Item-No.Bldg-No.FloorItembelonging
to:ManufacturerModel-No.:
Ident-No.:CapacityManufacture YearAdditional
1.1.1MCC #01000BasementDiesel Engine IDiesel-Generating-Set IMTU (Diesel Engine)

FRERK Model 20V 4000 G23 Engine No.: 528 102 001 P= 2200 kW;

Speed: 1500 rpm 2011 12 ea. Starter Batteries for Generator GA11 (Hoppecke 11OSP.HC385; 2V/459Ah) Engine Terminal Box for Generator GA11 (FRERK Aggregatebau GmbH, Aggregat No.: 10042501;

Typ: 002576 411SY; Bj: 2011) exhaust system cabling cooling system (Aggregates for cooling system, pipes, valves), fuel cooler for Generator GA11 Diesel control cabinet (DCC11) and auxiliary (AUX11) control Batteries for Generator GA11 (2 ea Hoppecke SB60; 12V/63Ah) fuel feed system 4 ea. electric motor operated jalousie (control and actuation) emergency OFF system for generator GA11 (control and actuation) 2 ea. air inlet ventilator for GA11 2 ea. service switches for GA11 (SS01; SS02; SS03)

1.1.2 MCC #01000 Basement Fuel Oil Day Tank for Diesel Engine I Diesel-Generating-Set I Krampitz Tanksystem GmbH Manufacturer-No.: 17865 1.95 m3 2011 fuel pump unit for System GA11 fuel pump unit control for System GA11 piping and cabling

1.1.3MCC #01000Basementsecondary containment
for Fuel Oil Day Tank for Diesel Engine IDiesel-Generating-Set IKrampitz Tanksystem GmbHManufacturer-No.: 17865-A2.26 m32011
1.1.4MCC #01000BasementGenerator IDiesel-Generating-Set IMarelli Generators GA11Type: MJB 560LB4 B34

Code: MJB5682 G22080

Nr. MY18629Power:
2576 kVA2011cabling
1.2.1MCC #01000BasementDiesel Engine IIDiesel-Generating-Set IIMTU (Diesel Engine)

FRERK Model 20V 4000 G23 Engine No.: 528 102 002 P= 2200 kW;

Speed: 1500 rpm 2011 12 ea. Starter Batteries for Generator GA12 (Hoppecke 11OSP.HC385; 2V/459Ah) Engine Terminal Box for Generator GA12 (FRERK Aggregatebau GmbH, Aggregat No.: 10042502;

Typ: 002576 411SY; Bj: 2011) exhaust system cabling cooling system (Aggregates for cooling system, pipes, valves), fuel cooler for Generator GA12 Diesel control cabinet (DCC12) and auxiliary (AUX12) control Batteries for Generator GA11 (2 ea Hoppecke SB60; 12V/63Ah) fuel feed system 4 ea. electric motor operated jalousie (control and actuation) emergency OFF system for generator GA12 (control and actuation) 2 ea. air inlet ventilator for GA12 2 ea. service switches for GA12 (SS01; SS02; SS03)

1.2.2 MCC #01000 Basement Fuel Oil Day Tank for Diesel Engine II Diesel-Generating-Set II Krampitz Tanksystem GmbH Manufacturer-No.: 17866 1.95 m3 2011 fuel pump unit for System GA12 fuel pump unit control for System GA12 piping and cabling

1.2.3MCC #01000Basementsecondary containment
for Fuel Oil Day Tank for Diesel Engine IDiesel-Generating-Set IIKrampitz Tanksystem GmbHManufacturer-No.: 17866-A2.26 m32011
1.2.4MCC #01000BasementGenerator IIDiesel-Generating-Set IIMarelli Generators GA12Type: MJB 560LB4 B34

Code: MJB5682 G22080

Nr. MY18886Power:
2576 kVA2011cabling
1.3.1MCC #01000BasementDiesel Engine IIIDiesel-Generating-Set IIIMTU (Diesel Engine)

FRERK Model 20V 4000 G23 Engine No.: 528 102 003 P= 2200 kW;

Speed: 1500 rpm 2011 12 ea. Starter Batteries for Generator GA13 (Hoppecke 11OSP.HC385; 2V/459Ah) Engine Terminal Box for Generator GA13 (FRERK Aggregatebau GmbH, Aggregat No.: 10042503;

Typ: 002576 2061; Bj: 2011) exhaust system cabling cooling system (Aggregates for cooling system, pipes, valves), fuel cooler for Generator GA13 Diesel control cabinet (DCC13) and auxiliary (AUX13) control Batteries for Generator GA13 (2 ea Hoppecke SB60; 12V/63Ah) fuel feed system 4 ea. electric motor operated jalousie (control and actuation) emergency OFF system for generator GA13 (control and actuation) 2 ea. air inlet ventilator for GA13 2 ea. service switches for GA13 (SS01; SS02; SS03)

1.3.2 MCC #01000 Basement Fuel Oil Day Tank for Diesel Engine III Diesel-Generating-Set III Krampitz Tanksystem GmbH Manufacturer-No.: 17867 1.95 m3 2011 fuel pump unit for System GA13 fuel pump unit control for System GA13 piping and cabling

1.3.3MCC #01000Basementsecondary containment
for Fuel Oil Day Tank for Diesel Engine IDiesel-Generating-Set IIIKrampitz Tanksystem GmbHManufacturer-No.: 17867-A2.26 m32011
1.3.4MCC #01000BasementGenerator IIIDiesel-Generating-Set IIIMarelli Generators GA13Type: MJB 560LB4 B34

Code: MJB5682 G22080

Nr. MY18887Power:
2576 kVA2011cabling
1.4.1MCC #01000BasementMaster Control Panelfor Generator GA11 to 13
(MCP, AUX10)FRERKMaster control Panel for Generator (=EEES4000=MCP)

devices and cabling

1.5.1MCC #01000buried tank / outside of MCCFuel storage tank ST01
Steel cylinder tankDiesel-Generating Set I to IIIFRERK25m3Vacuum leak detector VL01 for fuel storage tank ST01

Vaccuum leak detector VL03 for fuel pipe storage tank ST01 and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

1.5.2MCC #01000buried tank / outside of MCCFuel storage tank ST02
Steel cylinder TankDiesel-Generating Set I to IIIFRERK25m3Vacuum leak detector VL02 for fuel storage tank ST02

Vaccuum leak detector VL04 for fuel pipe storage tank ST02 and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

1.6.1MCC #01000BasementOvervoltage Protection OP10Diesel-Generating Set I to IIIFRERK
1.7.1MCC #01000Roof of Diesel-Generator HouseLoadbank Modul No. 1:

=EEES4003

=RA01 Diesel-Generating Set I to III Crestchic Loadbanks 700 kW Resistive Loadbank Fixed Chanel Mounted

Serial No. C4309700 kW
1.7.2MCC #01000Roof of Diesel-Generator HouseLoadbank Modul No. 2:

=EEES4003

= RA02 Diesel-Generating Set I to III Crestchic Loadbanks 700 kW Resistive Loadbank Fixed Chanel Mounted

Serial No. C4308700 kW
1.7.3MCC #01000Roof of Diesel-Generator HouseLoadbank Modul No. 3:

=EEES4003

=RA03 Diesel-Generating Set I to III Crestchic Loadbanks 700 kW Resistive Loadbank Fixed Chanel Mounted

Serial No. C4307700 kW
1.7.4MCC #01000Roof of Diesel-Generator HouseVentilator Cooler for Generator GA11:

=EEES4000

=VC11 Diesel-Generating-Set I GEA Type:

HT-7250/2128 3CA1 S32 D302

Contract No.: 1721157493 BJ: 2011 Item 01 Group of Fluid: EAU-Water Working pressure: 4 bar ; Test pressure: 6 bar; Volume: 209 ltr.

1.7.5 MCC #01000 Roof of Diesel-Generator House additional Aggregate to Ventilator Cooler for Generator GA11 Diesel-Generating-Set I GEA Type:

LT-7250/2128 2CA2 S32 D302

Contract No.: 1721157493 BJ: 2011 Item 01 Working pressure: 4 bar ; Test pressure: 6 bar; Volume: 124 ltr.

1.7.6 MCC #01000 Roof of Diesel-Generator House Ventilator Cooler for Generator GA12:

=EEES4000

=VC12 Diesel-Generating-Set II GEA Type:

HT-7250/2128 3CA1 S32 D302

Contract No.: 1721157493 BJ: 2011 Item 03 Group of Fluid: EAU-Water Working pressure: 4 bar ; Test pressure: 6 bar; Volume: 209 ltr.

1.7.7 MCC #01000 Roof of Diesel-Generator House additional Aggregate to Ventilator Cooler for Generator GA12 Diesel-Generating-Set II GEA Type:

LT-7250/2128 2CA2 S32 D302

Contract No.: 1721157493 BJ: 2011 Item 03 Working pressure: 4 bar ; Test pressure: 6 bar; Volume: 124 ltr.

1.7.8 MCC #01000 Roof of Diesel-Generator House Ventilator Cooler for Generator GA13:

=EEES4000

=VC13 Diesel-Generating-Set III GEA Type:

HT-7250/2128 3CA1 S32 D302

Contract No.: 1721157493 BJ: 2011 Item 02 Group of Fluid: EAU-Water Working pressure: 4 bar ; Test pressure: 6 bar; Volume: 209 ltr.

1.7.9 MCC #01000 Roof of Diesel-Generator House additional Aggregate to Ventilator Cooler for Generator GA13 Diesel-Generating-Set III GEA Type:

LT-7250/2128 2CA2 S32 D302

Contract No.: 1721157493 BJ: 2011 Item 02 Working pressure: 4 bar ; Test pressure: 6 bar; Volume: 124 ltr.

2.1 PX #07850 Technic-Room Diesel Engine Diesel-Generator-System Perkins (Diesel Engine) Perkins Model:

Engine No.: P= 800 kW;

Speed: 1500/1800 rpm 2014 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( Kunzler)

2.2 PX #07850 Technic-Room Fuel Oil Day Tank for Diesel Engine Diesel-Generator-System Krampitz Tanksystem GmbH Manufacturer-No.: 0.98 m3 2014 fuel pump unit for Generator System fuel pump unit control for Generator System piping and cabling

2.3PX #07850Technic-RoomAdditional Fuel Oil Tank for Diesel EngineDiesel-Generator-SystemCEMO Tanksystem GmbHManufacturer-No.:2000 l2014piping and cabling
2.4PX #07850Technic-Roomsecondary containment
for Fuel Oil Day Tank for Diesel EngineDiesel-Generator-SystemKrampitz Tanksystem GmbHManufacturer-No.:1.09 m320141 ea fuel detector in technic room (on floor)
2.5PX #07850Technic-RoomGeneratorDiesel-Generator-SystemKunzler GeneratorsType:
Model:Power:
800 kVA2014cabling
2.6PX #07850Technic-RoomMaster Control Panelfor Generator
( )KunzlerType:
Model:2014Master control Panel for Generator ( )

devices and cabling

2.7PX #07850buried tank / outsideFuel storage tank
Steel cylinder tankDiesel-Generator-System2014Vacuum leak detector VL01 for fuel storage tank

Vaccuum leak detector for fuel pipe storage tank and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

3.1 Clay Nord #03377 Outside Diesel Engine Diesel-Generator-System MTU (Diesel Engine) MTU Model:

Engine No.: P= 1000 kW;

Speed: 1500/1800 rpm 2012 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

3.2Clay Nord #03377OutsideGeneratorDiesel-Generator-SystemType:
Model:Power:
1000 kVA2012Generator, devices and cabling
3.3Clay Nord #03377OutsideMaster Control Panelfor Generator
( )Type:
Model:2012Master control Panel, devices and cabling
3.4Clay Nord #03377OutsideFuel tankDiesel-Generator-System1000 l2012Vaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

4.1 Clay #01757 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

4.2Clay #01757See ESP AECOMGenerator, devices and cabling
4.3Clay #01757See ESP AECOMMaster control Panel, devices and cabling
4.4Clay #01757See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

5.1 Clay Bushalte #01024 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

5.2Clay Bushalte #01024See ESP AECOMGenerator, devices and cabling
5.3Clay Bushalte #01024See ESP AECOMMaster control Panel, devices and cabling
5.4Clay Bushalte #01024See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

6.1 Clay Cont.Master #01036 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

6.2Clay Cont.Master #01036See ESP AECOMGenerator, devices and cabling
6.3Clay Cont.Master #01036See ESP AECOMMaster control Panel, devices and cabling
6.4Clay Cont.Master #01036See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

7.1 Clay Cont.Slave #01036 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

7.2Clay Cont.Slave #01036See ESP AECOMGenerator, devices and cabling
7.3Clay Cont.Slave #01036See ESP AECOMMaster control Panel, devices and cabling
7.4Clay Cont.Slave #01036See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

8.1 Clay #01050 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

8.2Clay #01050See ESP AECOMGenerator, devices and cabling
8.3Clay #01050See ESP AECOMMaster control Panel, devices and cabling
8.4Clay #01050See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

9.1 Clay Airfield Thomas #01086 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

9.2Clay Airfield Thomas #01086See ESP AECOMGenerator, devices and cabling
9.3Clay Airfield Thomas #01086See ESP AECOMMaster control Panel, devices and cabling
9.4Clay Airfield Thomas #01086See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

10.1 Clay Cont. Ruffo #01192 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

10.2Clay Cont. Ruffo #01192See ESP AECOMGenerator, devices and cabling
10.3Clay Cont. Ruffo #01192See ESP AECOMMaster control Panel, devices and cabling
10.4Clay Cont. Ruffo #01192See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

11.1 Clay AFN #01222 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

11.2Clay AFN #01222See ESP AECOMGenerator, devices and cabling
11.3Clay AFN #01222See ESP AECOMMaster control Panel, devices and cabling
11.4Clay AFN #01222See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

12.1 Clay Cont. MA-Weiler #01507 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

12.2Clay Cont. MA-Weiler #01507See ESP AECOMGenerator, devices and cabling
12.3Clay Cont. MA-Weiler #01507See ESP AECOMMaster control Panel, devices and cabling
12.4Clay Cont. MA-Weiler #01507See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

13.1 AEC #05301 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

13.2AEC #05301See ESP AECOMGenerator, devices and cabling
13.3AEC #05301See ESP AECOMMaster control Panel, devices and cabling
13.4AEC #05301See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

14.1 HBG Lodge #07890 See ESP AECOM 1 ea. Starter Batteries for Generator System ( ) exhaust system ( ) cabling cooling system ( ) Diesel control cabinet ( MTU)

14.2HBG Lodge #07890See ESP AECOMGenerator, devices and cabling
14.3HBG Lodge #07890See ESP AECOMMaster control Panel, devices and cabling
14.4HBG Lodge #07890See ESP AECOMVaccuum leak detector for fuel tank and pipe

and all connected and relevant items (e.g. pipes, valves, mech. & elektr. switches etc.)

&C&16USAG Wiesbaden Emergency Power Generator Systems Inventory List&R&"-,Bold"Exhibit D - Inventory Full Service M-R of Em. Gen._FY17 to FY19.xls last update: 20-Oct-2016 Page &P of &N &Z&F&RPage &P