W912ES21Q0115.pdf

PDF 878 KB Posted

Attached to
Electric Portable Submersible Water Pump
Solicitation number
W912ES21Q0115
Issued by

View the file

Other files

File Type Posted
W912ES21Q01150001.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEE ADDENDUM

(No Collect Calls)

W912ES21Q0115 16-Sep-2021

b. TELEPHONE NUMBER

651-290-5415

8. OFFER DUE DATE/LOCAL TIME

02:00 PM 27 Sep 2021

5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE

AUTHORIZED FOR LOCAL REPRODUCTION

PREVIOUS EDITION IS NOT USABLE

STANDARD FORM 1449 (REV. 2/2012)

Prescribed by GSA – FAR (48 CFR) 53.212

(TYPE OR PRINT)

(SIGNATURE OF CONTRACTING OFFICER)

ADDENDA ARE

26. TOTAL AWARD AMOUNT (For Gov t. Use Only )

23.

CODE 10. THIS ACQUISITION IS

SUCH ADDRESS IN OFFER

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT

BELOW IS CHECKED

TELEPHONE NO.

W912ES9. ISSUED BY

18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a. UNLESS BLOCK

7. FOR SOLICITATION

INFORMATION CALL:

a. NAME

THEODORE R HECHT JR

2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NUMBER

(TYPE OR PRINT)

30b. NAME AND TITLE OF SIGNER 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER

30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a.UNITED STATES OF AMERICA

0 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1. 52.212-4. FAR 52.212-3. 52.212-5 ARE ATTACHED.

25. ACCOUNTING AND APPROPRIATION DATA

1. REQUISITION NUMBER

20.

ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED.

OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, AND 30

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS

ARE NOT ATTACHED

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED

(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE

SET FORTH HEREIN, IS ACCEPTED AS TO ITEMS:

. YOUR OFFER ON SOLICITATION

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN

% FOR:SET ASIDE:UNRESTRICTED OR X

SMALL BUSINESSX

17a.CONTRACTOR/ CODE FACILITY

OFFEROR CODE

CONTRACTING DIVISION

USACE - ST PAUL

180 FIFTH STREET EAST

SUITE 700

SAINT PAUL MN 55101-1678

18a. PAYMENT WILL BE MADE BY CODE

RATED ORDER UNDER

DPAS (15 CFR 700)

13a. THIS CONTRACT IS A

13b. RATING

CODE15. DELIVER TO CODE 966325 16. ADMINISTERED BY

12. DISCOUNT TERMS11. DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

X SEE SCHEDULE

14. METHOD OF SOLICITATION

RFQ IFB RFPX

LOCK & DAM #7

JARROD BROWN

33018 HIGHWAY 61

LA CRESCENT MN 55947-9538

TEL: FAX:

FAX:

TEL: 651-290-5414 SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

8(A)

HUBZONE SMALL

BUSINESS

SIZE STANDARD:

NAICS:

333914

X

OFFER DATED

29. AWARD OF CONTRACT: REF.

DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND

EMAIL:

TEL:

31c. DATE SIGNED

SEE SCHEDULE

SCHEDULE OF SUPPLIES/ SERVICESITEM NO. QUANTITY UNIT UNIT PRICE AMOUNT

24.22.21.19.

WOMEN-OWNED SMALL BUSINESS (WOSB)

ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

32g. E-MAIL OF AUTHORIZED GOVERNMENT REPRESENTATIVE

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS

(CONTINUED)

PAGE 2 OF30

ACCEPTED, AND CONFORMS TO THE CONTRACT, EXCEPT AS NOTED: ______________________________________________________

32a. QUANTITY IN COLUMN 21 HAS BEEN

RECEIVED INSPECTED

32b. SIGNATURE OF AUTHORIZED GOVERNMENT

REPRESENTATIVE

32c. DATE 32d. PRINTED NAME AND TITLE OF AUTHORIZED GOVERNMENT

REPRESENTATIVE

32e. MAILING ADDRESS OF AUTHORIZED GOVERNMENT REPRESENTATIVE 32f . TELEPHONE NUMBER OF AUTHORIZED GOVERNMENT REPRESENTATIVE

37. CHECK NUMBER

FINALPARTIALCOMPLETE

36. PAYMENT35. AMOUNT VERIFIED

CORRECT FOR

34. VOUCHER NUMBER

FINAL

33. SHIP NUMBER

PARTIAL

38. S/R ACCOUNT NUMBER 39. S/R VOUCHER NUMBER 40. PAID BY

41a. I CERTIFY THIS ACCOUNT IS CORRECT AND PROPER FOR PAYMENT

41b. SIGNATURE AND TITLE OF CERTIFYING OFFICER 41c. DATE

42a. RECEIVED BY (Print)

42b. RECEIVED AT (Location)

42c. DATE REC'D (YY/MM/DD) 42d. TOTAL CONTAINERS

STANDARD FORM 1449 (REV. 2/2012) BACK

Prescribed by GSA – FAR (48 CFR) 53.212

AUTHORIZED FOR LOCAL REPRODUCTION

PREVIOUS EDITION IS NOT USABLE

SEE SCHEDULE

20.

SCHEDULE OF SUPPLIES/ SERVICES

21.

QUANTITY UNIT

22. 23.

UNIT PRICE

24.

AMOUNT

19.

ITEM NO.

Section SF 1449 - CONTINUATION SHEET

SCOPE OF WORK

TECHNICAL REQUIREMENTS

SUPPLY CONTRACT FOR LOCK 7

SUBMERSIBLE

PUMPING EQUIPMENT

INDEX

PARAGRAPH DESCRIPTION PAGE

PART 1 GENERAL

1.1 SCOPE 15161-1

1.2 APPLICABLE PUBLICATIONS 15161-1

1.3 SUBMITTALS 15161-2

PART 2 PRODUCTS

2.1 GENERAL REQUIREMENTS 15161-4

2.2 MATERIALS 15161-5

2.3 ELECTRIC SUBMERSIBLE PUMPS 15161-6

2.4 SPARE PARTS AND SPECIAL TOOLS 15161-10

PART 3 EXECUTION

3.1 FABRICATION AND MACHINING 15161-11

3.2 FACTORY TEST 15161-12

3.3 SHIPPING AND DELIVERY 15161-14

3.4 WARRANTY 15161-15

SUBMERSIBLE

PUMPING EQUIPMENT

PART 1 GENERAL

1.1 SCOPE: This section covers the requirements to supply an electric, portable, submersible, trash type pumps for the dewatering work at Lock and Dam 7 with an option for second pump.

1.2 APPLICABLE PUBLICATIONS: The following publications of the issues listed below, but referred to thereafter by basic designation only, form a part of this section to the extent referenced:

1.2.1 American Society for Testing and Materials (ASTM):

A27 (2020) Steel Castings, Carbon, for General Application.

A 36 (2019) Structural Steel.

A 48 (2021) Gray Iron Castings.

A 276 (2017) Stainless and Heat-Resisting Steel Bars and Shapes.

A 285 (2017) Pressure Vessel Plates, Carbon Steel, Low and Intermediate Tensile Strength.

A 516 (2015) Pressure Vessel Plates, Carbon Steel, for Moderate and Lower

Temperature Service.

A 564 (2019) Hot-Rolled and Cold-Finished Age-Hardening Stainless and Heat- Resisting Steel Bars and Shapes.

A 576 (2017) Steel Bars, Carbon, Hot Rolled, Special Quality.

A 668 (2020) Steel Forgings, Carbon and Alloy, for General Industrial Use.

B 148 (2018) Aluminum-Bronze Sand Castings.

B 584 (2014) Copper Alloy Sand Castings for General Applications.

1.2.4 National Fire Protection Association (NFPA):

No. 70 (2020) National Electrical Code (NEC).

1.3 SUBMITTALS: Government approval is required for the following submittals:

1.3.1 Shop Drawings including catalog cuts and manufacturer's data, shall be submitted for approval. Shop drawings shall be neat, legible, and of sufficient size to be easily read and/or reproduced. The following items shall be submitted:

a) Outline drawings of proposed pumps showing all pertinent dimensions and weight of the various components of the pumps. A listing of previous pumps produced, and their installation locations shall be furnished. A description of the pump service facility and location shall be submitted.

b) Dimensioned cross-sectional drawings of the pumps and components and motors. Motor data shall be furnished that shows dimensional data and operating speed. Wear ring system shall be indicated. Bearing system and bearing life data shall be provided. Pump shaft seal system shall be submitted.

c) The proposed coating (painting) systems and procedures for the pumps and components.

d) Factory certified pump capacity-head curves shall be provided with the brake horsepower (BHP) and the net positive suction head required (NPSHR) requirements presented; operating points shall be indicated. Efficiency data shall be plotted.

e) Warranty. A copy of the pump warranty for each pump provided shall be submitted.

f) Discharge Elbow and floor stand. Submit material and dimensional data.

g) Motor controllers and starters and disconnects.

1.3.2 Installation and Erection Instructions: The Contractor shall submit five copies of a printed and bound manual describing the procedures, to be followed for erecting, assembling, and installing the pumps. The proposed manuals shall be submitted with the pump shop drawing submittals. It shall describe all special procedures and outline special precautions. It shall also include such things as bolt torque values, permissible wear ring clearances, recommended instrument set-ups, recommended gages and instruments, bearing clearances, and similar details.

1.3.3 Operation and Maintenance Manual: The Contractor shall submit, prior to delivery of any pumps, manuals containing complete information in connection with the operation, lubrication, adjustment, routine and special maintenance, disassembly, repair, and re-assembly of the pumps and accessories. A total of 5 copies shall be submitted. The manual shall also have a listing of special tools required for working on the pumps. The manual shall include complete diagnostic information on the pumps and all approved shop drawing submittals on the pumps.

1.3.3.1 Parts list: The operation and maintenance manual shall have a complete parts list for the pumps.

The list shall clearly show all details and parts, and all parts shall be adequately described and have identification markings and include sources for all parts.

1.3.3.2 Manuals shall be made up with hard cover post type binders or 3-ring binders and printed on 8-1/2 inch by 11-inch-high quality paper with indexed, tabbed section dividers. Large sheets shall be neatly folded and installed with post hole reinforcements such that sheets can unfold without need to open binder posts.

Drawings, sketches, and parts lists incorporated in the manual may be reduced to page size provided such reductions are clear and easily legible, otherwise they may be folded into the manual.

PART 2 PRODUCTS

2.1.2 Standard Products: All pumps supplied shall be the product of a pump manufacturer who has produced at least 200 units of the same style pump required under this contract. Half of these units shall have been operating in the United States for at least five years prior to the contract award date. A record of this shall be furnished as a shop drawing. All pumps furnished under this contract shall be from the same pump manufacturer.

2.1.3 Service Availability. The pumps furnished shall be supported by a service organization. Service and parts shall be available within 300 miles of the Fountain City, Wisconsin area. This information shall be provided in a shop drawing.

2.1.5 Nameplates: Each major item of equipment shall have the manufacturer's name, address, type/style, model, serial number, and catalog number on a plate secured to the item of equipment. Nameplates shall be made of corrosion resisting metal with raised or depressed lettering on a contrasting-colored background.

2.1.6 Instruction Plates: As necessary, each item of equipment shall be equipped with suitably installed instruction plates including warnings and cautions describing special and important procedures to be followed during starting, operating, and servicing the equipment. The plates shall be made of corrosion resisting metal with raised or depressed lettering on a contrasting-colored background.

2.2 MATERIALS:

2.2.1 Materials not specifically described shall, as far as practicable, conform to the latest approved industry standard(s) covering the appropriate class or types of materials.

2.2.2 Designated items shall conform to the following:

Item Requirements

Cast Iron ASTM A 48, Class No. 30A, 30B and 30C Cast Steel ASTM A 27, Grade 65-35, annealed Copper Alloy Castings ASTM B 584, Alloy No. C93700 or C86300 Structural Steel ASTM A 36 Cold Rolled Steel Bars ASTM A 108, Minimum Working Strength 65,000 pounds per square inch Hot Rolled Steel Bars ASTM A 576, Grades: G10200, G10450, G11410 Hot Rolled Stainless ASTM A 564, Grade 517400

Bars and Shapes:

Steel Plates, Structural ASTM A 285, Grade B Steel Plates, Pressure ASTM A 516, Grade 55 Vessel Steel Forgings ASTM A 668, Class F

2.2.3 Discharge Elbows. Each pump shall have a pump discharge elbow furnished. The elbow shall be a flanged, 90° long radius, 8-inch discharge.

2.2.4 Stands. Each trash pump shall come equipped with a stand capable of supporting the pump and discharge elbow. The stand must allow the pump assembly to be positioned flat on the lock floor. Floor stand size shall be minimized to extent possible to save space. These pumps will be installed by the Government next to other pumps in a sump area of the lock.

2.3 ELECTRIC SUBMERSIBLE PUMPS:

2.3.1 Portable Trash Pump Requirements. The Contractor shall supply a portable trash pump. The pumps shall be the electric, centrifugal, submersible type with closed non-clog impellers. Pumps shall be 8-inch diameter. Each pump shall be capable of pumping solids up to 3" in diameter. Pumps shall be capable of pumping solids and suspended solids including sand and debris commonly found in river water.

2.3.2 Pump Quantities, Capacities, and Total Dynamic Head (T.D.H): Pump Quantity, capacities, and required pumping head as follows:

Quantity Pump Capacity Total Dynamic Head in Feet of Water (T.D.H) 1 with option for a second 2500 gpm 40

(1) Primary condition point: Discharge not less than pump size stated against a Total Dynamic Head in Feet of Water (TDH) as stated. Pumps shall be minimum 75% overall efficient at the condition point stated above. The Net Positive Suction Head (NPSH) required by the pump, at any point throughout the range of capacities and heads against it will operate, shall not be more than the NPSH available. The NPSH available shall be computed at the site elevation for Minneapolis, Minnesota and a water temperature of 85 degrees Fahrenheit.

2.3.3 Speed: The speed of the pumps shall not exceed values stated below. Pumps will be rejected if speeds exceed these values.

Pump Size Speed 2500 gpm 1200 RPM

2.3.4 Pump casings: Pump casings shall be made of ASTM A 48, Class 30, cast iron. The casing shall be of single piece design and shall have smooth fluid passages.

2.3.5 Nuts and bolts: All bolts used in assembling each pump and its supporting members shall be of corrosion resisting steel and shall be hexagonal type. Stainless steel cap screws conforming to ASTM A 276, Type 316, and used with silicon bronze nuts or stainless-steel nuts, will be permitted as will silicon bronze cap screws with tapped casting holes.

2.3.6 A wear ring system shall be installed to provide efficient sealing between the volute and impeller. The wear ring shall consist of a stationary ring made of bronze insert press-fitted into the volute inlet, and a rotating stainless-steel ASTM A276, Type 316 ring force-fitted into the impeller runner.

2.3.7 Impellers: Impellers shall be gray cast iron conforming to ASTM A48 Class 30, or of aluminum bronze conforming to ASTM B 148 Grade D; and non-clogging design having a long thrulet without acute turns.

The impellers shall be capable of handling solids found in stormwater such as trash and fibrous materials.

Impellers shall be capable of passing 3” solids. Impellers shall be capable of handling suspended solids such as sand and debris commonly found in river water.

2.3.7.1 Minor surface imperfections shall be filled and/or ground down as necessary to preserve the correct contour and outline of the impeller and restore the surface imperfections to the same degree of finish as the surrounding surfaces. Surface pits, depressions, projections, or overlaps showing greater than 1/16 of an inch variation from the general contour for that section shall be corrected.

2.3.8 Shafts and Seals: Pump and drive shaft shall be a single combined shaft. The pump shaft and drive shaft shall be of ASTM A276, Type 420 stainless steel or an alternate stainless steel, as approved, and shall be completely isolated from the pumped liquid. Carbon steel pump shafts with a stainless-steel sleeve will not be acceptable.

2.3.9 The pump shall be provided with a tandem mechanical rotating shaft seal system. Seals shall run in an oil reservoir. Lapped seal faces must be hydrodynamically lubricated at a constant rate. The lower seal unit, between the oil sump and the volute, shall contain the following:

Lower Seal Unit: One stationary silicon carbide and one positively driven silicon carbide rotating ring.

The upper seal unit, between the motor housing and oil sump, shall contain:

Upper Seal Unit: One positively driven silicon carbide rotating ring and one stationary silicon carbide seal.

Alternate seal materials will not be accepted. Positively driven means the rotating seal is driven from the shaft by virtue of a mechanical connection (i.e., set screw, clip, key, etc.). The use of an elastomeric sealing member driving the seal face by friction on the shaft surface shall not be permitted. Each seal interface shall be held in contact by its own spring system. The seals shall require neither maintenance nor adjustment but shall be easily inspected and replaceable. Shaft seals without a positively driven rotating member or conventional double mechanical seals containing a common single spring acting between the upper and lower unit shall not be accepted. Each pump shall be provided with an oil chamber for the shaft sealing system. The oil chamber shall be designed to assure that air is left in the oil chamber, to absorb the expansion of the oil due to temperature variations. The drain and inspection ports, with positive anti-leak seal, shall be easily accessible from the outside of the pump.

2.3.10 Bearings: The pump shaft shall rotate on at least two permanently lubricated bearings. The upper bearing shall be the angular contact ball type and the lower bearing shall consist of two or more rows of angular contact ball bearings. Each bearing shall have a minimum B10 bearing life (100,000 hours). The bearing life data shall be shown in a shop drawing.

2.3.11 Pump Lifting System: Each furnished pump shall be equipped with a lifting bar to facilitate handling.

The lifting bars shall be manufactured of stainless steel. The bar shall be so designed and arranged to allow safe handling of the pump as required during shipping, installation, and maintenance.

2.3.12 Cooling System: Each pump unit shall have an adequately designed cooling system, consisting of a water jacket which encircles the stator housing. The water jacket shall be provided with a separate circulation of the pumped liquid. Cooling media channels and ports shall be non-clogging by virtue of their dimensions. All cooling paths or ports shall be internal to the pump and motor water jacket to preclude clogging or physical abuse. Cooling system shall be designed to allow for continuous pump operation at rated capacity with the external water level at the minimum pump submergence level.

2.3.13 Torsional Vibration and Critical Speeds: The assembled pumping unit, consisting of the motor and pump shall be free of critical speeds or harmful torsional vibrations at all speeds encountered within the operating range.

2.3.14 Painting: Pump exteriors shall be painted with a PVC epoxy primer and a chloric rubber paint or epoxy paint or manufacturer’s standard paint system, as approved.

2.3.15 Electrical: Pump motors shall be squirrel-cage, induction, shell type design, housed in an air-filled watertight chamber, and NEMA Design B type. Oil filled motors will not be acceptable. The pump unit and motor unit shall be closed coupled to form a single integral unit. The stator winding and stator leads shall be insulated with moisture resistant Class F insulation which will resist a temperature of 155 oC. The stator shall be dipped and baked three times in Class F varnish. The motor shall be designed for continuous duty, capable of sustaining a minimum of ten starts per hour. The rotor bars and short circuit rings shall be made of copper or aluminum. Thermal switches shall be embedded in the stator lead coils to monitor the temperature of each phase winding.

2.3.15.1 Rating: Each motor shall be wound for 3-phase, 60 Hz, alternating current, and 480-volt operation.

The motor shall be designed for operation in a 20°C ambient temperature and all temperature rises shall be above this ambient temperature. The rated horsepower of the motor shall be not less than 110 percent of the determined maximum load requirement for the full capacity-head curve of the pump. The motor shall have a service factor of 1.15. The temperature rise above the ambient temperature for the class of insulation used shall be in accordance with paragraph MG 1-12.42 of NEMA MG 1.

2.3.16 Pump cables: Each pump shall be supplied with 100' of electrical cable. Each motor cable shall be suitable for submersible pump application and such information shall be indicated by a code or legend permanently embossed on the cable. Cable sizing for pump motors shall conform to NFPA No. 70.

2.3.16.1 Cable entry: The cable entry water seal design shall preclude specific torque requirements to insure a watertight and submersible seal. Cable entry system shall be the same for both the power and control cables. The cable entry shall be comprised of a single cylindrical elastomer grommet, flanked by washers, all having a close tolerance fit against the cable outside diameter and the entry inside diameter.

The assembly shall bear against a shoulder in the pump top. The cable entry junction chamber and motor shall be separated by a stator lead sealing gland or terminal board, which shall isolate the motor interior from foreign material gaining access through the pump top. The junction chamber, containing the terminal board, shall be sealed from the motor by elastomeric compression seal O-ring. Connection between the cable conductors and stator leads shall be made with threaded compressed type binding post permanently affixed to a terminal board and shall be made leak proof.

2.3.17 Alarms: The following alarm features shall be provided:

a) Over temperature alarm: The motor over temperature alarm circuit shall be actuated by three thermal sensors embedded in the stator windings of the pump motor (one switch in each stator phase). The pump motor shall stop on over temperature and not restart until the over temperature alarm is manually reset and the motor temperature has cooled to the appropriate temperature.

b) Overload alarm: The motor overload circuit on the pump motor shall stop the motor upon overload and not restart until the overload condition is corrected and manually reset.

c) Lower seal failure alarm: Leakage sensor shall be provided in the oil chamber. The sensor shall activate an alarm when water concentration exceeds 30%.

d) Stator Leakage Sensor: Sensor shall activate an alarm and stop the motor when any water is detected.

2.3.18 Pump Interface Modules. Pump supplier shall furnish any electrical interface modules necessary for the pump sensors to communicate with the control system. Interface modules shall be adaptable to any type of standard control system. Interface modules shall be match marked to each pump.

2.3.19 Float Switches. Provide each trash pump with attached float switch. Float switch shall be on-off only.

2.3.20 Motor Controllers with Disconnect Switch. The trash pump unit shall be equipped with a motor controller with integral disconnect switch. The motor controller shall include starters and be Full Voltage Non-Reversing single speed type.

2.3.21 Controller Features. Controllers shall have on/off selector switch. Switch shall be of the heavy-duty, oil-tight type; rated 600 volts ac. Contacts shall be rated for 10 amperes. Provide switch with escutcheon plate clearly marked to show operating positions “On” and “Off”. Motor overload protective devices and power monitor devices shall be connected in motor control circuit in "On" position.

2.3.21.1 The motor controller shall include a manually operated, lockable, non-fused switch which disconnects motor from power supply source. Provide disconnecting means capable of being locked out to prevent unexpected startup or release of stored energy in accordance with 29 CFR 1910.147. Motor Controller enclosure shall be type 3R as specified in NEMA 250.

2.3.22 Controller Requirements. The motor control shall include a 120-volt ac control relay. Relay shall be of the electrically operated, magnetically held, self-reset, open type, suitable for mounting inside the motor controller enclosure. Contacts shall be rated for 10 amperes. Motor controller shall be provided with three NEMA Class 20 thermal overload relay protection, one in each phase of the motors. Size of the Overload protective heater elements to be installed shall be based on motor nameplate data and shall include a manual reset-type pushbutton on outside of motor controller case.

2.3.22.1 The motor controller shall have a magnetic type undervoltage protection, size 3 contactor and shall have one spare normally open and one spare normally closed auxiliary contact that do not share common electrical connections. Motor control wire shall be stranded tinned copper switchboard wire with 600-volt flame-retardant insulation Type SIS meeting UL 44, or Type MTW meeting UL 1063. Hinge wire shall have Class K stranding. The minimum size of control wire shall be No. 14 AWG. Power wiring for 480-volt circuits and below shall be of the same type as control wiring and the minimum size shall be No.

12 AWG. Special attention shall be given to wiring and terminal arrangement on the terminal blocks to permit the individual conductors of each external cable to be terminated on adjacent terminal points.

Control circuit terminal blocks for control wiring shall be molded or fabricated type with barriers, rated not less than 600 volts. The terminals shall be removable binding, fillister or washer head screw type, or of the stud type with contact and locking nuts. The terminals shall be not less than No. 10 in size and shall have sufficient length and space for connecting at least two indented terminals for 10 AWG conductors to each terminal. The terminal arrangement shall be subject to the approval of the Contracting Officer and not less than four (4) spare terminals or 10 percent, whichever is greater, shall be provided on each block or group of blocks. Modular, pull apart, terminal blocks will be acceptable provided they are of the channel or rail-mounted type.

2.3.22.2 Load terminal blocks rated not less than 600 volts and of adequate capacity shall be provided for the conductors for NEMA Size 3 motor controllers and for other power circuits, except those for feeder tap units. The terminals shall be of either the stud type with contact nuts and locking nuts or of the removable screw type, having length and space for at least two indented terminals of the size required on the conductors to be terminated.

For conductors rated more than 50 amperes, screws shall have hexagonal heads. Conducting parts between connected terminals shall have adequate contact surface and cross-section to operate without overheating. Each connected terminal shall have the circuit designation or wire number placed on or near the terminal in permanent contrasting color.

2.4 SPARE PARTS AND SPECIAL TOOLS:

2.4.1 The Contractor shall furnish all specials tools that are unique to the pump for proper installation, testing, operation, and/or maintenance. Special tools shall be delivered with the pumps. Provide two sets of any special tools.

2.4.2 Spare Parts: All spare parts shall be duplicates of the original parts furnished and shall be interchangeable with those parts. The Contractor shall furnish at a minimum the following spare parts:

(a) One complete set of seal assemblies (upper and lower) for one 2500 gpm pump.

(b) One complete replacement set of: wear rings, stationary and rotating for one 2500 gpm pump.

(c) One complete replacement set of O-rings for one 2500 gpm pump.

PART 3 EXECUTION

3.1 FABRICATION AND MACHINING:

3.1.1 Machine Work: All tolerances, allowances, and gauges for metal fits between plain, non-threaded cylindrical parts shall conform to ASME B4.1 for the class of fit required.

3.1.2 Castings: Each casting shall have a mark number cast or stamped upon it. In addition, each casting weighing more than 500 pounds shall have the heat number cast or stamped upon it. Warped or otherwise distorted castings that are oversize to an extent that could interfere with proper fit with other parts of the machinery or structure will be rejected. Cracked castings of non-weldable materials (i.e., cast iron, etc.) will be rejected. Repairs to castings shall not be made without prior approval.

3.1.2.1 Casting repair: Castings shall have all unsound material or defects removed by chipping, machining, arc gouging, or grinding; and shall be repaired by welding. Welding repairs shall conform to the welding procedures which shall have been submitted and approved for the type material involved. Stress relief annealing, where required, shall be accomplished prior to final machining.

3.1.3 Bolted Connections: Bolts, nuts, and washers shall conform to the applicable requirements of PARAGRAPH: MATERIALS AND MATERIAL STANDARDS for the types required.

3.1.4 Holes for regular bolts shall be drilled or sub-drilled and reamed in the shop. Holes shall be accurately located, smooth, perpendicular to the member, and cylindrical.

3.1.5 Holes for fitted bolts shall be match-reamed or drilled in the shop. Holes shall be smooth, perpendicular to the member, and cylindrical. Burrs resulting from reaming shall be removed. The threads shall be entirely outside of the holes. The body diameter of the bolt shall have tolerances as recommended by ASME B4.1 for the class of fit required. Fitted bolts shall be fitted in reamed holes by selective assembly to provide an LN-2 fit.

3.1.6 Holes for high-strength bolts shall be accurately spaced, perpendicular to the member, and cylindrical.

If the thickness of the material is greater than the diameter of the bolt, the holes shall be either drilled full size or shall be sub-drilled and then reamed to full size. Poor matching of holes will be cause for rejection.

Drifting done during assembly shall not distort the metal or enlarge the holes. For slight mismatching, reaming to a larger diameter for the next standard size bolt will be allowed.

3.2 FACTORY TEST:

3.2.1 General: All pumps provided shall be factory tested and have certified factory test curves. No pumps shall be delivered to the project work site until the factory testing has been completed for that particular pump and the Government has accepted the factory test results. Testing shall be in accordance with HI "Standards for Centrifugal, Rotary and Reciprocating Pumps".

W912ES21Q0115

3.2.2 Performance Test: The test shall be sufficiently extensive and complete to demonstrate that the proposed pump operates without instability and complies with the required performance. Compliance with the contract requirements will be determined from the curves required below. The temperature of the water used for testing shall be approximately the same for all test runs.

3.2.3 Pump performance: The performance of the furnished pumps shall be determined by a series of test points sufficient in number to develop a constant speed curve over the range of total heads, from 5.0 feet to 50.0 feet (or to shut off head) inclusive, for the speeds involved. Tests shall be made using specified heads and a suction water elevation above the motor. Head differentials between adjacent test points shall not exceed 2.0 feet. If the plot of the data indicates a possibility of instability in the head versus capacity curve, a sufficient number of additional points shall be made to clearly define the head-capacity characteristics.

3.2.4 Test results: The results of the tests shall be plotted to show total head, brake horsepower, net positive suction head required, and efficiency as ordinates; all plotted against the pump discharge in gallons per minute as the abscissa. The above curves shall be plotted to a scale that shall permit reading head directly to five-tenths of one foot, capacity to 100 gallons per minute, efficiency to one percent, and power input to 2 horsepower. Net positive suction head required data may be based on original design data or previous test information.

3.2.5 Test Report: Each test report shall include as a minimum the following:

(a) A description of test procedure used.

(b) A discussion of test results.

(c) Conclusions.

(d) Copies of all recorded test data.

(e) Curves showing performance of furnished pump.

3.3 SHIPPING AND DELIVERY:

3.3.1 The Government work force shall be responsible for the installation and operation of the portable trash pumps.

3.3.2 Delivery. By October 22, 2021, the Contractor shall deliver all materials required by the provisions of this contract to:

Mississippi River Lock and Dam 7 33018 Highway 61 La Crescent MN 55947-9538

507-895-2170

3.3.3 Acceptance. Payment for pumping equipment shall be made upon acceptance at the designated point of shipment. Within five calendar days after delivery to the designated point of shipment, the items shall be inspected by the Government. The inspection shall include an accounting of the items delivered and a visual inspection to determine any possible damage during shipment. If this inspection reveals any defects or deviations from contract requirements which could render the items unsuitable for the use intended, the Contractor shall repair each such identified deficiency. In the event deficiencies cannot be acceptably corrected, the equipment will be subject to rejection.

3.3.4 Packaging and Marking: The Contractor shall insure to have the pumps delivered as completely assembled and wired as feasible to minimize site installation work. The manufacturer's standard packing method, as approved, for the pumps shall be submitted at least 10 calendar days prior to the shipping date.

Items to be shipped shall be protected against moisture or water damage and always kept dry. The pumps shall be crated to protect them from damage during shipment and storage: crating shall allow vertical storage. Any relay or other device which cannot withstand the hazards of shipment when mounted in place shall be carefully packed and shipped separately.

3.3.5 Spare Parts and Special Tools: Spare parts and special tools shall be packed separately using the manufacturer's standard packing method as approved. Spare parts shall be clearly labeled and marked.

3.3.6 Packing Lists: Packing lists shall accompany all items shipped and be placed in moisture-proof containers securely fastened to the side of each item. Two copies of each packing list shall be submitted to the Government at least ten calendar days prior to each shipment date.

3.4 PUMP WARRANTY

3.4.1 Pumps shall be covered under a 1-year industry standard warranty. Warranty period shall start from the date of delivery.

NOTES TO QUOTERS

This section provides general guidance for preparing the quotation in response to this solicitation. The Quoter’s response to this solicitation must include all data and information requested herein in accordance with these instructions.

Price Proposal: This is the solicitation in its entirety. Quoter to complete the following:

Standard Form 1449 Solicitation/Contract/Order for Commercial Items - Complete Blocks 17, and 30a/b/c

Acknowledgement of Amendments – Complete only as necessary and provide signed copies of the Standard Form 30 Amendment of Solicitation/Modification of Contract with your quote.

Price Quote– All pricing (unit, total, subtotal, grand total, etc.) must be in whole penny amounts.

o Note: Freight and/or shipping & handling charges shall be included in the unit price. Please do not quote freight charges separately.

FAR Clause 52.212-3 Offeror Representations and Certifications – Commercial Items (Feb 2021) Alternate I (Oct 2014) – This provision is included by reference. Review paragraph (b)(2) “Annual Representations and Certifications” of the basic clause at https://www.acquisition.gov/, complete as necessary and return one copy with your quote.

Submitting Quotes – All transmittals shall be submitted electronically to Theodore.R.Hecht@usace.army.mil and be clearly marked in the subject line of the email with the solicitation number, W912ES21Q0115. Quotes must be received no later than the date and time stated in the solicitation. Quotes received after the deadline are Late and may not be considered for contract award.

Questions – All questions concerning the solicitation document shall be submitted via email to Theodore.R.Hecht@usace.army.mil. Answers to questions will be provided to all quoters being solicited though an amendment, giving due regard to the proper protection of proprietary information.

QUOTERS SHALL BE REGISTERED IN SAM (System for Award Management) https://www.sam.gov to include the FAR and DFARS Reps and Certs sections (refer to FAR Clause 52.204-13 “System for Award Management Maintenance”).

INSTRUCTIONS FOR 252.232-7003

Due to system limitations the clause 252.232-7003 has been added to the contract. As the St. Paul District of the Corps of Engineers does not use WAWF, and our financial management system does not allow for direct electronic submission of payment requests the terms of clause 252.232-7003 do not apply to this contract. The vendor shall submit invoices via email to Michael.A.Holzer@usace.army.mil or by paper copy to:

US Army Corps of Engineers ATTN: Michael Holzer 431 North Shore Drive Fountain City, WI 54629

ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

SUBMERSIBLE PUMPING EQUIPMENT

FFP

NET AMT

0001AA 1 Each electric, portable, submersible pump

FFP

3 phase 480v electric, portable, submersible, trash type pumps for the dewatering work FOB: Destination

PSC CD: 4320

0001AB 1 Each OPTION Optional second pump

FFP

option to buy a second pump same as CLIN0001AA if pricing is low enough

PSC CD: 4320

INSPECTION AND ACCEPTANCE TERMS

Supplies/services will be inspected/accepted at:

CLIN INSPECT AT INSPECT BY ACCEPT AT ACCEPT BY

0001 N/A N/A N/A N/A 0001AA N/A N/A N/A Government 0001AB N/A N/A N/A Government

DELIVERY INFORMATION

CLIN DELIVERY DATE QUANTITY SHIP TO ADDRESS DODAAC /

CAGE

0001 N/A N/A N/A N/A

0001AA 22-OCT-2021 1 LOCK & DAM #7

JARROD BROWN

33018 HIGHWAY 61

LA CRESCENT MN 55947-9538

966325

0001AB 22-OCT-2021 1 (SAME AS PREVIOUS LOCATION)

966325

CLAUSES INCORPORATED BY REFERENCE

52.204-7 System for Award Management OCT 2018 52.204-13 System for Award Management Maintenance OCT 2018 52.204-16 Commercial and Government Entity Code Reporting AUG 2020 52.204-18 Commercial and Government Entity Code Maintenance AUG 2020 52.204-24 Representation Regarding Certain Telecommunications and

Video Surveillance Services or Equipment.

OCT 2020

52.212-1 Instructions to Offerors--Commercial Items JUL 2021 52.212-3 Alt I Offeror Representations and Certifications--Commercial

Items (FEB 2021) Alternate I

OCT 2014

52.212-4 Contract Terms and Conditions--Commercial Items OCT 2018 52.219-6 (Dev) Notice of Total Small Business Set-Aside (DEVIATION

2020-O0008).

OCT 2020

52.222-19 (Dev) Child Labor - Cooperation with Authorities and Remedies

(DEVIATION 2020-O0019)

JUL 2020

52.232-40 Providing Accelerated Payments to Small Business Subcontractors

DEC 2013

252.203-7000 Requirements Relating to Compensation of Former DoD Officials

SEP 2011

252.203-7005 Representation Relating to Compensation of Former DoD Officials

NOV 2011

252.204-7015 Notice of Authorized Disclosure of Information for Litigation Support

MAY 2016

252.204-7017 Prohibition on the Acquisition of Covered Defense Telecommunications Equipment or Services -- Representation

MAY 2021

252.204-7018 Prohibition on the Acquisition of Covered Defense Telecommunications Equipment or Services

JAN 2021

252.225-7001 Buy American And Balance Of Payments Program-- Basic DEC 2017 252.232-7003 Electronic Submission of Payment Requests and Receiving

Reports

DEC 2018

252.232-7010 Levies on Contract Payments DEC 2006 252.232-7017 Accelerating Payments to Small Business Subcontractors--

Prohibition on Fees and Consideration

APR 2020

CLAUSES INCORPORATED BY FULL TEXT

52.212-2 EVALUATION--COMMERCIAL ITEMS (OCT 2014)

(a) The Government will award a contract resulting from this solicitation to the responsible offeror whose offer conforming to the solicitation will be most advantageous to the Government, price and other factors considered. The following factors shall be used to evaluate offers:

1. Time schedule

2. Technical specifications

3. Price

Schedule and Technical Specifications when combined, are significantly more important than price.

(End of provision)

52.212-5 CONTRACT TERMS AND CONDITIONS REQUIRED TO IMPLEMENT STATUTES OR

EXECUTIVE ORDERS--COMMERCIAL ITEMS (JUL 2021)

(a) The Contractor shall comply with the following Federal Acquisition Regulation (FAR) clauses, which are incorporated in this contract by reference, to implement provisions of law or Executive orders applicable to acquisitions of commercial items:

(1) 52.203-19, Prohibition on Requiring Certain Internal Confidentiality Agreements or Statements (JAN 2017) (section 743 of Division E, Title VII, of the Consolidated and Further Continuing Appropriations Act, 2015 (Pub. L.

113-235) and its successor provisions in subsequent appropriations acts (and as extended in continuing resolutions)).

(2) 52.204-23, Prohibition on Contracting for Hardware, Software, and Services Developed or Provided by Kaspersky Lab and Other Covered Entities (Jul 2018) (Section 1634 of Pub. L. 115-91).

(3) 52.204-25, Prohibition on Contracting for Certain Telecommunications and Video Surveillance Services or Equipment. (AUG 2020) (Section 889(a)(1)(A) of Pub. L. 115-232).

(4) 52.209-10, Prohibition on Contracting with Inverted Domestic Corporations (Nov 2015).

(5) 52.233-3, Protest After Award (AUG 1996) (31 U.S.C. 3553).

(6) 52.233-4, Applicable Law for Breach of Contract Claim (OCT 2004) (Public Laws 108-77 and 108-78 (19 U.S.C. 3805 note)).

(b) The Contractor shall comply with the FAR clauses in this paragraph (b) that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items: (Contracting Officer check as appropriate.)

___ (1) 52.203-6, Restrictions on Subcontractor Sales to the Government (JUN 2020), with Alternate I (Oct 1995) (41 U.S.C. 4704 and 10 U.S.C. 2402).

____ (2) 52.203-13, Contractor Code of Business Ethics and Conduct (JUN 2020) (41 U.S.C. 3509).

____ (3) 52.203-15, Whistleblower Protections under the American Recovery and Reinvestment Act of 2009 (JUN 2010) (Section 1553 of Pub. L. 111-5). (Applies to contracts funded by the American Recovery and Reinvestment Act of 2009.)

___ (4) 52.204-10, Reporting Executive Compensation and First-Tier Subcontract Awards (JUN 2020) (Pub. L.

109-282) (31 U.S.C. 6101 note).

___ (5) [Reserved]

___ (6) 52.204-14, Service Contract Reporting Requirements (Oct 2016) (Pub. L. 111-117, section 743 of Div.

C).

___ (7) 52.204-15, Service Contract Reporting Requirements for Indefinite-Delivery Contracts (Oct 2016) (Pub.

L. 111-117, section 743 of Div. C).

___ (8) 52.209-6, Protecting the Government's Interest When Subcontracting with Contractors Debarred, Suspended, or Proposed for Debarment. (JUN 2020) (31 U.S.C. 6101 note).

____ (9) 52.209-9, Updates of Publicly Available Information Regarding Responsibility Matters (OCT 2018) (41 U.S.C. 2313).

____ (10) [Reserved]

____ (11)(i) 52.219-3, Notice of HUBZone Set-Aside or Sole-Source Award (MAR 2020) (15 U.S.C. 657a).

____ (ii) Alternate I (MAR 2020) of 52.219-3.

____ (12) (i) 52.219-4, Notice of Price Evaluation Preference for HUBZone Small Business Concerns (MAR 2020) (if the offeror elects to waive the preference, it shall so indicate in its offer) (15 U.S.C. 657a).

____ (ii) Alternate I (MAR 2020) of 52.219-4.

____ (13) [Reserved]

____ (14)(i) 52.219-6, Notice of Total Small Business Set-Aside (NOV 2020) (15 U.S.C. 644).

____ (ii) Alternate I (MAR 2020) of 52.219-6.

____ (15)(i) 52.219-7, Notice of Partial Small Business Set-Aside (NOV 2020) (15 U.S.C. 644).

____ (ii) Alternate I (MAR 2020) of 52.219-7.

____ (16) 52.219-8, Utilization of Small Business Concerns (OCT 2018) (15 U.S.C. 637(d)(2) and (3)).

____ (17)(i) 52.219-9, Small Business Subcontracting Plan (JUN 2020) (15 U.S.C. 637(d)(4)).

____ (ii) Alternate I (NOV 2016) of 52.219-9.

____ (iii) Alternate II (NOV 2016) of 52.219-9.

____ (iv) Alternate III (JUN 2020) of 52.219-9.

____ (v) Alternate IV (JUN 2020) of 52.219-9.

____ (18) (i) 52.219-13, Notice of Set-Aside of Orders (MAR 2020) (15 U.S.C. 644(r)).

____ (ii) Alternate I (MAR 2020) of 52.219-13.

____ (19) 52.219-14, Limitations on Subcontracting (MAR 2020) (15 U.S.C. 637(a)(14)).

____ (20) 52.219-16, Liquidated Damages—Subcontracting Plan (Jan 1999) (15 U.S.C. 637(d)(4)(F)(i)).

____ (21) 52.219-27, Notice of Service-Disabled Veteran-Owned Small Business Set-Aside (MAR 2020) (15 U.S.C. 657f).

XXX (22) (i) 52.219-28, Post Award Small Business Program Rerepresentation (NOV 2020) (15 U.S.C. 632(a)(2)).

____ (ii) Alternate I (MAR 2020) of 52.219-28.

____ (23) 52.219-29, Notice of Set-Aside for, or Sole Source Award to, Economically Disadvantaged Women- Owned Small Business (EDWOSB) Concerns (MAR 2020) (15 U.S.C. 637(m)).

____ (24) 52.219-30, Notice of Set-Aside for, or Sole Source Award to, Women-Owned Small Business Concerns Eligible Under the Women-Owned Small Business Program (MAR 2020) (15 U.S.C. 637(m)).

____ (25) 52.219-32, Orders Issued Directly Under Small Business Reserves (MAR 2020) (15 U.S.C. 644(r)).

____ (26) 52.219-33, Nonmanufacturer Rule (MAR 2020) (15 U.S.C. 637(a)(17)).

XXX (27) 52.222-3, Convict Labor (JUN 2003) (E.O. 11755).

____(28) 52.222-19, Child Labor--Cooperation with Authorities and Remedies (JAN 2020) (E.O. 13126).

XXX (29) 52.222-21, Prohibition of Segregated Facilities (APR 2015).

XXX (30)(i) 52.222-26, Equal Opportunity (SEPT 2016) (E.O. 11246).

____ (ii) Alternate I (FEB 1999) of 52.222-26.

____ (31)(i) 52.222-35, Equal Opportunity for Veterans (JUN 2020) (38 U.S.C. 4212).

____ (ii) Alternate I (JUL 2014) of 52.222-35.

XXX (32)(i) 52.222-36, Equal Opportunity for Workers with Disabilities (JUN 2020) (29 U.S.C. 793).

____ (ii) Alternate I (JUL 2014) of 52.222-36.

____ (33) 52.222-37, Employment Reports on Veterans (JUN 2020) (38 U.S.C. 4212).

____ (34) 52.222-40, Notification of Employee Rights Under the National Labor Relations Act (DEC 2010) (E.O.

13496).

XXX (35)(i) 52.222-50, Combating Trafficking in Persons (OCT 2020) (22 U.S.C. chapter 78 and E.O. 13627).

____ (ii) Alternate I (MAR 2015) of 52.222-50 (22 U.S.C. chapter 78 and E.O. 13627).

____ (36) 52.222-54, Employment Eligibility Verification (OCT 2015). (E. O. 12989). (Not applicable to the acquisition of commercially available off-the-shelf items or certain other types of commercial items as prescribed in 22.1803.)

____ (37)(i) 52.223-9, Estimate of Percentage of Recovered Material Content for EPA–Designated Items (MAY 2008) (42 U.S.C. 6962(c)(3)(A)(ii)). (Not applicable to the acquisition of commercially available off-the-shelf items.)

____ (ii) Alternate I (MAY 2008) of 52.223-9 (42 U.S.C. 6962(i)(2)(C)). (Not applicable to the acquisition of commercially available off-the-shelf items.)

____ (38) 52.223-11, Ozone-Depleting Substances and High Global Warming Potential Hydrofluorocarbons (JUN 2016) (E.O. 13693).

____ (39) 52.223-12, Maintenance, Service, Repair, or Disposal of Refrigeration Equipment and Air Conditioners

(JUN 2016) (E.O. 13693).

____ (40) (i) 52.223-13, Acquisition of EPEAT® Registered Imaging Equipment (JUN 2014) (E.O.s 13423 and 13514).

____ (ii) Alternate I (OCT 2015) of 52.223-13.

____ (41)(i) 52.223-14, Acquisition of EPEAT® Registered Televisions (JUN 2014) (E.O.s 13423 and 13514).

____ (ii) Alternate I (JUN 2014) of 52.223-14.

____ (42) 52.223-15, Energy Efficiency in Energy-Consuming Products (MAY 2020) (42 U.S.C. 8259b).

____ (43)(i) 52.223-16, Acquisition of EPEAT®-Registered Personal Computer Products (OCT 2015) (E.O.s 13423 and 13514).

____ (ii) Alternate I (JUN 2014) of 52.223-16.

XXX (44) 52.223-18, Encouraging Contractor Policies to Ban Text Messaging While Driving (JUN 2020) (E.O.

13513).

____ (45) 52.223-20, Aerosols (JUN 2016) (E.O. 13693).

____ (46) 52.223-21, Foams (JUN 2016) (E.O. 13693).

____ (47)(i) 52.224-3, Privacy Training (JAN 2017) (5 U.S.C. 552a).

____ (ii) Alternate I (JAN 2017) of 52.224-3.

____ (48) 52.225-1, Buy American--Supplies (JAN 2021) (41 U.S.C. chapter 83).

____ (49) (i) 52.225-3, Buy American--Free Trade Agreements--Israeli Trade Act (JAN 2021) (41 U.S.C. chapter 83, 19 U.S.C. 3301 note, 19 U.S.C. 2112 note, 19 U.S.C. 3805 note, 19 U.S.C. 4001 note, Pub. L. 103-182, 108-77, 108-78, 108-286, 108-302, 109-53, 109-169, 109-283, 110-138, 112-41, 112-42, and 112-43.

____ (ii) Alternate I (JAN 2021) of 52.225-3.

____ (iii) Alternate II (JAN 2021) of 52.225-3.

____ (iv) Alternate III (JAN 2021) of 52.225-3.

____ (50) 52.225-5, Trade Agreements (OCT 2019) 19 U.S.C. 2501, et seq., 19 U.S.C. 3301 note).

XXX (51) 52.225-13, Restrictions on Certain Foreign Purchases (FEB 2021) (E.O.'s, proclamations, and statutes administered by the Office of Foreign Assets Control of the Department of the Treasury).

____ (52) 52.225-26, Contractors Performing Private Security Functions Outside the United States (OCT 2016) (Section 862, as amended, of the National Defense Authorization Act for Fiscal Year 2008; 10 U.S.C. 2302 Note).

____ (53) 52.226-4, Notice of Disaster or Emergency Area Set-Aside (NOV 2007) (42 U.S.C. 5150

____ (54) 52.226-5, Restrictions on Subcontracting Outside Disaster or Emergency Area (NOV 2007) (42 U.S.C.

5150).

____ (55) 52.229-12, Tax on Certain Foreign Procurements (FEB 2021).

____ (56) 52.232-29, Terms for Financing of Purchases of Commercial Items (FEB 2002) (41 U.S.C. 4505, 10 U.S.C. 2307(f)).

____ (57) 52.232-30, Installment Payments for Commercial Items (JAN 2017) (41 U.S.C. 4505, 10 U.S.C. 2307(f)).

XXX (58) 52.232-33, Payment by Electronic Funds Transfer—System for Award Management (OCT 2018) (31 U.S.C. 3332).

____ (59) 52.232-34, Payment by Electronic Funds Transfer—Other than System for Award Management (JUL 2013) (31 U.S.C. 3332).

____ (60) 52.232-36, Payment by Third Party (MAY 2014) (31 U.S.C. 3332).

____ (61) 52.239-1, Privacy or Security Safeguards (AUG 1996) (5 U.S.C. 552a).

____ (62) 52.242-5, Payments to Small Business Subcontractors (JAN 2017)(15 U.S.C. 637(d)(13)).

____ (63)(i) 52.247-64, Preference for Privately Owned U.S.-Flag Commercial Vessels (FEB 2006) (46 U.S.C.

55305 and 10 U.S.C. 2631).

____ (ii) Alternate I (APR 2003) of 52.247-64.

____ (iii) Alternate II (FEB 2006) of 52.247-64.

(c) The Contractor shall comply with the FAR clauses in this paragraph (c), applicable to commercial services, that the Contracting Officer has indicated as being incorporated in this contract by reference to implement provisions of law or Executive orders applicable to acquisitions of commercial items: (Contracting Officer check as appropriate.)

_____ (1) 52.222-41, Service Contract…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .