W912P522B0003 TPlans_CEN RCC Berm Electrical 01.20.2022.pdf

PDF 9 MB Posted

Attached to
RCC BERM ELECTRICAL REWORK Federal contract opportunity
Solicitation number
W912P522B0003
Issued by
Department of the Army Corps of Engineers Engineering District Nashville

About this file

This federal contract opportunity notice solicits proposals for electrical rework work at the Center Hill RCC dam near Lancaster, Tennessee. The work includes removing some electrical equipment from the roller-compacted concrete berm and installing new electrical and mechanical equipment in a new building above the berm. Some existing electrical equipment in the berm gallery will be abandoned in place. New equipment will include lighting, controls, switches, a dehumidifier, and HVAC system. A pre-bid site visit is scheduled for March 2nd and proposals are due by March 28th. The contract will have a performance period of 329 calendar days. The U.S. Army Corps of Engineers Nashville District will administer the contract and designed the construction documents.

View the file

Other files for this federal contract opportunity

Other files attached to RCC BERM ELECTRICAL REWORK, newest first.
File Type Posted
W912P522B0003 - RCC Berm Electrical Rework Solicitation.pdf PDF
Wage Determinations TN20220122.pdf PDF
W912P522B0003 TSpecs_CEN RCC Berm Electrical 02.17.2022.pdf PDF
W912P522B0003 Bid Schedule CEN RCC Electrica 12.03.2021.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

D E

S C

R

IP

T

IO

N M

A

K

U

B

L

IV

W

H

P

-2

-B -0

V

IL

IS

IC

-X

X

-3

O

T-502 lo t im e a te

F il m

:3

:1

/2 c u s rs

\h x d k

\d o n ts \p w rk \c lr

\Q

-R

-T -5

.d g

G

J

13121110987654321

A SHEET ID

®of Engineers

US Army Corps

.S

Y

IN

IG

IT

I Z

CERTIFIED FINAL DOCUMENTS - RTA

Q4

IR

IA

.E

JB

SHEET ID

ALARM HORN

HINGES, TYP

DOOR SWITCH

BALANCED MAGNETIC

(SEE NOTE 8)

LOCATE AS REQUIRED,

HARDWARE

DOOR

DETAIL A

SEE NOTES 7 AND 8, TYP

QUANTITY AS REQUIRED)

JUNCTION BOX (SIZE AND

HARDWARE

WITH REQUIRED MOUNTING

GARAGE DOOR 'L' BRACKET

MOUNTING HARDWARE

WITH TAMPER RESISTANT

OVERHEAD DOOR TRACK BRACKET

OVERHEAD DOOR

SECURE SIDE

CHANNEL TRACK

OVERHEAD DOOR

ROLLER (TYP)

HINGE AND

FLOOR

FINISHED

REQUIRED)

CABLE (LENGTH AS

STEEL ARMORED FLEX

PREWIRED STAINLESS

WITH REDUCER (SIZE AS REQUIRED)

ARMORED FLEX CONDUIT FITTING

SEE NOTE 7 AND 8, TYP

FINISHED FLOOR

SECURE SIDE

ROUTE CONDUIT TO SECURITY CABINET SEC RCC-1.

" RGS CONDUIT WITH CIRCUIT S-BMS-L3.4

INTERIOR WALL

SEE NOTE 2

AND CONNECTORS

ARMORED FLEX CABLE

STAINLESS STEEL

MOUNTING HARDWARE

DOOR SWITCH AND

DOOR HEAD FRAME

DOOR STOP

SECURE SIDE (TYP)

MOUNTING AS REQUIRED

USE SPACERS OR BRACKETS FOR

MAGNET

" MAX2

SWITCH

MAGNET MAGNET

SIDE

SECURE

HARDWARE AS REQUIRED(SEE NOTES 3, 4, AND 8 )

JUNCTION BOX SURFACE MOUNTED WITH

HANDED DOORS )

NON-HINGED SIDE OF DOOR(TYPICAL FOR RIGHT OR LEFT

DOOR FRAME

DOOR EDGE

4"

1"(TYP )

MAX FROM DOOR EDGE

INTERIOR FRONT VIEW ELEVATION

(LEFT BANK SIDE SHOWN, RIGHT SIDE SIMILAR )

TYPICAL PERSONNEL DOOR WITH SECURITY DEVICES

INTERIOR VIEW

MAGNETIC SWITCH SENSOR MOUNTING DETAIL

TYPICAL OVERHEAD DOOR BALANCED

(LEFT BANK SIDE SHOWN, RIGHT SIDE SIMILAR )

SIDE VIEW

FRONT VIEW

SURFACE MOUNT DETAIL

TYPICAL SINGLE DOOR SWITCH

CL

Q

CABINET LOCATION

CONDUIT TO NEW SECURITY

S-AH-L1,S-BMS-L1,S-BMS-L2. ROUTE

2" RGS CONDUIT WITH CIRCUITS:

(SEE NOTE 10 )

BRACKET AND HARDWARE, TYP

WITH REQUIRED MOUNTING

" MAX GAP2

1" MIN TO 2 4

BALANCED MAGNETIC SWITCH

J.

TYP.

2, 3,4, AND 6),

CABLE(SEE NOTES

SST ARMORED FLEX

OF OVERHEAD DOOR. TWO SWITCHES TOTAL PER DOOR.

10. PROVIDE A BALANCED MAGNETIC SWITCH ON EACH SIDE

TO LOCATING SWITCHES INSIDE OF DOORS.

9. CONTRACTOR SHALL VERIFY DOOR HARDWARE PRIOR

OUT OF REACH FROM FINISHED FLOOR.

BE LOCATED IN PROXIMITY OF DOOR LOCATIONS AND BE

8. JUNCTION BOX AND POWER SUPPLY ENCLOSURES SHALL

ENCLOSURE.

AND CONDUITS FROM DEVICES TO THE INTENDED

7. USE 4" SQUARE JUNCTION BOX WITH COVER FOR CABLES

BUT SHALL BE WRAPPED AND TAPED TO THE CABLE.

AT THE ENCLOSURE. SHIELDS SHALL NOT BE TERMINATED AT DEVICE,

6. CABLES WITH SHIELDS SHALL HAVE SHIELDS GROUNDED ONLY

SEE CABLE SCHEDULE ON DRAWING Q4-T-605.

5. SEE GALLERY LAYOUT DRAWINGS FOR LOCATION OF DEVICES.

FINISHED WALLS AND CEILINGS WHERE APPLICABLE.

4. RGS CONDUITS SHALL BE CONCEALED BEHIND

BOX ENCLOSURE.

ONLY BE INSIDE THE DEVICE ENCLOSURE OR ASSIGNED

3. WIRE TERMINATIONS FOR SECURITY DEVICES SHALL

SPECIFICATIONS.

SUPPORT HARDWARE PER NEC AND PROJECT

AND CONDUITS SHALL BE INSTALLED WITH REQUIRED

2. ALL EXPOSED SECURITY DEVICES, ARMORED CABLES,

SEE DGN. Q4-G-002.

1. FOR GENERAL NOTES, LEGEND AND ABBREVIATIONS,

NOTES:

:4

-6

CCTV-L1

FO-CAM-L1

CABLE NUMBER (TYPICAL)

EP-102

S-TS-L1

360°

HORN-L1

ALARM

S-AH-L1

S-BMS-L2

S-BMS-L1

S-BMS-L4

JBS-BMS-L3

T-L1

BMS-L1 BMS-L2

BMS-L4BMS-L3

PHONE L1

FO-RCC-1

POWERHOUSE

TO

P-100

P-101

FO-PP-L

TERMINAL PANEL

WIRING

PATCH PANEL

COPPER

CONVERTER

MEDIA

CONTROLLER

SECURITY

POWER SUPPLY

24 VDC

EP-100

UPS-L

OUTPUT INPUT

SEE NOTE 5

GENERAL BLOCK DIAGRAM

FO-CAM-R1

EP-202

CCTV-R1

S-TS-R1

S-AH-R1

T-R1

S-BMS-R1

S-BMS-R2

S-BMS-R3

S-BMS-R4

R1

PHONE

BMS-

R2

BMS- HORN-R1

R4

R3

(CKT. 19)

LP-RCC-1

XFMR

NEW ESSENTIAL POWER

120V PANEL - EP-L1

SEC RCC-1

NEW CABINET -

SEE NOTE 6 SEE NOTE 4

T-601

SEE NOTE 7

NEW PANEL LP-RCC-2

POWER ZONE UNIT SUBSTATION.

SIMILAR AND EQUAL TO SQUARE D SEALED, MINI-

7. PROVIDE PANEL WITH INTEGRAL TRANSFORMER

6. REROUTE LINES TO NEW SECURITY CABINET RCC-1.

INSTALLED EQUIPMENT.

FOR GOVERNMENT FURNISHED GOVERNMENT

SEE SPECIFICATIONS INCLUDE 4RU SPARE SPACE

5. PROVIDE 19-INCH RACK CABINET RATED NEMA 3R.

SECURITY CABINET RCC-1.

SHEET E-201. GO THRU GALLERY AND UP TO NEW

4. ROUTE LINES THRU EMBEDDED CONDUIT SHOWN ON

SERVING THE LOCATION.

AND DEVICES SHALL BE FED FROM THE UPS PANEL

3. POWER SUPPLIES FOR ALL CONVERTERS, EQUIPMENT,

Q4-T-605.

2. SEE ASSOCIATED CABLE SCHEDULE ON DRAWING

Q4-G-002.

1. FOR LEGEND AND ABBREVIATIONS, SEE DRAWING

NEW WORK

0S

CENTER HILL

(SEE NOTE 1)

SCADA SYSTEM

EXISTING

FO-PH-S1

(SEE NOTE 1) NEW

FO-PP-PH

(TYPICAL)

FIBER OPTIC

CABLE NUMBER

(LEFT SIDE ONLY) FO-PP-L

(UPS-R)

TB

(SEC RCC-2)

CABINET - SEC RCC-1

FO TO ETHERNET

MEDIA CONVERTER

POWER SUPPLIES

PANEL LP-RCC-2

CABLE

ETHERNET

(SEE NOTE 3)

CUT-OFF

SEE NOTE 6

S-BMS-L2 S-BMS-L3 S-BMS-L4

ON CCTV CABINET

TAMPER SWITCH

BMS

HORN

PANEL

ESSENTIAL

120 VOLT

SECURITY BLOCK DIAGRAM

RCC REINFORCING BERM LEFT BANK

(SEE NOTE 1)

CCTV SYSTEM

FO-PH-TV1 FO-RCC-1

INPUT TO

EP-L1

NEW

(CCTV-R1)

PARENTHESIS ().

SIDE AS SHOWN RIGHT BANK IN

RCC REINFORCING BERM LEFT BANK

CCTV BLOCK DIAGRAM

EP-101

T-602

4. ROUTE CONDUIT FOR POWER SYSTEMS EXPOSED ON GALLERY WALLS.

3. ROUTE CONDUIT FOR SECURITY COMPONENTS EMBEDDED/CONCEALED IN GALLERY WALLS.

MODEL TS-7558-BOX. SEE SPECIFICATIONS.

WITH OPTO-ISOLATED INPUT/OUTPUT CHANNELS SIMILAR AND EQUAL TO TECHNOLOGIC SYSTEMS

2. THE SECURITY CONTROLLER SHALL BE A MULTI-FUNCTIONAL INDUSTRIAL CONTROLLER

THERE.

FROM THE PATCH PANEL TO THE EXISTING POWER-HOUSE EQUIPMENT AND MAKE FINAL CONNECTIONS

INDICATED BY THE GOVERNMENT. THE GOVERNMENT WILL INSTALL CABLES FO-PH-S1 AND FO-PH-TV1

NEW PATCH PANEL FO-PP-PH IN THE POWER-HOUSE TELEPHONE OR SPREAD ROOM IN LOCATION

1. CONTRACTOR SHALL INSTALL NEW FIBER OPTIC CABLE FO-RCC-1 FROM THE RCC STRUCTURE AND

SEE NOTE 4

AT RCC REINFORCING BERM

P-102

SEE NOTE 1

CHARGER

INVERTER

BYPASS

BATTERY

130 VDC

SEE NOTE 3.

RCC REINFORCING BERM LEFT SIDE

LP-RCC-1, CIRCUIT NO. 19

277/480 V PANEL

10 KVA, 480-120V, 1-PHASE

PANELBOARD WITH INTEGRAL

TRANSFORMER (MINI-POWER CENTER).

SUPPLY. SEE NOTE 4.

UNINTERRUPTIBLE POWER

1000VA, 120V,1-PHASE

T-603

FO-PH-T1 NEW

SEE NOTE 8

(FO-PP-R)

(UPS-R)

POWER SUPPLIES

GROUND BUS

MEDIA CONVERTER

POE SWITCH

OUTLETS

NEMA 5-20R

20A, 120V

FURNISHED GOVERNMENT INSTALLED EQUIPMENT.

PROVIDE 4RU SPARE SPACE FOR GOVERNMENT

EP-103 T-L1

120/208 VOLT

LIGHTING PANEL

LP-RCC-2

(SEE NOTE 9)

RJ45 JACK

CAT6 OUTLET

TO PANELBOARD

P-103

P-104EP-100

TELEPHONE BLOCK DIAGRAM

BERM LEFT BANK SIDE IS AS SHOWN.

EQUIPMENT ON RCC REINFORCING

UPS BLOCK DIAGRAM

(SEE NOTE 6)

TELEPHONE SYSTEM

SEE NOTE 7

EXCEPT THAT PHONE UNITS WILL BE FURNISHED BY OTHERS.

9. THE CONTRACTOR SHALL PROVIDE ALL TELEPHONE EQUIPMENT AND WIRING SHOWN INCLUDING JACKS

GOVERNMENT FURNISHED GOVERNMENT INSTALLED EQUIPMENT.

ONLY EQUIPMENT RELATED TO THE INDICATED SYSTEMS. PROVIDE 4RU SPARE SPACE FOR

8. THE SEC-RCC CABINETS ALSO CONTAIN EQUIPMENT OF OTHER SYSTEMS. THESE BLOCK DIAGRAMS SHOW

7. CONNECT NO. 4/0 AWG GROUND TO RCC GROUND BUS IN THE GALLERY.

PANELTO THE EXISTING POWER HOUSE EQUIPMENT AND MAKE FINAL CONNECTIONS THERE.

INDICATED BY THE GOVERNMENT. THE GOVERNMENT WILL INSTALL CABLE FO-PH-T1 FROM THE PATCH

NEW PATCH PANEL FO-PP-PH IN THE POWERHOUSE TELEPHONE OR SPREAD ROOM IN LOCATION

6. CONTRACTOR SHALL INSTALL NEW FIBER OPTIC CABLE FO-RCC-1 FROM THE RCC STRUCTURE AND

5. ROUTE CONDUIT FOR POWER SYSTEMS EXPOSED ON GALLERY WALLS.

APPROVED UPS SYSTEM.

AND SUPPLY EQUIPMENT INCLUDING WIRING AND OVER- CURRENT PROTECTION BASED ON

CONTRACTOR SHALL ALSO BE RESPONSIBLE TO SIZE THE ASSOCIATED UPS FEEDER

UPS BACK-UP REQUIREMENT AND AS APPROVED BY THE COR. SEE SPECIFICATIONS. THE

4. THE CONTRACTOR SHALL DETERMINE UPS RATING BASED ON ACTUAL LOADS AND 2-HOUR

3. FOR PANEL SCHEDULES FOR EP-L1, SEE DGN.Q4-T-604.

SEE SPECIFICATIONS.

2. PROVIDE BATTERY MODULES TO OPERATE LOADS FOR A MINIMUM OF 2 HOURS.

1. UPS SYSTEM EQUIPMENT IS RACK MOUNTED IN CABINETS SEC RCC-1.

T-604

AREA

GALLERY

CABINET

LOAD SERVED

SPACE

VA

LOAD LP-RCC-2

�A �B

�A

LOAD

SUB TOTALS: 3680

TOTAL LOAD: 8520 VA

SUB TOTALS:4,840

LOAD SERVED AREA

RECEPTACLE HIGH MAST POLE

SYSTEM RECEPTACLE

DEDICATED PHONE

SYSTEM RECEPTACLE

DEDICATED PHONE

SPARE

1,440

1,200

1,200

1 2

3 4

5 6

RECEPTACLES

CIRCUIT

ENCLOSURE: NEMA 1

NUMBER OF POLES: 12

MAIN BUS:60A

VOLTAGE: 240V, 1PH, 3W

CHARACTERISTICS:

MOUNTING: SURFACE MOUNTED

BRANCH CIRCUIT BREAKERS: 1P-20A, UNLESS NOTED OTHERWISE

MAIN CIRCUIT BREAKER: 2P-60A

SHORT CIRCUIT RATING: 10,00 SYM AMPS.

SITE

CAMERA CCTV-L1

& PWR SUPPLIES

PHONE-MEDIA CONVERTERS

LOAD EP-L1

CIRCUIT �B

MEDIA CONV & PWR SUPPLY

SECURITY CONTROLLER,

NUMBER OF POLES: 12

MAIN BUS:100A

VOLTAGE: 120V, 1PH, 3W

ALL BREAKERS TO BE GFCI TYPE

MOUNTING: SURFACE MOUNTED

BRANCH CIRCUIT BREAKERS: 1P-20A, UNLESS NOTED OTHERWISE

MAIN CIRCUIT BREAKER: 1P-100A

SUB TOTALS: 420 112 SUB TOTALS:

TOTAL LOAD: 532 VA

3 4

11 12

SPARE (SEE NOTE 2 )

SPARE (SEE NOTE 2 )

110SITE CAMERA CCTV-R1

2000ELEC ROOM HVAC

ELEC ROOM HVAC 2000 RECEPTACLE ELEC ROOM

�B

�B

ACTUAL EQUIPMENT LOADS WHEN SIZING THE UPS AND BATTERY SYSTEM.

2. THE CONTRACTOR SHALL INCLUDE THE INDICATED SPARE CAPACITY AND

1. SEE DRAWING Q4-T-603 FOR UPS SYSTEM BLOCK DIAGRAM.

T-605

SECURITY SYSTEMS CABLE SCHEDULE

CABLE NO. CABLE SIZE

1-48 FIBER

FO-RCC-2

FO-CAM-L1A

FO-CAM-R1A

FO-PH-S1

FO-PH-TV1

FO-PH-T1

1-24 FIBER

1-4 FIBER

1-1 FIBER

1-4 FIBER

1-1 FIBER

SEE REMARKS

S-BMS-L3

CAT6 UTP

CAT6 UTP

1-2/C #16

EP-101

EP-103

P-102

P-103

P-104

1-1/C #12 GND

2-1/C #12;

1-1/C #10 GND

2-1/C #10;

NEW FO-PP-PH (CENTER HILL POWER HOUSE)

FO-PP-L (RCC BERM SECURITY CABINET-1)

CCTV-L1 CAMERA TOWER FO BREAKOUT BOX

FO-PP-R (RCC BERM SECURITY CABINET-2)

CCTV-R1 CAMERA TOWER FO BREAKOUT BOX

FROM

SECURITY CABINET-1, SECURITY CONTROLLER

SECURITY CABINET-2, SECURITY CONTROLLER

120V ESSENTIAL POWER PANEL EP-L1

480V PANEL LP-RCC-1

120V PANEL LP-RCC-2

TO VIA REMARKS

CCTV-L1 CAMERA TOWER FO BREAKOUT BOX

CCTV-L1 CAMERA

CCTV-R1 CAMERA TOWER FO BREAKOUT BOX

CCTV-R1 CAMERA

EXISTING POWERHOUSE SCADA SYSTEM CABINET

EX POWERHOUSE CCTV FO PATCH PANEL

EX POWERHOUSE FO CABINET IN TELEPHONE ROOM

TELEPHONE L1 RJ45 OUTLET

TELEPHONE R1 RJ45 OUTLET

DOOR BALANCED MAGNET SWITCH L1

DOOR BALANCED MAGNET SWITCH L2

DOOR BALANCED MAGNET SWITCH L3

DOOR BALANCED MAGNET SWITCH L4

DOOR ALARM HORN L1

CCTV-L1 CAMERA TOWER JB TAMPER SWITCH

DOOR BALANCED MAGNET SWITCH R1

DOOR BALANCED MAGNET SWITCH R2

DOOR BALANCED MAGNET SWITCH R3

DOOR BALANCED MAGNET SWITCH R4

DOOR ALARM HORN R1

CCTV-R1 CAMERA TOWER JB TAMPER SWITCH

POWER HOUSE, DAM, NEW RIGHT BANK DUCT

CONDUIT

2" CONDUIT

1/2" FLEX

1/2" FLEX

CONDUIT AND EXISTING CABLE TRAY

CONDUIT, AND STAINLESS STEEL ARMORED FLEX CABLE

PROVIDED BY GOVERNMENT

24V DC POWER SUPPLIES

SECURITY CABINET-SEC RCC-1;

CCTV-L1 CAMERA

MEDIA CONVERTERS

TELEPHONE POWER SUPPLIES/

UPS-L, MAINTENANCE BYPASS SWITCH

DEDICATED RECEPTACLE

SECURITY CABINET-SEC RCC-1; 120V,20A

DEDICATED RECEPTACLE

SECURITY CABINET-SEC RCC-1; 120V,20A

" CONDUIT4

1" CONDUIT

INSTALL IN CONDUIT WITH CKT. EP-101

1 " CONDUIT

INSTALL IN CONDUIT WITH CABLE P-103

Q4-G-002.

1. FOR GENERAL NOTES, LEGEND, AND ABBREVIATIONS, SEE DRAWING

e c x d e

HORN-L1

JBS-BMS-L3

BMS-L1 BMS-L2

BMS-L4BMS-L3

PHONE L1

(CKT. 19)

480V PANEL

ESSENTIAL POWER

120V PANEL -

OUTPUT INPUT

SEC RCC-1

CABINET -

GENERAL BLOCK DIAGRAM

FO-RCC-2

EP-202

CCTV-R1

R2

BMS- HORN-R1

R4

R3

480V PANEL

ESSENTIAL POWER

EP-R1

120V PANEL -

SEC RCC-2

CABINET -

UPS-R

FO-PP-R

P-201

P-200

EP-200

TD-601

MINI-POWER CENTER

480-120V,10KVA,1PH

OUTPUTINPUT

PANEL LP-RCC-3

MINI-POWER CENTER

480-120V,10KVA,1PH

Q4-G-003.

1. FOR LEGEND AND ABBREVIATIONS, SEE DRAWING

TO BE REMOVED

:0

:5

-E

LP-RCC-2-1

5KV DS

EMBEDED CONDUIT SEE NOTE 5

DRY-TYPE

LP-RCC-2-1 LP-RCC-2-1 LP-RCC-2-1

PARTIAL PLAN

LP-RCC-2-5

ROLL UP DOOR 1

LP-RCC-1-1

FIXTURE TYPE "0"

400'-0"

IDENTIFICATION

(OR APPROVED EQUAL)

MANUFACTURER/CATALOG NO.

VOLTAGE/LAMP

LIGHTING FIXTURE SCHEDULE

REMARKS

TOTAL QUANTITY (13)

UNIT COMBOS

EMERGENCY LED EXIT/

"EX"

FACES, W/ 277V AC INPUT

LITHONIA LIGHTING ECR LED M6, DOUBLE

277 VOLTS, LED

STATUS INDICATOR, UL LISTED, DAMP LOCATION LISTING.

SEALED NICKEL CADMIUM RECHARGEABLE BATTERY, MAINTENANCE FREE, TEST SWITCH,

COMBINATION EMERGENCY LIGHTING UNIT AND EXIT, DUAL VOLTAGE INPUT 120V OR 277VAC,

LOOKING DOWNSTREAM

ELEVATION

/1

48" AFF

SW-1 LOCATION

3-WAY SWITCH

SEE SHEET Q4-RCC-E-501

NEW ELECTRICAL ROOM

18"AFF (TYP.)

120V GFCI RECEPT

EQUALLY SPACED

SEE NOTE 6

E-201

SEE NOTE 3

LP-RCC-1-13

6 FIXTURES "HM"

HIGH MAST POLE #1

EXISTING EQUIPMENT ROOM

ME

ME ME ME

ME ME ME

"M"

"ME"

TBD

TBD

UNV/70W

UNV/70W

4000K 1' x 4' LED SURFACE MOUNT ENCLOSED AND GASKETED NEMA 4X, IP66, IP67, AND NEMA NSF/ANSI SPLASH ZONE CERTIFIED 10,000 LUMEN

4000K 1' x 4' LED SURFACE MOUNT W/10W EMERGENCY BATTERY ENCLOSED AND GASKETED NEMA 4X, IP66, IP67, AND NEMA NSF/ANSI SPLASH ZONE CERTIFIED 10,000 LUMEN

JUNCTION BOX

CONDUIT TO GALLERY

2(4") EMBEDDED

6. ALL FIXTURES ARE TYPE 'M' UNLESS OTHERWISE NOTED.

AND COMMUNICATIONS.

5. USE EXISTING EMBEDDED CONDUIT TO ROUTE CIRCUITS FOR GALLERY LIGHTING, RECEPTACLES,

4. FIXTURE TYPE "O" SHALL NOT BE SWITCHED AND SHALL BE PHOTOCELL CONTROLLED.

3. INTERCEPT EXISTING HIGH MAST FEED AND ROUTE TO NEW PANEL LP-RCC-2 PANEL.

2. SEE PANEL SCHEDULE DRAWING NO. Q4-E-602.

1. FIXTURE TYPE "EX" SHALL NOT BE SWITCHED.

LP-RCC-1-1-SW1 & 2

NEW FIXTURE TYPE "M"

WALL MOUNTED 6' AFF.

GALLERY LIGHT FIXTURES

18"AFF (TYP.)

120V GFCI RECEPT

350'-0"

LP-RCC-1-6

LP-RCC-3-5

ROLL UP DOOR 2

GALLERY CEILING

'-0

GUTTER

NOT TO SCALE

LP-RCC-2-1 LP-RCC-2-1 LP-RCC-2-1 LP-RCC-2-1

SW-2 LOCATION

EQUALL

SP

ACED

(TYP.)

FIXTURE TYPE "M"

E-202

EXISTING EQUIPMENT ROOM

LP-RCC-1-14

6 FIXTURES "HM"

HIGH MAST POLE #2

TO GALLERY(SEE NOTE 5 )

EMBEDDED CONDUIT

FIXTURE TYPE "0"ME

MEME

MEME

SW-2 LOCATION

TYPE "EX"(TYP.)

LED EXIT

LIGHTING SWITCH.

7. VENTILATING FAN START/STOP PUSH BUTTON WILL BE INSTALLED IN THE SAME LOCATION OF THIS

6. ALL FIXTURES ARE TYPE 'M' UNLESS OTHERWISE NOTED.

AND COMMUNICATIONS.

5. USE EXISTING EMBEDDED CONDUIT TO ROUTE CIRCUITS FOR GALLERY LIGHTING, RECEPTACLES,

4. FIXTURE TYPE "O" SHALL NOT BE SWITCHED AND SHALL BE PHOTOCELL CONTROLLED.

3. INTERCEPT EXISTING HIGH MAST FEED AND ROUTE TO NEW PANEL LP-RCC-2 PANEL.

2. SEE PANEL SCHEDULE DRAWING NO. Q4-E-602.

1. FIXTURE TYPE "EX" SHALL NOT BE SWITCHED.

TO AVOID INTERFERENCE W/ EXIST. EQUIPMENT

NEED TO VERIFY IN FIELD BY THE CONTRACTOR

WALL MOUNTED 6'-7' AFF.

GALLERY LIGHT FIXTURES

E-501

31'-6"(MONOLITH WIDTH )

GUARDRAIL

CONTROL JOINT

IX

G BASEPLATE

27" x 27"

BELOW

CONDUITS DOWN TO GALLERY

EXISTING ELECTRICAL

SEE DETAIL 3 ON SHEET E-10

GROUNDING TEST STATION

LC-3

ELEC. SWITCH

"PVC SCH-804

3#8, 1#8 GND

TYPE "HM"

LIGHT FIXTURES

HIGH MAST LED

LC3-3

LC3-2

LC3-1

PHOTOCELL

PC

LC3

AUTO

OFF

ON

5A

500 VA

LIGHTING

TYPICAL AREA LIGHTING CONTROL

FUSED DISC. SW

240V, 30A, 2 POLE, NEMA 3R

LP-RCC-2-8

5. MOUNT NEXT TO HVAC UNIT. SEE MECHANICAL PLANS FOR EXACT LOCATION.

4. DOOR CONTACTS SEE SHEET T-502 FOR DETAILS.

3. LOCATE PHOTOCELL OUTDOOR AND AWAY FROM DIRECT LIGHT SOURCES.

BE ON CABINET DOOR AND EXTERNALLY ACCESSIBLE.

LIGHTING CONTACTOR CABINET. ON-OFF-AUTO SELECTOR SWITCH SHALL

2. AREA LIGHTING CONTROL DEVICES SHALL BE INSTALLED IN A NEMA 3R

TRANSFORMER & REROUTE TO NEW PANEL LP-RCC-1.

1. REMOVE 480V DISCONNECT INTERCEPT FEEDER FROM EXISTING

LP-RCC-2-5, 7

WP/GFCI

DEHUMIDIFIER

AIR-CONDITIONING SYSTEM

SEE SHEET T-601

NEW SECURITY CABINET

TYPE M

TYPE M

LP-RCC-2-?

E-601

50A

IN NEW ELECTRICAL ROOM

277/480V PANEL

30A 20A 20A

70A

35A

INSTALL PULL BOX EVERY 300'

30A

POWER HOUSE

500A

480V BUS

2-3/c 250kCMIL w/#4 GND

480-2400V

300kVA

IN 3" PVC COND. SCH-80

3-1/c #2 EPR CU 5kV

MANHOLE #9

ENCASEMENT FROM

APPROX. 75' CONCRETE

25A

2400-120/208V

45kVA Y

4-1/c #6 CU THHN

OVERLOOK BATHROOM

2400V SWITCH

PAD MOUNTED

2400/480V

225kVA

PB

112.5kVA

PULL BOX

AT PULL BOX #4

NO CABLE SPLICES

3 X 3-1/c #2 EPR CU 5kV

5 6 7 8

12 9

125A

200A 200A 200A

CONTRACTORS AC POWER PANEL

IN 2" COND.

1-1/c #4 CU FOR GND

3-1/c #3/0 CU THHN

200A

APPROX. 50FT

75kVA

3-1/c #2/0 CU THHN

45kVA Y

DISCONNECT

POLE MOUNTED

OVERHEAD FEEDER

APPROX. 100FT

150A

TRANSIT QUARTERS AC POWER PANEL

240/120V 1�

480-240/120V 1�

10kVA

IN 3/4" PVC CONDUIT SCH-40

2-1/c #10, 1-1/c #10 GND

IN 3/4" PVC CONDUIT SCH-40

2-1/c #8, 1-1/c #10 GND

IN 2" PVC CONDUIT SCH-40

3-1/c #3, 1-1/c #6 GND

CONDUIT SCH-80

EPR CU 5kV IN 4" PVC

3-1/c #2, 1-1/c #2 GND

5 kV MVS

2400-277/480V

45kVA

EXISTING RADIO TOWER PANEL

APPROX. 300'

APPROX. 400'

APPROX. 100'

APPROX. 150'

OFFICE AC POWER PANELs SHOP AC POWER PANEL

APPROX. 15'

IM

IZ

.1

SHALL INSTALL SURGE ARRESTORS AT THIS XFMR.

1. THIS TRANSFORMER SHALL BE DRY-TYPE.THE CONTRACTOR

NEW WORK

AREA LOAD SERVED

NEMA 3R CABINET CONT. "LC1"&"LC2"

POLE #1

HIGH MAST

6(HM)

10 kVA XFMR

(LP-RCC-2)

�A �B

�C

VAVAVA

SUB TOTALS: 7290 11602 6880

NUMBER OF POLES: 42

MAIN BUS: 100A

VOLTAGE: 277/480V, 3PH, 4W

MOUNTING: WALL MOUNTED

BRANCH CIRCUIT BREAKERS: 1P-20A, 2P-20A, 3P-20A, UNO

MAIN CIRCUIT BREAKER: 3P-70A

TOTAL LOAD: 35,337 VA

CIRCUIT CIRCUIT

�A �B �C

19 20

3501 3057 3007 SUB TOTALS:

6(HM)

POLE #2

HIGH MAST

CONTACTOR "LC4" NEMA 3R CABINET

NEMA 3R CABINETCONTACTOR "LC3"

AREALOAD SERVED

�C�B�A

VA VA VA

E-602

39(M ), 21(ME )

XMFR

LPP-RCC-2

20A 20A

TO GALLERY

5KV DS

DRY-TYPE

FIXTURE TYPE "L"

LP-RCC-1-1-SW1 & 2

400'-0"

TYPE "EX" (TYP.)

LED EXIT/UNIT COMBOS

SS

SS

ED-201

120V GFCI RECEPT(TYP.)

LOCATION

SW2 & SW3

EQUIPMENT ROOM

480V DS

LOCATION

SW2 & SW3

3. REMOVE EXISTING 480V DISCONNECT AND UNISTRUT FRAMING.

PLACE.

2. DISCONNECT SOURCE FEEDER TO EXISTING PANEL LP-RCC-1 AND ABANDON ALL EQUIPMENT IN

ALL FIXTURE ARE TYPE "M" UNLESS OTHERWISE STATED.

CONDUIT IN GALLERY AREA. REPLACE WITH DEVICES AS SHOWN. ALL LIGHTING FROM LP-RCC-1,

1. REMOVE ALL LIGHT FIXTURES, RECEPTACLES, LIGHT SWITCHES, EXIT SIGNAGE, AND ASSOCIATED

EMBEDED CONDUIT

HIGH MAST POLE #1

ROLL UP DOOR 1

REMOVED

TYPE "EX" (TYP.) TO BE

TO GALLERY

TYPE "EX" (TYP.)

350'-0"

ED-202

120V GFCI RECEPT(TYP.)

EQUIPMENT ROOM

HIGH MAST POLE #2

LP-RCC-1-8

ALL FIXTURES ARE "M" UNLESS OTHERWISE NOTED.

CONDUIT IN GALLERY AREA. REPLACE WITH DEVICES AS SHOWN. ALL LIGHTING FROM LP-RCC-1,

1. REMOVE ALL LIGHT FIXTURES, RECEPTACLES, LIGHT SWITCHES, EXIT SIGNAGE, AND ASSOCIATED

SW-4 LOCATION

ROLL UP DOOR 2

SW-4 LOCATION

REMOVED

TYPE "EX" (TYP.) TO BE

PB

POWER HOUSE

480V BUS

500A

APPROX. 300' 2-3/c 250kCMIL w/#4 GND

480-2400V

300kVA

EXISTING RADIO TOWER PANEL

30A

INSTALL PULL BOX EVERY 300'

EPR CU 5kV IN 4" PVC COND. SCH-80

MANHOLE #9

ENCASEMENT FROM

APPROX. 75' CONCRETE

AT PULL BOX #4

NO CABLE SPLICES

2400V SWITCH

PAD MOUNTED

125A

APPROX. 400'

75kVA

IN 2" COND.

3-1/c #3/0 CU THHN

APPROX. 50FT

200A

APPROX. 100'

3 X 3-1/c #2 EPR CU 5kV

3-1/c #2/0 CU THHN

APPROX. 15'

POLE MOUNTED

OVERHEAD FEEDER

APPROX. 100FT

150A

TRANSIT QUARTERS AC POWER PANEL CONTRACTORS AC POWER PANEL

APPROX. 150'

OFFICE AC POWER PANELs

200A 200A 200A

SHOP AC POWER PANEL

112.5kVA

2400/480V

225kVA

OVERLOOK BATHROOM

4-1/c #6 CU THHN

277/480V PANEL

20A 20A 20A

IN 2" PVC CONDUIT SCH-40

3-1/c #3, 1-1/c #6 GND

35A

5 kV MVS

ED-601

2400-277/480V

PANEL LP-RCC-1.

1. REMOVE EXISTING 480V DISCONNECT AND FEEDER TO

G-001

:2 e c x d e

\D

-G

NEW ELEC. BUILDING

RCC BERM

STAGING AREA.

WORK

LIMITS OF

SHOWN ON THIS DRAWING.

4. UNLESS OTHERWISE APPROVED BY THE COR, LIMITS OF WORK AREA SHALL BE AS

3. SEE DWG E-201 FOR LOCATION OF THE NEW ELECTRICAL ROOM.

EVERYTHING IN THE FIELD.

DETAILS ON THIS DRAWING ARE FOR REFERENCE. CONTRACTOR SHALL VERIFY

2. THE GOOGLE IMAGE, ROLLER COMPACTED CONCRETE(RCC) BERM, AND OTHER

IDENTIFIED AREA FOR THE STAGING AREA.

1. THE TRAILER IS NO LONGER AT THE PROJECT. CONTRACTOR SHALL USE THE

G-002

LP-RCC-1-1-SW1&2

ARC - GROUND CONDUCTOR

LONG DASH - NEUTRAL CONDUCTOR

SHORT DASH - PHASE CONDUCTOR

DESIGNATION AS FOLLOWS:

IS CONTROLLED BY SWITCH 1 & 2 WITH CONDUCTOR

DENOTES CIRCUIT 1 TO PANEL LP-RCC-1 AND THE LIGHT

FIXTURE TYPE "O"

EMERGENCY LED EXIT/UNIT COMBOS TYPE "EX"

FIXTURE TYPE "L"

DENOTES CIRCUIT 2 TO PANEL LP-RCC-2LP-RCC-2-2

Y - WYE CONNECTED

- DELTA CONNECTED

TRANSFORMER

FUSED DISCONNECT SWITCH

THERMAL-MAGNETIC CIRCUIT BREAKER

MOTOR OVERLOAD

LIMIT SWITCH

NORMALLY OPEN

FLOAT SWITCH

CONTROL CONTACT

NORMALLY CLOSED

CONTROL CONTACT

PUSH BUTTON

NORMAL OPEN

EMBEDED CONDUIT

LEGEND

120V GFCI, DUPLEX RECEPTACLE W/ IN-USE WEATHER-PROOF ENCLOSURE

ABBREVIATIONS

TRANSFORMERXFMR

KILO-VOLTS-AMPSkVA

WEATHER PROOFWP

VOLTS-AMPSVA

VOLTSV

UNINTERRUPTIBLE POWER SUPPLYUPS

TYPICALTYP

TAMPER SWITCHTS

SWITCHSW

STAINLESS STEELSST

SECURITYS, SEC

ROLLER COMPACTED CONCRETERCC

RIGID GALVANIZED STEEL CONDUITRGS

POLYVINYL CHLORIDEPVC

PATCH PANELPP

OVERLOADOL

LIMIT SWITCHLS

LIGHTING PANELLP

JUNCTION BOXJB

HORSE POWERHP

GROUNDGND

GROUND FAULT CIRCUIT INTERUPTERGFCI

FLOAT SWITCHFS

FO-PP-XX FIBER OPTIC PATCH PANEL (NUMBER AS NOTED)

FIBER OPTICFO

ESSENTIAL (UPS) POWER PANELEP

DISCONNECT SWITCHDS

DRAWINGDWG

CONTROL RELAYCR

CLOSED-CIRCUIT TELEVISIONCCTV

CCTV CAMERACAM

BALANCED MAGNETIC SWITCHBMS

ALARM HORNAH

ABOVE FINISHED GRADEAFG

ABOVE FINISHED FLOORAFF

AMPSA

CCTV CAMERA; UNIT NO. CCTV-L1

TAMPER SWITCH FOR SECURITY SYSTEM

DENOTES CIRCUIT 2 TO PANEL LP-RCC-2

Y - WYE CONNECTED

- DELTA CONNECTED

TRANSFORMER

FUSED DISCONNECT SWITCH

THERMAL-MAGNETIC CIRCUIT BREAKER

EMBEDDED/CONCEALED CONDUIT

UNIT NO. L

UNINTERRUPTIBLE POWER SUPPLY

LEGEND(CONT.)

LP-RCC-2-2

PLANS, AND SCHEDULES.

APPLY ONLY TO THE SECURITY DIAGRAMS, EQUIPMENT,

1. THE LEGEND AND ABBREVIATIONS ON THIS SHEET

REWORKED WITHOUT ADDITIONAL COST TO THE GOVERNMENT.

REMOVED,REPLACED,OR OTHERWISE SATISFACTORILY

IN THE TRADE.UNSIGHTLY INSTALLATIONS SHALL BE

LIKE MANNER BY PERSONS EXPERIENCED AND SKILLED

2. ALL WORK SHALL BE PERFORMED IN A NEAT, WORKMAN

AND DOCUMENTS.

SHOWN OR INFERRED ON THESE CONTRACT DRAWINGS

AND EQUIPMENT NECESSARY TO COMPLETE ALL WORK

3. CONTRACTOR SHALL PROVIDE ALL LABOR,MATERIAL,

PLETE AND OPERATIONAL SYSTEMS.

NATE ALL CIRCUITS AND RACEWAY TO PROVIDE COM-

THE CONTRACTOR PROVIDE,ROUTE,INSTALL, AND TERMI-

SHOWN ON THESE DRAWINGS, IT IS THE INTENT THAT

4. WHERE CIRCUIT AND RACEWAY ROUTINGS ARE NOT

LABEL PANEL AND CIRCUIT NUMBER.

INDICATING RECEPTACLE IS ON UPS POWER. ALSO,

5. FOR UPS RECEPTACLES PROVIDE PERMANENT LABEL

GFCI TYPE IN WEATHERPROOF ENCLOSURE.

ANY AREA EXPOSED TO THE ELEMENTS SHALL BE

6. ALL RECEPTACLES LOCATED IN GALLERY AREAS OR

IFICATIONS.

SUPPORT HARDWARE PER NEC AND PROJECT SPEC-

AND CONDUITS SHALL BE INSTALLED WITH REQUIRED

7. ALL EXPOSED SECURITY DEVICES, ARMORED CABLES,

BOX ENCLOSURE.

ONLY BE INSIDE THE DEVICE ENCLOSURE OR ASSIGNED

8. WIRE TERMINATIONS FOR SECURITY DEVICES SHALL

PREVENT WATER INTRUSION.

ALL J-BOXES AND SEAL ALL CONDUIT ENTRIES TO

SHALL BE LIQUID TIGHT. USE POTTED WIRE NUTS IN

9. ALL CONDUITS, FITTINGS, ELBOWS, J-BOXES, ETC.

M-501

-M

GUARDRAIL

-M

/8

BELOW

CONDUITS DOWN TO GALLERY

EXISTING ELECTRICAL

BASEPLATE

SEE NOTE 1.

DUCTLESS (THROUGH WALL)

AIR-CONDITIONING SYSTEM

SEE NOTE 2.

EQUIPMENT SCHEDULE

UNIT COOLING CAPCITY HEATING CAPACITY AIR FLOW POWER SUPPLY

MINI SPLIT

8,700 BTU/H 10,900 BTU/H 380 CFM

230V/1PH/60HZ

115V/1PH/60HZ- -

DRAINAGE PIPING

4. DRAINAGE PIPING TO RUN TO EXTERIOR OF MONOLITH.

3. ALL OUTDOOR PIPING SHALL BE INSULATED.

WITH A PUMP. SEE SPECIFICATIONS FOR DETAILS. LOCATION OF EQUIPMENT IS SUBJECT TO CHANGE

2. DEHUMIDIFIER HISENSE DH7021KP1G OR EQUIVALENT. DEHUMIDIFIER SHALL BE FURNISHED

EQUIPMENT IS SUBJECT TO CHANGE.

UNIT WILL REQUIRE DISCONNECT SWITCH, SEE DRAWING E-501 FOR DETAILS. LOCATION OF

1. DUCTLESS AIR CONDITIONING SYSTEM PANASONIC XE9WKUA OR EQUIVALENT.

Plans For

Nashville District of Engineers

W912P5-22-B-0003

January 2022

Center Hill Auxiliary Dam

RCC Berm Electrical Rework

Cumberland River Watershed

Dekalb County, Tennessee

Caney Fork River

DRAWING INDEX

SECURITY SYSTEM - CABLE SCHEDULEQ4-RCC-T-605

ELECTRICAL - 120V PANEL & UPS PANEL SCHEDULESQ4-RCC-T-604

SECURITY UPS & TELEPHONE - BLOCK DIAGRAMSQ4-RCC-T-603

SECURITY & CCTV BLOCK DIAGRAMSQ4-RCC-T-602

SECURITY BLOCK DIAGRAMQ4-RCC-T-601

SECURITY BLOCK DIAGRAM - DEMOQ4-RCC-TD-601

ELECTRICAL - SECURITY DETAILSQ4-RCC-T-502

SECURITY - EQUIPMENT CABINETS LAYOUTSQ4-RCC-T-501

ELECTRICAL ROOM - STRUCTURAL DETAILSQ4-RCC-S-501

STRUCTURAL NOTESQ4-RCC-S-001

ELECTRICAL ROOM - HVAC DETAILSQ4-RCC-M-501

480V PANEL SCHEDULEQ4-RCC-E-602

SINGLE LINE DIAGRAMQ4-RCC-E-601

SINGLE LINE DIAGRAM - DEMOQ4-RCC-ED-601

ELECTRICAL ROOM - DETAILSQ4-RCC-E-501

GALLERY LIGHTING DETAILSQ4-RCC-E-202

GALLERY LIGHTING DETAILS - DEMOQ4-RCC-ED-202

GALLERY LIGHTING DETAILSQ4-RCC-E-201

GALLERY LIGHTING DETAILS - DEMOQ4-RCC-ED-201

LEGEND & ABBREVIATIONSQ4-RCC-G-002

OVERALL SITE PLANQ4-RCC-G-001

DESCRIPTIONDRAWING #

CONTRACT DRAWINGS

Submitted:

Faron D. Bean, P.E.

(2.) The approval signatures appearing in the signature block on this sheet constitute approval of all drawings listed in the sheet index.

of individuals appear on these project documents within the scope of their employment as required by ER 1110-1-8152.

(1.) This project was designed by the Nashville District of the U.S. Army Corps of Engineers. The initials or signatures and registration designations

Note:

Mark P. Evans, P.E.

Chief, Electrical / Mechanical Section

Approved:

Robert W. Baulsir III, P.E.

Chief, Civil Design Branch

Project Engineer

Approval Recommended:Certified Final Documents - RTA

2022-01-20T18:01:59-0600

BEAN.FARON.DAVID.1110133924

2022-01-21T10:42:32-0600

EVANS.MARK.PHILIP.1152793533

2022-01-21T09:16:22-0600

BAULSIR.ROBERT.W.III.1258321525

1312111098765432

S-001

-S

ANCHORS TO ROLLAR COMPACTED CONCRETE(RCC).

ATTACHMENT OF STRUCTURAL STEEL MEMBERS TO THE EXISTING STRUCTURE SHALL BE ACHIEVED THROUGH POST-INSTALLED7.

FULL RESPONSIBILITY FOR THE DESIGN OF STRUCTURAL STEEL MEMBERS AND THEIR CONNECTIONS.

INTERPRETATION OF THE DESIGN LOADS AND CONTRACT DOCUMENT DETAILS. SUCH REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF

BE FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS REGARDING ARRANGEMENT AND SIZES OF MEMBERS AND THE CONTRACTOR'S

INDICATE SUPPLEMENTAL ACCESSORIES, AND DETAILS REQUIRED FOR PROPER INSTALLATION. REVIEW OF SHOP DRAWINGS SHALL

INCLUDE PLACING DRAWINGS FOR FRAMING MEMBERS SHOWING SIZE DESIGNATIONS, NUMBER, TYPE, LOCATION, AND SPACING.

OF THE CONTRACTOR. SUBMIT SHOP DRAWINGS SEALED BY AN ENGINEER LICENSED IN THE PROJECT STATE. SHOP DRAWINGS SHALL

DESIGN OF STRUCTURAL STEEL FRAMING ARRANGEMENT, MEMBERS, AND THEIR CONNECTIONS SHALL BE THE SOLE RESPONSIBILITY6.

SUBMITTED TO THE CONTRACTING OFFICER FOR REVIEW.

ALL STEEL EXPOSED TO WEATHER OR MOISTURE SHALL BE GALVANIZED, OR SHALL BE PROTECTED BY OTHER MEANS5.

PRE AND POST WELDING HEAT TREATMENT SHALL BE IN ACCORDANCE WITH APPLICABLE AWS.4.3

WELDING SHALL BE IN ACCORDANCE WITH AWS D1.1.4.2

ALL WELDERS SHALL BE AWS QUALIFIED FOR THE WELDING PROCEDURE WHICH THEY WILL PERFORM.4.1

WELDING4.

ANCHOR RODS SHALL CONFORM TO ASTM F1554.3.2

ALL BOLTS SHALL BE ASTM F3125 GRADE A325.3.1

BOLTS AND ANCHOR RODS3.

OTHER STEEL SHAPES (CHANNELS, ANGLES, PLATES )SHALL CONFORM TO ASTM A36.2.4

ROUND HOLLOW STRUCTURAL SECTIONS (HSS )SHALL CONFORM TO ASTM A500 GRADE C.2.3

SQUARE/RECTANGULAR HOLLOW STRUCTURAL STEEL SECTION (HSS )SHALL CONFORM TO ASTM A500 GRADE C.2.2

WIDE FLANGE SHAPED MEMBERS (W- )SHALL CONFORM TO ASTM A992.2.1

STRUCTURAL STEEL SHALL BE OF THE FOLLOWING GRADES UNLESS APPROVED OTHERWISE:2.

STRUCTURAL STEEL BUILDINGS" AND THE AISC 303 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES".

STRUCTURAL STEEL SHALL BE FABRICATED AND ERECTED ACCORDING TO THE ANSI/AISC 360 "SPECIFICATION FOR1.

STRUCTURAL STEEL METHODS AND MANUFACTURER BOND DATA PROVING ADEQUATE PERFORMANCE UNDER MORE ADVERSE CONDITIONS.

IF THESE CONDITIONS DO NOT EXIST, THE CONTRACTOR SHALL SUBMIT ALTERNATE DRILLING

-TEMPERATURES NOT EXCEEDING MANUFACTURER'S ALLOWABLE RANGES FOR STRUCTURAL USE

-CONCRETE CURED FOR A MINIMUM OF 21 DAYS

-DRY HOLE

-HOLES DRILLED WITH HAMMER DRILL WITH CARBIDE TIPPED DRILL BIT

THE FOLLOWING CONDITIONS SHALL BE PROVIDED:

ADHESIVE ANCHORS AND REINFORCING STEEL CAPACITY IS DEPENDENT UPON INSTALLATION CONDITIONS.7.

GALVANIZED PER ASTM B695, CLASS 65, TYPE I

MECHANICAL AND SCREW ANCHORS IN EXTERIOR NONCORROSIVE ENVIRONMENTS SHALL BE HOT-DIPPED 6.

ASTM A193 Gr. B8M TYPE 316 ALL THREAD ROD

CORROSIVE ENVIRONMENTS:

ASTM F1554 Gr. 36 ALL THREAD ROD, HOT DIPPED GALVANIZED PER ASTM B695, CLASS 65, TYPE I

EXTERIOR NONCORROSIVE ENVIRONMENTS:

ASTM F1554 Gr. 36 ALL THREAD ROD

INTERIOR NONCORROSIVE ENVIRONMENTS:

ADHESIVE ANCHOR INSERT SHALL BE:5.

TO CONSULTING WITH THE ARMY CORPS.

MEANS IN ORDER TO AVOID CONFLICT WITH INSTALLATION. THE CONTRACTOR SHALL NOT DAMAGE ANY REINFORCING STEEL PRIOR

REINFORCING BARS AT THE LOCATIONS OF THE CONCRETE ANCHORS OR REINFORCING, BY GPR, X-RAY, FERROSCAN, OR OTHER

THE CONTRACTOR SHALL REVIEW THE EXISTING STRUCTURAL DRAWINGS AND SHALL UNDERTAKE TO LOCATE THE POSITION OF THE

EXISTING REINFORCING BARS IN THE CONCRETE STRUCTURE MAY CONFLICT WITH SPECIFIC ANCHOR OR REINFORCING LOCATIONS.4.

PROOF OF CERTIFICATION SHALL BE MAINTAINED AT THE JOB SITE.

CURRENT AAI CERTIFICATION AS ACCREDITED BY ACI/CSRI IN ACCORDANCE WITH ACEI 318-14 17.8.2.2.

PER ACI 318-14 17.8.2.2, INSTALLATION OF ALL ADHESIVE ANCHOR PRODUCTS SHALL BE CONDUCTED BY AN INSTALLER HOLDING

PRODUCTS. TRAINING AND DOCUMENTATION SHALL OCCUR PRIOR TO COMMENCEMENT OF PRODUCT INSTALLATION. WHEN REQUIRED

SUBMIT TO THE CONTRACTING OFFICER DOCUMENTATION CONFIRMING TRAINING OF ALL PERSONNEL WHO WILL BE INSTALLING

THE CONTRACTOR SHALL ARRANGE ON SITE INSTALLATION TRAINING BY THE MANUFACTURER FOR EACH PRODUCT TO BE INSTALLED.3.

ANCHORS AND REINFORCING STEEL SHALL BE INSTALLED PER THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS(MPII )2.

REINFORCING STEEL IN PLACE OF MISSING OR MISPLACED ANCHORS.

OBTAIN APPROVAL FROM THE ARMY CORPS. CONTRACTING OFFICER PRIOR TO INSTALLING POST-INSTALLED ANCHORS OR

DELEGATED DESIGN SHOP DRAWINGS(AFTER REVIEW CONDUCTED BY ARMY CORPS. CONTRACTING OFFICER )CONTRACTOR SHALL

POST-INSTALLED ANCHORS AND REINFORCING STEEL SHALL ONLY BE USED WHERE SPECIFIED ON THE DESIGN DETAILS, INCLUDING1.

POST-INSTALLED ANCHORS AND REINFORCING STEEL

ANCHORS TO ROLLAR COMPACTED CONCRETE(RCC).

ATTACHMENT OF COLD-FORMED STEEL MEMBERS TO THE EXISTING STRUCTURE SHALL BE ACHIEVED THROUGH POST-INSTALLED3.

STEEL STRUCTURAL MEMBERS AND THEIR CONNECTIONS.

DETAILS. SUCH REVIEW SHALL NOT RELIEVE THE CONTRACTOR OF FULL RESPONSIBILITY FOR THE DESIGN OF THE COLD-FORMED

ARRANGEMENT AND SIZES OF MEMBERS AND THE CONTRACTOR'S INTERPRETATION OF THE DESIGN LOADS AND CONTRACT DOCUMENT

INSTALLATION. REVIEW OF SHOP DRAWINGS SHALL BE FOR CONFORMANCE WITH THE CONTRACT DOCUMENTS REGARDING

SPACING. INDICATE SUPPLEMENTAL STRAPPING, BRACING, SPLICES, BRIDGING, ACCESSORIES, AND DETAILS REQUIRED FOR PROPER

INCLUDE PLACING DRAWINGS FOR FRAMING MEMBERS SHOWING SIZE AND GAGE DESIGNATIONS, NUMBER, TYPE, LOCATION, AND

OF THE CONTRACTOR. SUBMIT SHOP DRAWINGS SEALED BY AN ENGINEER LICENSED IN THE PROJECT STATE. SHOP DRAWINGS SHALL

DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS, FRAMING SYSTEM, AND THEIR CONNECTIONS SHALL BE THE SOLE RESPONSIBILITY2.

FOR THE DESIGN OF COLD-FORMED STEEL STRUCTURAL MEMBERS".

1. COLD-FORMED STEEL DESIGN, FABRICATION, AND ERECTION SHALL BE IN ACCORDANCE WITH AISI S100 "NORTH AMERICAN SPECIFICATION

COLD-FORMED METAL STUDS

TEMPORARY CONNECTIONS TO PERMANENT STRUCTURES MUST BE APPROVED BY THE CONTRACTING OFFICER.

THE STRUCTURES MAY NOT BE STABLE UNTIL ALL STRUCTURAL ELEMENTS ARE IN PLACE AND PROPERLY CONNECTED.

THE CONTRACTOR IS RESPONSIBLE FOR THE TEMPORARY BRACING OF THE STRUCTURES. 6.

WHERE, H = MEAN ROOF HEIGHT OF BUILDING

SEISMIC LOADING, 2010 TABLE 12.12-1PER ASCE-7

WIND LOADING (10-YR WIND SPEEDS)H/400

BUILDING DRIFT UNDER LATERAL LOADING

WHERE, L = SPAN LENGTH (INCHES OR FEET)BETWEEN CENTERLINES OF SUPPORTS

L/240 L/360 ROOF MEMBERS:

DEAD + LIVE LOADLIVE LOAD

MAXIMUM ESTIMATED DEFLECTIONS AND BUILDING DRIFT SHOULD BE AS FOLLOWS:5.

-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS USING FLAT STRAP BRACING

-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS SHEATHED WITH WOOD PANELS

-STRUCTURAL STEEL MOMENT FRAMES

CONTRACTOR MAY SELECT FROM THE FOLLOWING:

LATERAL LOAD RESISTING SYSTEM:

SEISMIC DESIGN CATEGORY = A

SEISMIC DESIGN VALUE, T = 1.0s Sd1 = 0.062

SEISMIC DESIGN VALUE, T = 0.2s Sds = 0.120

SITE CLASS = A

MCE GROUND MOTION, T = 1.0s S1 = 0.117

MCE GROUND MOTION, T = 0.2s Ss = 0.225

IMPORTANCE FACTOR Ie = 1.0

RISK CATEGORY I

SEISMIC LOADS4.

-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS USING FLAT STRAP BRACING

-LIGHT-FRAME (COLD-FORMED)SHEAR WALLS SHEATHED WITH WOOD PANELS

-STRUCTURAL STEEL MOMENT FRAMES

CONTRACTOR MAY SELECT FROM THE FOLLOWING:

LATERAL FORCE RESISTING SYSTEM:

INTERNAL PRESSURE COEFFICIENT, GCpi = +/- 0.18

RISK CATEGORY = I

EXPOSURE = C

NOMINAL DESIGN WIND SPEED (3-SECOND GUST)= 89 MPH

ULTIMATE DESIGN WIND SPEED (3-SECOND GUST)= 115 MPH

WIND LOADS3.

FLAT ROOF SNOW LOAD Pf = 6 PSF

SNOW IMPORTANCE FACTOR I = 0.8

SNOW THERMAL FACTOR Ct = 1.1

SNOW EXPOSURE FACTOR Ce = 0.9

GROUND SNOW LOAD Pg = 10 PSF

SNOW

ROOF 20 PSF

GRAVITY LOADS2.

STRUCTURE IS TO BE DESIGNED IN ACCORDANCE WITH THE INTERNATIONAL BUILDING CODE(IBC )2015.1.

CODE/DESIGN CRITERIA

S-501

12'-0"

3'-0"

22'-0"

/8

MONOLITH BETWEEN STA. 1+35 AND 1+60

4'-0"

BASEPLATE

PROPOSED BUILDING

INTERIOR FACE OF

PROPOSED BUILDING

EXTERIOR FACE OF

ELEC. SWITCH

6'-9" TO EXISTING CONDUIT

EXISTING GUARDRAIL 2" Ø

SEE SHEET E-501

EXISTING CONDUIT

MIN. 18"

FACE OF SPILLWAY

FOR MAINTENANCE)

(LOWERED WHEN REQUIRED

10'-0" DIA. LIGHT FIXTURE

T-502 FOR REQUIREMENTS

REFER TO SPECS AND

PERSONNEL DOOR

BY THE CONTRACTOR AND SHALL BE SUBMITTED FOR GOVERNMENT APPROVAL.

TO VIEW THE RCC DAM SPILLWAY. THE EXACT SIZE SHALL BE SELECTED

4. WINDOW (SIZE OF ABOUT 3'X4') SHALL BE PROVIDED TO ALLOW FIELD PERSONNEL

TO INSTALLATION / REMOVAL OF THE EXISTING AND NEW EQUIPMENT.

INTERFERENCE WITH THE EXISTING EQUIPMENT AND TO ALLOW

AND SHALL BE SUBMITTED FOR GOVERNMENT APPROVAL TO AVOID

3. DOOR SIZE AND EXACT LOCATION SHALL BE SELECTED BY THE CONTRACTOR

2. SEE DRAWING Q4-E-201 FOR LOCATION OF NEW ELECTRICAL ROOM.

WALL DESIGN SYSTEMS WILL NOT INTERFERE WITH LIGHT FIXTURE.

1. GC TO COORDINATE SO STRUCTURAL DESIGN AND EXTERIOR

T-501

OR TUBING ARE USED

WATERTIGHT CAP IF PIPE

ON TOP AND SIDES

MINIMUM 3" AIR SPACE

OF BOX AND SUNSHADE.

AIR SPACE BETWEEN BACK

MOUNT PANEL WITH 1"

WHITE ENAMEL PAINT

MAXIMUM SUN PROTECTION

WITH RUST RESISTANT,

PAINT ALL METAL SURFACES

YAGI ANTENNA

- (FUTURE BY OTHERS)

PROTECTION FOR ANTENNA

IMAGINARY CONE OF LIGHTNING

STEEL BACK PLATE.

TOP AND SIDES, WITH 3/16"

12 GAGE STEEL SUNSHADE,

(TYP 4 PLACES EACH LEG)

ANCHOR WITH 4" EMBEDMENT

5/8" STAINLESS STEEL EXPANSION

(TYP 4 PLACES EACH LEG)

ANCHOR WITH 4" EMBEDMENT

5/8" STAINLESS STEEL EXPANSION

GROUND SYSTEM

RCC BERM

BARE SOLID CU

#2 AWG

SIDE VIEW

60° 60

24"

STEEL BACK PLATE.

TOP AND SIDES, WITH 3/16"

12 GAGE STEEL SUNSHADE,

21 3/4" x 20" x 11"

PANEL DIMENSIONS:

ENC16/18

CONTROL PANEL

APART.64

33LEG 90

TWO PLACES EACH

BASE PLATES,

" GALVANIZED 8

GUSSETS TO

WELD GALVANIZED

GALVANIZED 2" TUBING, LEGS

2" RGS ELECTRICAL CONDUIT

FRONT VIEW

INSTRUMENTATION SYSTEM CABINET

ALLOW REAR ACCESS TO THE EQUIPMENT.

2. INSTALL SECURITY CABINETS SPACED FROM THE WALL AS INDICATED TO

1. INSTALL ALL FLOOR MOUNTED CABINETS ON 6" CONCRETE PAD.

File details come from the government source that posted it. Updated .