The contract is for replacing/upgrading the electrical service distribution systems to 34 campsites at the Berry Bend Public Use Area in Benton County, MO. It is an Invitation for Bid (IFB) for a Firm-Fixed Price contract with an estimated value between $500,000 and $1,000,000. The Q&A covers questions about geotechnical requirements, whether the bid is flat rate or has a rock adder option, compaction testing requirements, and the use of Schedule 80 roll pipe instead of conduit sticks. The agency handling this contract is the Department of the Army Corps of Engineers, Engineering District Kansas City.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W912DQ24B1009 Berry Bend Electrical Upgrade
Q: “Are there any geos requirements and if so, have they already been performed?”
A: No Geotechnical report, just as built or red line drawings of utilities after completion.
Q: “Are we bidding flat rate or is rock adder an option?”
A: Lump sum bid, contractor needs to consider all factors into their bid.
Q: “Is compaction testing required?”
A: 3.5.2.1 shows the compaction requirements of this contract.
Q: “Are there any special open trenching requirements?”
A: Contractor must follow 385-1-1.
Q: “Can we use Sch 80 roll pipe rather than sticks of conduit?”
A: Would need to see the specification sheet for Sch 80 roll pipe. Needs to be Schedule 80 electrical rated for use with 90°C conductors; maximum ambient temperature is 122°F.