Inspection Report of Turbine Bay Crane at Ozark Powerhouse Rev 1
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
www.sievertelectric.com
INSPECTION REPORT OF TURBINE BAY CRANE
(150/15T) AT OZARK POWERHOUSE
PREPARED FOR
CONTRACTING DIVISION
USACE, LITTLE ROCK (W9127S)
700 W. CAPITOL AVE, RM 7315
LITTLE ROCK AR 72201-3225
PREPARED BY
SIEVERT CRANE AND HOIST,
DIVISION OF SIEVERT ELECTRIC
1230 S HANNAH AVE,
FOREST PARK, IL 60130
CONTRACT # W9127S-15-P-0139
NOVEMBER 05, 2015
Sievert Electric 1230 South Hannah Ave.
Forest Park, IL 60130
Phone: 708-771-1600
Fax: 708-771-3124 www.sievertelectric.com
INSPECTION REPORT
PAGE: ____ OF ____1 6
JOB NO:_________________41728
CUSTOMER:__________________________________OZARK POWERHOUSE
ADDRESS:___________________________________
1598 LOCK & DAM RD., RUSSELLVILLE,
AR 72802
LOCATION/DESC:_____________________________OZARK POWERHOUSE
SCHEDULED DATE:_________________10/19/15
DIVISION:__________________________________
PHONE:_____________________________________
OWNER ID:__________________________________26719
EQUIPMENT TYPE:____________________________________________________________________________TR-DG TOP RUNNING CRANE - CAB CONTROLLED MOTOR DRIVEN
MAKE/MODEL:________________________________
INSPECTED BY:______________________________JOSH GUYER
SYSTEM SERIAL #:___________________________6845
INSPECTED ON:______________________________10/19/15
BRIDGE
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
BRIDGE - INSPECTION
XMOTOR
XMOTOR BRAKE
XGEAR REDUCER
XEND TRUCKS
XWHEELS
XCATWALK ACCESS - GUARD RAIL
XBRIDGE GIRDERS -CRACKED WELD AT
END OF RAIL ON THE
DOWNSTREAM/RIVERSID
E OF RAIL.
XCONTROL PANELS
XLIGHTS -ONE LIGHT NEAR
OPERATORS CAB IS
UNPLUGGED
INTENTIONALLY DUE
TO IT BLINDING
OPERATOR DURING
OPERATION.
XWARNING DEVICES
XMAIN COLLECTORS / COLLECTOR POLE -ALL 6 COLLECTOR
INSERTS ARE WORN
AND SHOULD BE
REPLACED. (100 AMP
DUCTOBAR)
150/15 TONBRIDGE CAPACITY:
BROADLINE CORP.BRIDGE MANUFACTURER:
480 VACBRIDGE POWER SUPPLY:
115VACBRIDGE CONTROL:
VFDBRIDGE DRIVE:
SERIAL NUMBER: 6845
Printed Date: November 11, 2015 03:56 PM
Visual inspection only. Customer is ultimately reponsible for safety, safe use, and start of shift inspections.
PAGE: ____ OF ____2 6
CUSTOMER:__________________________________OZARK POWERHOUSE LOCATION/DESC:_____________________________Ozark Powerhouse
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
XBRIDGE CROSS CONDUCTORS
XCLEARANCES
XLOAD TEST
XDISCONNECT SWITCH
XBUMPERS
XCAPACITY MARKINGS
XMOUNTING BOLTS
SERIAL NUMBER:
HOIST - ELECTRIC WIRE ROPE
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
HOIST - ELEC WIRE ROPE
XLOWER BLOCK
XWIRE ROPE
XMOTOR
XMOTOR BRAKE
XGEARED LIMIT SWITCH
XBLOCK LIMIT SWITCH
XGEAR REDUCER -OIL IS LEAKING AT
VARIOUS SHAFT SEALS
ON SECONDARY DRUM
GEAR REDUCER. OIL
LEVEL IS EMPTY. AL
SEALS ON DRUM
REDUCER SHOULD BE
REPLACED AND NEW
OIL TO PROPER
LEVEL.
XSHAFTS
XROPE DRUM
XUPPER BLOCK
XCONTROL PANELS
XCLEARANCES
XCAPACITY AND WARNING SIGNS
BROADLINE CORP.MANUFACTURER:
75 TONHOIST CAPACITY:
480 VACHOIST POWER SUPPLY:
115 VACHOIST CONTROL:
VARIABLEHOIST SPEED:
#1 MAINOWNER ID NUMBER:
MAIN HOIST #1
SERIAL NUMBER:
HOIST - ELECTRIC WIRE ROPE
BROADLINE CORP.MANUFACTURER:
15 TONHOIST CAPACITY:
480 VACHOIST POWER SUPPLY:
115 VACHOIST CONTROL:
VARIABLEHOIST SPEED:
#1 AUX.OWNER ID NUMBER:
AUX. #1
Printed Date: November 11, 2015 03:56 PM
Visual inspection only. Customer is ultimately
PAGE: ____ OF ____3 6
CUSTOMER:__________________________________OZARK POWERHOUSE LOCATION/DESC:_____________________________Ozark Powerhouse
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
HOIST - ELEC WIRE ROPE
XLOWER BLOCK
XWIRE ROPE
XMOTOR
XMOTOR BRAKE
XGEARED LIMIT SWITCH
XBLOCK LIMIT SWITCH
XGEAR REDUCER -OIL IS LEAKING
FROM OIL SEAL
BETWEEN PRIMARY
REDUCER AND DRUM
REDUCER. OIL LEVEL
IN DRUM REDUCER IS
EMPTY. SHOULD
REPLACE ALL SEALS
ON DRUM REDUCER AND
ADD NEW OIL TO
PROPER LEVEL.
XSHAFTS
XROPE DRUM
XUPPER BLOCK
XCONTROL PANELS
XCLEARANCES
XCAPACITY AND WARNING SIGNS
SERIAL NUMBER:
HOIST - ELECTRIC WIRE ROPE
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
HOIST - ELEC WIRE ROPE
LOWER BLOCK X -MONITOR: CABLE ON
CABLE REEL HAS A
BULGE IN ONE AREA,
BUT THE IS NO
BROKEN INSULATION
OR SIGNS OF BROKEN
WIRES.
XWIRE ROPE -WHEN HOOK IS
LOWERED, THE WIRE
ROPE TWISTS AND
CAUSES WIRE ROPE TO
RUB AGAINST ITSELF.
RECOMMEND REMOVING
WIRE ROPE AND RE-
REEVING TO REMOVE
TWIST.
XMOTOR
BROADLINE CORP.MANUFACTURER:
75 TONHOIST CAPACITY:
480 VACHOIST POWER SUPPLY:
115 VACHOIST CONTROL:
VARIABLEHOIST SPEED:
#2 MAINOWNER ID NUMBER:
MAIN HOIST #2
Printed Date: November 11, 2015 03:56 PM
Visual inspection only. Customer is ultimately
PAGE: ____ OF ____4 6
CUSTOMER:__________________________________OZARK POWERHOUSE LOCATION/DESC:_____________________________Ozark Powerhouse
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
XMOTOR BRAKE
XGEARED LIMIT SWITCH
XBLOCK LIMIT SWITCH
XGEAR REDUCER
XSHAFTS
XROPE DRUM
XUPPER BLOCK
XCONTROL PANELS
XCLEARANCES
SERIAL NUMBER:
TROLLEY - ELECTRIC
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
TROLLEY - ELECTRIC
XMOTOR
XMOTOR BRAKE
XTRAVERSE REDUCER
XEND TRUCK
XWHEELS
XBUMPERS
XDROP LUGS / SWEEPS
XCONTROL PANELS
XEND STOPS
XCAPACITY AND WARNING SIGNS
XCLEARANCES -A MID RAIL SHOULD
BE ADDED TO
EXISTING RAIL ON
DOWNSTREAM SIDE OF
TROLLEY. 2"X2"X117
1/4" SQUARE TUBING.
90 TONTROLLEY CAPACITY:
BROADLINE CORP.MANUFACTURER:
115 VACTROLLEY CONTROL:
#1 MAINOWNER ID NUMBER:
VARIABLETROLLEY SPEED:
480 VACTROLLEY POWER SUPPLY:
#1 MAIN TROLLEY
SERIAL NUMBER:
TROLLEY - ELECTRIC
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
TROLLEY - ELECTRIC
XMOTOR
XMOTOR BRAKE
75 TONTROLLEY CAPACITY:
BROADLINE CORP.MANUFACTURER:
115 VACTROLLEY CONTROL:
#2 MAINOWNER ID NUMBER:
VARIABLETROLLEY SPEED:
480 VACTROLLEY POWER SUPPLY:
DOWNSTREAM MAIN TROLLEY #2
Printed Date: November 11, 2015 03:56 PM
Visual inspection only. Customer is ultimately
PAGE: ____ OF ____5 6
CUSTOMER:__________________________________OZARK POWERHOUSE LOCATION/DESC:_____________________________Ozark Powerhouse
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
XTRAVERSE REDUCER
XEND TRUCK
XWHEELS
XBUMPERS -UPSTREAM/LAND SIDE
BUMPER SPRING IS
BROKEN. SPRING
NEEDS TO BE
REPLACED.
XDROP LUGS / SWEEPS
XCONTROL PANELS
XEND STOPS
XCAPACITY AND WARNING SIGNS
XCLEARANCES
SERIAL NUMBER:
RUNWAY
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
RUNWAY - INSPECTION
XRAILS / BEAMS - WEAR
XSPLICE PLATES -SECOND AND SECOND
TO LAST SPLICE
PLATE FROM LAND
SIDE ON UPSTREAM
SIDE OF RUNWAY HAS
A LOOSE BOLT ON
EACH. ON DOWNSTREAM
SIDE OF RUNWAY,
THIRD SPLICE PLATE
FROM LAND SIDE, HAS
LOOSE BOLTS. ALL
LOOSE BOLTS SHOULD
BE TIGHTENED.
XJ-BOLTS / CLIPS / HANGERS -ON UPSTREAM SIDE,
THERE IS A LOOSE
RAIL CLAMP NUT NEXT
THE SECOND TO LAST
SPLICE PLATE FROM
LAND SIDE. ON
DOWNSTREAM SIDE
THERE ARE A FEW
LOOSE RAIL CLAMP
NUTS NEAR THIRD
SPLICE PLATE FROM
LAND SIDE.
XEND STOPS -THERE ARE NO END
STOP PLATES MOUNTED
TO WALL ON
RIVERSIDE OF RUNWAY
LIKE THERE IS ON
THE LAND SIDE. A
12"X12"X1" SHOULD
ASCE RAILBEAM TYPE:
135#BEAM SIZE:
DUCTOBAR DUAL 100ACOLLECTORS:
INSUL8POWER BAR:
NSA15-1019000038
Printed Date: November 11, 2015 03:56 PM
Visual inspection only. Customer is ultimately
PAGE: ____ OF ____6 6
CUSTOMER:__________________________________OZARK POWERHOUSE LOCATION/DESC:_____________________________Ozark Powerhouse
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
BE ANCHORED TO THE
WALL ON BOTH SIDES
OF RIVERSIDE.
XCONDUCTORS -ONE SPLICE CAP IS
BROKEN IN HALF
BETWEEN THE THIRD
AND FOURTH TURBINE.
NEEDS TO BE
REPLACED TO PREVENT
COLLECTOR SHOE FROM
COMING OUT OF
CONDUCTOR BAR
INSULATION GROOVE.
SERIAL NUMBER:
TOP RUNNING CRANE - CAB CONTROLLED
TR-DGTYPE:
MOTOR DRIVENDRIVE TYPE:
150/15 TONCAPACITY:
BROADLINE CORP.MANUFACTURER:
SERIAL NUMBER:
CAB
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
CAB - INSPECTION
XOPERATOR'S CAB
XCONTROLS
XLIGHTING
XFIRE EXTINGUISHER
XLADDERS
STARFLITE SYSTEMS INC.MANUFACTURER:
JOYSTICKCONTROL TYPE:
115 VACCONTROL VOLTAGE:
05-934
SERIAL NUMBER:
RADIO
COMPONENT OK REPAIR REPLACE MONITOR COMMENTS
RADIO - INSPECTION
XHOUSING
XRADIO CONTROL
XBUTTONS
MAGNETEKMANUFACTURER:
SLTXMODEL NUMBER:
175-01618ID NUMBER:
273507-TX1
Printed Date: November 11, 2015 03:56 PM
Visual inspection only. Customer is ultimately
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 1 Rev 1
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
www.sievertelectric.com
CONTENTS
Inspection Report Summary
1.1 Project Information
1.2 Procedure
1.3 Results
1.3.1 Bridge
1.3.2 Main Hoist #1
1.3.3 Aux Hoist #1
1.3.4 Main Hoist #2
1.3.5 Trolley #1
1.3.6 Trolley #2
1.3.7 Runway
1.4 Conclusion
1.5 Closing
Appendix A: Pictures
Appendix B: Estimated Cost for the Repairs
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 2
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
www.sievertelectric.com
INSPECTION REPORT SUMMARY
November 11, 2015
Contracting Division
USACE, Little Rock (W9127S)
700 W. Capitol Ave, RM 7315
Little Rock AR 72201-3225
Subject: Inspection Report for Turbine Bay Crane, Ozark Powerhouse, Russellville Project Office.
Sievert Job No.: 41728
Mr. David Glorit, In general accordance with our Contract No.: W9127S-15-P-0139 with the Contracting
Division of the United States Army Corps of Engineers (USACE), Sievert Crane and Hoist, a division of Sievert Electric, has completed engineering services associated with the Turbine
Bay Crane located at Ozark Powerhouse, 1204 Aux Arc Road Ozark, Arkansas 72949. This report describes our understanding of the project information; the service performed, and presents the findings along with our conclusions and recommendations.
1.1 Project Information
The crane is a double girder crane with a capacity of 150 Ton and has two hoist trolleys.
Figure 1, shows the layout of the crane and shows the terminology used to identify the directions used in this report.
Hoist Trolley #1 : Located at Upstream Side of the Crane
Main Hoist #1 : 75 Ton
Aux Hoist #1 : 15 Ton
Hoist Trolley #2 : Located at Downstream Side of the Crane
Main Hoist #2 : 75 Ton
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 3
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
www.sievertelectric.com
Figure 1: Layout of the crane
1.2 Procedure
The project commenced with the assessment and preparation of Accident prevention plan and activity hazard analysis. Once complete the plans were submitted to the Contracting office and subsequently approved.
The inspection was performed from October 19, 2015 to October 22, 2015. The inspection generally consisted of performing visual observations and obtaining measurement of selected components of crane using Vernier Calliper. The observations included:
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 4
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
www.sievertelectric.com
Visually scanning the accessible portion of each of the individual components and the associated connections in the structural framing.
Checking for metal shavings in the gear reducers using magnets.
Checking the general operations/functioning of the crane (bridge, hoists and trolleys).
Inspecting the rope for broken wires by spooling the wire rope
Measuring the diameter of the wire rope at various locations of the wire rope.
Measuring the tread width of the runway at various random locations.
1.3 Results
This section provides a general summary of the typical issues noted during the inspection.
Appendix A shows the photographic documentation of these issues.
1.3.1 Bridge
There is a crack in the weld between the trolley rail (for cross travel of the hoist trolley) and the Girder.
Figure 2: Location of the damaged weld on crane
One of the crane lights is unplugged intentionally; because the light falls directly on the operators eyes causing lack of visibility to the operator during operation.
All the 6 main collector inserts (100 Amp Ductobar) are worn and need to be replaced.
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 5
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
www.sievertelectric.com
1.3.2 Main Hoist #1
Oil level in the Gear Reducer/ Gearbox was empty. There is oil leakage at various shaft seals on secondary drum gear reducer. The oil seals need to be replaced and the gear reducer needs to be filled with oil to proper level
1.3.3 Aux Hoist #1
Oil level in the Gear Reducer/ Gearbox was empty. There is oil leakage between the primary and the secondary gear reducer. Seals on drum gear reducer are worn and need to be replaced and the gear reducer needs to be filled with oil to proper level.
1.3.4 Main Hoist #2
Cable Reel: There is a bulge on the cable in the cable reel. There is no sign of broken insulation or wires. This needs to be monitored periodically.
Wire Rope: When the hook is lowered the wire rope rubs against itself, this is mainly due to the twist in the wire rope. We recommend removing the wire rope and performing re-reeving to remove the twist.
1.3.5 Trolley #1
There is an unsafe opening on the trolley on the downstream side; we recommend adding a mid-section guard rail to the existing hand rail to reduce the opening.
1.3.6 Trolley #2
The bumper spring (Upstream and Land side) on the trolley is broken and needs to be replaced.
1.3.7 Runway
Upstream Side Runway
There are loose bolts on splice plates at couple of locations. One of these splice plates is second from the land side and the other is second from riverside.
There is a loose rail clamp nut near second to last splice plate from land side.
Downstream Side Runway
There is a loose bolt connection on the third splice plate from the land side.
There are a few loose rail clamp nuts near third splice plate from land side.
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 6
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
www.sievertelectric.com
All the loose connections must be tightened.
End Stops: There are no End Stop plates mounted on the wall on the riverside of the runway. A 12” x 12” x 1” plate should be anchored to the wall on both the runways at riverside.
Conductors: One of the slice caps located between the third and fourth turbine is broken in half and needs to be replaced to prevent collector shoe from coming out of the conductor bar insulation.
Paint flakes: Both the runways have chipped off paint flakes, but there is no wear of the runways.
1.4 Conclusion
The results of the inspection conducted by Sievert Crane and Hoist indicate that a major problem with the crane is the “rubbing of ropes” for Hoist #2 and we highly recommend removing the wire rope and performing “re-reeving” in order to remove the twist in the rope. The crane is functionally in good condition1, we advise to take into consideration the recommendations presented in this report, which will improve the life of the crane and safety for the crane operators.
Note 1: Visual inspection only, Customer is ultimately responsible for safety, safe use, and start of shift inspections
1.5 Closing
We appreciate the opportunity to Sievert Crane and Hoist for these services and would be glad to discuss any of the results contained in this report. If we can be of any further assistance, please do not hesitate to contact our office.
Sincerely, Scott Sievert
Project Manager
Sievert Crane and Hoist
1230 S Hannah Ave, Forest Park, IL. 60130
708-771-1600
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 7
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
FAX 708-771-3124
APPENDIX A: PICTURES
Picture 1: Damaged weld between the girder and rail
Picture 2: Unplugged Light under the bridge
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 8
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
Picture 3: Worn out collector inserts
Picture 4: Main Hoist #1 Oil Seals damaged and low oil level in the Secondary Gear Reducer
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 9
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
Picture 5: Aux Hoist #1, oil seals broken, oil need to be filled in the Secondary Gear Reducer
Picture 6: Main Hoist #2, Cable reel, Bulge on the cable
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 10
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
Picture 7: Main Hoist #2, Rope rubbing against each other at lower hook position
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 11
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
Picture 8: Trolley #1, recommended additional mid rail
Picture 9: Trolley #2, Location of broken bumper
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 12
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
Picture 10: Trolley #2, View of the broken bumper
Picture 11: Runway Upstream side, loose bolt connection on the splice plate
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 13
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
Picture 12: Runway, Recommended end stops on the riverside end
Picture 13: Broken conductor splice plate
Inspection Report of Turbine Bay Crane at Ozark Powerhouse 14
Specialists in hoists, cranes, and electrical service since 1913
1230 South Hannah Avenue
Forest Park, IL. 60130-2448
708-771-1600
Picture 14: Paint Flakes on the runway