EX. NBP-C#5
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
UE
PB
PB
NBP-C #6
EX. MDP-C
NBP-C #7
EX. NBP-C #4
NBP-C #8
EX. NBP-C #3
1,3
2,4
5,7
6,8
9,11
10,12
1,3
2,4 5,7
6,8 9,11
1,3
2,4
5,7
T
M
E101
E101
E101
TYP. OF 14
E101 w w w .te tra te ch .c om
C
H U
R C
H S
TR
EE
T, S
U
IT
E
H
U N
TS
VI
LL
E, A
LA
BA
M
A
TE
L.
: 2
-5
-0
NOTES:
2 RUNS OF 2-350KCMIL(P.), 1-350KCMIL(N.), 1 #4(G.)-2"C
2-350KCMIL(P.), 1-350KMCIL(N.), 1 #4(G.)-2"C
6 #2(P.), 3#2(N.), 3 #8(G.)-2"C
2 #2(P.), 1#2(N.), 1 #8(G.)-1"C
8 #2/0(P.), 4#2/0(N.), 4 #6(G.)-3"C
6 #2/0(P.), 3#2/0(N.), 3 #6(G.)-2 1/2"C
4 #2/0(P.), 2#2/0(N.), 2 #6(G.)-2 1/2"C
2 #2/0(P.), 1#2/0(N.), 1 #6(G.)-2 1/2"C
10 #2/0(P.), 5#2/0(N), 5 #6(G.)-3 1/2"C
ADD 2-200/2 CIRCUIT BREAKERS TO EXISTING 800A SERVICE PANEL.
MATCH EXISTING MANUFACTURE, STYLE AND AIC RATING.
EXISTING UTILITY TRANSFORMER TO BE UPGRADED BY UTILITY. CONTRACTOR
RESPONSIBLE FOR COMPENSATION TO UTILITY FOR ELECTRICAL SERVICE UPGRADES..
NEW 200A METER BASE BY CONTRACTOR, COORDINATE WITH LOCAL
UTILITY. CONTRACTOR RESPONSIBLE FOR COMPENSATION
TO UTILITY FOR ELECTRICAL SERVICE UPGRADES.
SEE SHEET E101 FOR SYMBOL LEGEND
http://www.tetratech.com/
NBP-D#1
MDP-D
NBP-D#6
NBP-D#2
NBP-D#3
NBP-D#4
NBP-D#5
PB
PB
PB
UE PB
PB
PB
PB
PB
PB
PB
PB
PB
PB
PB PB
PB
PB
PB
PB
PB
PB
T
7 7
11 11
E201
E201
E201
TYP OF 30
E201
E201
E201
E201
6,8
5,7
2,4
1,3
1,3
2,4
5,7
6,8 10,12
9,11
1,3
2,4
5,7
6,8 1,3
2,4
5,7
6,8
1,3
2,4
9,11
10,12
1,3
2,4
5,7
6,8
10,12
9,11 w w w .te tra te ch .c om
C
H U
R C
H S
TR
EE
T, S
U
IT
E
H
U N
TS
VI
LL
E, A
LA
BA
M
A
TE
L.
: 2
-5
-0
5 RUNS OF 2-350KCMIL(P.), 1-350KCMIL(N.), 1 #4(G.)-2"C1
2 4 RUNS OF 2-350KCMIL(P.), 1-350KCMIL(N.), 1 #4(G.)-2"C
3 3 RUNS OF 2-350KCMIL(P.), 1-350KCMIL(N.), 1 #4(G.)-2"C
4 2 RUNS OF 2-350KCMIL(P.), 1-350KCMIL(N.), 1 #4(G.)-2"C
5 2-350KCMIL(P.), 1-350KCMIL(N.), 1 #4(G.)-2"C
6 6 #2(P.), 3#2(N.), 3 #8(G.)-2"C
7 2 #2(P.), 1#2(N.), 1 #8(G.)-1"C
8 8 #2/0(P.), 4#2/0(N.), 4 #6(G.)-3"C
9 6 #2/0(P.), 3#2/0(N.), 3 #6(G.)-2 1/2"C
12 2-250KCMIL(P.), 1#250KCMIL(N.), 1#4(G.)-2"C
4 #2/0(P.), 2#2/0(N.), 2 #6(G.)-2 1/2"C
2 #2/0(P.), 1#2/0(N.), 1 #6(G.)-2 1/2"C
NOTES:
SEE SHEET E201 FOR SYMBOL LEGEND
13 NEW 200 KVA PAD MOUNT TRASFORMER BY UTILITY. COORDINATE
LOCATION AND REQUIREMENTS PER LOCAL UTILITY. CONTRACTOR
RESPONSIBLE FOR COMPENSATION TO UTILITY FOR ELECTRICAL
SERVICE.
http://www.tetratech.com/ w w w .te tra te ch .c om
C
H U
R C
H S
TR
EE
T, S
U
IT
E
H
U N
TS
VI
LL
E, A
LA
BA
M
A
TE
L.
: 2
-5
-0
EX
60/3
EX
60/3 NEW BOOSTER
PUMP #1
10 H.P.
240V, 3PH
NEW BOOSTER
PUMP #2
10 H.P.
240V, 3PH
3#10, 1#10(G.) 3/4"C.
EX. ELEC
PANEL "P"
EX. EQUIPMENT
CONTROL PANEL
"CP"
EX. WIREWAY, DISCONNECTS AND
STARTERS FOR BOOSTER PUMPS.
EX. PHASE CONVERTERS
FOR BOOSTER AND WELL
PUMPS.
5.
4.
3.
2.
1.
ELECTRICAL NOTES
VERIFY EX. CONDUCTOR, FUSE, CIRCUIT BREAKER AND DISCONNECT SIZES AS SHOWN
ON THIS DRAWING. PROVIDE A $5000. ALLOWANCE TO REPLACE CONDUCTORS, FUSES,
DISCONNECTS OR CIRCUIT BREAKERS. TO MATCH THESE CONDITIONS.
BECOME FAMILIAR WITH THE MECHANICAL AND DRAWINGS PRIOR TO THE
INSTALLATION OF THE ELECTRICAL SYSTEMS
ELECTRICAL WORK SHALL CONFORM TO THE N.E.C. AS A MINIMUM STANDARD.
ITEMS SPECIFIED BY BRAND NAME ARE ON AN "OR EQUAL" BASIS (UNLESS
OTHERWISE NOTED).
FIELD ADJUST THE CONDUIT AND EQUIPMENT LAYOUT TO CLEAR ANY OBSTACLES
THAT MIGHT BE IN THE WAY.
REFER TO THE APPROPRIATE DRAWING FOR THE EXACT LOCATION OF EQUIPMENT
INSTALLED UNDER DIVISIONS OF THE DOCUMENTS WHICH REQUIRE ELECTRICAL SERVICE.
EX. NEMA
SIZE 2
STARTER
EX.
30H.P MAX
ROTO PHASE
PHASE CONVERTER
EX. 60A DISCONNECT
W/ 35A TIME DELAY
FUSES
EX.
PANEL
"P"
EX. WIREWAY
EX.
175/2 C.B.
L1
L2
T1 T2 T3
EX. EQUIPMENT
CONTROL PANEL
"CP"
EX. 60A
DISCONNECT
EX. 60A
DISCONNECT
EX. 60A DISCONNECT
W/ 35A TIME DELAY
FUSESEX. 60A DISCONNECT
W/ 35A TIME DELAY
FUSES
NEW BOOSTER
PUMP #1
NEW BOOSTER
PUMP #2
10 10
EX. 3#6,1#8(G.)-1"C
EX. 2#2,1#6(G)-1"C.
EX. 3#10,1#10(G.)-3/4"C
3#10,1#10(G)-3/4"C
EX. 3#10,1#10(G.)-3/4"C
EX. 3#10,1#10(G.)-3/4"C
THE ELECTRICAL SCOPE OF WORK IN THIS AREA IS TO PROVIDE A NEW ELECTRICAL
CONNECTION TO FOR TWO BOOSTER PUMPS THAT ARE BEING REPLACED AND ANY
WORK AS DESCRIBED IN THE NOTES BELOW.
WELLHOUSE BOOSTER PUMP STATION
CAMP SITE AREA C
http://www.tetratech.com/
| E102 ADDENDUM 1.pdf |
| E-202 ADDENDUM 1 |
| E-204 ADDENDUM 1 |