COMBINED SYNOPSIS/SOLICITATION

This notice is being posted as an avenue to provide Request for Quotes, W912HN19Q1000. This is a combined synopsis/solicitation for commercial supply prepared in accordance with the format in FAR Subpart 12.6, as supplemented with additional information in this notice. THIS

ANNOUNCEMENT CONSTITUTES THE ONLY SOLICITATION; QUOTES ARE BEING

REQUESTED AND A WRITTEN SOLICITATION WILL NOT BE ISSUED. This procurement will be 100% set aside for only Small Businesses. The North American Industry Classifications System (NAICS) is 541690 with a small business size standard of $15M. This solicitation document incorporates provisions and clauses in effect through Federal Acquisition Circular (FAC) 2005-100.

Title of Requirement: Compliance Emission Testing of Nine (9) Peak Shave Generators

Description of Requirement: Provide compliance testing of nine Model L16-567 Diesel peak shaving generators located at Building 25910, Fort Gordon, Georgia. The purpose of the test is to determine compliance with the Reciprocating Internal Combustion Engines (RICE) Maximum Achievable Control Technology.

Submission Requirements: Quotes should be E-mailed to Mr. Brent W. Ingram by 11:00 a.m.

Eastern Time on 22 January 2019 at brent.w.ingram@usace.army.mil. Please courtesy copy, Mr.

Adrian Goolsby at adrian.e.goolsby@usace.army.mil.

Basis for Award: The Government will make an award to the lowest priced offer which is deemed responsive, responsible, and technically acceptable. The price must be determined to be fair and reasonable. This is in accordance with Federal Acquisition Regulations (FAR) 52.212-2, Evaluation

– Commercial Items, and FAR 9.104.

The Government reserves the right to cancel this solicitation.

mailto:adrian.e.goolsby@usace.army.mil

W912HN19Q1000 Page 2 of 47 U.S. Army Corps of Engineers – Savannah District

Point of Contact: Brent Ingram Phone: (912) 652-5954

Email: brent.w.ingram@usace.army.mil

Please complete the following form in addition to the price quote starting on page 4.

CONTRACTOR: _____________________________________________________________

DUNS NO.: _____________________________________________________________

CAGE CODE: _____________________________________________________________

TAX ID NO.: _____________________________________________________________

E-MAIL: _____________________________________________________________

PHONE NO.: _____________________________________________________________

DATE OF QUOTE: ___________________________________________________________

Quote Prepared By: _____________________________ ____________________________

(Printed Name and Title) (Signature) The Contractor, certifies by signing this document, understands and complies with the requirements listed in the Performance Work Statement (PWS) and shall provide service meeting or exceeding the requirements.

mailto:brent.w.ingram@usace.army.mil

W912HN19Q1000 Page 3 of 47

NOTES TO OFFEROR

Note 1: Quotes shall meet the Technical Requirements to be eligible for an award. PARTIES INTERESTED IN RESPONDING TO THIS RFQ may submit their Quote in accordance with standard commercial practice (i.e. Quote form, letterhead, etc.) and MUST INCLUDE THE FOLLOWING INFORMATION: Solicitation number; offerors complete mailing and remittance addresses; discount terms, DUNS number, and Tax Identification Number. Any prospective awardee shall be registered and active in the System Award Management (SAM) database prior to any award of a contract resulting from this solicitation. Offerors may obtain information on registration and annual confirmation requirements via the Internet at http://www.acquisition.gov or by calling 866-606-8220.

Note 2: All questions are to be directed no later than 11:00 a.m. Eastern Time, 7 calendar days prior to quote due date to Brent Ingram at brent.w.ingram@usace.army.mil.

Note 3: The Taxpayer Identification Number may be used by the Government to collect and report on any delinquent amounts arising out of the contractor’s relationship with the Government.

Note 4: The completed Offeror Representations and Certifications-Commercial Items (FAR 52.212-3) or Notation that company is registered in SAM (https://www.sam.gov) must be submitted along with each Quote.

Note 5: All quotes on unit prices will include shipping cost to FOB destination and not added separately.

Note 6: This acquisition will utilize Simplified Acquisition Procedures pursuant to FAR 13.1.

Note 7: To be determined technically acceptable, potential offerors shall submit for evaluation purposes, references from one (1) completed project that meets or exceeds this requirement. Offerors shall provide contact information, project name, and project location that demonstrate organizations capability to provide compliance testing of Diesel peak shaving generators services to be eligible for an award.

Submit this information in the space provide on page 5 or include an attachment (limited to 2 pages).

Note: 8: Site Visit 1100 on 8 January 2019. West side of Building 25910, located on 8th Ave. Look for large generators.

Check in at the Gate 1 Visitor Center. Requirements to gain access to base are in the following links.

Here's the links:

http://gordon.army.mil/visitor_information.html http://gordon.army.mil/visitors/

Failure to visit the project site will not relieve the contractor from responsibility for performance of the work and compliance with the terms and conditions of any resultant contract. In no event will a failure to inspect the site constitute grounds for a claim after award of the purchase order.

http://gordon.army.mil/visitor_information.html http://gordon.army.mil/visitors/

W912HN19Q1000

Section B - Supplies or Services and Prices

ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

0001 1 Job Task 1

Abbreviated Accident Prevention Plan and Workplan (APP/WP) FOB: Destination

NET AMT

0002 1 Job Task 2

Compliance Emission Testing

0003 1 Job Task 3

Compliance Emission Testing Report

0004 1 Job Task 4

Contractor Manpower Reporting & Accounting (CMRA)

Section C - Descriptions and Specifications

Performance Work Statement for

Compliance Emission Testing Of Nine (9) Peak Shave Generators at Fort Gordon, GA

1. Introduction and Background

Fort Gordon has an existing Part 70 Air Operating Permit that requires emissions testing every 3 years per the Georgia Air Quality Act, O.C.G.A Section 12-9-1, et seq and the Georgia Rules for Air Quality Control, Chapter 391-3-1.

This Performance Work Statement (PWS) describes the professional services required to provide compliance testing of nine Model L16-567 Diesel peak shaving generators located at Building 25910, Fort Gordon, Georgia. The purpose of the test is to determine compliance with the Reciprocating Internal Combustion Engines (RICE) Maximum Achievable Control Technology, (MACT) requirements referenced in the Fort Gordon Part 70 Operating Permit Number: 9711- 245-0021-V-03-0, dated April 8, 2016. The RICE compliance testing will be conducted in accordance with 40 CFR Part 63 National Emission Standards for Hazardous Air Pollutants (NESHAP), Subpart ZZZZ, Stationary RICE.

1. GENERAL REQUIREMENTS:

1.1 Responsibility

The Contractor shall perform all services stated for the project in accordance with established criteria, standards, and instructions and shall assume all responsibility for the accuracy and completeness of the work. Quality of work accomplished under this contract will be a determining factor in consideration of the Contractor for future work. The Contractor and all subcontractors must comply with statutes and regulations of the State of Georgia. Should the Contractor receive any directions or instructions that are beyond the PWS, the Contractor shall not proceed with such directions or instructions, but shall notify the Contracting Officer (KO) in writing describing the changes and impact on the effort within ten calendar days. The KO will then evaluate the need for a modification to the Contractor’s task order.

1.2 Release of Information

The Contractor shall neither publicize nor release in any manner information or data regarding projects on which they may be working or negotiating with this office, nor discuss prior to public release by this office, a project, any future design of the project, or any planning with anyone not directly concerned with the execution of the project. Any inquiries about the project shall be referred to the Contracting Officer (KO) or the United States Army Corps of Engineers (USACE), Savannah District, Public Affairs Officer. The above restrictions are not intended to interfere with notification of Federal, State, and local agencies as may be required by applicable laws and regulations regarding releases of hazardous materials and substances and other such materials covered therein. To this end, it is the Contractor's obligation to be familiar with applicable Federal, State, and local laws, regulations, and procedures regarding such reporting. Such notifications should also be made when there is a reasonable likelihood of harm to persons on or around the project area resulting from a release of potentially dangerous material. Where time permits, the Contractor will coordinate such notifications with the KO.

1.3 Professional Judgment

The Contractor shall use their professional judgment to make suggestions to improve the quality of the work, reduce any unnecessary work (and associated cost), and improve the final product (workplan, design, report, etc.). The Contractor shall also ensure that the USACE meets all reporting requirements under applicable laws and regulations.

1.4 Project Stakeholders

For the purposes of this PWS, the project stakeholder is Fort Gordon. Required level of involvement may differ from site to site and the Contractor shall be responsible for obtaining comments with appropriate approval or concurrence on project deliverables consistent with applicable regulatory drivers.

1.5 Quality monitoring and measurement

The contractor will be evaluated periodically during performance of this task order to ensure compliance with the proposed and accepted performance goals, regulations, and guidance, and to document that acceptance criteria (AC), delivery schedule, and the overall completion of the project are being met. This evaluation will be performed according to a Quality Assurance Surveillance Plan (QASP). A programmatic QASP will be provided by the government. The QASP will highlight key quality control activities or events that the COR will use to determine when inspections can be conducted to assess progress toward completion of the project.

Failure to adequately complete any service or submittal to at least a satisfactory level of quality or timeliness may result in a repeat of the work, or a poor performance evaluation, or both.

1.6 Site Security Measures

The USACE and their representative shall have access to the work area for inspection at all times. The contractor shall remain in compliance with all rules, codes, standards, and regulations governing the safety of all individuals at the worksite and shall be solely responsible for any injuries, accidents, exposures or liabilities occurring due to non-compliance or failure to secure the work area.

1.7 Site Visit

Prior to the submission of any quotes, all offerors are required to visit the project site location to become familiar with the project requirements. A quote will not be rejected only because the offeror fails to visit the project site. Failure to visit the project site will not relieve the contractor from responsibility for performance of the work and compliance with the terms and conditions of any resultant contract. In no event will a failure to inspect the site constitute grounds for a claim after award of the purchase order.

1.8 Hours Of Work

All other shall be accomplished between the hours of 0730 thru 1630 hours daily, Monday through Friday on non-Government holidays. Legal holidays falling on Saturday are observed on the proceeding Friday and those falling on Sunday are observed on the following Monday.

Work outside these hours will be allowed if coordinated in advance with the Site Lead.

1.9 Photographs

Photographs or slides of Fort Gordon facilities will not be taken without prior approval, base security and other approving officials. All photographic products will be the property of the government. The Contractor shall take photographs to document work and to be used by the Fort Gordon. All photographs shall be submitted in a digital format.

2.0 Tasks

2,1 Task 1 Abbreviated Accident Prevention Plan and Workplan (APP/WP) The contractor shall submit Abbreviated Accident Prevention Plan with brief workplan (APP/WP) in compliance with ng EM 385-1-1, Appendix A. Plans will include copies of all required training and clearances including but not limited to CPR, First Aid and Blood-borne pathogens certifications and any other OSHA required training (training in fall protection, noise, etc.). The designated Site-Specific Safety and Health Officer‘s (SSHO) documentation of training and experience as well as annual 8-hour safety training shall be submitted.

Progress Reports While fieldwork is ongoing pursuant to the tasks listed below, the Contractor shall also submit daily progress reports and weekly summary progress reports documenting the field activities performed, or progress reports for each session, if applicable. A copy of all field notes shall be submitted within 30 days of the completion of the field work.

DELIVERABLES:

The deliverables for this task are:

• Work plan w/ APP

• Schedule

• Progress reports

• Meeting minutes

• All other associated documentation

2.2 Task 2

Compliance Emission Testing The contractor will conduct the required compliance emission testing on nine Model L16-567 Diesel peak shaving generators. The testing will be conducted in accordance with the RICE MACT requirements, the facilities Part 70 Operating Permit and the Test Protocol included as part of this PWS. The testing will require a minimum of three sixty minute test runs on each of the nine units. Each unit will be tested with the unit operating at 90% - 100% load condition.

Testing by EPA Method 10 will be performed on each unit at the inlet and outlet stack location for the determination of Carbon Monoxide (CO). Testing will also be performed by EPA Method 3A at the inlet and outlet locations for Oxygen and Carbon Dioxide.

Sufficient lead time will be necessary for Fort Gordon to bring the generators up to peak operating capacity. The contractor will coordinate the testing time with the site Lead, Mr. Mike

Mctier at 706-339-7494. Operating time at this location is usually from 7:30 AM to 4:00 PM, extended hours may be permitted by coordinating with Mr. Mike Mctier as well.

The calibration and quality assurance procedures of EPA 40 CFR 60 Appendix A for the identified test methods in accordance with the “Quality Assurance Handbook for Air Pollution Measurement System” Volume III Stationary Source-Specific Methods will be followed throughout the duration of the field testing. The most current revision of each test method will be used.

120V/50 amp Electrical Service is available, 220 can be hardwired into service is plug is supplied. Power sources are approximately 200 feet from generator area.

The contractor is responsible for providing all labor, materials, equipment and analysis to perform the compliance emission testing.

DELIVERABLE:

• Testing of all nine generators in compliance with Fort Gordon Permit 9711-245-

0021-V-03-0, dated April 8, 2016 is required to be completed no later than February 21, 2019.

2.3 Task 3

Compliance Emission Testing Report Following completion of the compliance emission testing the contractor will prepare a report detailing the testing procedures, Q/A procedures, results and conclusions. The report should include detailed test data and results for each of the nine generators as well as evaluation of the results in compliance with the Part 70 Operating Permit.

A Draft Compliance Emission Testing Report will be submitted 15 Days following completion of the Compliance Emission Testing. Following receipt of government comments the Final Draft of the report will be submitted within 10 days.

• Draft Report (Electronic Only)

• Final Report (Electronic Only)

2.4 Task 4: Contractor Manpower Reporting & Accounting (CMRA)

The Office of the Assistant Secretary Fort Gordon (Manpower & Reserve Affair) operates and maintains a secure Army data collection site where the contractor shall report ALL contractor manpower (including sub-contractor manpower) required for using the following web site:

https://contractormanpower.army.pentagon.mil.

Enter all specific data required in accordance with applicable, Federal, State, and local regulations.

Enter all required information and information below into CMRA:

• Contracting Office, Contracting Officer, and Contracting Officer’s Representative.

• Contract number, including task and delivery order number.

• Beginning and ending dates covered by reporting period.

https://contractormanpower.army.pentagon.mil/

• Contractor names, address, phone number, e-mail address, and identity of contractor employee entering data.

• Estimated direct labor hours (including sub-contractors).

• Estimated direct labor dollars paid this reporting period (including sub-contractors).

• Total payments (including sub-contractors).

• Predominant Federal Service Code (FSC) reflecting services provided by contractor (and separate predominant FSC for each sub-contractor if different).

• Estimated total cost (if any) incurred to comply with this reporting requirement.

Organizational title associated with the Unit Identification Code (UIC) for Fort Gordon Requiring Activity (Fort Gordon Requiring Activity is responsible for providing the contractor with its UIC for the purpose of reporting this information).

• Locations where contractor and sub-contractors perform the work (specified by zip code in the United States and nearest city, country, when in an overseas location, using standardized nomenclature provided on website).

• Number of contractor and sub-contractor employees deployed in theater this reporting period (by country).

• Presence of deployment or contingency contract language

2.4 Period of Performance

The Period of Performance is 30 days following award of purchase order.

3.0 PLANS AND MANAGEMENT

3.1 Project Management

The contractor shall assign a principal or key employee to serve as the contractor's Project Manager (PM) for this task order. The contractor's PM shall oversee the coordination and execution of the entire project and shall be capable of administering all instructions from the Savannah District USACE and obtaining answers to all questions related to the project during the course of the contract period.

3.2 Coordination and Points of Contact

The contractor shall coordinate through the USACE PM and USACE TM. All requests made to the contractor by other agencies shall be referred to the USACE PM for action. During the execution of the work under this task order, the contractor shall keep in close liaison with the USACE and Fort Gordon points of contact listed below:

Name Position Phone Number/ Fax/ Email

Tracey Epperley COR (912) 652-5718/6012 Tracey.L.Epperley@usace.army.mil

Anna Butler Project Manager (PM) (912) 652-5515/6012 Anna.h.butler@usace.army.mil

Renee Hill Technical Manager (TM), EN-GG

(912) 652-5671/5311 Alison.R.hill@usace.army.mil

Mike Mctier Ft Gordon Site Lead (706) 339-7494

Brock M. Tyson Ft Gordon Air Compliance Coordinator jill.r.scarborough.civ@mail.mil mailto:Alison.R.hill@usace.army.mil

3.3 Project Records

All material and information gathered and/or developed in the performance of the tasks listed in the contract shall be the property of the U.S. Government. Data gathered during the period of performance of this project shall not be used or distributed by the Contractor without specific written Government permission. At the completion of the project, the Contractor shall provide to the USACE PM a complete set of project records including all correspondence, memorandums, trip reports, confirmation notices, test results, submittals, photographs, and any other records or documents generated as a result of the project. The project records shall be submitted in both hard copies and in electronic file format. All final text files generated by the Contractor shall be furnished to the USACE Project Manager in Adobe Acrobat compatible software and IBM PC compatible format. All laboratory analytical data shall be furnished in SEDD Stage 2b format. Discussion with the Corps on the format for the electronic data is mandatory. However, a general guideline is that all photos should be ‘.jpg’ files, and text should be in ‘.pdf’ file formats (version 10.1 compatible). All final drawings and figures in the reports and plans generated by the Contractor shall be furnished in 3D files in Micro Station 4.0 format or latest Corps CADD standards (.dgn files). The files shall be submitted on Compact Disc media. Three (3) copies shall be submitted.

3.4 Submittals

General Requirements All reports and documents will be completed in time for their thorough and complete review, appropriate revision to occur, and required delivery schedules to be observed. To facilitate attainment of this goal, the project deliverables schedule will be routinely and regularly updated.

Draft reports are considered “drafts” only in the sense that they have not been reviewed and approved by the government. In all respects draft reports shall be complete, free of grammatical/typographical errors, and in the proper format. It is not generally desirable however, for draft reports to be bound (except when their length makes in impractical) or in color. The Contractor shall incorporate all comments received prior to submitting the final reports. Comment responses shall be annotated to note what and where in the documents the changes were made. All reports shall be double-sided on recycled paper. The Contractor shall coordinate the cover letters with the USACE.

Subsequent to the technical review and recommendations by the Contracting Officer's Technical Representative and the installation, the Contracting Officer reserves the right to require additional changes and submissions of revised drafts until an acceptable report is received. To be successful, revisions should be limited to two per deliverable. Any subsequent draft submissions will be prepared and submitted at no additional cost to the Government. If the correction/change requested is not addressed within the draft report, an itemized explanation of why no correction/change was made to the draft report shall be submitted.

The Contractor shall deliver the specified number of copies of each report shown in Table 5-1 to the following addressees (addresses to be verified by Contractor):

COR:

U.S. Army Corps of Engineers, Savannah District Attn: Tracey Epperley, Project Manager (PM) 100 W. Oglethorpe Ave.

Savannah, GA 31401 Tel: 912-652-5597 Email: Tracey.L.Epperley@usace.army.mil mailto:Tracey.L.Epperley@usace.army.mil

3.4 Deliverables

The contractor shall submit all deliverables in draft and final format as required within the specific instructions of each task order, including the format, number of copies, and distribution. At a minimum, all final copies of documents shall include one copy in PDF format (*.pdf) submitted on CD-ROM disk.

Drawings should be submitted in PDF format.

Table 3-1 List of Submittals Deliverable Frequency # of Copies Medium/Format Submit To Schedule NLT 5 Days from NTP 1, electronic copy

PDF electronic file

COR

Submit Draft

NLT 10 Days from NTP

1, electronic copy PDF electronic File

COR

Final App/Workplan

NLT 15 Days from NTP

1, electronic copy PDF and 3 CDs COR

Progress Reports

Daily and Weekly while conducting field

1, electronic copy PDF electronic file

COR

Meeting Minutes

NLT 3 days after conclusion of meeting

1, electronic copy

PDF electronic file

COR

Draft Compliance Report

15 days following completion of testing

1, electronic copy

PDF electronic file

COR

Final Compliance report

10 days after receiving review t

1, electronic copy

PDF and 3 CDs COR

4.0 ANTITERRORISM (AT) AND OPERATION SECURITY (OPSEC)

AT Level I Training: This provision/contract text is for contractor employees with an area of performance within an Army controlled installation, facility, or area. All contractor employees, to include subcontractor employees, requiring access to Army installations, facilities, and controlled access areas shall complete AT Level I awareness training within 30 calendar days after contract start date or effective date of incorporation of this requirement into the contract, whichever is applicable. The contractor shall submit certificates of completion for each affected contractor employee and subcontractor employee to the COR or to the KO, if a COR is not assigned within 30 calendar days after completion of training by all employees and subcontractor personnel.

Access and General Protection/Security Policy and Procedures: Contractor and all associated sub-contractors’ employees shall comply with applicable installation, facility, and area commander installation/facility access and local security policies and procedures (provided by government representative). The contractor shall also provide all information required for background checks to meet installation access requirements to be accomplished by installation

Provost Marshall Office, Director of Emergency Services, or Security Office. Contractor workforce must comply with all personal identity verification requirements as directed by DOD, HQDA, and/or local policy. In addition to the changes otherwise authorized by the changes clause of this contract, should the Force Protection Condition (FPCON) at any individual facility or installation change, the Government may require changes in contractor security matters or processes.

iWATCH Training: The contractor and all associated sub-contractors shall brief all employees on the local iWATCH program (training standards provided by the requiring activity ATO).

This local developed training will be used to inform employees of the types of behavior to watch for and instruct employees to report suspicious activity to the COR. This training shall be completed within 60 calendar days of contract award and within 45 calendar days of new employees commencing performance with the results reported to the COR NLT 30 calendar days after contract award.

Army Training Certification Tracking System (ATCTS) registration for contractor employees who require access to government information systems. All contractoremployees with access to a government information systems must be registered in the ATCTS (Army Training Certification Tracking System) at commencement of services, and must successfully complete the DOD Information Assurance Awareness prior to access to the IS and then annually thereafter.

For contracts that require OPSEC Training. Per AR 530-1 Operations Security, the contractor employees must complete Level I OPSEC Awareness training. New employees must be trained within 30 calendar days of their reporting for duty and annually thereafter. OPSEC Awareness for Military Members, DoD Employees and Contractors is available at the following website: http://cdsetrain.dtic.mil/opsec/index.htm

For Cyber Awareness (Information assurance (IA)/information technology (IT)) training.

All contractor employees and associated sub-contractor employees must complete the DoD Cyber awareness training before issuance of network access and annually thereafter. All contractor employees working IA/IT functions must comply with DoD and Army training requirements in DoDD 8570.01, DoD 8570.01-M and AR 25-2 within six months of appointment to IA/IT functions. DoD Cyber Awareness Challenge Training is available at the following website:

https://ia.signal.army.mil/DoDIAA/

Threat Awareness Reporting Program. For all contractors with security clearances. Per AR 381-12 Threat Awareness and Reporting Program (TARP), contractor employees must receive annual TARP training by a CI agent or other trainer as specified in 2-4b of AR 381-12.

Emergency Services: Emergency medical treatment and services for Contractor personnel is the responsibility of the Contractor.

https://ia.signal.army.mil/DoDIAA/

Appendix A: Fort Gordon Test Protocols

TEST PROTOCOLS

for

FEBRUARY 2019 COMPLIANCE EMISSION TESTING

of

NINE (9) PEAK SHAVE GENERATORS

at

FORT GORDON, GEORGIA

By:

U.S. Army Corps of Engineers, Savannah District

November 2018

Test Protocol for Compliance Emission Testing of Nine (9) Peak Shave Generators at Fort Gordon, GA

Test Requirements

Testing is to be conducted on nine (9) Model L16-567 Diesel peak shaving generators located at Building 25910, Fort Gordon, Georgia. The purpose of the test is to determine compliance with the Reciprocating Internal Combustion Engines (RICE) Maximum Achievable Control Technology, (MACT) requirements referenced in the facilities Part 70 Operating Permit Number: 9711-245-0021-V-03-0, dated April 8, 2016. The RICE compliance testing will be conducted in accordance with 40 CFR Part 63 National Emission Standards for Hazardous Air Pollutants (NESHAP), Subpart ZZZZ, Stationary RICE. Table 1, below, lists the technical details of the RICE Generators to be tested.

TABLE 1: RICE GENERATORS LOCATED at BUILDING 25910

Generator ID NO. Description MACT CO Limit G002

(Group 2) 2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G003 (Group 2)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G004 (Group 2)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G005 (Group 2)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G006 (Group 2)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G007 (Group 2)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G008 (Group 3)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G009 (Group 3)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

G010 (Group 3)

2125 HP output (1500kWe, 15.9 MMBtu/hr @ 113 gph input)

23 ppmvd @ 15% O2

The testing will require a minimum of three (3) sixty (60) minute test runs on each of the nine units. Each unit will be tested with the unit operating at 90% - 100% load condition. Testing by EPA Method 10 will be performed on each unit at the inlet and outlet stack location for the determination of Carbon Monoxide (CO). Testing will also be performed by EPA Method 3A at the inlet and outlet locations for Oxygen and Carbon Dioxide. The Final Report will provide test data compared to the applicable emissions standards of 23 ppmdv at 15% O2 and a CO reduction of 70%.

The calibration and quality assurance procedures of EPA 40 CFR 60 Appendix A for the identified test methods in accordance with the “Quality Assurance Handbook for Air Pollution Measurement System” Volume III Stationary Source-Specific Methods will be followed throughout the duration of the field testing. The most current revision of each test method will be used. Table 2 contains the test parameter, EPA method, sample method, number of tests, test duration and parameters collected.

TABLE 2: TEST METHODOLOGY

Parameter EPA Method

Sample Method

Number of Test

Test Duration (Minutes)

Parameters Collected

Oxygen and CO2 3A Paramagnetic 3 60 % (Inlet & Outlet)

Carbon Monoxide

(CO)

10 Gas Filter Correlation

3 60 ppm (Inlet & Outlet)

Moisture 4 Garvimetric 3 60 ppmdv (outlet)

Pressure* Differential Pressure

3 60 Control Panel

Temperature* Temperature 3 60 Control Panel *The change in pressure and temperature across the catalyst will be collected at the control panel

Instrumentation

A Thermo 410i O2 analyzer will be used to measure oxygen by US EPA Method 3A. The technical specifications for the Thermo Environmental Instruments Model 410i oxygen continuous emission monitor are contained in Table 3.

Table 3: Technical Specifications of the Thermo Oxygen Monitor

Manufacturer Thermo Environmental Instruments, Inc Model Number 410i Detection Principle Paramagnetic transducer Range 0-25.0% Linearity +/- 0.1% of fullscale Repeatability +/- 0.1% of fullscale Response 90% full scale in less than 2.5 seconds Zero Drift +/- 0.1% of fullscale per 24 hours Span Drift +/- 0.1% of fullscale per 24 hours

Source: Thermo Environmental Instruments, Inc.

A Thermo Environmental Instruments Model 48C monitor will be used to measure CO concentrations by US EPA Method 10. The technical specifications for the Thermo Environmental Instruments Model 48C monitor are contained in Table 4.

Table 4:

Technical Specifications of Thermo Model 48C Carbon Monoxide Monitor

Manufacturer Thermo Environmental Instruments, Inc.

Model Number Model 48C Detection Principle Gas Filter Correlation Range 0-456.0 ppm Precision < 0.1 ppm Response Time 1 minute @ 1 liter per minute and 30 second integration time to 90% full scale range Zero Drift < 4 ppm over 24 hours Span Drift < 2 % of full scale over 24 hours Sample Flow Rate 0.5 – 2 liter per minute Operating Temperature 0-45 EC Zero Noise Level 2 ppm RMS with time constant = 10 seconds Linearity < 1% of full scale for all ranges

Source: Thermo Environmental Instruments, Inc.

Calibration Procedures

All of the emission testing equipment will be calibrated according to the procedures outlined in the US EPA 40 CFR Part 60 Appendix “A” and the Quality Assurance Handbook for Air Pollution Measurement Systems, Volume III, US EPA-600/4-94-038c. A copy of calibration records will be provided as an appendix in the final report.

QA/QC Procedures

The quality assurance procedures of EPA 40 CFR 60 Appendix A for the identified test methods as according to the ”Quality Assurance Handbook for Air Pollution Measurement System” Volume III Stationary Source‐Specific Methods will be followed throughout the duration of the field testing. The most current CFR revision of each method will be used

Health and Safety

The facility is responsible for providing safe and adequate access to the test location to conduct emissions testing as outlined in 40 CFR 60.8. Individuals performing the test will comply with all applicable health and safety requirements set by the facility, and associated safety organization including but not limited to ISNetworld, TAPPI Safe, etc. Field personnel will have the standard personal protection equipment, including hard hat, steel toe boots, safety glasses, hearing protection, leather gloves, and safety clothing.

Facility Requirements

The scope and quantity of work in the project will require management and coordination to complete the testing as proposed; therefore, it is important that the facility ensures that the test team is provided:

1. Site specific safety requirements. A safe work platform in the form of catwalks, temporary scaffolding, or aerial lift, if required.

2. Equipment and test locations. A suitable area for the mobile laboratory. The area must be clear from all obstacles and debris prior to arrival and be no more than 100 feet from the sampling location.

3. Adequate stack/duct sampling ports (minimum 2 ports at 90 degrees) located to meet EPA Method 1 criteria of a minimum of 2x the stack diameter downstream of last disturbance, and 1/2x the stack diameter upstream of any disturbance. The ports shall be installed and cleaned prior to the arrival of the test team. The ports must be in a condition ready to accept standard sampling probes, and all port caps and/or flanges must be loosened.

4. Power Requirements ‐ a minimum of a 50 amp, 220‐240 VAC single phase or 30 amp 480 VAC single‐phase electrical power within 100 feet of the test (stack) location. Two additional 110v 20 amp electrical power will be required within 100’ of the test location.

5. Operational data ‐ of the plant / units that are being tested at the required test conditions according to the agreed‐upon testing schedule. Facility staff will record and provide all unit and/or operational data needed for the proper documentation of process conditions.

6. A plant radio for communication with the plant operators for emergencies or process changes and load verification, and for synchronization of test start/stop times.

7. Emergency and evacuation procedures with any applicable site contact numbers. Full access to the facility’s Material Safety Data Sheets, plus site‐specific safety equipment, are also required.

Should conditions develop beyond the test team’s control, making the building or premises in which the team is working dangerous, the team reserves the right to discontinue the work until such dangerous conditions are corrected.

References

EPA Method 3A, Determination of Oxygen and Carbon Dioxide Concentrations in Emissions form Stationary Sources, date August 8, 2017. https://www.epa.gov/sites/production/files/2017- 08/documents/method_3a.pdf

EPA Method 10, Determination of Carbon Monoxide Emissions form Stationary Sources, date August 8, 2017. https://www.epa.gov/sites/production/files/2017-08/documents/method_10.pdf

Wage Determination:

WD 15-4465 (Rev.-7) was first posted on www.wdol.gov on 07/10/2018

REGISTER OF WAGE DETERMINATIONS UNDER | U.S. DEPARTMENT OF LABOR

THE SERVICE CONTRACT ACT | EMPLOYMENT STANDARDS ADMINISTRATION

By direction of the Secretary of Labor | WAGE AND HOUR DIVISION

| WASHINGTON D.C. 20210

| Wage Determination No.: 2015-4465 Daniel W. Simms Division of | Revision No.: 7 Director Wage Determinations| Date Of Revision: 07/03/2018

Full Wage Determination can be found at https://www.wdol.gov/wdol/scafiles/std/15-4465.txt?v=7 https://www.epa.gov/sites/production/files/2017-08/documents/method_10.pdf https://www.wdol.gov/wdol/scafiles/std/15-4465.txt?v=7

Section E - Inspection and Acceptance

INSPECTION AND ACCEPTANCE TERMS

Supplies/services will be inspected/accepted at:

CLIN INSPECT AT INSPECT BY ACCEPT AT ACCEPT BY

0001 N/A N/A N/A Government 0002 N/A N/A N/A Government 0003 N/A N/A N/A Government 0004 N/A N/A N/A Government

Section F - Deliveries or Performance

DELIVERY INFORMATION

CLIN DELIVERY DATE QUANTITY SHIP TO ADDRESS DODAAC /

CAGE

0001 POP 30-JAN-2019 TO

21-FEB-2019

N/A GEOTECHNICAL & HTRW BRANCH

ANNA BUTLER

100 W. OGLETHORPE AVE.

SAVANNAH GA 31401

(912) 652-5515

W912HN

0002 POP 30-JAN-2019 TO

21-FEB-2019

N/A (SAME AS PREVIOUS LOCATION)

0003 POP 30-JAN-2019 TO

N/A (SAME AS PREVIOUS LOCATION)

0004 POP 30-JAN-2019 TO

N/A (SAME AS PREVIOUS LOCATION)

Section I - Contract Clauses

CLAUSES INCORPORATED BY REFERENCE

52.204-13 System for Award Management Maintenance OCT 2018 52.204-18 Commercial and Government Entity Code Maintenance JUL 2016 52.204-19 Incorporation by Reference of Representations and

Certifications.

DEC 2014

52.232-39 Unenforceability of Unauthorized Obligations JUN 2013 52.232-40 Providing Accelerated Payments to Small Business

Subcontractors

DEC 2013

52.243-1 Alt I Changes--Fixed Price (Aug 1987) - Alternate I APR 1984 52.246-1 Contractor Inspection Requirements APR 1984 52.249-4 Termination For Convenience Of The Government (Services)

(Short Form)

APR 1984

252.203-7000 Requirements Relating to Compensation of Former DoD Officials

SEP 2011

252.203-7002 Requirement to Inform Employees of Whistleblower Rights SEP 2013 252.204-7012 Safeguarding Covered Defense Information and Cyber

Incident Reporting

OCT 2016

252.204-7015 Notice of Authorized Disclosure of Information for Litigation Support

MAY 2016

252.232-7003 Electronic Submission of Payment Requests and Receiving Reports

JUN 2012

252.232-7010 Levies on Contract Payments DEC 2006 252.243-7001 Pricing Of Contract Modifications DEC 1991 252.244-7000 Subcontracts for Commercial Items JUN 2013

CLAUSES INCORPORATED BY FULL TEXT

52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR

EXECUTIVE ORDERS--COMMERCIAL ITEMS (OCT 2018)

(a) The Contractor shall comply with the following Federal Acquisition Regulation (FAR) clauses, which are incorporated in this contract by reference, to implement provisions of law or Executive orders applicable to acquisitions of commercial items:

(1) 52.203-19, Prohibition on Requiring Certain Internal Confidentiality Agreements or Statements (JAN 2017) (section 743 of Division E, Title VII, of the Consolidated and Further Continuing Appropriations Act, 2015 (Pub. L.

113-235) and its successor provisions in subsequent appropriations acts (and as extended in continuing resolutions)).

(2) 52.204-23, Prohibition on Contracting for Hardware, Software, and Services Developed or Provided by Kaspersky Lab and Other Covered Entities (Jul 2018) (Section 1634 of Pub. L. 115-91).

(3) 52.209-10, Prohibition on Contracting with Inverted Domestic Corporations (Nov 2015).

(4) 52.233-3, Protest After Award (AUG 1996) (31 U.S.C. 3553).

(5) 52.233-4, Applicable Law for Breach of Contract Claim (OCT 2004) (Public Laws 108-77 and 108-78 (19 U.S.C. 3805 note)).

(b) The Contractor shall comply with the FAR clauses in this paragraph (b) that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items: (Contracting Officer check as appropriate.)

___ (1) 52.203-6, Restrictions on Subcontractor Sales to the Government (Sept 2006), with Alternate I (Oct 1995) (41 U.S.C. 4704 and 10 U.S.C. 2402).

____ (2) 52.203-13, Contractor Code of Business Ethics and Conduct (Oct 2015) (41 U.S.C. 3509).

____ (3) 52.203-15, Whistleblower Protections under the American Recovery and Reinvestment Act of 2009 (June 2010) (Section 1553 of Pub. L. 111-5). (Applies to contracts funded by the American Recovery and Reinvestment Act of 2009.)

___ (4) 52.204-10, Reporting Executive Compensation and First-Tier Subcontract Awards (Oct 2018) (Pub. L. 109-

282) (31 U.S.C. 6101 note).

___ (5) [Reserved]

___ (6) 52.204-14, Service Contract Reporting Requirements (Oct 2016) (Pub. L. 111-117, section 743 of Div.

C).

___ (7) 52.204-15, Service Contract Reporting Requirements for Indefinite-Delivery Contracts (Oct 2016) (Pub.

L. 111-117, section 743 of Div. C).

___ (8) 52.209-6, Protecting the Government's Interest When Subcontracting with Contractors Debarred, Suspended, or Proposed for Debarment. (Oct 2015) (31 U.S.C. 6101 note).

____ (9) 52.209-9, Updates of Publicly Available Information Regarding Responsibility Matters (Oct 2018) (41 U.S.C. 2313).

____ (10) [Reserved]

____ (11)(i) 52.219-3, Notice of HUBZone Set-Aside or Sole-Source Award (NOV 2011) (15 U.S.C. 657a).

____ (ii) Alternate I (NOV 2011) of 52.219-3.

____ (12) (i) 52.219-4, Notice of Price Evaluation Preference for HUBZone Small Business Concerns (OCT 2014) (if the offeror elects to waive the preference, it shall so indicate in its offer) (15 U.S.C. 657a).

____ (ii) Alternate I (JAN 2011) of 52.219-4.

____ (13) [Reserved]

XX (14)(i) 52.219-6, Notice of Total Small Business Set-Aside (NOV 2011) (15 U.S.C. 644).

____ (ii) Alternate I (NOV 2011).

____ (iii) Alternate II (NOV 2011).

____ (15)(i) 52.219-7, Notice of Partial Small Business Set-Aside (June 2003) (15 U.S.C. 644).

____ (ii) Alternate I (Oct 1995) of 52.219-7.

____ (iii) Alternate II (Mar 2004) of 52.219-7.

____ (16) 52.219-8, Utilization of Small Business Concerns (Oct 2018) (15 U.S.C. 637(d)(2) and (3)).

____ (17)(i) 52.219-9, Small Business Subcontracting Plan (Aug 2018) (15 U.S.C. 637(d)(4)).

____ (ii) Alternate I (Nov 2016) of 52.219-9.

____ (iii) Alternate II (Nov 2016) of 52.219-9.

____ (iv) Alternate III (Nov 2016) of 52.219-9.

____ (v) Alternate IV (Aug 2018) of 52.219-9.

____ (18) 52.219-13, Notice of Set-Aside of Orders (NOV 2011) (15 U.S.C. 644(r)).

____ (19) 52.219-14, Limitations on Subcontracting (JAN 2017) (15 U.S.C. 637(a)(14)).

____ (20) 52.219-16, Liquidated Damages—Subcon-tracting Plan (Jan 1999) (15 U.S.C. 637(d)(4)(F)(i)).

____ (21) 52.219-27, Notice of Service-Disabled Veteran-Owned Small Business Set-Aside (NOV 2011) (15 U.S.C.

657f).

XX (22) 52.219-28, Post Award Small Business Program Rerepresentation (July 2013) (15 U.S.C. 632(a)(2)).

____ (23) 52.219-29, Notice of Set-Aside for, or Sole Source Award to, Economically Disadvantaged Women- Owned Small Business Concerns (Dec 2015) (15 U.S.C. 637(m)).

____(24) 52.219-30, Notice of Set-Aside for, or Sole Source Award to, Women-Owned Small Business Concerns Eligible Under the Women-Owned Small Business Program (Dec 2015) (15 U.S.C. 637(m)).

XX (25) 52.222-3, Convict Labor (June 2003) (E.O. 11755).

____(26) 52.222-19, Child Labor--Cooperation with Authorities and Remedies (Jan 2018) (E.O. 13126).

XX (27) 52.222-21, Prohibition of Segregated Facilities (Apr 2015).

XX (28)(i) 52.222-26, Equal Opportunity (SEPT 2016) (E.O. 11246).

____ (ii) Alternate I (Feb 1999) of 52.222-26.

____ (29)(i) 52.222-35, Equal Opportunity for Veterans (OCT 2015)(38 U.S.C. 4212).

____ (ii) Alternate I (July 2014) of 52.222-35.

XX (30)(i) 52.222-36, Equal Opportunity for Workers with Disabilities (JUL 2014) (29 U.S.C. 793).

____ (ii) Alternate I (July 2014) of 52.222-36.

____ (31) 52.222-37, Employment Reports on Veterans (FEB 2016) (38 U.S.C. 4212).

____ (32) 52.222-40, Notification of Employee Rights Under the National Labor Relations Act (Dec 2010) (E.O.

13496).

XX (33)(i) 52.222-50, Combating Trafficking in Persons (March 2, 2015) (22 U.S.C. chapter 78 and E.O. 13627).

____ (ii) Alternate I (March 2, 2015) of 52.222-50 (22 U.S.C. chapter 78 and E.O. 13627).

____ (34) 52.222-54, Employment Eligibility Verification (Oct 2015). (E. O. 12989). (Not applicable to the acquisition of commercially available off-the-shelf items or certain other types of commercial items as prescribed in 22.1803.)

____ (35)(i) 52.223-9, Estimate of Percentage of Recovered Material Content for EPA–Designated Items (May 2008) (42 U.S.C. 6962(c)(3)(A)(ii)). (Not applicable to the acquisition of commercially available off-the-shelf items.)

____ (ii) Alternate I (May 2008) of 52.223-9 (42 U.S.C. 6962(i)(2)(C)). (Not applicable to the acquisition of commercially available off-the-shelf items.)

____ (36) 52.223-11, Ozone-Depleting Substances and High Global Warming Potential Hydrofluorocarbons (June, 2016) (E.O. 13693).

____ (37) 52.223-12, Maintenance, Service, Repair, or Disposal of Refrigeration Equipment and Air Conditioners (June, 2016) (E.O. 13693).

____ (38) (i) 52.223-13, Acquisition of EPEAT® Registered Imaging Equipment (Jun 2014) (E.O.s 13423 and 13514).

____ (ii) Alternate I (OCT 2015) of 52.223-13.

____ (39)(i) 52.223-14, Acquisition of EPEAT® Registered Televisions (Jun 2014) (E.O.s 13423 and 13514).

____ (ii) Alternate I (Jun 2014) of 52.223-14.

____ (40) 52.223-15, Energy Efficiency in Energy-Consuming Products (Dec 2007) (42 U.S.C. 8259b).

____ (41)(i) 52.223-16, Acquisition of EPEAT[supreg]-Registered Personal Computer Products (OCT 2015) (E.O.s 13423 and 13514).

____ (ii) Alternate I (Jun 2014) of 52.223-16.

XX (42) 52.223-18, Encouraging Contractor Policies to Ban Text Messaging While Driving (Aug 2011) (E.O.

13513).

____ (43) 52.223-20, Aerosols (June, 2016) (E.O. 13693).

____ (44) 52.223-21, Foams (June, 2016) (E.O. 13693).

____ (45)(i) 52.224-3, Privacy Training (JAN 2017) (5 U.S.C. 552a).

____ (ii) Alternate I (JAN 2017) of 52.224-3.

____ (46) 52.225-1, Buy American--Supplies (May 2014) (41 U.S.C. chapter 83).

____ (47) (i) 52.225-3, Buy American--Free Trade Agreements--Israeli Trade Act (May 2014) (41 U.S.C. chapter 83, 19 U.S.C. 3301 note, 19 U.S.C. 2112 note, 19 U.S.C. 3805 note, 19 U.S.C. 4001 note, Pub. L.

103-182, 108-77, 108-78, 108-286, 108-302, 109-53, 109-169, 109-283, 110-138, 112-41, 112-42, and 112-43.

____ (ii) Alternate I (May 2014) of 52.225-3.

____ (iii) Alternate II (May 2014) of 52.225-3.

____ (iv) Alternate III (May 2014) of 52.225-3.

____ (48) 52.225-5, Trade Agreements (AUG 2018) 19 U.S.C. 2501, et seq., 19 U.S.C. 3301 note).

____ (49) 52.225-13, Restrictions on Certain Foreign Purchases (JUNE 2008) (E.O.'s, proclamations, and statutes administered by the Office of Foreign Assets Control of the Department of the Treasury).

____ (50) 52.225-26, Contractors Performing Private Security Functions Outside the United States (Oct 2016) (Section 862, as amended, of the National Defense Authorization Act for Fiscal Year 2008; 10 U.S.C. 2302 Note).

____ (51) 52.226-4, Notice of Disaster or Emergency Area Set-Aside (Nov 2007) (42 U.S.C. 5150

____ (52) 52.226-5, Restrictions on Subcontracting Outside Disaster or Emergency Area (Nov 2007) (42 U.S.C.

5150).

____ (53) 52.232-29, Terms for Financing of Purchases of Commercial Items (Feb 2002) (41 U.S.C. 4505, 10 U.S.C. 2307(f)).

____ (54) 52.232-30, Installment Payments for Commercial Items (Jan 2017) (41 U.S.C. 4505, 10 U.S.C. 2307(f)).

XX (55) 52.232-33, Payment by Electronic Funds Transfer—System for Award Management (Oct 2018) (31 U.S.C.

3332).

____ (56) 52.232-34, Payment by Electronic Funds Transfer—Other than System for Award Management (July 2013) (31 U.S.C. 3332).

____ (57) 52.232-36, Payment by Third Party (MAY 2014) (31 U.S.C. 3332).

____ (58) 52.239-1, Privacy or Security Safeguards (Aug 1996) (5 U.S.C. 552a).

____ (59) 52.242-5, Payments to Small Business Subcontractors (JAN 2017)(15 U.S.C. 637(d)(12)).

____ (60)(i) 52.247-64, Preference for Privately Owned U.S.-Flag Commercial Vessels (Feb 2006) (46 U.S.C.

Appx. 1241(b) and 10 U.S.C. 2631).

____ (ii) Alternate I (Apr 2003) of 52.247-64.

____ (iii) Alternate II (Feb 2006) of 52.247-64.

(c) The Contractor shall comply with the FAR clauses in this paragraph (c), applicable to commercial services, that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items: (Contracting Officer check as appropriate.)

_____ (1) 52.222-17, Nondisplacement of Qualified Workers (May 2014) (E.O. 13495).

XX (2) 52.222-41, Service Contract Labor Standards (AUG 2018) (41 U.S.C. chapter 67).

XX (3) 52.222-42, Statement of Equivalent Rates for Federal Hires (MAY 2014) (29 U.S.C. 206 and 41 U.S.C.

chapter 67).

_____ (4) 52.222-43, Fair Labor Standards Act and Service Contract Labor Standards--Price Adjustment (Multiple Year and Option Contracts) (AUG 2018) (29 U.S.C. 206 and 41 U.S.C.