Text version

RFI Group #3

KTR RFI

Originating Company

Originator (Full Name) Discipline Full RFI Question

Full RFI Response (Leave Blank)

Whiting-Turner Kyle Krueger

Roofing

Drawing A-191, detail 3 shows a new slate tile roofing to match the existing, however no information about slate tile is given in the specifications. This appears to conflict with Drawing A-442 which calls for “Slate Look fiberglass roof shingles (match existing Ecostar empire Slate, Solor to match existing, or approved equal.)” Please confirm we should follow direction provided on A442, and not provide natural slate, or provide alternate direction.

Follow direction on A-442 for the roofing material on the elevator tower. This note includes the product information from the client on the slate-look fiberglass shingles that are currently being installed on an adjacent building. - SMDK

Whiting-Turner Kyle Krueger

Metals

Several notes in the drawings still state that the contractor shall remove exterior handrails for stockpile and reuse; for example, see note 2/AD-130 for example. Please confirm that all railings and railing components will be moved by others prior to the start of this project and we should price furnish and installation of all new railings (see note 2/A205 for example).

The Contractor will be required to remove the existing railings that remain, and add them to the stockpile of railings that have been previously removed under the on-going project (Phase I). Based on the amount and quality of the handrail pile, the Contractor and the Contracting Officer will collaborate on a path-forward for use of the rails. For the proposal, the Contractor shall price the procurement and installation of all new rails. See Spec section 01 05 00, paragraph 1.4.

(CTR)

Whiting-Turner Kyle Krueger

General

RFP Section 5.1, FACTOR 1 states relevant projects must “demonstrate…completion…within six years of the original date of issuance of this RFP.”

Is it permissible to submit a project currently under construction as long as it is more than 75% complete?

No. The project must be "physically and successfully" complete (100%) within six years of the original date of the issuance of the

RFP. (TML)

(All RFI’s #4 and #67 below pertain to Doors/Frames/Hardware only)

Whiting-Turner Kyle Krueger

Doors

Door 043A is pair per door schedule & floor plans but has Set HW-1 which is for single door. Please clarify correct hardware set.

Door 043A will use HW-39, edited as follows:

HW-39 PR 3'-0" x 7'-0" HM x HM - 90 MIN Qty Item ANSI/BHMA 6 ea Hinges 5" x 4-1/2" BB8111 2 ea Exit Device Type 2 x 14, lever always active 2 ea Closers C02021 1 ea Floor Stop

Whiting-Turner Kyle Krueger

Doors

Doors C01, C02, G101 and G102 have no door or frame type listed. Please provide door and frame information.

See Head Detail 6 / A-G501, Jamb Detail 7 / A-G501, Sill Detail 8 / A- G501. For door C01, Door type is A and Frame type is 2. For doors C02, G101, & G102, Door type is B and Frame type is 2.

Whiting-Turner Kyle Krueger

Doors

Doors C01, C02, G101 and G102 have Sets HW67, HW-68 and HW69. These sets are not listed in Door Hardware specification 087100. Please clarify correct hardware set.

Hardware sets should be added to specification as follows to match adjacent facility condenser and generator yard door hardware:

HW-67 3'-0" x 7'-0" HM x HM - Condenser Yard Qty Item ANSI/BHMA 3 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Latchset F75 1 ea Padlock NIC 1 ea Hasp A83241, Fixed Staple 1 ea Overhead Holder C52511

HW-68 PR 3'-0" x 7'-0" HM x HM - Condenser Yard Qty Item ANSI/BHMA 6 ea Hinges 5" x 4-1/2" BB8111 1 ea Latchset F75 1 ea Hasp A83241, Fixed Staple 1 ea Padlock NIC 1 ea Manual Flush Bolt Door Head Only 1 ea Overhead Holder C52511

HW-69 PR 3'-0" x 7'-0" HM x HM - Generator Enclosure Qty Item ANSI/BHMA 6 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Latchset F75 1 ea Hasp A83241, Fixed Staple 1 ea Padlock NIC 1 ea Manual Flush Bolt Door Head Only 1 ea Overhead Holder C52511

Whiting-Turner Kyle Krueger

Doors

Doors 171A & 234A are STC 50 but have Set HW-6 which is for STC45. Will this hardware set suffice for an STC 50 door assembly? Please clarify correct hardware set.

Doors 171A and 234A will use HW-13, with Floor Stop instead of Wall stop. Per client request, all door hardware sets needing a stop shall have floor stops, not wall stops.

Whiting-Turner Kyle Krueger Doors

Door 225A has no STC rating but has Set HW-6 which is for STC45. Please clarify correct hardware set.

Door 225A will use HW-46.

Whiting-Turner Kyle Krueger

Doors

Door 342B is fire rated STC50 hollow metal door but has Set HW-6 which is for non-rated STC45 wood door. Please clarify correct hardware set.

Door 342B will use HW-56.

Whiting-Turner Kyle Krueger

Doors

Door 140B is 90 min but has hardware set HW-10 which is for 45min door and is noted as “not used.” Please clarify correct hardware set.

Please correct hardware set to the following:

HW-10 PR 3'-0" x 7'-0" HM x HM - 90 MIN Rated / STC 50 Qty Item ANSI/BHMA 6 ea Hinges 5" x 4-1/2" BB8111 2 ea Exit Device Type 2 x 08 2 ea Closers C02021 1 set Gaskets R0Y255 2 ea Door Bottoms R0Y336 1 ea Astragal R0Y825 2 ea Floor Stops 1 ea Threshold 1 ea Card Reader NIC 1 ea Keypad 2 ea BMS

Whiting-Turner Kyle Krueger

Doors

Doors 101A, 120B, 201A, 205B, 233B, 304A, 324B and 358B are 45 min but have Set HW-16A which is for 90 min doors.

Please clarify correct hardware set.

Use HW-16C for the listed doors. Add HW-16C hardware set to door spec as follows:

HW-16C 3'-0 x 7'-0" HM x HM - BLAST / 45 MIN / STC 50 Qty Item ANSI/BHMA 3 ea Hinges 5" x 4-1/2" - NRP BB8111 1 ea Exit Device Type 2 x 01, no exterior trim 1 ea Closer C02021 1 set Gaskets R0Y255 1 ea Door Bottom R0Y336 1 ea Threshold 1 ea BMS

Whiting-Turner Kyle Krueger

Doors

Doors 118A and 142A are STC45 wood doors but have Set HW-19 which is for STC50 hollow metal door. Please clarify correct hardware set.

Add HW-19C door spec per following and change listed doors to HW- 19C.

HW-19C PR 3'-0" x 7'-0" WD x HM - STC 45 Qty Item ANSI/BHMA 6 ea Hinges 5" x 4-1/2" BB8111 2 ea Exit Device Type 2 x 14, lever always active 2 ea Closers C02011 1 set Gaskets R0Y255 2 ea Door Bottoms R0Y336 1 ea Astragal R0Y825 2 ea Floor Stop 1 ea Threshold

Whiting-Turner Kyle Krueger Doors

Door 120A is wood door but has Set HW-19 which is for hollow metal door. Please clarify correct hardware set.

Change HW-19 title description to spec to:

"HW-19 PR 3'-0" x 7'-0" WD x HM - STC 50".

Whiting-Turner Kyle Krueger

Doors

Door 138A is single door no side panel but has Set HW-16 and double door in door schedule notes. Set 16 is for door with side panel. Please clarify correct hardware set.

Door 138A will use HW-16A.

Whiting-Turner Kyle Krueger

Doors

Door 137B is non STC blast door but has Set HW-16B which is for a non-blast STC door.

Please clarify correct hardware set.

This door should not be blast rated. It should be a 90 MIN STC 50 rated door using hardware set HW-56, which matches the responses for the doors in this same location on the second and thrid levels of the building (Doors 219C & 342B). The adjacent wall construction should be per type D2 as 2-HR fire rated and STC 50, not D3 as currently shown.

Whiting-Turner Kyle Krueger

Doors

Door 141A is STC45 wood door but has Set HW-19B which is for STC50 hollow metal door. Please clarify correct hardware set.

Revise hardware set HW-19B to the following:

HW-19B PR 3'-0" x 7'-0" WD x HM - STC 45 Qty Item ANSI/BHMA 6 ea Hinges 5" x 4-1/2" BB8111 2 ea Exit Device Type 2 x 14, lever always active 2 ea Closers C02011 1 set Gaskets R0Y255 2 ea Door Bottoms R0Y336 1 ea Astragal R0Y825 2 ea Floor Stop 1 ea Threshold 1 ea Card Reader NIC 2 ea BMS

Whiting-Turner Kyle Krueger

Doors

Door 169A is single door no side panel 45 min but has Set HW-16 which is for door with side panel 90 min. Please clarify correct hardware set.

Use HW-16C as follows:

HW-16C 3'-0 x 7'-0" HM x HM - BLAST / 45 MIN / STC 50 Qty Item ANSI/BHMA 3 ea Hinges 5" x 4-1/2" - NRP BB8111 1 ea Exit Device Type 2 x 01, no exterior trim 1 ea Closer C02021 1 set Gaskets R0Y255 1 ea Door Bottom R0Y336 1 ea Threshold 1 ea BMS

Whiting-Turner Kyle Krueger

Doors

Door 219C has door type C and frame type 4 which are blast but Blast Door is not listed in Door Schedule notes. Please clarify blast requirements for this door.

Door 219C will be Door type A and Frame Type 1.

Whiting-Turner Kyle Krueger

Doors

Door 219C is a single “blast door” per door type & frame type but has Set HW-15 which is for pair of non-blast doors. Please clarify correct hardware set.

Door 219C will use HW-56.

Whiting-Turner Kyle Krueger

Doors

Door 228B is pair of wood doors but has set HW-19A which is for pair of hollow metal doors. Please clarify correct hardware set.

Change HW-19A title description to spec to:

"HW-19A PR 3'-0" x 7'-0" WD x HM - STC 50 / 90 MIN".

Whiting-Turner Kyle Krueger

Doors

Door 338A is single door no side panel but has Set HW-16 which is for door with side panel. Should this be changed to hardware set HW-16A? Please clarify correct hardware set.

Yes, Door 338A will use HW-16A. Door schedule will be revised from HW-16 to HW-16A.

Whiting-Turner Kyle Krueger

Doors

Doors 233A, 356A and 358A are 45 min wood doors non-STC but has Set HW-20 which is for a non-rated STC50 hollow metal door. Please clarify correct hardware set.

Doors 233A, 356A, and 358A are 45 STC / 0 MIN rated doors. Listed doors will use HW-20C.

Whiting-Turner Kyle Krueger Doors

Door 338B is a hollow metal door but has Set HW-20B which is for wood door. Please clarify correct hardware set.

Door 338B will use HW-20F.

Whiting-Turner Kyle Krueger

Doors

Door 009A is a non-STC 45 min door but has Set HW-26A which is for STC50 90 min door. Please clarify correct hardware set.

Door 009A will use HW-26.

Whiting-Turner Kyle Krueger

Doors

Doors 004A and 032A are non-rated STC45 doors but have Set HW-27 which is for 45 min non-STC door. Should the 45 on door schedule be moved from STC rating column to Fire rating column? Please clarify correct hardware set and STC/Fire Rating information.

Walls should be type A2, which is 1-HR fire and STC 45 construction.

Doors 004A and 032A should match these ratings as 45 STC / 45 MIN fire rating - door schedule should be revised to 45 STC/ 45 MIN ratings for these doors. Use new door hardware set HW-10A for these doors, see below:

HW-10A PR 3'-0" x 7'-0" HM x HM - 45 MIN Rated / STC 45 Qty Item ANSI/BHMA 6 ea Hinges 5" x 4-1/2" BB8111 2 ea Exit Device Type 2 x 08 2 ea Closers C02021 1 set Gaskets R0Y255 2 ea Door Bottoms R0Y336 1 ea Astragal R0Y825 2 ea Floor Stops 1 ea Threshold

Whiting-Turner Kyle Krueger

Doors

Doors 024A and 032B are STC45 but have Set HW-24 which is for non-STC doors.

Please clarify correct hardware set.

Change HW-24 title description to spec to:

"HW-24 3'-0" x 7'-0" HM x HM - STC 45 / 45 MIN".

Whiting-Turner Kyle Krueger

Doors

Doors 103A and 204A are pair of STC45 wood doors but have Set HW-27A which is for pair of non-STC hollow metal doors.

Please clarify correct hardware set.

Change HW-27A title description in spec to:

"HW-27A PR 3'-0" x 7'-0" WD x HM - STC 45 / 45 MIN".

Whiting-Turner Kyle Krueger

Doors

Doors 106A, 150A, 203A, 317A and 354A are 45 min STC45 wood doors but have Set HW-26A which is for 90 min STC50 hollow metal door. Please clarify correct hardware set.

Change HW-26A title description in spec to:

"HW-26A 3'-0" x 7'-0" WD x HM - STC 45 / 45 MIN".

Whiting-Turner Kyle Krueger

Doors

Door 226A is non-rated STC45 wood door but has Set HW-26A which is for 90 min STC50 hollow metal door. Please clarify correct hardware set.

Door 226A should be 45 STC / 45 MIN to match wall construction.

Change HW-26A title description in spec to:

"HW-26A 3'-0" x 7'-0" WD x HM - STC 45 / 45 MIN".

Whiting-Turner Kyle Krueger

Doors

Door 364A is pair of wood doors but has Set HW-19A which is for pair of hollow metal doors. Please clarify correct hardware set.

Change HW-19A title description to spec to:

"HW-19A PR 3'-0" x 7'-0" WD x HM - STC 50 / 90 MIN".

Whiting-Turner Kyle Krueger

Doors

Door 133A is pair of wood doors but has Set HW-30 which is for pair of hollow metal doors. Please clarify correct hardware set.

Change HW-30 title description to spec to:

"HW-30 PR 3'-0" x 7'-0" WD x HM - STC 45 / 45 MIN".

Whiting-Turner Kyle Krueger

Doors

Door 166A is a single STC45 wood door but has Set HW-30 which is for pair of non-STC hollow metal doors. Please clarify correct hardware set.

Door 166A will use HW-6.

Whiting-Turner Kyle Krueger

Doors

Door 336A is STC45 45 min pair of wood doors but has set HW-30 which is for pair of non-STC non-rated hollow metal doors.

Please clarify correct hardware set.

Change HW-30 title description in spec to:

"HW-30 PR 3'-0" x 7'-0" WD x HM - STC 45 / 45 MIN".

Whiting-Turner Kyle Krueger

Doors

Door 340A is a single non-rated wood door but has Set HW-31 which is for pair of rated hollow metal doors. Please clarify correct hardware set.

Create HW-7A for Door 340A as follows:

HW-7A 3'-0" x 7'-0" WD x HM Qty Item ANSI/BHMA 3 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Lockset F86 1 ea Closer C02021 1 ea Floor Stop

Whiting-Turner Kyle Krueger

Doors

Door 135A is pair of wood doors but has Set HW-31A which is for pair of hollow metal doors. Please clarify correct hardware set.

Add hardware set HW-31D (0 STC / 0 MIN WD door) Door schedule should be revised to include HW-31D as follows:

HW-31D PR 3'-0" x 7'-0" WD x HM Qty Item ANSI/BHMA 6 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Lockset F86 1 ea Coordinator Type 21B 2 ea Closers C02021 1 ea Floor Stop L02102 1 PR Automatic Flush Bolts

Whiting-Turner Kyle Krueger

Doors

Doors 170A, 215A and 337A are pair of wood doors but have Set HW-31B which is for pair of hollow metal doors. Please clarify correct hardware set.

Change HW-31B title description to spec to:

"HW-31B PR 3'-0" x 7'-0" WD x HM - STC 45 / 45 MIN".

Whiting-Turner Kyle Krueger

Doors

Door 214A has Set HW-31C. There is no set listed in spec. Please provide a different set or provide Set HW-31C.

Two HW-31B's are listed in the specs, the latter HW-31B will be revised to HW-31C as follows:

HW-31C PR 3'-0" x 7'-0" WD x HM - 45 MIN / STC 45 Qty Item ANSI/BHMA 6 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Lockset F86 1 ea Coordinator Type 21B 2 ea Closers C02021 1 ea Floor Stop L02102 1 PR Automatic Flush Bolts 1 ea Card Reader NIC 2 ea BMS

Whiting-Turner Kyle Krueger

Doors

Doors 012A and 033A are non-STC doors but have Set HW-32 which is for STC50 door. Please clarify correct hardware set.

Door schedule should be revised to HW-32A for Doors.012A, 033A & 002A (located at basement stair towers) Add HW-32A as follows:

HW-32A 3'-0" x 7'-0" HM x HM - 90 MIN Qty Item ANSI/BHMA 3 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Exit Device Type 1 x 14, lever always active 1 ea Closer C02011 1 ea Floor Stop 1 ea BMS (see Security shts)

Whiting-Turner Kyle Krueger

Doors

Doors 149A, 168A and 330A are STC45 wood doors but has set HW-37 which is for STC40 hollow metal door. Please clarify correct hardware set.

Door 149A is 40 STC per wall type A3. Change HW-37 title description in spec to:

"HW-37 3'-0" x 7'-0" WD x HM - STC 40 ".

Doors 168A and 330A are 45 STC per wall type A4. Create hardware set HW-37A to be used on these 2 doors as follows:

HW-37A 3'-0" x 7'-0" x 1-3/4" WD x HM - STC 45 Qty Item ANSI/BHMA 3 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Lockset F76A 1 ea Floor Stop 1 set Gaskets R0Y164 1 ea Door Bottom R0Y336 1 ea Threshold

Whiting-Turner Kyle Krueger

Doors

Door 218A is a non-STC wood door but has Set HW-37 which is for a STC40 hollow metal door. Please clarify correct hardware set.

Use HW-7 for door 218A.

Whiting-Turner Kyle Krueger

Doors

Door 013B is a single 6’-10” non-blast door but has Set HW-38 which is for a pair of 7’- 10” blast doors. Please clarify correct hardware set.

Create hardware set HW-37B for use on door 013B as follows:

HW-37B 3'-0" x 6'-10" x 1-3/4" HM x HM Qty Item ANSI/BHMA 3 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Lockset F76A 1 ea Floor Stop 1 set Gaskets R0Y164 1 ea Door Bottom R0Y336 1 ea Threshold

Whiting-Turner Kyle Krueger

Doors

Door 015A is 6-10” but has Set HW-40 which is for 7’-0” doors. Please clarify correct hardware set.

Create hardware set HW-40B for use on door 015A as follows:

HW-40B PR 3'-0" x 6'-10" HM x HM Qty Item ANSI/BHMA 6 ea Hinges 4-1/2" x 4-1/2" BB8111 1 ea Lockset F86 1 ea Coordinator Type 21B 2 ea Closers C02021 2 ea Floor Stop

Whiting-Turner Kyle Krueger Doors

Door 019A is non-rated but has Set HW-42 which is for 90 min doors. Please clarify correct hardware set.

Door 019A is 90 MIN. Correct set is provided as HW-42.

Whiting-Turner Kyle Krueger Doors

Door 020A is a 3’-4” door but has set HW-43 which is for 3’-0” door. Please clarify correct hardware set.

Change title of set to "HW-43 3'-4" x 7'-0" HM x HM - 90 MIN /

STC 50"

Whiting-Turner Kyle Krueger

Doors

Doors 117A, 117B, 118B, 146A, 211A, 212A, 314A, 333A, 334A and 359A are STC45 doors but have Set HW-44 which is for STC50 doors. Please clarify correct hardware set.

Change title of set to "HW-44 3'-0" x 7'-0" WD x HM - STC 45"

Whiting-Turner Kyle Krueger Doors

Door 140A is 45 min but has Set HW-51A which is for 90 min door. Please clarify correct hardware set.

Change title of set to: "HW-51A PR 3'-0"/3'-0" x 7'-0" HM x HM -

BLAST / 45 MIN / STC 50"

Whiting-Turner Kyle Krueger Doors

Door 018A is non-STC door but has Set HW- 53A which is for a STC50 door. Please clarify correct hardware set.

Door 018A will be removed per Amendment 1.

Whiting-Turner Kyle Krueger

Doors

Doors 105A, 105C, 125A, 137A, 153A, 202A, 202B, 206A, 206B, 229A, 329A, 329C, 342A, 342C, 355A and 355C are non- STC wood doors but have Set HW-56 which is for STC50 hollow metal door. Please clarify correct hardware set.

Door 153A is shown in wall type C2, which is STC 50 and 90 MIN fire rated. This door should remian with hardware set HW-56 with the following changed title:

"HW-56 3'-0" x 7'-0" WD x HM - 90 MIN Rated / STC 50" Remaining 15 doors listed in comment should use new set HW-56B as follows:

HW-56B 3'-0" x 7'-0" WD x HM - 90 MIN Rated Qty Item ANSI/BHMA 3 ea Hinges 5" x 4-1/2" BB8111 1 ea Exit Device Type 1 x 14, Lever always active 1 ea Closers C02061 1 set Gaskets R0Y165 1 ea Door Bottom R0Y336 1 ea Threshold L02102 1 ea Kick Plates J102 1 ea BMS 1 ea Card Reader

Whiting-Turner Kyle Krueger

Doors

Doors 219A, 219B, 315A and 315C are wood but have Set HW-56 which is for hollow metal doors. Please clarify correct hardware set.

Doors 219C, 315A, 315C, 342B are shown in wall type C2, which is STC 50 and 90 MIN fire rated. These doors should remain with hardware set HW-56 with the following changed title:

"HW-56 3'-0" x 7'-0" WD x HM - 90 MIN Rated / STC 50" Doors 219A & 219B should use new set HW-56B as follows:

HW-56B 3'-0" x 7'-0" WD x HM - 90 MIN Rated Qty Item ANSI/BHMA 3 ea Hinges 5" x 4-1/2" BB8111 1 ea Exit Device Type 1 x 14, Lever always active 1 ea Closers C02061 1 set Gaskets R0Y165 1 ea Door Bottom R0Y336 1 ea Threshold L02102 1 ea Kick Plates J102 1 ea BMS 1 ea Card Reader

Whiting-Turner Kyle Krueger

Doors

Door 104A is non rated non-STC 3’-0” blast door but has Set HW-56A which is for 90 min STC50 3’-6”non-blast door. Please clarify correct hardware set.

Door 104A is in wall type R0, which is STC 50. Door 104A should be STC 50 and Blast rated. Hardware set HW-56A is correct with the following edits:

HW-56A 3'-0" x 7'-0" HM x HM - STC 50 / BLAST Resistant Qty Item ANSI/BHMA 3 ea Hinges 5" x 4 1/2" BB8111 1 ea Exit Device Type 1 x 14, Lever always active 1 ea Closers C02061 1 set Gaskets ROY165 1 ea Door Bottom ROY336 1 ea Threshold L02102 1 ea Kick Plates J102 1 ea BMS

Whiting-Turner Kyle Krueger

Doors

Doors 124A, 136A and 152A are non-rated 3’-0” blast doors but have Set HW-56A which is for 90 min 3’-6”non-blast door.

Please clarify correct hardware set.

Doors 124A, 136A, & 152A are in wall type R0, which is STC 50.

Doors should be STC 50 and Blast rated. Hardware set HW-56A is correct with the following edits:

HW-56A 3'-0" x 7'-0" HM x HM - STC 50 / BLAST Resistant Qty Item ANSI/BHMA 3 ea Hinges 5" x 4 1/2" BB8111 1 ea Exit Device Type 1 x 14, Lever always active 1 ea Closers C02061 1 set Gaskets ROY165 1 ea Door Bottom ROY336 1 ea Threshold L02102 1 ea Kick Plates J102 1 ea BMS

Whiting-Turner Kyle Krueger

Doors

Doors 132A, 151A, 213A and 335A are a 7’- 0” doors but have Set HW-65 which is for 7’- 10” door. Please clarify correct hardware set.

Revise hardware set title to:

"HW-65 3'-0" x 7'-0" WD x HM" and reduce number of hinges from "4 ea" to "3 ea".

Whiting-Turner Kyle Krueger Doors

Door 021A is hollow metal door but has Set HW-65A which is for wood door. Please clarify correct hardware set.

Revise hardware set title to:

"HW-65A 3'-0" x 7'-0" HM x HM" and reduce number of hinges from '4 ea" to "3 ea".

Whiting-Turner Kyle Krueger Doors

Doors 028A, 029A and 030A are single but have door type B. Should door type be A?

Please clarify correct door type.

Listed doors are single doors and should be door type A.

Whiting-Turner Kyle Krueger

Doors

Specification 087100 part 2.5 Finishes calls for stainless steel hinges for exterior doors.

Unfortunately all hardware sets have ANSI BB8111 listed. This is for steel based ferrous hinge. It is our understanding that the model number takes precedence. If stainless steel hinges are required, model number should be changed to BB5111 where required. Please clarify with a list of doors where stainless steel hinges are required.

All new exterior doors should have stainless steel hinges per 2.5 Finishes. This effects all exterior door sets including HW-51, HW-1A, HW-16, HW-16A, HW-51A, and Hardware sets at the Condenser yard, Generator Enclosure, and Doghouse Door at Fire Pump Room as shown in Amendment #1. Per 3.6 Hardware Sets (second paragraph) "The door hardware sets listed below are provided to establish a general intent to develop the final submittal for review." Per this statement, please consider the model numbers within the hardware sets as a guide only and take the requirements for individual components in Part 2 of the specification as requirements.

Whiting-Turner Kyle Krueger

Doors

Sets HW-1, HW-1A, HW-16, HW-16A, HW-

16B, HW-26A, HW-26B, HW-26C, HW-27,

HW-27A, HW-38, HW-51, HW-51A, HW-

52, HW-53, HW-53A, HW-56 and HW-56A have no means of stop listed. Please provide missing information.

Door Closers are required for all Fire Rated doors to meet code. Blast-resistant doors need them as well. Please add closers to the following sets: HW-1, HW-16, HW-16A, HW-16B, HW-26A, HW-26B, HW-

27, HW-27A, HW-38, HW-51, HW-51A, HW-52, HW-53, HW-53A,

HW-56, HW-56A.

Add Floor stops for all remaining non-fire rated hardware sets listed, unless closer is needed to provide a complete tested sound assembly on STC rated doors (provide closer if needed for STC tested assembly): HW-1A, HW-26C

Whiting-Turner Kyle Krueger

Doors

Every lockset/latchset is bored except one in Set HW-15 that has ANSI 36 which is for preassembled (passage) latchset. This appears to be a possible error. Please confirm this is correct or provide additional information.

Also set has electric strike. Why? You can just open the door since it is passage function. Please confirm electric strike is required.

Per responses above included in this RFI, HW-15 is no longer in use on any doors in this project. Please delete set.

Whiting-Turner Kyle Krueger

Doors

Sets HW-15, HW-31, HW-31A, HW-31B and HW-40A have automatic flush bolts but no dust proof strike which we believe is required by code. Should dust proof strike be added?

Add dust proof strike if required by code. Per spec section 3.6 Hardware Sets (second paragraph) "The door hardware sets listed below are provided to establish a general intent to develop the final submittal for review." The sets shown are a guideline. Please submit hardware sets for Designer to review that meet required codes and intent for the door operation.

Whiting-Turner Kyle Krueger Doors

Set HW-40 has no means of securing inactive leaf. Is this the intent? If no, please provide additional info.

Add 1 PR of automatic flush bolts to HW-40.

Whiting-Turner Kyle Krueger

Doors

Set HW-40A has automatic flush bolts but no means of closing both leaves. Is this the intent? If no, please provide additional info.

Add 2 closers to set HW-40A. Closers are required for the fire rating and will provide closing for both leaves.

Whiting-Turner Kyle Krueger

Doors

Set HW-56 and HW-56A are for fire rated doors but have closer with hold open arm.

Labeled doors cannot be held open by code.

Please clarify.

Hold-open feature on closers can be eliminated in sets the contractor sends in to the designer for review for these doors.

Whiting-Turner Kyle Krueger

Doors

Set HW-30 has kick plates but no closers.

Kick plates are normally used when door have closers. This appears to be a potential error. Please clarify. Also the Cipher model number listed in 087100 part 2.3.16 requires a cylinder but no cylinder is listed. Please provide missing information.

Closers should be added to this set. Per previous responses, this is a fire rated door set and closers are required per code.

Whiting-Turner Kyle Krueger

Doors

Sets HW-31, HW-31A and HW-31B are pair of doors but only one means of stop is listed.

Please provide second means of stops.

Provide 2 floor stops foreach of these double-door sets instead of the currently-shown 1 floor stop at each set.

Whiting-Turner Kyle Krueger

Doors

Door 001A has door type G (Non-blast) but has Blast listed in door schedule notes.

Should blast be deleted in notes or should blast be added to door type G like door type C and D?

Door type for 001A should be revised to "E", which should be a "DBL

UNEVEN BLAST".

Whiting-Turner Kyle Krueger Doors

Frame type 4 does not provide transom height just “see sch.”. Please provide transom height.

Transom height shall be field verified as we are placing the blast doors into existing openings.

Whiting-Turner Kyle Krueger

Doors

Hollow metal spec only lists Level 1 for frames. Interior doors are 18ga and exterior doors are 14ga, but all frames are 18ga?

Please confirm. Also spec lists both KD frames and welded frames. May knock down frames be used at all HM doors?

Exterior door frames are all blast-resistant assemblies that should be built to withstand the blast pressures for the project. See Blast-resistant Doors spec. At a minimum, exterior doors and frames should both be 14 ga, welded frames - but the tested blast assembly requirements shall be met for each of them.

Whiting-Turner Kyle Krueger

Doors

029B is a cased opening (no door) but is STC50 and 90 min. Should STC & fire ratings be deleted or door added? If door requested to be added, please provide hardware and other missing information.

Cased opening 029B will not have STC or Fire ratings. Ratings should be removed from door schedule for this door.

Sheet1