Addendum 1 Summary of Itemized Changes.pdf

PDF 193 KB Posted

Attached to
Amendment 0004 to this Solicitation
Solicitation number
W912L709R0007
Issued by

About this file

Amend0003 - Addendum 1 Summary of Itemized Changes

View the file

Other files

File Type Posted
207238 E801D.pdf PDF
207238 E202.pdf PDF
207238 E801C.pdf PDF
207238 E802.pdf PDF
207238 E203.pdf PDF
207238 E301C.pdf PDF
207238 M405.pdf PDF
207238 E201B.pdf PDF
207238 E601.pdf PDF
Tullahoma Addendum 2 A and S large plans 082109.pdf PDF
207238 E400.pdf PDF
207238 E001.pdf PDF
Addendum 2 Summary of Itemized Changes.pdf PDF
207238 E201D.pdf PDF
Tullahoma Addendum 2 specification updates 082109.pdf PDF
207238 M502.pdf PDF
207238 E103.pdf PDF
207238 E201A.pdf PDF
2007042 ADD1 E Supplemental Dwgs 081109.pdf PDF
2007042 ADD1 P Supplemental Dwgs 081109.pdf PDF
2007042-02_csit_vs2000.dwg DWG drawing
2007042 ADD1 CAS Supplemental Dwgs 081109.pdf PDF
2007042-02_CBAS_vs2000.dwg DWG drawing
Plans P200-P403 Posted 7-22-09.zip ZIP file
Plans E Sheets Posted 7-22-09.zip ZIP file
Plans M Sheets Posted 7-22-09.zip ZIP file
Plans MPE001-MPE007 Posted 7-22-09.zip ZIP file
Plans P100A-P104 Posted 7-22-09.zip ZIP file
Plans P Sheets Posted 7-22-09.zip ZIP file
Plans FP101A-G202 Posted 7-22-09.zip ZIP file
Plans M001-M104 Posted 7-22-09.zip ZIP file
Plans C-L Sheets Posted 7-22-09.zip ZIP file
Plans A203-A402 Posted 7-22-09.zip ZIP file
Plans E301-E700 Posted 7-22-09.zip ZIP file
Plans G Sheets Posted 7-22-09.zip ZIP file
Plans C001-C401 Posted 7-22-09.zip ZIP file
Plans A901-A1102 Posted 7-22-09.zip ZIP file
Plans A101-A202b Posted 7-22-09.zip ZIP file
Plans M201A-M406 Posted 7-22-09.zip ZIP file
Plans S Sheets Posted 7-22-09.zip ZIP file
Plans A501-A605 Posted 7-22-09.zip ZIP file
List of Drawings -Tullahoma RC Project.pdf PDF
Plans S201A-S501 Posted 7-22-09.zip ZIP file
Plans S100A-S103 Posted 7-22-09.zip ZIP file
Plans ID101a-L102 Posted 7-22-09.zip ZIP file
Specifications document Posted 7-22-09.zip ZIP file
Plans E001-E203 Posted 7-22-09.zip ZIP file
Plans Cover Vol 1 2 Posted 7-22-09.zip ZIP file
Plans A101-A302 7-20-09.zip ZIP file
Plans C001-Cover Vol1 Vol 2.zip ZIP file
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Section /

Dwg.

Name

Para. /

Detail

1 000005 LIST OF DRAWINGS Dwg. Index

Add, "E3.02 MECH EQUIPMENT - SECOND FLOOR PLAN" and "E3.03

MECH EQUIPMENT VEHICLE MAINT BLDG FLOOR PLAN"

2 010100 SUMMARY OF WORK 1.1

Change to read, "Dwg.s, general provisions of the Contract, including Contract Clauses and other Division 1 specification sections, apply to work of this section.

3 010100 SUMMARY OF WORK 1.2.C Delete, "approximately 46,633 sf" and "approximately 3,193 sf."

4 010100 SUMMARY OF WORK 1.3.A

Add, "and Section 232113; including items such as ground boring, piping, valves, fittings, for water loop system of ground coupled water source heat pump, geothermal heat exchanger, hydronic piping, and other features as required for a complete and operable geothermal system. Delete 40’-0” x 30’-0” mechanical yard as shown on Dwg. C1.01."

5 010100 SUMMARY OF WORK 1.3.B

Add, "including items such as automatic activation, connection to building electrics, 8'-0" x 20'-0" concrete pad shown on Dwg. C1.01, 480/277V, 3-phase, 4-wire, 60 Hz, 0.8 power factor, and other features as required for a complete and operable emergency generator system."

6 010100 SUMMARY OF WORK 1.6.E

Delete the words "General and Supplementary Conditions" and insert "Contract Clauses" in their place.

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

7 010100 SUMMARY OF WORK 1.15.B Delete the word, "any"throughout the paragraph.

8 010100 SUMMARY OF WORK 1.16

Delete the words, "General Conditions" and insert "the Contract" in their place.

9 010300

SPECIAL PROJECT

PROCEDURES 1.1.A Change to read, "Refer to Section 013010."

10 010300

SPECIAL PROJECT

PROCEDURES 1.1.B

Delete article or paragraph and all subparagraphs, if any, in their entirety.

11 010300

SPECIAL PROJECT

PROCEDURES 1.1.C

Delete article or paragraph and all subparagraphs, if any, in their entirety.

12 010300

SPECIAL PROJECT

PROCEDURES 1.2

Delete article or paragraph and all subparagraphs, if any, in their entirety.

13 010300

SPECIAL PROJECT

PROCEDURES 1.3 In Article title change from "G702A"to "G703."

14 010300

SPECIAL PROJECT

PROCEDURES 1.3.A

Change from "G702A"to "G703"throughout the paragraph. Delete, "Within twenty (20) calendar days from Notice to Proceed."

15 010300

SPECIAL PROJECT

PROCEDURES 1.5 At the end of the paragraph, add, "unless indicated otherwise."

16 010370 WEATHER DELAYS 1.3.C

Change to read, "A Weather Delay Day may be counted if adverse weather prevents work on the project critical activities for fifty percent (50%) or more of the Contractor’s scheduled work day, including a weekend day or holiday if Contractor has scheduled construction activity that day."

17 012000 PROJECT MEETINGS 1.1

Delete article or paragraph and all subparagraphs, if any, in their entirety.

Hart Freeland Roberts, Inc.

Brentwood, TN Page 1 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

18 012000 PROJECT MEETINGS 1.4 Change from "G702A"to "G703"throughout the paragraph.

19 012000 PROJECT MEETINGS 1.6

Delete article or paragraph and all subparagraphs, if any, in their entirety.

20 013000 SUBMITTALS 1.1.A

In first sentence, change from " bi-weekly"to " as indicated." In second sentence, delete " bi-weekly."

21 013000 SUBMITTALS 1.1.B

Change second sentence to read, "Contractor shall utilize the latest edition of Prima Vera, Microsoft Project or other approved software for preparation of this schedule."

22 013000 SUBMITTALS 1.2.A Change from "G702A"to "G703"throughout the paragraph.

23 013000 SUBMITTALS 1.5.C.1 In first sentence, delete "where required."

24 013000 SUBMITTALS 1.5.C.2

Change from "Divisions 15 and 16"to "Divisions 21, 22, 23, 26, 27, and 28."Delete the word, " respectively."

25 013000 SUBMITTALS 1.5.G.2

Change from "Divisions 15 and 16"to "Divisions 21, 22, 23, 26, 27, and 28." Delete the word, "respectively."

26 013000 SUBMITTALS 1.5.K.4

Change from "Divisions 15 and 16"to "Divisions 21, 22, 23, 26, 27, and 28."Delete the word, "respectively."

27 013010

ADMINISTRATIVE

PROCEDURES 1.6 In Article title change from "G702A"to "G703."

ADMINISTRATIVE

Change days from "twenty (20)"to "five (5)."Change the third sentence to read, "The Government has determined that Primavera

Project Planner, Version 3.0 and Microsoft Project meet the

28 013010

ADMINISTRATIVE

PROCEDURES 1.4.A

Project Planner, Version 3.0 and Microsoft Project meet the minimum requirements." Delete the word, "his."

29 013010

ADMINISTRATIVE

PROCEDURES 1.5.A

Change days from "twenty (20)"to " five (5)."Change from " into CSI

16 Division"to " according to Project Manual Table of Contents."

30 013010

ADMINISTRATIVE

PROCEDURES 1.5.B

Change days from "twenty (20)"to " five (5)." Change from " into

CSI 16 Division"to " according to Project Manual Table of Contents."

31 013010

ADMINISTRATIVE

PROCEDURES 1.6.A Change from "G702A"to "G703"throughout the paragraph.

32 013010

ADMINISTRATIVE

PROCEDURES 3.1.A

In first sentence change days from " 10"to "two (2)." In second sentence change days from " 10"to "three (3)."

33 013010

ADMINISTRATIVE

PROCEDURES 3.1.B

Delete article or paragraph and all subparagraphs, if any, in their entirety.

34 013010

ADMINISTRATIVE

PROCEDURES 3.1.G

Change first sentence to read, "Submit revised schedules with each

Application for Payment and as indicated, identifying changes since previous version."

35 013400

SUBMITTAL

REQUIREMENTS

DWG

M2.01b Provide shop drawings for radiant floor heating system.

36 014000

QUALITY CONTROL

SERVICES 1.1

Delete the words "General and Supplementary Conditions" and insert "Contract Clauses" in their place.

38 017000 CONTRACT CLOSEOUT 1.3.A Change from "G702A"to "G703"throughout the paragraph.

NOT USED

Brentwood, TN Page 2 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

39 017000 CONTRACT CLOSEOUT 1.3.E Add, "Refer to Section 017300 for additional requirements."

40 017000 CONTRACT CLOSEOUT 1.3.G Add, "Refer to Section 017200 for additional requirements."

41 017200

PROJECT RECORD

DOCUMENTS 1.1.B.1

Change to read, "Documents affecting work of this Section include, but are not necessarily limited to, Contract Clauses and Sections in

Division 1 of these Specifications and Section 017000."

42 017200

PROJECT RECORD

DOCUMENTS 1.2.A Change from "General Conditions"to "Contract Clauses."

43 017300

OPERATION AND

MAINTENANCE DATA 1.1.B.1

Change to read, "Documents affecting work of this Section include, but are not necessarily limited to, Contract Clauses and Sections in

Division 1 of these Specifications and Section 017000."

44 017300

OPERATION AND

MAINTENANCE DATA 3.1.C.2 Change from "General Conditions"to "Contract Clauses."

45 034500

ARCHITECTURAL

PRECAST CONCRETE 2.9.B.1 Delete, "to match Contracting Officer's control sample(s). "

Change to read, "Color: Match PCI Plate 113

1. Color: Buff/Tan

2. Concrete Color: white

46 034500

ARCHITECTURAL

PRECAST CONCRETE 2.9.C

2. Concrete Color: white

3. Texture: Sandblasted

4. Exposure: Light

5. Description: Fine Aggregate: buff concrete sand;

6. Coarse Aggregate: 1/2 to 1/4 in. brown limestone;

7. Pigment: buff "

47 042000

UNIT MASONRY

ASSEMBLIES 2.1.E

Add, "4. Interior decorative CMU do not require integral water repellant and where painted may be manufacturer’s standard color."

48 042000

UNIT MASONRY

ASSEMBLIES 2.3.A

Change to read, "Single Wythe Joint Reinforcement: Ladder type, steel wire, hot dip galvanized to ASTM A153 Class B-2, 1.50 ounce hot-dipped zinc-coated after fabrication, No. 9 inch side rods with

No. 9 crossties at non-load bearing walls and 3/16” side rods with

No. 9 crossties at all load bearing walls; factory prefabricated corner and tee sections."

49 042000

UNIT MASONRY

ASSEMBLIES 2.3.B Change side rods from No. 9 to 3/16 inch.

50 042000

UNIT MASONRY

ASSEMBLIES 3.8.B

Change to read, "B. For running bond, install horizontal joint reinforcement dry before mortar is applied over it. Install joint reinforcing at 8” o.c. at load bearing walls and at 16” o.c. at non-load bearing walls. For stack bond, install horizontal joint reinforcement at 8 inches on center dry before mortar is applied over it."

Brentwood, TN Page 3 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

51 042300

GLASS UNIT

MASONRY 2.1

Add, "B. Interior Applications: Same pattern and size as exterior glass units, except delete white thermal insulation; add opaque finish where indicated on public (non-toilet) side. Provide opaque finish by acid etching, resulting in a satin (no fingerprint) sheen, uniform opaque appearance. As a performance alternative

Contractor may provide regular glass blocks with custom opaque inserts in color as selected by Contracting Officer."

52 042300

GLASS UNIT

MASONRY

2.1.A.3, 4, &

Change properties as follows: Insulation Value from " (U value): 0.51

BTU/sq ft/h/degree F"to " (R-value): 2.06," Visible Light

Transmittance from " 38 percent"to " 50-55%," and Shading

Coefficient: from " 0.65"to " 0.45."

Add, "J. Abrasive Nosings: Number 20 virgin grain aluminum oxide abrasive, integrally cast into walking surface, 1/32 inch deep minimum; feature strip along back edge; number 43 prime and secondary aluminum ingot, low copper content, shot blast finish;

1/16 inch deep cross hatching and fluting; minimum 4 inches wide;

full width of stair for concrete-filled pan stairs and stair width less

6” (3” on each end) for poured concrete stairs; maximum length possible without spliced joints. Drill for mechanical anchors and countersink. Locate not more than 4 inches (100 mm) from ends

53 055000 METAL FABRICATIONS 2.1

countersink. Locate not more than 4 inches (100 mm) from ends and not more than 12 inches (300 mm) o.c., evenly spaced between ends, unless otherwise indicated. Provide closer spacing if recommended by manufacturer. Provide anchors for embedding units in concrete, either integral or applied to units, as standard with manufacturer."

54 055000 METAL FABRICATIONS 3.2

Add, "E. Provide nosings on all interior cast-in-place stairs. Center nosings on tread widths. For nosings embedded in concrete steps or curbs, align nosings flush with riser faces and level with tread surfaces."

55 055100 METAL STAIRS 2.1

Add, "N. Nonslip-Aggregate Concrete Finish: Factory-packaged abrasive aggregate made from fused, aluminum-oxide grits or crushed emery; rustproof and nonglazing; unaffected by freezing, moisture, or cleaning materials."

56 055100 METAL STAIRS 2.1

Add, "O. Woven-Wire Mesh (Called out on Dwg.s as “Steel

Grating”): Intermediate-crimp, diamond square pattern, 2-inch (50-

mm) woven-wire mesh, made from 0.135-inch (3.5-mm) nominal diameter wire complying with ASTM A 510 (ASTM A 510M)."

57 055100 METAL STAIRS 2.4.B

At end of paragraph, add, "..and infill panels made from woven wire mesh crimped into 1-by-1/2-by-1/8-inch steel channel frames.

Orient wire mesh with diamonds vertical."

Brentwood, TN Page 4 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

58 055100 METAL STAIRS 3.2

Add, "G. Place and finish concrete fill for treads and platforms with nonslip-aggregate concrete finish to comply with Section 030500 -

Basic Concrete Materials and Methods."

59 072119

FOAMED-IN-PLACE

INSULATION 3

Add, "3.5 SCHEDULE

A. Exterior Walls: Provide foamed-in-place insulation in concrete masonry units in exterior walls and in locations as indicated on

Dwg.s."

Add, "3.5 SCHEDULE

B. Interior Walls and Partitions: Provide foamed-in-place insulation in all walls between spaces that are air conditioned and those that are heated and ventilated only. Provide interior foamed-in-place insulation in locations such as:

1. Assembly Hall 107, except walls adjacent to Break #3 B101, Table

Storage B111, 1175th Heated Storage 2312 C112, and 30th Heated

Storage 1000 C107;

2. Corridor 106, except wall adjacent to Break #3 B101;

3. Alcove C118;

4. Break #3 B101, except walls adjacent to Assembly Hall 107 and

60 072119

FOAMED-IN-PLACE

INSULATION 3

4. Break #3 B101, except walls adjacent to Assembly Hall 107 and

Corridor 106;

5. Table Storage B1111 in wall adjacent to Scullery B110;

6. Supply Officer C109 except wall adjacent to Supply Officer C110;

7. Supply Officer C110 except wall adjacent to Supply Officer C109;

8. Men’s Lockers C106 at wall adjacent to 30th Heated Storage 1000

C107 only;

9. Stairs 102;

10. Stairs 103; and

11. Maintenance Bay Office 301."

61 083323

OVERHEAD COILING

DOORS 2.1

Delete article or paragraph and all subparagraphs, if any, in their entirety.

62 083459 VAULT DOORS 1.3.B

Add, "Include product data and operational videotapes or DVD’s on locks, security safe, and security cabinet."

Brentwood, TN Page 5 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

Change to read, "“X-09 High Security Lock” with the “CDX-09 High

Security Pedestrian Exit Device” by Kaba Mas Corporation, Lexington, KY (no substitutions); Meet Federal Specification FF-L-

2740A; tamper-resistant, electromechanical lock with companion strike and lever handle exit device and the following features:

1. Power: Internal, self-powered by “PowerStar” technology, which uses an internal generator that creates all necessary power. No batteries or external wiring required.

2. Three Modes of Operation: 1. Single Combination Mode (1 million combinations) – allows access by dialing a six-digit combination; 2. Dual Combination Mode (500 billion combinations) allows access only when two separate codes are entered within 40 seconds of one another; 3. Supervisor / Subordinate Mode (2 million combinations) – allows access by a subordinate’s code only after a supervisor’s code has been entered.

3. LCD: Limited View Liquid Crystal Display with indicator arrows make dialing easy and exact.

4. Audit: Records all openings and the record is non-resettable.

Records unsuccessful attempts after 3 incorrect combination attempts and resets after a correct opening.

63 083459 VAULT DOORS 2.2.D

attempts and resets after a correct opening.

5. Door Prep: Designed to fit industry standard mounting pattern."

64 083459 VAULT DOORS 2.2.J

Add, "J. Security Key Safe: One-drawer, field safe, special letter size cabinet in grey color, base plate to secure safe to floor and six supplementary control containers; meet FS AA-F-358 H class 6;

1. “Model 7110-00-919-9306,” “Model 489-1-1 Base Plate,” and

“Model 489-102 Control Container” by Hamilton Products Group, Inc., Amelia, OH or approved substitution.

2. Lock: “Model 8560” by Sargent and Greenleaf (no substitutions)."

65 083459 VAULT DOORS 2.2.K

Add, "K. Security Cabinet: Five-drawer, grey unit, one lock on control drawer secures all drawers, meet FS AA-F-358 H class 6;

1. “Model 7110-00-919-9193” by Hamilton Products Group, Inc., Amelia, OH or approved substitution.

2. Lock: Meet FS FF-L-2740; “X-09 High Security Lock” ” by Kaba Mas

Corporation, Lexington, KY (no substitutions)."

66 083459 VAULT DOORS 3.2.C

Add, "C. Install security key safe and cabinet inside vault according to manufacturer's requirements in location as directed by

Contracting Officer’s Representative."

67 083614

STEEL SECTIONAL

OVERHEAD DOORS 2.1

Delete article or paragraph and all subparagraphs, if any, in their entirety.

68 NOT USED

Brentwood, TN Page 6 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

Under Set #22 - Office, after "Provide one Combination Lock at

D114 only"Add, "..as follows: “X-09 High Security Lock” with the

“CDX-09 High Security Pedestrian Exit Device” by Kaba Mas

Corporation, Lexington, KY (no substitutions); meet Federal

Specification FF-L-2740A; the tamper-resistant, electromechanical lock with companion strike and lever handle exit device and the following features:

1. Power: Internal, self-powered by “PowerStar” technology, which uses an internal generator that creates all necessary power. No batteries or external wiring required.

2. Three Modes of Operation: 1. Single Combination Mode (1 million combinations) – allows access by dialing a six-digit combination; 2. Dual Combination Mode (500 billion combinations) allows access only when two separate codes are entered within 40 seconds of one another; 3. Supervisor / Subordinate Mode (2 million combinations) – allows access by a subordinate’s code only after a supervisor’s code has been entered.

3. LCD: Limited View Liquid Crystal Display with indicator arrows make dialing easy and exact.

69 087100 DOOR HARDWARE 3.5

make dialing easy and exact.

4. Audit: Records all openings and the record is non-resettable.

Records unsuccessful attempts after 3 incorrect combination attempts and resets after a correct opening.

5. Door Prep: Designed to fit industry standard mounting pattern."

70 092116

GYPSUM BOARD

ASSEMBLIES 1.1.D Change to read, "Metal channel ceiling and soffit framing."

71 092116

GYPSUM BOARD

ASSEMBLIES 2.3

Add, "L. Continuous Soffit Vents: Aluminum, hat-channel shape, with stamped louvers or perforations; 2 inches (51 mm) wide and not less than 96 inches (2438 mm) long.

1. Net-Free Area: 6 sq. in./linear ft. (420 sq. cm/m).

2. Finish: White paint."

72 092116

GYPSUM BOARD

ASSEMBLIES 2 Add, "2.5 SUSPENSION SYSTEMS"

Brentwood, TN Page 7 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

73 092116

GYPSUM BOARD

ASSEMBLIES 2

Add, "2.5.A. Hanger Attachments to Concrete:

1. Anchors: Fabricated from corrosion-resistant materials with holes or loops for attaching wire hangers and capable of sustaining, without failure, a load equal to 5 times that imposed by construction as determined by testing according to ASTM E 488 by an independent testing agency.

2. Powder-Actuated Fasteners: Suitable for application indicated, fabricated from corrosion-resistant materials with clips or other devices for attaching hangers of type indicated, and capable of sustaining, without failure, a load equal to 10 times that imposed by construction as determined by testing according to ASTM E 1190 by an independent testing agency."

74 092116

GYPSUM BOARD

ASSEMBLIES 2

Add, "2.5.B. Wire Hangers: ASTM A 641/A 641M, Class 1 zinc coating, soft temper, 0.162-inch (4.12-mm) diameter.

C. Carrying Channels: Cold-rolled, commercial-steel Dwg. with a base-metal thickness of 0.0538 inch (1.37 mm) and minimum 1/2-inch- (12.7-mm-) wide flanges.

1. Depth: 2-1/2 inches (64 mm)."

Add, "2.5.D. Furring Channels (Furring Members):

75 092116

GYPSUM BOARD

ASSEMBLIES 2

Add, "2.5.D. Furring Channels (Furring Members):

1. Cold-Rolled Channels: 0.0538-inch (1.37-mm) bare-steel thickness, with minimum 1/2-inch- (12.7-mm-) wide flanges, 3/4 inch (19.1 mm) deep.

2. Steel Studs: ASTM C 645.

a. Minimum Base-Metal Thickness: 0.0312 inch (0.79 mm).

b. Depth: 3-5/8 inches (92.1 mm).

3. Hat-Shaped, Rigid Furring Channels: ASTM C 645, 7/8 inch (22.2

mm) deep.

a. Minimum Base Metal Thickness: 0.0312 inch (0.79 mm).

4. Resilient Furring Channels: 1/2-inch- (12.7-mm-) deep members designed to reduce sound transmission.

a. Configuration: Asymmetrical or hat shaped."

76 092116

GYPSUM BOARD

ASSEMBLIES 3.2

Change title of Artilce from " METAL STUD INSTALLATION"to "

METAL FRAMING INSTALLATION."

77 092116

GYPSUM BOARD

ASSEMBLIES 3.5

Change title of Article from "CEILING FRAMING INSTALLATION"to

"CEILING FRAMING AND SUSPENSION SYSTEM INSTALLATION."

Brentwood, TN Page 8 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

Add, "H. Suspend hangers from building structure as follows.

1. Install hangers plumb and free from contact with insulation or other objects within ceiling plenum that are not part of supporting structural or suspension system.

a. Splay hangers only where required to miss obstructions and offset resulting horizontal forces by bracing, countersplaying, or other equally effective means.

2. Where width of ducts and other construction within ceiling plenum produces hanger spacings that interfere with locations of hangers required to support standard suspension system members, install supplemental suspension members and hangers in the form of trapezes or equivalent devices.

a. Size supplemental suspension members and hangers to support ceiling loads within performance limits established by referenced installation standards.

3. Wire Hangers: Secure by looping and wire tying, either directly to structures or to inserts, eye screws, or other devices and fasteners that are secure and appropriate for substrate, and in a manner that will not cause hangers to deteriorate or otherwise fail.

4. Do not attach hangers to permanent metal forms. Furnish cast-in-

78 092116

GYPSUM BOARD

ASSEMBLIES 3.5

4. Do not attach hangers to permanent metal forms. Furnish cast-in-place hanger inserts that extend through forms.

5. Do not attach hangers to rolled-in hanger tabs of composite steel floor deck.

6. Do not connect or suspend steel framing from ducts, pipes, or conduit."

79 092116

GYPSUM BOARD

ASSEMBLIES 3.5.A

At end of paragraph Add, " but not less than those required by referenced installation standards for assembly types and other assembly components indicated. "

80 092116

GYPSUM BOARD

ASSEMBLIES 3.5.C

Add, "Isolate suspension systems from building structure where they abut or are penetrated by building structure to prevent transfer of loading imposed by structural movement."

81 092116

GYPSUM BOARD

ASSEMBLIES 3.5.G

Add, "Sway-brace suspension systems with hangers used for support."

82 092116

GYPSUM BOARD

ASSEMBLIES 3.7.L Add, "Install continuous soffit vents."

Brentwood, TN Page 9 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

83 096500 RESILIENT FLOORING 2.4

Add, "2.4 MATERIALS – STATIC DISSIPATIVE VINYL COMPOSITION

TILE FLOORING

A. Vinyl-Composition Tile: ASTM F1066, Class 2, asbestos-free;

design and color as selected by Contracting Officer's Representative from manufacturer's premium range.

1. Size: 12 x 12 inch, +/- 0.016 inch in 12 inches.

2. Out of Squareness: 0.010 inch maximum.

3. Thickness: 1/8 inch thick, +/- 0.005 inch.

4. Electrical Resistance:

a. PTP: 1.1 X 107 to 5.5 X 109 @100 Volts

b. RTG: 1.1 X 106 to 8.5 X 108 @100 Volts"

Add, "3.7 INSTALLATION – STATIC DISSIPATIVE FLOORING

A. Install static-control resilient floor covering according to manufacturer's written instructions and with oversight by manufacturer's representative.

B. Embed grounding strips in static-control adhesive. Extend grounding strips beyond perimeter of static-control resilient floor covering surfaces to ground connections.

C. Adhere floor coverings to substrates using a full spread of static-control adhesive applied to substrate to produce a completed

84 096500 RESILIENT FLOORING 3.7

control adhesive applied to substrate to produce a completed installation without open cracks, voids, raising and puckering at joints, telegraphing of adhesive spreader marks, and other surface imperfections.

D. Scribe and fit to door frames and other obstructions."

85 101300 DIRECTORIES 2.1.A.2

Change to read, "Format: Header row with two 11-inch wide vertical divider columns to accommodate 92 strips."

86 101300 DIRECTORIES 2.1.A.5 Change to read, "Size: Nominally 36” wide x 28” high x 6” deep."

87 101300 DIRECTORIES 2.1.A.11 Change to read, "Mounting Type: Pedestal mount."

88 101300 DIRECTORIES 2.1.D.1 Change letter height from 3/8"to 1/2"

89 101300 DIRECTORIES 3.2.B Change first sentence to read, "Mount directories on floor."

90 101300 DIRECTORIES 3.2.C

Delete, "Mount directories 60 inches from finished floor to centerline of sign."

91 101400 SIGNAGE 2.1.B Delete paragraph and sub-paragraphs underneath.

92 101400 SIGNAGE 2.2.A.1 Change metal from bronze to aluminum.

93 101400 SIGNAGE 2.2.A

Add, "6. Design: Provide Tennessee state patch and National Guard logos per Dwg.s."

Brentwood, TN Page 10 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

94 101400 SIGNAGE 2.3

Add, "B. Cut letters and numbers from solid plate material of thickness indicated. Produce precisely cut characters with square cut, smooth edges.

1. Metal: Aluminum.

2. Color(s): As selected by Contracting Officer from manufacturer's full range.

3. Mounting: Concealed studs, noncorroding for substrates encountered."

95 101400 SIGNAGE 2.7.B Delete paragraph and sub-paragraphs underneath.

96 101400 SIGNAGE 2.7

Add, "C. Aluminum Finish: Superior performance organic coating meeting AAMA 2605-98; cleaned with chromium phosphate pretreatment, primed to 0.2 min. mil dry film thickness with inhibitive thermo-cured primer and 1.2 min. mil dry film thickness, thermo-cured, 2-coat fluoropolymer coating produced with minimum 70 percent resin; color as selected by Contracting Officer from manufacturer's premium range."

97 102800 TOILET ACCESSORIES 2.4 After Article title, PAPER TOWEL DISPENSERS, add " (PTD & PT)"

98 102800 TOILET ACCESSORIES 2.5

After Article title, SANITARY (FEMININE) NAPKIN DISPOSAL UNITS, add " (FNDU & FN)" 98 102800 TOILET ACCESSORIES 2.5 add " (FNDU & FN)"

99 102800 TOILET ACCESSORIES 2.6 After Article title, TOILET PAPER DISPENSERS, add " (PTD & PT)"

100 102800 TOILET ACCESSORIES 2.7 After Article title, GRAB BARS , add " (GB & HCGB)"

101 102800 TOILET ACCESSORIES 2.8 After Article title, SOAP DISPENSERS, add " (SD & LS)"

102 102800 TOILET ACCESSORIES 2.9.A

After Article title, MIRRORS, add " (MR & MIR-36)"At end of paragraph Add, "provide mirrors with one piece shelf assembly in locations as indicated, with 5 inch projection, 3/4 inch return edges on front and sides, front return edge hemmed, 22 gage."

103 102800 TOILET ACCESSORIES 2.10

After Article title, SHOWER COMPONENTS, add, "(SCR & CR)." In paragraph B, at beginning of paragraph Add, "Provide each curtain rod with…"Add, "C. Curtains by Government."

104 102800 TOILET ACCESSORIES 2.12

Change paragraph A to read, "Hat, Robe, and Coat Hook Units (HH):

Concealed Mount Heavy Duty Hook: One-piece brass casting with satin nickel- plated finish; 12 gage, concealed, steel mounting plate;

supports 300 pounds minimum downward pull."Add, "B. Robe, Towel, and Clothing Hook Units (RH): Surface Mount Single Robe

Hook: 2 inches wide, 304 stainless steel, with flange and 16 gage mounting bracket which locks to concealed 16 gage wall plate with

304 stainless steel wall plate."

105 102800 TOILET ACCESSORIES 2.13 After Article title, JANITOR’S ACCESSORIES , add " (BH)"

106 102800 TOILET ACCESSORIES 2.14 Change Article title to read, "UNDER LAVATORY GUARD (UG)."

Brentwood, TN Page 11 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

107 102800 TOILET ACCESSORIES 2.15

Add, "2.15 FOLDING SHOWER SEAT (SS & FS)

A. Folding Shower Seat, Handicap: L-Shape, one-piece water resistant, ivory colored solid phenolic or teakwood, 1/2"thick; 16 gage 304 stainless steel frame and guide bracket; left-hand or right-hand configuration as indicated on Dwg.s. Provide support for 250 pound load. Padded cushion type seat will not be permitted."

108 114000

FOOD SERVICES

EQUIPMENT 3.5

Everywhere in the Remarks column, delete, " (nc)" and " 1 ea. One year parts & labor from date of installation (nc). 1 ea. One year parts & 90 day labor on chemical dispensing equipment (nc)."

109 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 30, Dishwashing Machine, under Remarks column, delete, "

**BY OTHERS**EXTRA RACKS Extended Total for Item No. 30."

FOOD SERVICES

Item 40, Spray Assembly, under Remarks column, change

Acceptable Manufacturer to read, "1 ea. Pre-Rinse Unit; T & S Brass

Model No. B-0133-B 12 lbs. total Class: 77.5; EasyInstall Pre-Rinse

Unit, wall mount. Base faucet w/spring check cart. & lever handles

2" dia., flanges w ½ NPT female eccentric flanged inlets, 35-½" H, 15" overhang, 8-¼ clear, 18" riser, B-0107 spray valve, B-0044-H flex

110 114000

FOOD SERVICES

EQUIPMENT 3.5

15" overhang, 8-¼ clear, 18" riser, B-0107 spray valve, B-0044-H flex s/s hose, 6" wall bracket."

111 114000

FOOD SERVICES

EQUIPMENT 3.5

In Remarks column, add, "Custom fabricated to configuration as indicated on Dwg.s; 30" wide."

112 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 45, Kettle, under Remarks column, delete, " 1 ea. Standard one year limited warranty (nc)."

113 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 46, Pan, under Remarks column, delete, " 1 ea. Standard one year limited warranty (nc)."

114 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 48, Range, under Remarks column, delete, " 1 ea. Standard one year limited warranty (range) (nc)."

115 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 49, Oven, under Remarks column, delete, "Accessories: 2 ea.

NOTE: Contact factory for pricing on option and accessories," " 1

ea. Standard one year limited warranty (nc)," and " *** NOT

AVAILABLE*** STAINLESS STEEL INTERIOR OVEN LINER."

116 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 55, Vegetable Peeling Machine, under Remarks column, delete, " 1 ea. One year parts & labor from date of installation (nc)."

117 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 67, Frozen Food Cabinet, under Remarks column, delete, " 4-doors," " 1 ea. 5-yr. compressor warranty within the USA, valued at

$80.00 net included in equipment price" and " 1 ea. V2E Full 2-year parts/labor service warranty within the USA valued at #135 net included in equipment price, std."Change from " Hemetcally"to "

Hermetically."

Brentwood, TN Page 12 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

118 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 68, Refrigerator, under Remarks column, delete, " 1 ea. 5-yr.

compressor warranty within the USA, valued at $80.00 net included in equipment price 1 ea. V2E Full 2-year parts/labor service warrant within the USA valued at $135.00 net included in equipment price, std."

119 114000

FOOD SERVICES

EQUIPMENT 3.5

Item 69, Refrigerator, under Remarks column, delete, " 1 ea. 5-yr.

compressor warranty within the USA, valued at $80.00 net included in equipment price 1 ea. V2E Full 2-year parts/labor service warrant within the USA valued at $135.00 net included in equipment price, std."

120 210100

FIRE PROTECTION

GENERAL PROVISIONS

NEW

SECTION

Add Section to Project Manual and make appropriate changes to

Table of Contents

121 220100

PLUMBING GENERAL

PROVISIONS 1.8.A Change from " final acceptance"to "Substantial Completion."

122 220100

PLUMBING GENERAL

PROVISIONS 1.9.A Change from " final inspection"to "Substantial Completion."

123 221516

GENERAL SERVICE

COMPRESSED AIR

PIPING AND VALVES

NEW

SECTION

Add Section to Project Manual and make appropriate changes to

Table of Contents123 221516 PIPING AND VALVES SECTION Table of Contents

124 224213

COMMERCIAL

PLUMBING FIXTURES 2 Delete P-17

125 224213

COMMERCIAL

PLUMBING FIXTURES 2 Change P-23 to read, "Planter Drain: Zurn Z352."

126 230100

GENERAL PROVISIONS

OF HVAC SYSTEMS 1.3.C

Change from " review of Designer"to " written approval from

Contracting Officer’s Representative."

127 230100

GENERAL PROVISIONS

OF HVAC SYSTEMS 1.7.A

Delete 2.b in its entirety; delete the words "steam distribution and chilled water" from 2.d and replace with "Piping"

128 230100

GENERAL PROVISIONS

OF HVAC SYSTEMS 1.8.A Change from " final acceptance"to "Substantial Completion."

129 230100

GENERAL PROVISIONS

OF HVAC SYSTEMS 1.9.A Change from " final inspection"to "Substantial Completion."

130 230100

GENERAL PROVISIONS

OF HVAC SYSTEMS 1.9.A.3 Delete the words " Videotape" and replace with "DVD."

Brentwood, TN Page 13 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

131 230710 INSULATION 2.3

Add, "I. For externally insulated sheet metal ducts when above grade exposed-to-the-weather outside building, cover duct insulation with two coats of weather protective and vapor barrier coating equivalent to Childers Encacel having proven ability to withstand a wide range of temperatures without cracking or crazing and that is highly resistant to damage by bumping and abrasion.

Product color to be white unless otherwise noted. Apply coating in accordance with manufacturers’ published instructions using first coat reinforced with glass cloth and final coat to provide minimum

30 mil thick smooth surface free of voids. Contractor Para. to wrap externally insulated sheet metal ducts with 60 mil EPDM rubber roofing material equal to Carlisle "Sure-Seal." Material to be white in color. All longitudinal seams to be on underside of duct. Seams are to be sealed per manufacturer's installation instructions."

132 230923

DIRECT DIGITAL

CONTROL/BUILDING

AUTOMATION

SYSTEM (DDC/BAS)

RE-ISSUE

SECTION

Delete Section as previously issued and replace with the attached

Section.

HYDRONIC

133 232120

HYDRONIC

SPECIALTIES 1.1.A Replace the word "Compression" with " Expansion."

134 232120

HYDRONIC

SPECIALTIES 2.1.A Add the company "Spirotherm" as acceptable manufacturer.

135 232120

HYDRONIC

SPECIALTIES 2.2 Replace the word "Compression" with " Expansion" in Para. A.

136 232120

HYDRONIC

SPECIALTIES 2.2.C

Change to read "Air and Dirt Separator" ; in Para. C.2 delete, "tangential" ; in Para. C.3, change to read, "Design internal air collector tube to direct released air into expansion tank." ; Para. C.6 should read "Provide dirt dirt collection chamber and blowdown connection on bottom of unit to facilitate routine cleaning of unit" ;

and in Para. C.8, replace the words "Bell & Gossett ITT Rolairtrol" with "Spirotherm 'Spirovent Dirt'."

137 233310

SHEET METAL

SPECIALTIES 2.3

Delete article or paragraph and all subparagraphs, if any, in their entirety.

138 233310

SHEET METAL

SPECIALTIES 2.9

Add article entitled "CEILING FILTER GRILLE A. Provide Titus 50-FF or approved equal filter grille at all locations indicated on drawings.

Grilles to be complete with 1/2" cube eggcrate aluminum grid, hinged face and frame to hold 1"thick filter. Finish to be baked-on, off-white enamel. Border to be lay-in style for T-bar lay-in ceilings and surface style for rigid ceilings or exposed application. Filters to be 1"thick, 30 percent medium-efficiency Farr 30/30 or approved equal disposable type."

Brentwood, TN Page 14 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

139 233813

KITCHEN HOOD AND

FIRE PROTECTION

SYSTEM 1.1

Add, "F. Provide water washdown system complete with controls and cabinet. System to serve all hoods," and "G. Provide fan speed control and heat sensors."

140 233813

KITCHEN HOOD AND

FIRE PROTECTION

SYSTEM 1.2.A

Change first sentence to read, "A. Submit complete hood, fan, water washdown, and fire protection system shop drawings, wiring and control diagrams, and test and balance report to Designer for approval."

141 235733

GEOTHERMAL HEAT

EXCHANGER TITLE

Add the phrase " - OPTION NO. I"to the end of the section title and update footer and Table of Contents

142 237511

100% OUTSIDE AIR

ROOFTOP UNITS

NEW

SECTION

Add Section to Project Manual and make appropriate changes to

Table of Contents

143 238146

WATER SOURCE HEAT

PUMPS 2.7 Change from "Control panel"to "Unit."

144 238146

WATER SOURCE HEAT

PUMPS 2.9

Change to read, "2.9 Provide terminal strip for connection to DDC controller provided by TAC Controls."

145 238146

WATER SOURCE HEAT

PUMPS 2.11 Delete paragraph and sub-paragraphs underneath.

146 238146

WATER SOURCE HEAT

PUMPS 2.12 Delete paragraph and sub-paragraphs underneath.

WATER SOURCE HEAT Add, "Provide two-position automatic valve interlocked to shut off

147 238146

WATER SOURCE HEAT

PUMPS 2.14

Add, "Provide two-position automatic valve interlocked to shut off water when compressor is de-energized."

148 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 1.4.D Change from "Architect"to "Contracting Officer’s Representative."

149 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 1.5.C

Change from " Engineer's"to "Contracting Officer’s

Representative’s."

150 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 1.6.A Change from " final acceptance"to "Substantial Completion."

151 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 3.5.C

Change from " final observation and acceptance"to "Substantial

Completion."

152 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 3.9.A

Change to read, "Contracting Officer’s Representative’s office may provide periodic observation of the progress of work specified herein. Contracting Officer’s Representative’s office may also observe tests required of Contractor as called for in other sections of specifications."

153 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 3.9.B Delete last sentence.

154 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 3.9.C Change from " Engineer"to "Contracting Officer’s Representative."

Brentwood, TN Page 15 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

155 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 3.9.D Delete paragraph and sub-paragraphs underneath.

156 260100

GENERAL PROVISIONS

FOR ELEC SYSTEMS 3.10.B

Change from " final acceptance, whichever is earliest"to

"Substantial Completion" and delete the word, " any."

157 260526

GROUNDING AND

BONDING FOR ELEC

SYSTEMS 3.1.E Change from " Engineer"to "Contracting Officer’s Representative."

158 263213

EMERGENCY

STANDBY ENGINE

GENERATOR SYSTEM 1.1.A Change from "Alternate No. 3"to " Option No. 2 ."

159 263213

EMERGENCY

STANDBY ENGINE

GENERATOR SYSTEM 1.1.D

Change from " date of Owner's acceptance of equipment"to

"Substantial Completion ."

160 263213

EMERGENCY

STANDBY ENGINE

GENERATOR SYSTEM 2.2.A Change from " natural gas"to " full diesel."

161 263213

EMERGENCY

STANDBY ENGINE

GENERATOR SYSTEM 2.3.B

Delete, "Vendor shall consult with and coordinate special extreme cold weather needs with Electrical Engineer. " 161 263213 GENERATOR SYSTEM 2.3.B cold weather needs with Electrical Engineer. "

162 263213

EMERGENCY

STANDBY ENGINE

GENERATOR SYSTEM 2.6.A

Change to read, "Subbase Fuel Tank: Provide a 72-hour subbase fuel tank and associated fuel line connection."

163 263213

EMERGENCY

STANDBY ENGINE

GENERATOR SYSTEM 3.1.E

Change from "After Owner acceptance"to "Before Substantial

Completion" and delete "and/or vendor."

164 264113

LIGHTNING

PROTECTION 3.1.A Change from "Architect"to "Contracting Officer’s Representative."

165 264113

LIGHTNING

PROTECTION 3.1.C

Change second sentence to read, "At Substantial Completion provide a copy of such application to Contracting Officer’s

Representative."

166 265100

INTERIOR LIGHTING

AND LAMPS 2.1.A

Change to read, "Provide lighting fixtures indicated by type on lighting fixture schedule on Dwg.s or approved substitution."

167 265600

EXTERIOR LIGHTING

AND LAMPS 1.2.B

Change to read, "submit a sample fixture which will be returned after review."

168 265600

EXTERIOR LIGHTING

AND LAMPS 1.2.C Delete paragraph.

169 265600

EXTERIOR LIGHTING

AND LAMPS

2.1.A &

2.1.C At end of sentence Add, "or approved substitute."

170 271004 TELEPHONE SERVICE

RE-ISSUE

SECTION

Delete Section 271004 as previously issued and subsitute the attached Section 271004 in its place.

171 271006

MATV/CATV CABLE

SYSTEM

NEW

SECTION

Add Section to the Project Manual and make the appropriate change to the Table of Contents.

Brentwood, TN Page 16 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

172 271500

STRUCTURED VOICE

AND DATA CABLING

INFRASTRUCTURE

NEW

SECTION

Add Section to the Project Manual and make the appropriate change to the Table of Contents.

173 275112

BACKGROUND

MUSIC/PAGING

SYSTEM

NEW

SECTION

Add Section to the Project Manual and make the appropriate change to the Table of Contents.

174 323113

CHAIN LINK FENCES

AND GATES

RE-ISSUE

SECTION

Delete Section 323113 as previously issued and subsitute the attached Section 323113 in its place.

175 323120

SECURITY METAL

FENCES AND GATES

RE-ISSUE

SECTION

Delete Section 323120 as previously issued and subsitute the attached Section 323120 in its place.

176 G1.01 GENERAL DATA Dwg. Index

Add, "E3.02 MECH EQUIPMENT - SECOND FLOOR PLAN" and " E3.03

MECH EQUIPMENT VEHICLE MAINT BLDG FLOOR PLAN"

G2.01 &

G2.02 LIFE SAFETY PLANS

Wall

Description

Symbols

Under new 1-hour CMU, fill in the blank beside the U.L. number with " U905."

G2.01 &

G2.02 LIFE SAFETY PLANS

Wall

Description

Symbols Under new 2-hour CMU, change from " UBC"to " IBC."

CIVL SITE NOTES AND

DRAINAGE

Erosion

Siltation

Control

179 C0.01

DRAINAGE

STRUCTURES

Control

Notes Note 31, add, "…and as indicated on Dwg. L1.02."

180 C0.01

CIVL SITE NOTES AND

DRAINAGE

STRUCTURES

Stormwater

Pollution

Prevention

Notes Note 13, add, "…except as indicated on Dwg. L1.02."

181 C0.01.01

CIVIL SITE NOTES AND

DRAINAGE

STRUCTURES SWPP Notes Change Dwg. per attached Supplemental Dwg.

182 C1.01.01 SITE PLAN Site Plan Change Dwg. per attached Supplemental Dwg.

183 C1.01.02 SITE PLAN Site Plan Change Dwg. per attached Supplemental Dwg.

184 C1.01.03 SITE PLAN Site Plan Change Dwg. per attached Supplemental Dwg.

C2.01.C0

GRADING AND

DRAINAGE PLAN

ENLARGEMENT Site Plan Change Dwg. per attached Supplemental Dwg.

186 C3.01.01 SITE DETAILS Detail 13 Change Dwg. per attached Supplemental Dwg.

187 C3.01.02 SITE DETAILS Detail 3 Change Dwg. per attached Supplemental Dwg.

Brentwood, TN Page 17 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

188 C3.02 SITE DETAILS Detail 4

Change “8’ Fence With Barbed Wire” to “6’ Fence with Barbed

Wire.” At corner and terminating post concrete footings, change dimensions from those indicated to 16 inch minimum diameter and

52 inch depth. At line post concrete footings, change dimensions from those indicated to 12 inch minimum diameter and 40 inch minimum depth. At all footings provide minimum 4" between end of post and bottom of footing.

189 C3.02.01 SITE DETAILS

Entrance

Sign Detail Change Dwg. per attached Supplemental Dwg.

190 C3.04.01 SITE DETAILS

Detail 4

Riser/Berm

Detail Change Dwg. per attached Supplemental Dwg.

191 C3.04.02 SITE DETAILS Detail 13 Change Dwg. per attached Supplemental Dwg.

192 C3.05.01 SITE DETAILS

Detail 1

Equipment

Pad Change Dwg. per attached Supplemental Dwg.

193 C3.05.02 SITE DETAILS

Detail 2, Plan &

Elevation Change Dwg. per attached Supplemental Dwg.193 C3.05.02 SITE DETAILS Elevation Change Dwg. per attached Supplemental Dwg.

194 C3.05.03 SITE DETAILS

Detail 2, Section Change Dwg. per attached Supplemental Dwg.

195 C4.01.01 UTILITY PLAN Site Plan Change Dwg. per attached Supplemental Dwg.

196 L1.01 PLANTING PLAN

Planting

Plan

At the entrance sign, add the note, " do not locate plants such that site sign will be blocked from view when plants reach maturity."

197 L1.02 PLANTING PLAN

General

Notes Note 12: At end of sentence, delete “tions.”

198 L1.02 PLANTING PLAN

General

Notes

Note 13: Change from “Owner and Landscape Architect” to

“Contracting Officer.”

199 L1.02 PLANTING PLAN

General

Notes

Note 3: Change to read, “Observation: Contracting Officer's

Representative may observe trees and shrubs either at place of growth or at site before planting for compliance with requirements for genus, species, variety, size, and quality. Contracting Officer's

Representative retains the right but not a duty to observe trees and shrubs further for size and condition of balls and root systems, insects, injuries, and latent defects and to reject unsatisfactory or defective material at any time during progress of work. Remove rejected trees or shrubs immediately from Project site. Notify

Contracting Officer's Representative of sources of planting materials seven days in advance of delivery to site.”

200 L1.02 PLANTING PLAN

General

Notes

Note 4: In second sentence, change from “Owner and Landscape

Architect” to “Contracting Officer.”

Brentwood, TN Page 18 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

201 A1.01 FIRST FLOOR PLAN

Floor Plan

General

Notes Add, "5. At Recycle Bin area, bins are not in Contract."

202 A1.01 FIRST FLOOR PLAN

Floor Plan

General

Notes

Add, "6. In addition to foamed-in-place insulation already required for CMU in exterior walls, provide foamed-in-place insulation in all walls between spaces that are air conditioned and those that are heated and ventilated only."

203 A1.01 FIRST FLOOR PLAN

Floor Plan

General

Notes

Add, "7. In kitchen, toilets, and other areas with floor drains, slope floor to floor drains for drainage."

204 A1.01.01 FIRST FLOOR PLAN Floor Plan Change Dwg. per attached Supplemental Dwg.

A2.01a, b, c, & d QUADRANT PLANS Floor Plans

Change key note designations on floor plans from "CT"to "PT"to indicate paper towel dispenser; from " MS"to "SS"to indicate stainless steel shelving (not in contract); and from " MT"to " MR"to indicate a mirror.

After indication for TT, toilet tissue (roll) dispenser, add, "indicated as 'TPD' on A9.01."After indication for PT, paper towel (folded) dispenser, add, "indicated as 'PTD' on A9.01."After indication for LS, liquid soap dispenser, add, "indicated as 'SD' on A9.01."After indication for GB, grab bar, add, "indicated as 'HCGB' on

A2.01a, b, c, & d

AND

A2.02a

QUADRANT PLANS &

ENLARGED SECOND

FLOOR PLAN W/

CANOPY

Abbrev

Keynotes indication for GB, grab bar, add, "indicated as 'HCGB' on

A9.01."Change indication for MR to read, "mirror unit; see A9.01 for locations with stainless steel shelf."After indication for CR, shower curtain rod, add, "indicated as 'SCR' on A9.01."Delete "SS Soap

Dish."After indication for SS, stainless steel shelving, N.I.C., add, "indicated as 'SSS' on A9.01."After indication for FN, feminine napkin disposal, add, "indicated as 'FNDU' on A9.01."Correct spelling error at " TR" from "trans"to "trash."Add, "FS - Folding

Shower Seat."

207 A2.01a QUADRANT PLAN 'A'

Floor Plan

Keynotes Note 12, change walk off mat size from 6'-0" x 4'-0"to 6'-0" x 6'-0" .

208 A2.01a QUADRANT PLAN 'A' Floor Plan

In Space Fac. Maint. #1 B112, delete the interior elevation flag, 6/A9.02.

209 A2.01a QUADRANT PLAN 'A' Floor Plan

At elevator shaft, change fire wall designation from 1-hour rated to

2-hour rated.

210 A2.01b QUADRANT PLAN 'B' Floor Plan

In Kitchen B107 at sink, add liquid soap disenser (LS) and paper towel dispenser (PT).

211 A2.01b

QUADRANT PLAN 'B'

Kitchen Equipment

Kitchen

Equipment

Keynotes

Add the General Note, " Refer to Section 114000 for indication of

Contractor-Provided and Government-Furnished, Contractor-

Installed items."

212 A2.01b

QUADRANT PLAN 'B'

Kitchen Equipment

Kitchen

Equipment

Keynotes

In Note 5 delete the words, " double bowl" and in Note 42 change the word, " window"to " counter."

213 A2.01b

QUADRANT PLAN 'B'

Kitchen Equipment Floor Plan Delete note regarding air compressor connection.

Brentwood, TN Page 19 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

214 A2.01c QUADRANT PLAN 'C' Floor Plan

In Physical Fitness C116, on plan east wall, add note, "Provide mirrors, full height and full width of wall."

215 A2.01c QUADRANT PLAN 'C' Floor Plan

In F. Lockers C101, in lower left-hand corner of space, at dashed square indication, add, "TR."

216 A2.01c QUADRANT PLAN 'C' Floor Plan

In F. Toilet C102, change from " FD"to " FN"to indicate feminine napkin disposal, 3 places inside toilet stalls.

217 A2.01c QUADRANT PLAN 'C' Floor Plan

In Men's Shower C117 and Female Shower C103, add, "grab bars are not required above folding shower seats."

218 A2.01c QUADRANT PLAN 'C' Floor Plan

In Female Shower C103, add, "provide soap dish at each shower station."

219 A2.01d.1 QUADRANT PLAN 'D' Floor Plan Change Dwg. per attached Supplemental Dwg.

220 A2.02a

ENLARGED SECOND

FLOOR PLAN

W/CANOPY

Enlarged

Plan

Change key note designations on floor plans from "CT"to "PT"to indicate paper towel dispenser; from " MS"to "SS"to indicate stainless steel shelving (not in contract); and from " MT"to " MR"to indicate a mirror.

221 A2.02a

ENLARGED SECOND

FLOOR PLAN

W/CANOPY

Enlarged

Plan

In F. Toilet 213, inside the toilet stall change from " FD"to " FN"to indicate a feminine napkin disposal.

In LRN CTR/LIBRARY 204, add the note, "Provide modular bookcases

222 A2.02a

ENLARGED SECOND

FLOOR PLAN

W/CANOPY

Enlarged

Plan

In LRN CTR/LIBRARY 204, add the note, "Provide modular bookcases on east, west, and plan south walls as shown. Provide each bookcase as follows: 36" wide by 12" deep by 72" high plus 4" base for resilient base (76 inches total height); 3/4"thick, plastic laminate side, top, bottom, and back panels; five adjustable, melamine-covered particleboard or MDF core shelves, 1"thick."Change bookcase quantity on plan south wall from 4 to 3; center bookcases on wall."

223 A2.03

MAINTENANCE

TRAINING WORK BAY

PLANS/ELEVS

REPLACE

DRAWING Delete Dwg. as originally issued and replace with the attached.

224 A2.04

MAINTENANCE

TRAINING WORK BAY

SECTIONS

REPLACE

DRAWING Delete Dwg. as originally issued and replace with the attached.

225 A3.01

DOOR SCHEDULE AND

DETAILS Door Types

At OH2, change height from 16'-0"to 14'-0" . Delete door type HG.

At Door Type NV, at "A, B" add the note, " refer to door schedule for fire rated locations."At full glass door delete "D".

226 A3.01

DOOR SCHEDULE AND

DETAILS

Door Frame

Types

At Door Types S2, D2, and CO, delete reference to 2" heads. At Door

Types SL1 and SL2 delete dimensions of 7'-2" and 4'-0" . Add, "Refer to Door Schedule for door height; refer to head and jamb details on

A3.02 for head height indications.

227 A3.01

DOOR SCHEDULE AND

DETAILS

Door

Schedules

Delete columns labeled " HDWR" and " KEYNOTES."Add the note, "

Refer to Section 087100 - Door Hardware for types, quantities, and locations of hardware."

Brentwood, TN Page 20 of 30

Name

Para. /

Detail

Reference Item

No.

Description

Tullahoma Readiness Center

NGB #470043

HFR Job No. 2007042.00 Addendum No. 1

11-Aug-09

228 A3.01

DOOR SCHEDULE AND

DETAILS

Door

Schedules

At Second Floor, add, "Frames are all hollow metal; head and jamd detail 1/A3.02."

229 A3.01

DOOR SCHEDULE AND

DETAILS

Door

Schedules

At Door A101 change from "SL1"to "S2" and add the remark, " for adjacent glazing refer to window type K."At Door 301 change from

"SL1"to "S2" and add the remark, " for adjacent glazing refer to window type RR."At Door B106 change from "SL1"to "S2" and add the remark, " for adjacent glazing refer to window type M."At Door

D101 change from "SL1"to "S2" and add the remark, " for adjacent glazing refer to window type K."At…