W912ES24B0001-0003 PLAN SHEET CU501 Replacement - OHB Ring Levee 24Jan24 .pdf

PDF 508 KB Posted

Attached to
Ring Levee - Oxbow, Hickson, & Bakke (OHB) - Fargo Moorhead Metropolitan Area Flood Risk Management Project
Solicitation number
W912ES24B0001
Issued by

About this file

This document includes a plan sheet and federal contract opportunity notice. The plan sheet provides specifications for a storm sewer replacement project that is part of the Oxbow, Hickson, and Bakke Ring Levee portion of the Fargo-Moorhead Metropolitan Area Flood Risk Management Project. Work includes earthwork, excavation, storm sewer piping, riprap placement, and turf establishment.

The federal contract opportunity is seeking bids for construction of the OHB Ring Levee. It is a 100% small business set aside with an anticipated value between $10-25 million. The solicitation was issued by the U.S. Army Corps of Engineers, St. Paul District in accordance with FAR Part 14 procedures. The NAICS code is 237990 for other heavy and civil engineering construction with a size standard of $45 million. Payment and performance bonds are required in accordance with FAR Part 28.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

B

2/3 OD

D + 24in

(OD+B)/8

D

VARIES

3ft MIN.

MANHOLE

1/3 HEIGHT OF

6in MIN.

VARIES

C

D

AB

2ft

1.5ft

22'

2ft

54" DIA.

BACKFILL IN 12in LIFTS

OF 6in LIFTS

BACKFILL IN MAXIMUM

SPECIFICATIONS

OHSA SAFETY

SLOPE AS PER

OF 12in LIFTS

BACKFILL IN MAXIMUM

ROCK BED MATERIAL

SPECIFICATIONS

OHSA SAFETY

SLOPE AS PER

ON STRUCTURE SCHEDULE

CASTING AND LID AS NOTED

CHIMNEY SEAL

COVER

CONCRETE

RUBBER SLEEVE

EXTERNAL

AND WITH A 9"

PER ASTM C443

SEAL ALL JOINTS

DETAIL

CONNECTION

SEE PIPE

TO CHANNEL

FILLET SLOPE

12in O.C.

STEPS @

WITH COVER

2in LIP TO BE INTEGRAL

RIPRAP

FILTER FABRIC

GEOTEXTILE

FILTER FABRIC

GEOTEXTILE

(2" MIN. - 6" MAX.)

ADJUSTING RINGS

BACKFILL IN 12in LIFTS

RCP FLARED END SECTION

W/BOLT (TYP)

HINGED CONNECTION

6in MIN 4in MAX

INSIDE AND OUT

3000 PSI CONCRETE

4ft 4ft

4ft

4ft

4ft 4ft

4ft

4ft

4ft4ft 4ft4ft

PIPE CROSSED

PIPE

STORM SEWER

SEWER PIPE

WATER OR

CROSSED

PIPE

1.5ft

DETAIL

DETAIL

DETAIL

DETAIL

DETAIL

DETAIL

BOB

LMP

LMP

JDE

12/8/2023

21990

CU501

FMM43B_CU500---.dgn

DETAIL

1/23/2024

Amendment 003

INSTALL 60 DEGREES FROM TOP.

TIE LAST 3 PIPE JOINTS. USE 2 TIE BOLT FASTENERS PER JOINT.

ALL RIPRAP USED SHALL BE R20.

MATCH FLOWLINE OF RIPRAP TO FLOWLINE OF FLARED END SECTION.

MATCH TOP OF RIPRAP TO THE TOP EDGE (SIDES) OF FLARED END SECTION.

NOTES:

SECTION B-B

TYPICAL DIMENSIONS

A

48"

54"

60"

66"

72"

78"

84"

90"

96"

102"

108"

120"

B

5"

5.5"

6"

6.5"

7"

7.5"

8"

8.5"

9"

9.5"

10"

11"

C

66"

72"

78"

86"

92"

100"

106"

114"

120"

127"

132"

146"

D

6"

6"

8"

8"

8"

8"

8"

8"

8"

12"

12"

12"

SECTION A-A

PLAN VIEW

27" AND

SMALLER

30"-60"

60"+

IF ROCK

BEDDING

6"

6"

4"

3"

144" 13" 174" 12"

A-A

B-B

FINISHED GROUND

PIPE SIZE B

AT 60 DEGREES FROM TOP.

THE JOINTS. 2 TIE BOLT FASTENERS PER JOINT. INSTALL

ALL STORM SEWER UNDER THE STREET SHALL BE TIED AT

DETAIL SHALL BE USED FOR ALL MANHOLES AND CATCH BASINS.

ARE INCIDENTAL TO MANHOLE INSTALLATION.

ROCK FOR BEDDING AND COMPACTED GRANULAR MATERIAL

ADJUSTING RINGS.

2. ALL STRUCTURES 72in OR LARGER SHALL HAVE 1ft OF

WITH AN ECCENTRIC CONE FOR APPLICABLE SIZES.

1. TOP BARREL SECTION AND COVER SHALL BE SUBSTITUTED

NOTE:

ASTM A153.

3. ALL PARTS SHALL BE HOT DIP GALVANIZED PER

PER JOINT. INSTALL AT 60 DEGREES FROM TOP.

2. TIE LAST 3 PIPE JOINTS. USE 2 TIE BOLT FASTENERS

FABRICATION.

TO FLARED END SECTION. HOT DIP GALVANIZE AFTER

1. PROVIDE 3 ANCHOR CLIPS TO FASTEN TRASH RACK

NOTES:

24" MAX

6" MAX

TRASH RACK SIZING

PIPE SIZE

12"-18"

21"-42"

48"-72"

BOLTS

5/8"

3/4"

1"

BARS

3/4Ø

1"Ø

1 1/4"Ø

RCP PIPE

ABOVE CROSSING

SECTION A-A

BELOW CROSSING

SECTION B-B

PLAN VIEWPLAN VIEW

WATER OR SEWER PIPE

B-BA-A

BEDDING

PIPE

ON PIPE BEDDING

BOARD INSTALLED

INSULATION

2in POLYSTYRENE

WATER OR SEWER PIPE

3. WATER SERVICES MAY BE INSULATED WITH AN APPROVED ENCASEMENT INSULATION IN LIEU OF DETAIL.

POLYSTYRENE INSULATION BOARD SHALL BE USED.

2. IF AMOUNT OF CLEAR DISTANCE BETWEEN PIPES IS LESS THAN 1.0', 2 LAYERS OF 2"

1. THIS DETAIL APPLIES TO BOTH MAINS & SERVICES WHERE CROSSING IS WITHIN 24".

NOTES:

DENSITY

PROCTOR

95% STANDARD

COMPACTED TO

NATIVE SOIL

SPECIFICATION 31 00 00.00 13

SELECT GRANULAR FILL PER

SLEEVE

EXTERNAL RUBBER

C990 AND WITH A 9"

WITH MASTIC PER ASTM

SEAL TOP SLAB JOINT

DRAWN BY:

CHECKED BY:

DATE:

REVISED:

REVISED:

PROJ. MANAGER:

PROJ. DESIGNER:

REVISED:

54321

D

B

A

RECORD:

FILE NAME:

C

W O

R K

P A

C K

A G

E

B

S

T O

R M

S E

W E

R

O X

B O

W

H

IC

K S

O N

B

A K

K E

R

IN

G L

E V

E E

P

H A

S E

B

PROJECT NO.

C A

S S

C O

U N

T Y

N

O R

T H

D A

K O

T A

R E

E

NI

G N

E L

ANOISSEFORP

D

E R

E T

SI

G

E R

ATOKAD HTR

O

N

PE-6087

BRETT O. BAILLY

DATE: 01/23/2024

T

IM

E

D

A T

E

M

O D

E L

N A

M E

F

IL

E

L

NOT TO SCALE

RCP STORM TRENCH*

NOT TO SCALE

MANHOLE/CATCH BASIN TRENCH

NOT TO SCALE

STORM SEWER MANHOLE/CATCH BASIN

NOT TO SCALE

RIPRAP AT FLARED END SECTION OUTLET

NOT TO SCALE

TRASH RACK - RCP FLARED END SECTION

NOT TO SCALE

STORM SEWER PIPE CONNECTION

D E

T A

IL

S

S

T O

R M

S E

W E

R

NOT TO SCALE

INSULATION FOR STORM CROSSING