH L3
DOOR BALANCED MAGNET SWITCH L4
DOOR ALARM HORN L1
CCTV-L1 CAMERA TOWER JB TAMPER SWITCH
DOOR BALANCED MAGNET SWITCH R1
DOOR BALANCED MAGNET SWITCH R2
DOOR BALANCED MAGNET SWITCH R3
DOOR BALANCED MAGNET SWITCH R4
DOOR ALARM HORN R1
CCTV-R1 CAMERA TOWER JB TAMPER SWITCH
POWER HOUSE, DAM, NEW RIGHT BANK DUCT
CONDUIT
2" CONDUIT
1/2" FLEX
1/2" FLEX
CONDUIT AND EXISTING CABLE TRAY
CONDUIT, AND STAINLESS STEEL ARMORED FLEX CABLE
PROVIDED BY GOVERNMENT
24V DC POWER SUPPLIES
SECURITY CABINET-SEC RCC-1;
CCTV-L1 CAMERA
MEDIA CONVERTERS
TELEPHONE POWER SUPPLIES/
UPS-L, MAINTENANCE BYPASS SWITCH
DEDICATED RECEPTACLE
SECURITY CABINET-SEC RCC-1; 120V,20A
DEDICATED RECEPTACLE
SECURITY CABINET-SEC RCC-1; 120V,20A
" CONDUIT4
1" CONDUIT
INSTALL IN CONDUIT WITH CKT. EP-101
1 " CONDUIT
INSTALL IN CONDUIT WITH CABLE P-103
Q4-G-002.
1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS, SEE DRAWING
e c x d e
HORN-L1
JBS-BMS-L3
BMS-L1 BMS-L2
BMS-L4BMS-L3
PHONE L1
(CKT. 19)
480V PANEL
ESSENTIAL POWER
120V PANEL -
OUTPUT INPUT
SEC RCC-1
CABINET -
GENERAL BLOCK DIAGRAM
FO-RCC-2
EP-202
CCTV-R1
R2
BMS- HORN-R1
R4
R3
480V PANEL
ESSENTIAL POWER
EP-R1
120V PANEL -
SEC RCC-2
CABINET -
UPS-R
FO-PP-R
P-201
P-200
EP-200
TD-601
MINI-POWER CENTER
480-120V,10KVA,1PH
OUTPUTINPUT
PANEL LP-RCC-3
MINI-POWER CENTER
480-120V,10KVA,1PH
Q4-G-003.
1. FOR LEGEND AND ABBREVIATIONS, SEE DRAWING
TO BE REMOVED
:0
:5
-E
LP-RCC-2-1
5KV DS
EMBEDED CONDUIT SEE NOTE 5
DRY-TYPE
LP-RCC-2-1 LP-RCC-2-1 LP-RCC-2-1
PARTIAL PLAN
LP-RCC-2-5
ROLL UP DOOR 1
LP-RCC-1-1
FIXTURE TYPE "0"
400'-0"
IDENTIFICATION
(OR APPROVED EQUAL)
MANUFACTURER/CATALOG NO.
VOLTAGE/LAMP
LIGHTING FIXTURE SCHEDULE
REMARKS
TOTAL QUANTITY (13)
UNIT COMBOS
EMERGENCY LED EXIT/
"EX"
FACES, W/ 277V AC INPUT
LITHONIA LIGHTING ECR LED M6, DOUBLE
277 VOLTS, LED
STATUS INDICATOR, UL LISTED, DAMP LOCATION LISTING.
SEALED NICKEL CADMIUM RECHARGEABLE BATTERY, MAINTENANCE FREE, TEST SWITCH,
COMBINATION EMERGENCY LIGHTING UNIT AND EXIT, DUAL VOLTAGE INPUT 120V OR 277VAC,
LOOKING DOWNSTREAM
ELEVATION
/1
48" AFF
SW-1 LOCATION
3-WAY SWITCH
SEE SHEET Q4-RCC-E-501
NEW ELECTRICAL ROOM
18"AFF (TYP.)
120V GFCI RECEPT
EQUALLY SPACED
SEE NOTE 6
E-201
SEE NOTE 3
LP-RCC-1-13
6 FIXTURES "HM"
HIGH MAST POLE #1
EXISTING EQUIPMENT ROOM
ME
ME ME ME
ME ME ME
"M"
"ME"
TBD
TBD
UNV/70W
UNV/70W
4000K 1' x 4' LED SURFACE MOUNT ENCLOSED AND GASKETED NEMA 4X, IP66, IP67, AND NEMA NSF/ANSI SPLASH ZONE CERTIFIED 10,000 LUMEN
4000K 1' x 4' LED SURFACE MOUNT W/10W EMERGENCY BATTERY ENCLOSED AND GASKETED NEMA 4X, IP66, IP67, AND NEMA NSF/ANSI SPLASH ZONE CERTIFIED 10,000 LUMEN
JUNCTION BOX
CONDUIT TO GALLERY
2(4") EMBEDDED
6. ALL FIXTURES ARE TYPE 'M' UNLESS OTHERWISE NOTED.
AND COMMUNICATIONS.
5. USE EXISTING EMBEDDED CONDUIT TO ROUTE CIRCUITS FOR GALLERY LIGHTING, RECEPTACLES,
4. FIXTURE TYPE "O" SHALL NOT BE SWITCHED AND SHALL BE PHOTOCELL CONTROLLED.
3. INTERCEPT EXISTING HIGH MAST FEED AND ROUTE TO NEW PANEL LP-RCC-2 PANEL.
2. SEE PANEL SCHEDULE DRAWING NO. Q4-E-602.
1. FIXTURE TYPE "EX" SHALL NOT BE SWITCHED.
LP-RCC-1-1-SW1 & 2
NEW FIXTURE TYPE "M"
WALL MOUNTED 6' AFF.
GALLERY LIGHT FIXTURES
18"AFF (TYP.)
120V GFCI RECEPT
350'-0"
LP-RCC-1-6
LP-RCC-3-5
ROLL UP DOOR 2
GALLERY CEILING
'-0
GUTTER
NOT TO SCALE
LP-RCC-2-1 LP-RCC-2-1 LP-RCC-2-1 LP-RCC-2-1
SW-2 LOCATION
EQUALL
SP
ACED
(TYP.)
FIXTURE TYPE "M"
E-202
EXISTING EQUIPMENT ROOM
LP-RCC-1-14
6 FIXTURES "HM"
HIGH MAST POLE #2
TO GALLERY(SEE NOTE 5 )
EMBEDDED CONDUIT
FIXTURE TYPE "0"ME
MEME
MEME
SW-2 LOCATION
TYPE "EX"(TYP.)
LED EXIT
LIGHTING SWITCH.
7. VENTILATING FAN START/STOP PUSH BUTTON WILL BE INSTALLED IN THE SAME LOCATION OF THIS
6. ALL FIXTURES ARE TYPE 'M' UNLESS OTHERWISE NOTED.
AND COMMUNICATIONS.
5. USE EXISTING EMBEDDED CONDUIT TO ROUTE CIRCUITS FOR GALLERY LIGHTING, RECEPTACLES,
4. FIXTURE TYPE "O" SHALL NOT BE SWITCHED AND SHALL BE PHOTOCELL CONTROLLED.
3. INTERCEPT EXISTING HIGH MAST FEED AND ROUTE TO NEW PANEL LP-RCC-2 PANEL.
2. SEE PANEL SCHEDULE DRAWING NO. Q4-E-602.
1. FIXTURE TYPE "EX" SHALL NOT BE SWITCHED.
TO AVOID INTERFERENCE W/ EXIST. EQUIPMENT
NEED TO VERIFY IN FIELD BY THE CONTRACTOR
WALL MOUNTED 6'-7' AFF.
GALLERY LIGHT FIXTURES
E-501
31'-6"(MONOLITH WIDTH )
GUARDRAIL
CONTROL JOINT
IX
G BASEPLATE
27" x 27"
BELOW
CONDUITS DOWN TO GALLERY
EXISTING ELECTRICAL
SEE DETAIL 3 ON SHEET E-10
GROUNDING TEST STATION
LC-3
ELEC. SWITCH
"PVC SCH-804
3#8, 1#8 GND
TYPE "HM"
LIGHT FIXTURES
HIGH MAST LED
LC3-3
LC3-2
LC3-1
PHOTOCELL
PC
LC3
AUTO
OFF
ON
5A
500 VA
LIGHTING
TYPICAL AREA LIGHTING CONTROL
FUSED DISC. SW
240V, 30A, 2 POLE, NEMA 3R
LP-RCC-2-8
5. MOUNT NEXT TO HVAC UNIT. SEE MECHANICAL PLANS FOR EXACT LOCATION.
4. DOOR CONTACTS SEE SHEET T-502 FOR DETAILS.
3. LOCATE PHOTOCELL OUTDOOR AND AWAY FROM DIRECT LIGHT SOURCES.
BE ON CABINET DOOR AND EXTERNALLY ACCESSIBLE.
LIGHTING CONTACTOR CABINET. ON-OFF-AUTO SELECTOR SWITCH SHALL
2. AREA LIGHTING CONTROL DEVICES SHALL BE INSTALLED IN A NEMA 3R
TRANSFORMER & REROUTE TO NEW PANEL LP-RCC-1.
1. REMOVE 480V DISCONNECT INTERCEPT FEEDER FROM EXISTING
LP-RCC-2-5, 7
WP/GFCI
DEHUMIDIFIER
AIR-CONDITIONING SYSTEM
SEE SHEET T-601
NEW SECURITY CABINET
TYPE M
TYPE M
LP-RCC-2-?
E-601
50A
IN NEW ELECTRICAL ROOM
277/480V PANEL
30A 20A 20A
70A
35A
INSTALL PULL BOX EVERY 300'
30A
POWER HOUSE
500A
480V BUS
2-3/c 250kCMIL w/#4 GND
480-2400V
300kVA
IN 3" PVC COND. SCH-80
3-1/c #2 EPR CU 5kV
MANHOLE #9
ENCASEMENT FROM
APPROX. 75' CONCRETE
25A
2400-120/208V
45kVA Y
4-1/c #6 CU THHN
OVERLOOK BATHROOM
2400V SWITCH
PAD MOUNTED
2400/480V
225kVA
PB
112.5kVA
PULL BOX
AT PULL BOX #4
NO CABLE SPLICES
3 X 3-1/c #2 EPR CU 5kV
5 6 7 8
12 9
125A
200A 200A 200A
CONTRACTORS AC POWER PANEL
IN 2" COND.
1-1/c #4 CU FOR GND
3-1/c #3/0 CU THHN
200A
APPROX. 50FT
75kVA
3-1/c #2/0 CU THHN
45kVA Y
DISCONNECT
POLE MOUNTED
OVERHEAD FEEDER
APPROX. 100FT
150A
TRANSIT QUARTERS AC POWER PANEL
240/120V 1�
480-240/120V 1�
10kVA
IN 3/4" PVC CONDUIT SCH-40
2-1/c #10, 1-1/c #10 GND
IN 3/4" PVC CONDUIT SCH-40
2-1/c #8, 1-1/c #10 GND
IN 2" PVC CONDUIT SCH-40
3-1/c #3, 1-1/c #6 GND
CONDUIT SCH-80
EPR CU 5kV IN 4" PVC
3-1/c #2, 1-1/c #2 GND
5 kV MVS
2400-277/480V
45kVA
EXISTING RADIO TOWER PANEL
APPROX. 300'
APPROX. 400'
APPROX. 100'
APPROX. 150'
OFFICE AC POWER PANELs SHOP AC POWER PANEL
APPROX. 15'
IM
IZ
.1
SHALL INSTALL SURGE ARRESTORS AT THIS XFMR.
1. THIS TRANSFORMER SHALL BE DRY-TYPE.THE CONTRACTOR
NEW WORK
AREA LOAD SERVED
NEMA 3R CABINET CONT. "LC1"&"LC2"
POLE #1
HIGH MAST
6(HM)
10 kVA XFMR
(LP-RCC-2)
�A �B
�C
VAVAVA
SUB TOTALS: 7290 11602 6880
NUMBER OF POLES: 42
MAIN BUS: 100A
VOLTAGE: 277/480V, 3PH, 4W
MOUNTING: WALL MOUNTED
BRANCH CIRCUIT BREAKERS: 1P-20A, 2P-20A, 3P-20A, UNO
MAIN CIRCUIT BREAKER: 3P-70A
TOTAL LOAD: 35,337 VA
CIRCUIT CIRCUIT
�A �B �C
19 20
3501 3057 3007 SUB TOTALS:
6(HM)
POLE #2
HIGH MAST
CONTACTOR "LC4" NEMA 3R CABINET
NEMA 3R CABINETCONTACTOR "LC3"
AREALOAD SERVED
�C�B�A
VA VA VA
E-602
39(M ), 21(ME )
XMFR
LPP-RCC-2
20A 20A
TO GALLERY
5KV DS
DRY-TYPE
FIXTURE TYPE "L"
LP-RCC-1-1-SW1 & 2
400'-0"
TYPE "EX" (TYP.)
LED EXIT/UNIT COMBOS
SS
SS
ED-201
120V GFCI RECEPT(TYP.)
LOCATION
SW2 & SW3
EQUIPMENT ROOM
480V DS
LOCATION
SW2 & SW3
3. REMOVE EXISTING 480V DISCONNECT AND UNISTRUT FRAMING.
PLACE.
2. DISCONNECT SOURCE FEEDER TO EXISTING PANEL LP-RCC-1 AND ABANDON ALL EQUIPMENT IN
ALL FIXTURE ARE TYPE "M" UNLESS OTHERWISE STATED.
CONDUIT IN GALLERY AREA. REPLACE WITH DEVICES AS SHOWN. ALL LIGHTING FROM LP-RCC-1,
1. REMOVE ALL LIGHT FIXTURES, RECEPTACLES, LIGHT SWITCHES, EXIT SIGNAGE, AND ASSOCIATED
EMBEDED CONDUIT
HIGH MAST POLE #1
ROLL UP DOOR 1
REMOVED
TYPE "EX" (TYP.) TO BE
TO GALLERY
TYPE "EX" (TYP.)
350'-0"
ED-202
120V GFCI RECEPT(TYP.)
EQUIPMENT ROOM
HIGH MAST POLE #2
LP-RCC-1-8
ALL FIXTURES ARE "M" UNLESS OTHERWISE NOTED.
CONDUIT IN GALLERY AREA. REPLACE WITH DEVICES AS SHOWN. ALL LIGHTING FROM LP-RCC-1,
1. REMOVE ALL LIGHT FIXTURES, RECEPTACLES, LIGHT SWITCHES, EXIT SIGNAGE, AND ASSOCIATED
SW-4 LOCATION
ROLL UP DOOR 2
SW-4 LOCATION
REMOVED
TYPE "EX" (TYP.) TO BE
PB
POWER HOUSE
480V BUS
500A
APPROX. 300' 2-3/c 250kCMIL w/#4 GND
480-2400V
300kVA
EXISTING RADIO TOWER PANEL
30A
INSTALL PULL BOX EVERY 300'
EPR CU 5kV IN 4" PVC COND. SCH-80
MANHOLE #9
ENCASEMENT FROM
APPROX. 75' CONCRETE
AT PULL BOX #4
NO CABLE SPLICES
2400V SWITCH
PAD MOUNTED
125A
APPROX. 400'
75kVA
IN 2" COND.
3-1/c #3/0 CU THHN
APPROX. 50FT
200A
APPROX. 100'
3 X 3-1/c #2 EPR CU 5kV
3-1/c #2/0 CU THHN
APPROX. 15'
POLE MOUNTED
OVERHEAD FEEDER
APPROX. 100FT
150A
TRANSIT QUARTERS AC POWER PANEL CONTRACTORS AC POWER PANEL
APPROX. 150'
OFFICE AC POWER PANELs
200A 200A 200A
SHOP AC POWER PANEL
112.5kVA
2400/480V
225kVA
OVERLOOK BATHROOM
4-1/c #6 CU THHN
277/480V PANEL
20A 20A 20A
IN 2" PVC CONDUIT SCH-40
3-1/c #3, 1-1/c #6 GND
35A
5 kV MVS
ED-601
2400-277/480V
PANEL LP-RCC-1.
1. REMOVE EXISTING 480V DISCONNECT AND FEEDER TO
G-001
:2 e c x d e
\D
-G
NEW ELEC. BUILDING
RCC BERM
STAGING AREA.
WORK
LIMITS OF
SHOWN ON THIS DRAWING.
4. UNLESS OTHERWISE APPROVED BY THE COR, LIMITS OF WORK AREA SHALL BE AS
3. SEE DWG E-201 FOR LOCATION OF THE NEW ELECTRICAL ROOM.
EVERYTHING IN THE FIELD.
DETAILS ON THIS DRAWING ARE FOR REFERENCE. CONTRACTOR SHALL VERIFY
2. THE GOOGLE IMAGE, ROLLER COMPACTED CONCRETE(RCC) BERM, AND OTHER
IDENTIFIED AREA FOR THE STAGING AREA.
1. THE TRAILER IS NO LONGER AT THE PROJECT. CONTRACTOR SHALL USE THE
G-002
LP-RCC-1-1-SW1&2
ARC - GROUND CONDUCTOR
LONG DASH - NEUTRAL CONDUCTOR
SHORT DASH - PHASE CONDUCTOR
DESIGNATION AS FOLLOWS:
IS CONTROLLED BY SWITCH 1 & 2 WITH CONDUCTOR
DENOTES CIRCUIT 1 TO PANEL LP-RCC-1 AND THE LIGHT
FIXTURE TYPE "O"
EMERGENCY LED EXIT/UNIT COMBOS TYPE "EX"
FIXTURE TYPE "L"
DENOTES CIRCUIT 2 TO PANEL LP-RCC-2LP-RCC-2-2
Y - WYE CONNECTED
- DELTA CONNECTED
TRANSFORMER
FUSED DISCONNECT SWITCH
THERMAL-MAGNETIC CIRCUIT BREAKER
MOTOR OVERLOAD
LIMIT SWITCH
NORMALLY OPEN
FLOAT SWITCH
CONTROL CONTACT
NORMALLY CLOSED
CONTROL CONTACT
PUSH BUTTON
NORMAL OPEN
EMBEDED CONDUIT
LEGEND
120V GFCI, DUPLEX RECEPTACLE W/ IN-USE WEATHER-PROOF ENCLOSURE
ABBREVIATIONS
TRANSFORMERXFMR
KILO-VOLTS-AMPSkVA
WEATHER PROOFWP
VOLTS-AMPSVA
VOLTSV
UNINTERRUPTIBLE POWER SUPPLYUPS
TYPICALTYP
TAMPER SWITCHTS
SWITCHSW
STAINLESS STEELSST
SECURITYS, SEC
ROLLER COMPACTED CONCRETERCC
RIGID GALVANIZED STEEL CONDUITRGS
POLYVINYL CHLORIDEPVC
PATCH PANELPP
OVERLOADOL
LIMIT SWITCHLS
LIGHTING PANELLP
JUNCTION BOXJB
HORSE POWERHP
GROUNDGND
GROUND FAULT CIRCUIT INTERUPTERGFCI
FLOAT SWITCHFS
FO-PP-XX FIBER OPTIC PATCH PANEL (NUMBER AS NOTED)
FIBER OPTICFO
ESSENTIAL (UPS) POWER PANELEP
DISCONNECT SWITCHDS
DRAWINGDWG
CONTROL RELAYCR
CLOSED-CIRCUIT TELEVISIONCCTV
CCTV CAMERACAM
BALANCED MAGNETIC SWITCHBMS
ALARM HORNAH
ABOVE FINISHED GRADEAFG
ABOVE FINISHED FLOORAFF
AMPSA
CCTV CAMERA; UNIT NO. CCTV-L1
TAMPER SWITCH FOR SECURITY SYSTEM
DENOTES CIRCUIT 2 TO PANEL LP-RCC-2
Y - WYE CONNECTED
- DELTA CONNECTED
TRANSFORMER
FUSED DISCONNECT SWITCH
THERMAL-MAGNETIC CIRCUIT BREAKER
EMBEDDED/CONCEALED CONDUIT
UNIT NO. L
UNINTERRUPTIBLE POWER SUPPLY
LEGEND(CONT.)
LP-RCC-2-2
PLANS, AND SCHEDULES.
APPLY ONLY TO THE SECURITY DIAGRAMS, EQUIPMENT,
1. THE LEGEND AND ABBREVIATIONS ON THIS SHEET
REWORKED WITHOUT ADDITIONAL COST TO THE GOVERNMENT.
REMOVED,REPLACED,OR OTHERWISE SATISFACTORILY
IN THE TRADE.UNSIGHTLY INSTALLATIONS SHALL BE
LIKE MANNER BY PERSONS EXPERIENCED AND SKILLED
2. ALL WORK SHALL BE PERFORMED IN A NEAT, WORKMAN
AND DOCUMENTS.
SHOWN OR INFERRED ON THESE CONTRACT DRAWINGS
AND EQUIPMENT NECESSARY TO COMPLETE ALL WORK
3. CONTRACTOR SHALL PROVIDE ALL LABOR,MATERIAL,
PLETE AND OPERATIONAL SYSTEMS.
NATE ALL CIRCUITS AND RACEWAY TO PROVIDE COM-
THE CONTRACTOR PROVIDE,ROUTE,INSTALL, AND TERMI-
SHOWN ON THESE DRAWINGS, IT IS THE INTENT THAT
4. WHERE CIRCUIT AND RACEWAY ROUTINGS ARE NOT
LABEL PANEL AND CIRCUIT NUMBER.
INDICATING RECEPTACLE IS ON UPS POWER. ALSO,
5. FOR UPS RECEPTACLES PROVIDE PERMANENT LABEL
GFCI TYPE IN WEATHERPROOF ENCLOSURE.
ANY AREA EXPOSED TO THE ELEMENTS SHALL BE
6. ALL RECEPTACLES LOCATED IN GALLERY AREAS OR
IFICATIONS.
SUPPORT HARDWARE PER NEC AND PROJECT SPEC-
AND CONDUITS SHALL BE INSTALLED WITH REQUIRED
7. ALL EXPOSED SECURITY DEVICES, ARMORED CABLES,
BOX ENCLOSURE.
ONLY BE INSIDE THE DEVICE ENCLOSURE OR ASSIGNED
8. WIRE TERMINATIONS FOR SECURITY DEVICES SHALL
PREVENT WATER INTRUSION.
ALL J-BOXES AND SEAL ALL CONDUIT ENTRIES TO
SHALL BE LIQUID TIGHT. USE POTTED WIRE NUTS IN
9. ALL CONDUITS, FITTINGS, ELBOWS, J-BOXES, ETC.
M-501
-M
GUARDRAIL
-M
/8
BELOW
CONDUITS DOWN TO GALLERY
EXISTING ELECTRICAL
BASEPLATE
SEE NOTE 1.
DUCTLESS (THROUGH WALL)
AIR-CONDITIONING SYSTEM
SEE NOTE 2.
EQUIPMENT SCHEDULE
UNIT COOLING CAPCITY HEATING CAPACITY AIR FLOW POWER SUPPLY
MINI SPLIT
8,700 BTU/H 10,900 BTU/H 380 CFM
230V/1PH/60HZ
115V/1PH/60HZ- -
DRAINAGE PIPING
4. DRAINAGE PIPING TO RUN TO EXTERIOR OF MONOLITH.
3. ALL OUTDOOR PIPING SHALL BE INSULATED.
WITH A PUMP. SEE SPECIFICATIONS FOR DETAILS. LOCATION OF EQUIPMENT IS SUBJECT TO CHANGE
2. DEHUMIDIFIER HISENSE DH7021KP1G OR EQUIVALENT. DEHUMIDIFIER SHALL BE FURNISHED
EQUIPMENT IS SUBJECT TO CHANGE.
UNIT WILL REQUIRE DISCONNECT SWITCH, SEE DRAWING E-501 FOR DETAILS. LOCATION OF
1. DUCTLESS AIR CONDITIONING SYSTEM PANASONIC XE9WKUA OR EQUIVALENT.
Plans For
Nashville District of Engineers
W912P5-22-B-0003
January 2022
Center Hill Auxiliary Dam
RCC Berm Electrical Rework
Cumberland River Watershed
Dekalb County, Tennessee
Caney Fork River
DRAWING INDEX
SECURITY SYSTEM - CABLE SCHEDULEQ4-RCC-T-605
ELECTRICAL - 120V PANEL & UPS PANEL SCHEDULESQ4-RCC-T-604
SECURITY UPS & TELEPHONE - BLOCK DIAGRAMSQ4-RCC-T-603
SECURITY & CCTV BLOCK DIAGRAMSQ4-RCC-T-602
SECURITY BLOCK DIAGRAMQ4-RCC-T-601
SECURITY BLOCK DIAGRAM - DEMOQ4-RCC-TD-601
ELECTRICAL - SECURITY DETAILSQ4-RCC-T-502
SECURITY - EQUIPMENT CABINETS LAYOUTSQ4-RCC-T-501
ELECTRICAL ROOM - STRUCTURAL DETAILSQ4-RCC-S-501
STRUCTURAL NOTESQ4-RCC-S-001
ELECTRICAL ROOM - HVAC DETAILSQ4-RCC-M-501
480V PANEL SCHEDULEQ4-RCC-E-602
SINGLE LINE DIAGRAMQ4-RCC-E-601
SINGLE LINE DIAGRAM - DEMOQ4-RCC-ED-601
ELECTRICAL ROOM - DETAILSQ4-RCC-E-501
GALLERY LIGHTING DETAILSQ4-RCC-E-202
GALLERY LIGHTING DETAILS - DEMOQ4-RCC-ED-202
GALLERY LIGHTING DETAILSQ4-RCC-E-201
GALLERY LIGHTING DETAILS - DEMOQ4-RCC-ED-201
LEGEND & ABBREVIATIONSQ4-RCC-G-002
OVERALL SITE PLANQ4-RCC-G-001
DESCRIPTIONDRAWING #
CONTRACT DRAWINGS
Submitted:
Faron D. Bean, P.E.
(2.) The approval signatures appearing in the signature block on this sheet constitute approval of all drawings listed in the sheet index.
of individuals appear on these project documents within the scope of their employment as required by ER 1110-1-8152.
(1.) This project was designed by the Nashville District of the U.S. Army Corps of Engineers. The initials or signatures and registration designations
Note:
Mark P. Evans, P.E.
Chief, Electrical / Mechanical Section
Approved:
Robert W. Baulsir III, P.E.
Chief, Civil Design Branch
Project Engineer
Approval Recommended:Certified Final Documents - RTA
2022-01-20T18:01:59-0600
BEAN.FARON.DAVID.1110133924
2022-01-21T10:42:32-0600
EVANS.MARK.PHILIP.1152793533
2022-01-21T09:16:22-0600
BAULSIR.ROBERT.W.III.1258321525
1312111098765432
S-001
-S
ANCHORS TO ROLLAR COMPACTED CONCRETE(RCC).
ATTACHMENT OF STRUCTURAL STEEL MEMBERS TO THE EXISTING STRUCTURE SHALL BE ACHIEVED THROUGH POST-INSTALLED7.
FULL RESPONSIBILITY FOR THE DESIGN OF STRUCTURAL STEEL MEMBERS AND THEIR CONNECTIONS.
INTERPRETATION OF THE DESIGN LOADS AND CONTRACT DOCUMENT DETAILS. SUCH REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF
BE FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS REGARDING ARRANGEMENT AND SIZES OF MEMBERS AND THE CONTRACTOR'S
INDICATE SUPPLEMENTAL ACCESSORIES, AND DETAILS REQUIRED FOR PROPER INSTALLATION. REVIEW OF SHOP DRAWINGS SHALL
INCLUDE PLACING DRAWINGS FOR FRAMING MEMBERS SHOWING SIZE DESIGNATIONS, NUMBER, TYPE, LOCATION, AND SPACING.
OF THE CONTRACTOR. SUBMIT SHOP DRAWINGS SEALED BY AN ENGINEER LICENSED IN THE PROJECT STATE. SHOP DRAWINGS SHALL
DESIGN OF STRUCTURAL STEEL FRAMING ARRANGEMENT, MEMBERS, AND THEIR CONNECTIONS SHALL BE THE SOLE RESPONSIBILITY6.
SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW.
ALL STEEL EXPOSED TO WEATHER OR MOISTURE SHALL BE GALVANIZED, OR SHALL BE PROTECTED BY OTHER MEANS5.
PRE AND POST WELDING HEAT TREATMENT SHALL BE IN ACCORDANCE WITH APPLICABLE AWS.4.3
WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1.4.2
ALL WELDERS SHALL BE AWS QUALIFIED FOR THE WELDING PROCEDURE WHICH THEY WILL PERFORM.4.1
WELDING4.
ANCHOR RODS SHALL CONFORM TO ASTM F1554.3.2
ALL BOLTS SHALL BE ASTM F3125 GRADE A325.3.1
BOLTS AND ANCHOR RODS3.
OTHER STEEL SHAPES (CHANNELS, ANGLES, PLATES )SHALL CONFORM TO ASTM A36.2.4
ROUND HOLLOW STRUCTURAL SECTIONS (HSS )SHALL CONFORM TO ASTM A500 GRADE C.2.3
SQUARE/RECTANGULAR HOLLOW STRUCTURAL STEEL SECTION (HSS )SHALL CONFORM TO ASTM A500 GRADE C.2.2
WIDE FLANGE SHAPED MEMBERS (W- )SHALL CONFORM TO ASTM A992.2.1
STRUCTURAL STEEL SHALL BE OF THE FOLLOWING GRADES UNLESS APPROVED OTHERWISE:2.
STRUCTURAL STEEL BUILDINGS" AND THE AISC 303 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES".
STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED ACCORDING TO THE ANSI/AISC 360 "SPECIFICATION FOR1.
STRUCTURAL STEEL METHODS AND MANUFACTURER BOND DATA PROVING ADEQUATE PERFORMANCE UNDER MORE ADVERSE CONDITIONS.
IF THESE CONDITIONS DO NOT EXIST, THE CONTRACTOR SHALL SUBMIT ALTERNATE DRILLING
-TEMPERATURES NOT EXCEEDING MANUFACTURER'S ALLOWABLE RANGES FOR STRUCTURAL USE
-CONCRETE CURED FOR A MINIMUM OF 21 DAYS
-DRY HOLE
-HOLES DRILLED WITH HAMMER DRILL WITH CARBIDE TIPPED DRILL BIT
THE FOLLOWING CONDITIONS SHALL BE PROVIDED:
ADHESIVE ANCHORS AND REINFORCING STEEL CAPACITY IS DEPENDENT UPON INSTALLATION CONDITIONS.7.
GALVANIZED PER ASTM B695, CLASS 65, TYPE I
MECHANICAL AND SCREW ANCHORS IN EXTERIOR NONCORROSIVE ENVIRONMENTS SHALL BE HOT-DIPPED 6.
ASTM A193 Gr. B8M TYPE 316 ALL THREAD ROD
CORROSIVE ENVIRONMENTS:
ASTM F1554 Gr. 36 ALL THREAD ROD, HOT DIPPED GALVANIZED PER ASTM B695, CLASS 65, TYPE I
EXTERIOR NONCORROSIVE ENVIRONMENTS:
ASTM F1554 Gr. 36 ALL THREAD ROD
INTERIOR NONCORROSIVE ENVIRONMENTS:
ADHESIVE ANCHOR INSERT SHALL BE:5.
TO CONSULTING WITH THE ARMY CORPS.
MEANS IN ORDER TO AVOID CONFLICT WITH INSTALLATION. THE CONTRACTOR SHALL NOT DAMAGE ANY REINFORCING STEEL PRIOR
REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE ANCHORS OR REINFORCING, BY GPR, X-RAY, FERROSCAN, OR OTHER
THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE
EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR OR REINFORCING LOCATIONS.4.
PROOF OF CERTIFICATION SHALL BE MAINTAINED AT THE JOB SITE.
CURRENT AAI CERTIFICATION AS ACCREDITED BY ACI/CSRI IN ACCORDANCE WITH ACEI 318-14 17.8.2.2.
PER ACI 318-14 17.8.2.2, INSTALLATION OF ALL ADHESIVE ANCHOR PRODUCTS SHALL BE CONDUCTED BY AN INSTALLER HOLDING
PRODUCTS. TRAINING AND DOCUMENTATION SHALL OCCUR PRIOR TO COMMENCEMENT OF PRODUCT INSTALLATION. WHEN REQUIRED
SUBMIT TO THE CONTRACTING OFFICER DOCUMENTATION CONFIRMING TRAINING OF ALL PERSONNEL WHO WILL BE INSTALLING
THE CONTRACTOR SHALL ARRANGE ON SITE INSTALLATION TRAINING BY THE MANUFACTURER FOR EACH PRODUCT TO BE INSTALLED.3.
ANCHORS AND REINFORCING STEEL SHALL BE INSTALLED PER THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS(MPII )2.
REINFORCING STEEL IN PLACE OF MISSING OR MISPLACED ANCHORS.
OBTAIN APPROVAL FROM THE ARMY CORPS. CONTRACTING OFFICER PRIOR TO INSTALLING POST-INSTALLED ANCHORS OR
DELEGATED DESIGN SHOP DRAWINGS(AFTER REVIEW CONDUCTED BY ARMY CORPS. CONTRACTING OFFICER )CONTRACTOR SHALL
POST-INSTALLED ANCHORS AND REINFORCING STEEL SHALL ONLY BE USED WHERE SPECIFIED ON THE DESIGN DETAILS, INCLUDING1.
POST-INSTALLED ANCHORS AND REINFORCING STEEL
ANCHORS TO ROLLAR COMPACTED CONCRETE(RCC).
ATTACHMENT OF COLD-FORMED STEEL MEMBERS TO THE EXISTING STRUCTURE SHALL BE ACHIEVED THROUGH POST-INSTALLED3.
STEEL STRUCTURAL MEMBERS AND THEIR CONNECTIONS.
DETAILS. SUCH REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF FULL RESPONSIBILITY FOR THE DESIGN OF THE COLD-FORMED
ARRANGEMENT AND SIZES OF MEMBERS AND THE CONTRACTOR'S INTERPRETATION OF THE DESIGN LOADS AND CONTRACT DOCUMENT
INSTALLATION. REVIEW OF SHOP DRAWINGS SHALL BE FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS REGARDING
SPACING. INDICATE SUPPLEMENTAL STRAPPING, BRACING, SPLICES, BRIDGING, ACCESSORIES, AND DETAILS REQUIRED FOR PROPER
INCLUDE PLACING DRAWINGS FOR FRAMING MEMBERS SHOWING SIZE AND GAGE DESIGNATIONS, NUMBER, TYPE, LOCATION, AND
OF THE CONTRACTOR. SUBMIT SHOP DRAWINGS SEALED BY AN ENGINEER LICENSED IN THE PROJECT STATE. SHOP DRAWINGS SHALL
DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS, FRAMING SYSTEM, AND THEIR CONNECTIONS SHALL BE THE SOLE RESPONSIBILITY2.
FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS".
1. COLD-FORMED STEEL DESIGN, FABRICATION, AND ERECTION SHALL BE IN ACCORDANCE WITH AISI S100 "NORTH AMERICAN SPECIFICATION
COLD-FORMED METAL STUDS
TEMPORARY CONNECTIONS TO PERMANENT STRUCTURES MUST BE APPROVED BY THE CONTRACTING OFFICER.
THE STRUCTURES MAY NOT BE STABLE UNTIL ALL STRUCTURAL ELEMENTS ARE IN PLACE AND PROPERLY CONNECTED.
THE CONTRACTOR IS RESPONSIBLE FOR THE TEMPORARY BRACING OF THE STRUCTURES. 6.
WHERE, H = MEAN ROOF HEIGHT OF BUILDING
SEISMIC LOADING, 2010 TABLE 12.12-1PER ASCE-7
WIND LOADING (10-YR WIND SPEEDS)H/400
BUILDING DRIFT UNDER LATERAL LOADING
WHERE, L = SPAN LENGTH (INCHES OR FEET)BETWEEN CENTERLINES OF SUPPORTS
L/240 L/360 ROOF MEMBERS:
DEAD + LIVE LOADLIVE LOAD
MAXIMUM ESTIMATED DEFLECTIONS AND BUILDING DRIFT SHOULD BE AS FOLLOWS:5.
-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS USING FLAT STRAP BRACING
-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS SHEATHED WITH WOOD PANELS
-STRUCTURAL STEEL MOMENT FRAMES
CONTRACTOR MAY SELECT FROM THE FOLLOWING:
LATERAL LOAD RESISTING SYSTEM:
SEISMIC DESIGN CATEGORY = A
SEISMIC DESIGN VALUE, T = 1.0s Sd1 = 0.062
SEISMIC DESIGN VALUE, T = 0.2s Sds = 0.120
SITE CLASS = A
MCE GROUND MOTION, T = 1.0s S1 = 0.117
MCE GROUND MOTION, T = 0.2s Ss = 0.225
IMPORTANCE FACTOR Ie = 1.0
RISK CATEGORY I
SEISMIC LOADS4.
-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS USING FLAT STRAP BRACING
-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS SHEATHED WITH WOOD PANELS
-STRUCTURAL STEEL MOMENT FRAMES
CONTRACTOR MAY SELECT FROM THE FOLLOWING:
LATERAL FORCE RESISTING SYSTEM:
INTERNAL PRESSURE COEFFICIENT, GCpi = +/- 0.18
RISK CATEGORY = I
EXPOSURE = C
NOMINAL DESIGN WIND SPEED (3-SECOND GUST)= 89 MPH
ULTIMATE DESIGN WIND SPEED (3-SECOND GUST)= 115 MPH
WIND LOADS3.
FLAT ROOF SNOW LOAD Pf = 6 PSF
SNOW IMPORTANCE FACTOR I = 0.8
SNOW THERMAL FACTOR Ct = 1.1
SNOW EXPOSURE FACTOR Ce = 0.9
GROUND SNOW LOAD Pg = 10 PSF
SNOW
ROOF 20 PSF
GRAVITY LOADS2.
STRUCTURE IS TO BE DESIGNED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE(IBC )2015.1.
CODE/DESIGN CRITERIA
S-501
12'-0"
3'-0"
22'-0"
/8
MONOLITH BETWEEN STA. 1+35 AND 1+60
4'-0"
BASEPLATE
PROPOSED BUILDING
INTERIOR FACE OF
PROPOSED BUILDING
EXTERIOR FACE OF
ELEC. SWITCH
6'-9" TO EXISTING CONDUIT
EXISTING GUARDRAIL 2" Ø
SEE SHEET E-501
EXISTING CONDUIT
MIN. 18"
FACE OF SPILLWAY
FOR MAINTENANCE)
(LOWERED WHEN REQUIRED
10'-0" DIA. LIGHT FIXTURE
T-502 FOR REQUIREMENTS
REFER TO SPECS AND
PERSONNEL DOOR
BY THE CONTRACTOR AND SHALL BE SUBMITTED FOR GOVERNMENT APPROVAL.
TO VIEW THE RCC DAM SPILLWAY. THE EXACT SIZE SHALL BE SELECTED
4. WINDOW (SIZE OF ABOUT 3'X4') SHALL BE PROVIDED TO ALLOW FIELD PERSONNEL
TO INSTALLATION / REMOVAL OF THE EXISTING AND NEW EQUIPMENT.
INTERFERENCE WITH THE EXISTING EQUIPMENT AND TO ALLOW
AND SHALL BE SUBMITTED FOR GOVERNMENT APPROVAL TO AVOID
3. DOOR SIZE AND EXACT LOCATION SHALL BE SELECTED BY THE CONTRACTOR
2. SEE DRAWING Q4-E-201 FOR LOCATION OF NEW ELECTRICAL ROOM.
WALL DESIGN SYSTEMS WILL NOT INTERFERE WITH LIGHT FIXTURE.
1. GC TO COORDINATE SO STRUCTURAL DESIGN AND EXTERIOR
T-501
OR TUBING ARE USED
WATERTIGHT CAP IF PIPE
ON TOP AND SIDES
MINIMUM 3" AIR SPACE
OF BOX AND SUNSHADE.
AIR SPACE BETWEEN BACK
MOUNT PANEL WITH 1"
WHITE ENAMEL PAINT
MAXIMUM SUN PROTECTION
WITH RUST RESISTANT,
PAINT ALL METAL SURFACES
YAGI ANTENNA
- (FUTURE BY OTHERS)
PROTECTION FOR ANTENNA
IMAGINARY CONE OF LIGHTNING
STEEL BACK PLATE.
TOP AND SIDES, WITH 3/16"
12 GAGE STEEL SUNSHADE,
(TYP 4 PLACES EACH LEG)
ANCHOR WITH 4" EMBEDMENT
5/8" STAINLESS STEEL EXPANSION
(TYP 4 PLACES EACH LEG)
ANCHOR WITH 4" EMBEDMENT
5/8" STAINLESS STEEL EXPANSION
GROUND SYSTEM
RCC BERM
BARE SOLID CU
#2 AWG
SIDE VIEW
60° 60
24"
STEEL BACK PLATE.
TOP AND SIDES, WITH 3/16"
12 GAGE STEEL SUNSHADE,
21 3/4" x 20" x 11"
PANEL DIMENSIONS:
ENC16/18
CONTROL PANEL
APART.64
33LEG 90
TWO PLACES EACH
BASE PLATES,
" GALVANIZED 8
GUSSETS TO
WELD GALVANIZED
GALVANIZED 2" TUBING, LEGS
2" RGS ELECTRICAL CONDUIT
FRONT VIEW
INSTRUMENTATION SYSTEM CABINET
ALLOW REAR ACCESS TO THE EQUIPMENT.
2. INSTALL SECURITY CABINETS SPACED FROM THE WALL AS INDICATED TO
1. INSTALL ALL FLOOR MOUNTED CABINETS ON 6" CONCRETE PAD.
File details come from the government source that posted it. Updated .