AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The purpose for this amendment is to extend the quotation due date until August 1, 2022 and to revse the Technical Specif ications by removing item 18. All other terms and conditions remain unchanged.
If you are submitting an offer, ensure that you acknow ledge receipt of this amendment by completing Blocks 8 and 15A. The signed amendment (SF30) shall be included in the proposal submission.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 12
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 20-Jul-2022
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912EF22Q0172
X 9B. DATED (SEE ITEM 11)
22-Jun-2022
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
20-Jul-2022
CODE
USAED, WALLA WALLA - CONTRACTING DIV.
RUTH A. JOHNSON
201 N. THIRD AVENUE
WALLA WALLA WA 99362-1976
W912EF 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912EF22Q0172
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 1449 - CONTINUATION SHEET
SOLICITATION/CONTRACT FORM
The required response date/time has changed from 21-Jul-2022 10:00 AM to 01-Aug-2022 10:00 AM.
The following have been modified:
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
ICE HARBOR LOCK AND DAM
480V Breaker/Bucket Replacement for SU and CQO Motor Control Centers
1.0 BACKGROUND
480V motor control centers (MCCs) for generators and auxiliary systems were installed when Ice Harbor Lock and Dam was built. The breakers and control systems in these MCCs are failing and replacement parts are difficult to locate or can’t be purchased. Installing new components into an existing MCC compartment (bucket/unit) can require modifications or may not fit. Replacing the entire bucket is easy to implement and cost less when accounting for labor. The following specifications pertain to the purchase of 480V buckets and main breakers for existing MCCs to replace failing components.
2.0 SCOPE OF WORK
The successful offeror shall furnish complete 480V MCC units and main breakers indicated in the Bid Item List with salient characteristic stated below. All items must be purchased from the same manufacturer and multiple quantity items must be purchased at the same time. A bucket will be one of the following unit types: starter unit, solid-state reduced-voltage starter unit, feeder unit or main breaker. All units will include at least one molded-case circuit breaker.
1. MCC starter unit with 50A circuit breaker for 2-speed, 1-winding motor, NEMA 2 starter, red/green/amber lights, Eaton part number FJ946EEASC12B18P10P11P12T11U13U17, with the following salient features:
1.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 28 inches in height
1.2. 480VAC service voltage
1.3. 120VAC control voltage
1.4. 50 Amp Molded-Case Circuit Breaker
1.4.1. 480VAC
1.4.2. 3 pole
1.4.3. Interrupt Rating 65kAIC symmetrical
1.4.4. Thermal-magnetic trip unit
1.5. NEMA 2 starter
1.5.1. 100 VA control power transformer, fused
1.5.2. A200 Starter
1.5.3. Bi-metallic overload
1.6. Red “RUN” light
1.7. Green “STOPPED” light
1.8. Amber “RUN” light
1.9. 14-gauge control wire
1.10. Wiring diagram inside starter unit door
1.11. Terminal strip
2. MCC starter unit with 20A circuit breaker, NEMA 2 starter, red/green lights, Eaton part number
FJ206EEASC12B18P10P11T11U13U17Z1, except a 20 Amp breaker in place of a 50 A breaker, with the following salient features:
2.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
2.2. 480VAC service voltage
2.3. 120VAC control voltage
2.4. 20 Amp Molded-Case Circuit Breaker
2.4.1. 480VAC
2.4.2. 3 pole
2.4.3. Interrupt Rating 65kAIC symmetrical
2.4.4. Thermal-magnetic trip unit
2.5. NEMA 2 starter
2.5.1. 100 VA control power transformer, fused
2.5.2. A200 Starter
2.5.3. Bi-metallic overload
2.6. Red “RUN” light
2.7. Green “STOPPED” light
2.8. 14-gauge control wire
2.9. Wiring diagram inside starter unit door
2.10. Terminal strip
3. MCC starter unit with 20A circuit breaker, NEMA 2 starter, red/green lights, start/stop pushbuttons, Eaton part number FJ206EEASC12B18P10P11T11U13U17P30P31Z1, except a 20 Amp breaker in place of a 50 A breaker, with the following salient features:
3.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
3.2. 480VAC service voltage
3.3. 120VAC control voltage
3.4. 20 Amp Molded-Case Circuit Breaker
3.4.1. 480VAC
3.4.2. 3 pole
3.4.3. Interrupt Rating 65kAIC symmetrical
3.4.4. Thermal-magnetic trip unit
3.5. NEMA 2 starter
3.5.1. 100 VA control power transformer, fused
3.5.2. A200 Starter
3.5.3. Bi-metallic overload
3.6. Red “RUN” light
3.7. Green “STOPPED” light
3.8. “START” pushbutton
3.9. “STOP” pushbutton
3.10. 14-gauge control wire
3.11. Wiring diagram inside starter unit door
3.12. Terminal strip
4. MCC starter unit with 50A circuit breaker, NEMA 2 starter, red/green lights, Eaton part number
FJ206EEASC12B18P10P11T11U13U17, with the following salient features:
4.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
4.2. 480VAC service voltage
4.3. 120VAC control voltage
4.4. 50 Amp Molded-Case Circuit Breaker
4.4.1. 480VAC
4.4.2. 3 pole
4.4.3. Interrupt Rating 65kAIC symmetrical
4.4.4. Thermal-magnetic trip unit
4.5. NEMA 2 starter
4.5.1. 100 VA control power transformer, fused
4.5.2. A200 Starter
4.5.3. Bi-metallic overload
4.6. Red “RUN” light
4.7. Green “STOPPED” light
4.8. 14-gauge control wire
4.9. Wiring diagram inside starter unit door
4.10. Terminal strip
5. MCC solid-state reduced voltage starter unit, red/green lights, Eaton part number
FJ306BEASC13P10P11T11U17Z1, with the following salient features:
5.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 28 inches in height
5.2. 480VAC service voltage
5.3. 120VAC control voltage
5.4. Red “RUN” light
5.5. Green “STOPPED” light
5.6. 14-gauge control wire
5.7. Wiring diagram inside starter unit door
5.8. Terminal strip
6. MCC feeder unit with 20A/30A dual breakers, Eaton part number FJF2BD14B12T11 with the following salient features:
6.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
6.2. 20 Amp Molded-Case Circuit Breaker
6.2.1. 480VAC
6.2.2. 3 pole
6.2.3. Interrupt Rating 65kAIC symmetrical
6.2.4. Thermal-magnetic trip unit
6.2.5. Form C bell alarm contact
6.3. 30 Amp Molded-Case Circuit Breaker
6.3.1. 480VAC
6.3.2. 3 pole
6.3.3. Interrupt Rating 65kAIC symmetrical
6.3.4. Thermal-magnetic trip unit
6.3.5. Form C bell alarm contact
6.4. Terminal strip
7. MCC feeder unit with 50A/20A dual breakers, Eaton part number FJF2FB14T11 with the following salient features:
7.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
7.2. 50 Amp Molded-Case Circuit Breaker
7.2.1. 480VAC
7.2.2. 3 pole
7.2.3. Interrupt Rating 65kAIC symmetrical
7.2.4. Thermal-magnetic trip unit
7.3. 20 Amp Molded-Case Circuit Breaker
7.3.1. 480VAC
7.3.2. 3 pole
7.3.3. Interrupt Rating 65kAIC symmetrical
7.3.4. Thermal-magnetic trip unit
7.4. Terminal strip
8. MCC feeder unit with 50A/50A dual breakers, Eaton part number FJF2FF14T11 with the following salient
8.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
8.2. 50 Amp Molded-Case Circuit Breaker
8.2.1. 480VAC
8.2.2. 3 pole
8.2.3. Interrupt Rating 65kAIC symmetrical
8.2.4. Thermal-magnetic trip unit
8.3. 50 Amp Molded-Case Circuit Breaker
8.3.1. 480VAC
8.3.2. 3 pole
8.3.3. Interrupt Rating 65kAIC symmetrical
8.3.4. Thermal-magnetic trip unit
8.4. Terminal strip
9. MCC feeder unit with 100A/100A dual breakers, Eaton part number FJF2LL14T11 with the following salient features:
9.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
9.2. 100 Amp Molded-Case Circuit Breaker
9.2.1. 480VAC
9.2.2. 3 pole
9.2.3. Interrupt Rating 65kAIC symmetrical
9.2.4. Thermal-magnetic trip unit
9.3. 100 Amp Molded-Case Circuit Breaker
9.3.1. 480VAC
9.3.2. 3 pole
9.3.3. Interrupt Rating 65kAIC symmetrical
9.3.4. Thermal-magnetic trip unit
9.4. Terminal strip
10. MCC feeder unit with 30A breaker, Eaton part number FJF1D14T11 with the following salient features:
10.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
10.2. 30 Amp Molded-Case Circuit Breaker
10.2.1. 480VAC
10.2.2. 3 pole
10.2.3. Interrupt Rating 65kAIC symmetrical
10.2.4. Thermal-magnetic trip unit
10.3. Terminal strip
11. MCC feeder unit with 40A breaker, Eaton part number FJF1E14T11 with the following salient features:
11.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
11.2. 40 Amp Molded-Case Circuit Breaker
11.2.1. 480VAC
11.2.2. 3 pole
11.2.3. Interrupt Rating 65kAIC symmetrical
11.2.4. Thermal-magnetic trip unit
11.3. Terminal strip
12. MCC starter unit with 300A circuit breaker without starter, red/green lights, elapse time meter, Eaton part number FJK1T14B12M12P10P11U13U17T11Z1, except a 300 Amp breaker in place of a 400 A breaker and no motor starter, with the following salient features:
12.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 42 inches in height
12.2. 480VAC service voltage
12.3. 120VAC control voltage
12.4. 300 Amp Molded-Case Circuit Breaker
12.4.1. 480VAC
12.4.2. 3 pole
12.4.3. Interrupt Rating 65kAIC symmetrical
12.4.4. Thermal-magnetic trip unit
12.4.5. Form C bell alarm contact
12.5. Mini elapsed time meter
12.6. Red “RUN” light
12.7. Green “STOPPED” light
12.8. 14 gauge control wire
12.9. Wiring diagram inside starter unit door
12.10. Terminal strip
13. MCC starter unit with 30A circuit breaker, NEMA 2 starter, red/green lights, Eaton part number
FJ206EEASC12B18P10P11T11U13U17B12Z1, except a 30 Amp breaker in place of a 50 A breaker, with the following salient features:
13.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
13.2. 480VAC service voltage
13.3. 120VAC control voltage
13.4. 30 Amp Molded-Case Circuit Breaker
13.4.1. 480VAC
13.4.2. 3 pole
13.4.3. Interrupt Rating 65kAIC symmetrical
13.4.4. Thermal-magnetic trip unit
13.4.5. Form C bell alarm contact
13.5. NEMA 2 starter
13.5.1. 100 VA control power transformer, fused
13.5.2. A200 Starter
13.5.3. Bi-metallic overload
13.6. Red “RUN” light
13.7. Green “STOPPED” light
13.8. 14-gauge control wire
13.9. Wiring diagram inside starter unit door
13.10. Terminal strip
14. MCC starter unit with 50A circuit breaker, NEMA 2 starter, red/green lights, Eaton part number
FJ206EEASC12B18P10P11T11U13U17B12, with the following salient features:
14.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
14.2. 480VAC service voltage
14.3. 120VAC control voltage
14.4. 50 Amp Molded-Case Circuit Breaker
14.4.1. 480VAC
14.4.2. 3 pole
14.4.3. Interrupt Rating 65kAIC symmetrical
14.4.4. Thermal-magnetic trip unit
14.4.5. Form C bell alarm contact
14.5. NEMA 2 starter
14.5.1. 100 VA control power transformer, fused
14.5.2. A200 Starter
14.5.3. Bi-metallic overload
14.6. Red “RUN” light
14.7. Green “STOPPED” light
14.8. 14-gauge control wire
14.9. Wiring diagram inside starter unit door
14.10. Terminal strip
15. MCC feeder unit with 20A/20A dual breakers, Eaton part number FJF2BB14B12T11 with the following salient
15.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
15.2. 20 Amp Molded-Case Circuit Breaker
15.2.1. 480VAC
15.2.2. 3 pole
15.2.3. Interrupt Rating 65kAIC symmetrical
15.2.4. Thermal-magnetic trip unit
15.2.5. Form C bell alarm contact
15.3. 20 Amp Molded-Case Circuit Breaker
15.3.1. 480VAC
15.3.2. 3 pole
15.3.3. Interrupt Rating 65kAIC symmetrical
15.3.4. Thermal-magnetic trip unit
15.3.5. Form C bell alarm contact
15.4. Terminal strip
16. MCC feeder unit with 50A/50A dual breakers, Eaton part number FJF2FF14B12T11 with the following salient features:
16.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
16.2. 50 Amp Molded-Case Circuit Breaker
16.2.1. 480VAC
16.2.2. 3 pole
16.2.3. Interrupt Rating 65kAIC symmetrical
16.2.4. Thermal-magnetic trip unit
16.2.5. Form C bell alarm contact
16.3. 50 Amp Molded-Case Circuit Breaker
16.3.1. 480VAC
16.3.2. 3 pole
16.3.3. Interrupt Rating 65kAIC symmetrical
16.3.4. Thermal-magnetic trip unit
16.3.5. Form C bell alarm contact
16.4. Terminal strip
17. MCC feeder unit with 100A/20A dual breakers, Eaton part number FJF2LB14B12T11 with the following salient features:
17.1. Fits in a Westinghouse Type 11-300 MCC with a door 20 inches wide and 14 inches in height
17.2. 100 Amp Molded-Case Circuit Breaker
17.2.1. 480VAC
17.2.2. 3 pole
17.2.3. Interrupt Rating 65kAIC symmetrical
17.2.4. Thermal-magnetic trip unit
17.2.5. Form C bell alarm contact
17.3. 20 Amp Molded-Case Circuit Breaker
17.3.1. 480VAC
17.3.2. 3 pole
17.3.3. Interrupt Rating 65kAIC symmetrical
17.3.4. Thermal-magnetic trip unit
17.3.5. Form C bell alarm contact
17.4. Terminal strip
18. 14-inch blank door, Eaton part number 6264A91G01 with the following salient features:
18.1. Fits on a Westinghouse Type 11-300 MCC
18.2. Door height is 14 inches
18.3. Door width is 20 inches
3.0 SPECIFICATIONS
3.1 References
Unless noted otherwise, the design, fabrication, testing, and performance of all systems/components shall be in accordance with the standards and codes, where applicable, of the following agencies most recent releases:
1. National Electrical Manufacturers Association (NEMA)
2. American National Standards Institute (ANSI)
3. National Electric Code (ANSI/NFPA 70)
4. Institute of Electrical and Electronic Engineers (IEEE)
5. International Electrotechnical Commission (IEC)
6. Underwriters Laboratories (UL)
3.2 Equipment
3.2.1 Motor Controllers
Conform to NEMA ICS 1, NEMA ICS 2, and UL 508 for motor controllers. Ensure controllers have thermal overload protection in each phase.
3.2.1.1 Magnetic Motor Controllers
3.2.1.1.1 Full-Voltage Controllers
Provide full-voltage, full-magnetic devices for the control and protection of single- and three-phase, 60 Hz, squirrel-cage induction motors in accordance with NEMA ICS 1, NEMA ICS 2, and UL 508 for magnetic motor controllers.
Ensure that the operating coil assembly operates satisfactorily between 85 percent and 110 percent of rated coil voltage. Provide 120 V, 60 Hz motor control circuits.
Provide the controllers with two normally open and two normally closed auxiliary contacts rated according to NEMA ICS 1 and NEMA ICS 2, in addition to the sealing-in contact for the control circuits.
Provide solderless pressure wire terminal connectors for line and load connections to the controllers.
Include three manual-reset thermal-overload devices for overcurrent protection, one in each pole of the controller. Provide thermal-overload relays of bimetallic type with continuous-current ratings and service-limit current ratings. Ensure that ratings have a plus or minus 15 percent adjustment to compensate for ambient operating conditions.
Provide an externally operable manual-reset button to reestablish control power to the holding coil of the electromagnet. After the controller has tripped from overload, ensure that resetting the motor-overload device does not restart the motor.
3.2.1.1.2 Reduced-Voltage Starters
Conform to the requirements for full-voltage controllers for reduced-voltage starters, except for voltage, and to the following additional requirements:
(1) Fully protect the motor during all phases of motor starting with an overload device in each motor leg.
Rate the starter contacts to withstand the switching surges during selector to full voltage. Provide a starter that contains the sensing and timing devices necessary to monitor motor operation and select the correct time for selector to full voltage.
(2) Ensure adequate ventilation of resistors and autotransformers used for starting. Ventilate solid-state starters for starting cycles as well as any follow-on restart-run cycles. Operate external control circuits or solid-state starters at a maximum of 120 VAC.
(3) For solid-state starters, provide adjustable starting torque from 0 percent to 50 percent of applied voltage, minimum. Provide autotransformer starters with a minimum of three taps above 50 percent reduced voltage.
3.2.1.2 Combination Motor Controllers
The following requirements are in addition to the requirements specified for magnetic motor controller:
Provide combination motor controllers for the control and protection of single- and three-phase, 60 Hz, AC squirrel-cage induction motors with branch-circuit disconnecting and protective devices in accordance with NEMA ICS 1, NEMA ICS 2, and NEMA ICS 6.
For combination motor controllers, include magnetic motor controllers and molded-case circuit breakers or motor circuit protectors (MCPs) in metal enclosures in accordance with NEMA 250 or MCC draw-out assemblies with control-power transformers, selector switches, pushbuttons, and indicating lights as follows:
(1) Provide full-voltage, full-magnetic devices for magnetic motor controllers and enclosures.
(2) Provide thermal-magnetic breakers for molded-case circuit breakers.
(3) Provide control-power transformers 120 VAC maximum, selector switches, pushbuttons, and pilot lights as required. Red light indicates “Run” and green light indicates “Stop”.
(4) Identify combination motor controllers with identification plates affixed to the front cover of the controller.
3.2.2 Molded-Case Circuit Breakers
Protective devices shall be UL489 Listed molded case circuit breakers with inverse time and instantaneous tripping characteristics.
Circuit breakers shall be operated by a toggle-type handle and shall have a quick-make, quick-break over-center switching mechanism that is mechanically trip-free. Automatic tripping of the breaker shall be clearly indicated by the handle position. Contacts shall be nonwelding silver alloy and arc extinction shall be accomplished by means of DE-ION arc chutes. A push-to-trip button on the front of the circuit breaker shall provide a local manual means to exercise the trip mechanism.
Circuit breakers shall have a minimum symmetrical interrupting capacity as stated in salient characteristics.
For enhanced load protection and safety, all molded-case circuit breakers from 15 – 600 amps with interrupting ratings of 65kAIC (480V) / 100kAIC (240V) and higher shall be UL listed as current limiting type.
Where indicated provide UL listed circuit breakers for applications at 100% of their continuous ampere rating in their intended enclosure.
Circuit breakers 600-ampere frame and below shall be have thermal-magnetic trip units and inverse time-current characteristics.
3.2.3 Control Devices
3.2.3 Low Voltage Contactors
Provide magnetic contactors in accordance with NEMA ICS 1 and NEMA ICS 2 as required for the control of low-voltage, 60-Hz, primary windings of low-voltage transformers.
Provide core-and-coil assembly that operates satisfactorily with coil voltage between 85 percent and 110 percent of its voltage rating.
Provide contactors that are designed with a normally open holding-circuit auxiliary contact for control circuits, with a rating in accordance with NEMA ICS 1 and NEMA ICS 2.
Furnish solderless pressure wire terminal connectors, or make available for line and load connections to contactors in accordance with NEMA ICS 1 and NEMA ICS 2.
Provide magnetic contactors with a rating in accordance with NEMA ICS 1 and NEMA ICS 2.
3.2.3.1 Electromechanical Contactors
Contactors shall have UL certification to achieve IEC 947, type 2 coordination when subjected to 100,000 ampere short-circuit fault currents.
Magnetic contactors through NEMA Size 9 shall be equipped with double break silver alloy contacts.
Coils shall be of molded construction through NEMA Size 9.
Coils shall be permanently marked with voltage, frequency and part number.
NEMA Size 00 through 2 contactors shall be suitable for adding a minimum of any combination of six (6) normally open or normally closed contacts. Size 3 through 8 contactors shall be suitable for the addition of up to eight (8) external auxiliary contacts of any combination of normally open or normally closed contacts.
3.2.3.2 Microprocessor-Based Contactors
Provide electromechanical type contactors with coil control integrated into a single or dual microcontroller.
The contactor shall operate over a temperature range of -40 to 149 degrees F (-40 to 65 degrees C) and shall meet or exceed the following Standards and Certifications: UL, NEMA ICS1, ICS2, ICS5, IEC 60947-4-1. Devices shall meet Electromagnetic Compatibility (EMC) Requirements per EMC IEC 61000- 4.
Provide a microcontroller with the following features:
a. Monitor the nominal 24 VDC and adjust the Pulse Width Modulation (PWM) accordingly to minimize utilized power and maximize contact sealed force.
b. Energizes coil at full voltage and then applies Pulse Width Modulation.
c. Monitors user control inputs (i.e., permissive, stop, forward, reverse, local reset, remote reset, test/test to trip). Control inputs shall be rated 24VDC (3–5 mA) with a plug and unplug lockable control connector.
The contactor voltage shall be nominal 24VDC from 20VDC to 28VDC.
Contactors shall have replaceable fixed and movable contacts, size 1 and larger.
3.2.4 Control-Circuit Transformers
Provide control-circuit transformers within the enclosure of magnetic contactors and motor controllers when the line voltage exceeds 120V.
Provide an encapsulated dry-type, single-phase, 60-Hz transformer, with a 120V (or 24V) isolated secondary winding. Do not provide a transformer with a rated primary voltage less than the rated voltage of the controller, or a rated secondary current less than the continuous-duty current of the control circuit.
Provide voltage regulation of the transformer such that, with rated primary voltage and frequency, the secondary voltage is not less than 95 percent nor more than 105 percent of rated secondary voltage.
Provide a source of supply for control-circuit transformers at the load side of the main disconnecting device. Protect the secondary winding of the transformer and control-circuit wiring against overloads and short circuits, with fuses selected in accordance with NEMA ICS 6. Ground the secondary winding of the control-circuit transformer in accordance with NEMA ICS 6.
3.2.5 Control Relays
Provide magnetic control relays for energizing and de-energizing the coils of magnetic contactors or other magnetically operated devices, in response to variations in the conditions of electric control devices in accordance with NEMA ICS 1, and NEMA ICS 2.
Ensure that the core-and-coil assembly operates satisfactorily with coil voltages between 85 percent and 110 percent of their voltage rating.
Provide relays that are designed to accommodate normally open and normally closed contacts.
Provide 120V, 60-Hz, magnetic control relays with a continuous-contact rating of 10 A, and with current-making and -breaking ability in accordance with NEMA ICS 1 and NEMA ICS 2, two normally open and two normally closed.
3.2.6 Pushbuttons
For low-voltage AC full-voltage magnetic pushbutton controllers, provide heavy-duty, oil-tight NEMA 250, momentary-contact devices rated 600 V. Pushbuttons shall be non-illuminated with a button color of black or red for “Run” and green for “Stop”.
Provide pushbuttons that are designed with normally open, circuit-closing contacts; normally closed circuit-opening contacts; and two-circuit normally open and normally closed circuit-closing and -opening contacts.
Ensure that pushbutton-contact ratings are in accordance with NEMA ICS 1 and NEMA ICS 2, with contact designation A600.
Identify pushbuttons in door with identification plates affixed to the front cover in a prominent location.
3.2.7 Selector Switches
Provide heavy-duty, oil-tight, maintained-contact selector switches for low-voltage control circuits, with the number of positions and the marking of identification plates in accordance with NEMA ICS 1 and
NEMA ICS 2.
Identify selector switches in door with engraved identification plates affixed to the front cover in a prominent location.
3.2.8 Indicating Lights
Provide oil-tight indicating lamps with flush mounted base and translucent convex lens. Red light indicates “Run” and green light indicates “Stop”.
3.3 Execution
Standard factory tests shall be performed on the equipment provided under this section. All tests shall be in accordance with the latest version of NEMA and UL standards.
4.0 SUBMITTALS
Vendor shall submit with its quote detailed product information, to include manufacturer cut sheets and manufacturer and/or vendor drawings and diagrams showing any needed product alteration or customization.
Product data must provide sufficient detail to demonstrate that the proposed product(s) are capable of integrating seamlessly with Ice Harbor Project’s existing system(s). Information shall be submitted to the technical point of contact at site (through Contracting Office), for technical approval. Submittals are due within 15 calender days of contract award.
Approval of the material submitted shall in no way relieve the Contractor from the responsibility of complying with the requirements of the specifications as to the suitability and quality of materials and workmanship.
5.0 WARRANTY
All items shall be covered by the manufacturer’s standard warranty on all parts, labor, and workmanship from factory defects.
6.0 OPERATION AND MAINTENANCE MANUALS
Three (3) complete hardcopies and one (1) electronic copy of the Operation and Maintenance Manuals (O&M Manuals) shall be submitted for the MCC buckets and main breakers. The O&M Manuals shall include order-specific instructions on the installation, maintenance, repair, troubleshooting, warranty, and a list of recommended spare parts (if applicable). Any information pertaining to models or components not supplied under this contract shall be crossed out.
The O&M Manuals shall also include a sheet at the front of the manuals listing the name, phone number, contact information for the manufacturer, and a distributor where spare parts can be purchased. The complete contract award number (as found on the contract Award document) shall also be included.
7.0 SHIPMENT AND DELIVERY
Perform delivery, handling, and storage of items conforming to the manufacturer's requirements and best industry practices. The Government will assist with unloading the items at the site. Verify the condition and quantity of the items upon delivery by the Contracting Officer and acknowledge receipt and condition thereof in writing. If delivered items are damaged or a shortage is determined, notify the Contracting Officer of such in writing within 24 hours after delivery.
All items shall be delivered FOB to Ice Harbor Lock and Dam by Aug 31, 2022 or within 8 weeks after approval of all submittals. The Contractor shall be responsible for packing and shipping the items in a manner that will ensure undamaged and complete arrival to the Project site. No shipments are allowed other than normal business hours of Monday thru Thursday 7:00 a.m. to 4:00 p.m., excluding federal holidays.
All shipments shall be delivered to:
Ice Harbor Lock and Dam 2763 Monument Drive Burbank, WA 99323
(End of Summary of Changes)