QUESTION #1:
Checking with our wire and rope people there is not a shackles made that will meet your requirements that will fit the chain. Most only have a load limit of 55,000 lbs.
ANSWER # 1:
The chains and shackles are not required. Only the stop log is to be provided. As a reminder, the contractor is still required to deliver and unload the unit.
QUESTION #2:
Technical question Solicitation W912HN09T0094 1 Stop Log- Kerr Scott Reservoir
"On Drawing 5666-M15 there is roller Bearings as well as Bearing covers and seal housings called out. We were able to find bearings that were equivalent with exception to the case being steel not bronze or brass. Would this be okay or do you know where we can get them with bronze or brass cases. Both the bearing covers and seal housings are no longer available. If we were to machine this out of block it would be terribly expensive. How would you like us to quote these items?
ANSWER #2:
I assume that the contractor meant "cage" not case. SKF can provide the bearing with a brass cage. However, steel is acceptable. The drawing calls for the housing and cover to be cast steel not machined.
QUESTION #3:
Technical question Solicitation W912HN09T0094 1 Stop Log- Kerr Scott Reservoir
Another quick question on this solicitation is where we are to offload the stoplog at. If it is to be offloaded and placed or just offloaded in a storage yard?
Cant find weld sybols for either the flage of the ST beams to the skin plate or the 3/4" end plates to the skin plate. What welds (fillet, partial or full pen) do you want us to quote. Also what size?
ANSWER #3:
The stop log will be off loaded in a storage yard.
The weld symbols and sizes are shown in detail A-1 on M17.
Welds are to be full penetration.