This is a Quote Item List for submersible 4-conductor cable required by the U.S. Army Corps of Engineers at McNary Lock & Dam. The solicitation (W912EF25Q0017) seeks two 1000-foot spools of specialized underwater cable to be delivered by October 8, 2024.

The cable must meet specific technical requirements including: 14 AWG (41 x #30) stranded copper conductors, 600V insulation rating, high density polyethylene insulation, polyurethane outer jacket (minimum 0.70 inches thick), maximum diameter of 0.630 inches, and maximum weight of 190 pounds per 1000 feet. The cable must withstand extreme temperatures (-20°F to 130°F), turbulent water conditions, and constant environmental exposure. Additional specifications include non-wicking water blocking compound, color-coded conductors (black, white, red, green), minimum bend diameter of 14 inches or less, and 24-inch interval markings with rated voltage, type, manufacturer, and other required information.

View the file

Other files for this federal contract opportunity

Other files attached to MNA ESBS Cable, newest first.
File Type Posted
TECHNICAL SPECIFICATIONS ESBS Cable.docx DOCX document
W912EF25Q0017 Solicitation_Released.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

McNary Lock & Dam

QUOTE ITEM LIST

McNary Lock & Dam

EXTENDED SUBMERSIBLE BARRIER SCREEN (ESBS) CABLE

October 8, 2024

Vendor Name: ___________________________________________________________

Address: ______________________________________________________________________________

Phone #: ___________________________ Email:__________________________________________

DUNs #: ________________________ Cage Code: ____________________

Registered In SAM: _________ (Yes/No)

QUOTE ITEM LIST

ITEM
DESCRIPTION
QNTY
U/M
U/Price
AMOUNT
0001
SUBMERSIBLE 4 CONDUCTOR 14 AWG CABLE. The cable shall be insulated, shielded, and contain water blocking. The cable must be capable of being installed underwater in all weather conditions and temperatures. It will be exposed to the environment 365 days per year and 5may be subjected to low temperatures of 20 degrees below zero Fahrenheit and 130 degrees above zero Fahrenheit. It will be exposed to water, direct sunlight, extreme temperatures, and wind. It must be able to withstand turbulent water conditions without deteriorating the cable.

The cable shall be delivered in TWO (2) 1000-foot spools.

The cable shall contain four 14 AWG (41 x #30) stranded copper conductors.

Conductors shall be insulated for 600V.

Insulation shall be high density polyethylene.

An outer polyurethane jacket shall cover the insulated conductors.

The conductors shall be color coded as black, white, red, and green.

The cable shall be wrapped with polyester tape.

The cable bundle shall be coated overall with a polyurethane jacket of thickness not less than 0.70 inches.

The diameter of the cable shall not exceed 0.630 inches.

The weight, in air, of the cable shall not exceed 190 pounds per 1000 feet.

The cable shall contain a non-wicking water blocking compound which is normally used in underwater environments and plastic rods between the conductors and the outer jacket.

Water blocking shall be used to fill all voids between conductors and outer jacket of cable and shall be chemically compatible with all other cable materials.

The water blocking shall not be injected through the outer jacket; it shall be applied during cable manufacture thereby preventing injection incisions in the jacket.

The cable shall have a minimum bend diameter of 14 inches or less.

The cable, and reel, shall be marked, in accordance with the National Electrical Code. The cable shall be durably marked on the surface at intervals not exceeding 24 inches with the maximum rated voltage, proper type letter (or letters) of cable, the manufacturer’s name, the AWG size or circular mil, number of conductors, and other special considerations for the cable (i.e. water blocking).