7N26QA155 LOP FP Amendment 2.pdf
PDF 4 MB Posted
- Attached to
- LOP Fire Protection and Unwatering Pump System
- Solicitation number
- W9127N26QA155
About this file
STANDARD FORM 30 - AMENDMENT 0002 TO SOLICITATION W9127N26QA155
This is Amendment 0002 to solicitation W9127N26QA155 issued by the U.S. Army Corps of Engineers, Portland District Contracting Division. The amendment extends the solicitation closing date from September 9, 2026 to September 11, 2026 and revises the Statement of Work in response to ProjNet inquiries. The effective date is September 4, 2026. All other terms and conditions remain unchanged.
The Statement of Work covers procurement of fire protection and unwatering pump systems for Lookout Point Powerhouse in Lane County, Oregon. The project requires a complete vertical pump/motor assembly (650 GPM at 200 feet head, 50 HP nominal), a 0.25 HP jockey pump system (90 psi), a fire pump controller panel (UL listed for fire pump service), a manual transfer switch for dual-purpose pump operation, overload protection compatible with existing equipment, piping materials (10-inch and 6-inch carbon steel pipe with associated fittings, flanges, bolts, nuts, washers, and gaskets), a waterflow alarm switch, and two cold-cutting split-frame clamshell pipe cutting tools (4-8 inch and 6-12 inch). All equipment must be new with FOB destination delivery. The contractor must provide comprehensive documentation including operations and maintenance manuals, performance curves, factory test reports with government witnessed testing, cut-sheets, and descriptive drawings demonstrating full compliance with specified standards. Deliveries must occur Monday through Thursday between 7:00 a.m. and 3:00 p.m. Pacific Time to the Lookout Point facility in Lowell, Oregon. The contractor must assign all applicable manufacturer warranties to the Government and provide warranty documentation enabling direct claims without contractor involvement.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 7N26QA155 LOP FP Amendment 3.pdf | ||
| 7N26QA155 LOP FP Conformed Amendment 1.pdf | ||
| 7N26QA155 LOP FP Amendment 1.pdf | ||
| 7N26QA155 LOP FP Solicitation.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers is extended. is not extended.
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
(a) By completing items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER.
If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NUMBER AS DESCRIBED IN ITEM 14.
CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER
NUMBER IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print) 16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
15B. CONTRACTOR/OFFEROR
(Signature of person authorized to sign)
15C. DATE SIGNED 16B. UNITED STATES OF AMERICA
(Signature of Contracting Officer)
16C. DATE SIGNED
Previous edition unusable STANDARD FORM 30 (REV. 11/2016) Prescribed by GSA FAR (48 CFR) 53.243
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT 1. CONTRACT ID CODE PAGE OF PAGES
2. AMENDMENT/MODIFICATION NUMBER 3. EFFECTIVE DATE 4. REQUISITION/PURCHASE REQUISITION NUMBER 5. PROJECT NUMBER (If applicable)
6. ISSUED BY CODE 7. ADMINISTERED BY (If other than Item 6) CODE
8. NAME AND ADDRESS OF CONTRACTOR (Number, street, county, State and ZIP Code) (X) 9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED (SEE ITEM 11)
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED (SEE ITEM 13)
CODE FACILITY CODE
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
Block 14 (Description of Amendment/Modification):
The purpose of this amendment is as follows:
Extend the solicitation closing date to 09/11/2026.
Revise the SOW in response to ProjNet inquiries. Additions are highlighted in orange, deletions are not shown.
All other terms and conditions remain unchanged.
Solicitation/Contract Form
The following changes have been made:
INFORMATION FROM TO
Response Due Date
09 Sep 2026 11 Sep 2026
Description/Specifications/Statement of Work
Miscellaneous text in this section has been modified to:
STATEMENT OF WORK
LOOKOUT POINT POWERHOUSE FIRE PROTECTION AND UNWATERING PUMP SYSTEM
PROCUREMENT, LANE COUNTY, OREGON
1. PROJECT BACKGROUND:
A deep drawdown of the Lookout Point reservoir will dewater the penstock, cutting off the facility's service water. This will disable critical systems, including fire protection. These systems are essential for maintaining primary power to the facility and for ensuring fire safety.
W9127N26QA1550002
2. MEASUREMENT AND PAYMENT:
All equipment must be new, including FOB destination delivery, and meet or exceed all of the following requirements.
0001. Vertical Pump/Motor Assembly - 650 GPM at 200 feet Head (Water) (50HP nominal):
Provide new Vertical Pump type Centrifugal or Mixed Flow with the following characteristics.
a. Target Service Point:
i. 650 GPM
ii. 200 ft Nominal Head (Assumed Total Dynamic Head for Curve)
iii. Service point to left of Best Efficiency Point (Require a flatter trajectory to left of service point as well)
iv. Sump Characteristics for Service Point (Elevations expressed in NGVD 29 datum)
1. Motor Mount EL: 715 feet
2. Fire Operation Water Surface EL: 690-695 feet
3. Unwatering Operation Surface EL: Pump on at 675 off at 663
4. Sump Floor EL: 662 feet
b. Pump Features
i. Dead-Head Capable / Mechanical Seal
ii. Product (Water) Lubricated (Open or enclosed shaft allowed)
iii. Shaft Enclosing tube supports using flange sandwiched spiders
iv. Suction Strainer with 0.5" openings
v. Flanged Column, in 10 foot sections
vi. Above Floor, Short Radius Elbow Discharge
vii. Vacuum Breaker / Air Release Valve Mounted on Discharge Head
viii. Supplementary Lubrication Water Connection on Motor Mount, Discharge Head.
c. Provide pump components as indicated for a complete assembly.
d. Vertical lineshaft manufactured for lubrication of the line-shaft bearings by the water being pumped.
e. Pumping unit shall meet AWWA E103.
f. Provide pump materials in accordance with HI 9.1-9.5 for corrosion, erosion, and abrasion resistance.
g. Supply all necessary couplings, bearing brackets and supports needed to fully install the pump and motor.
h. Motor Requirements:
i. Must be squirrel cage
ii. Must be hollow shaft.
iii. Must have vertical orientation.
iv. Must have integrated thrust bearing.
v. Must operate on 460 VAC.
vi. Must operate satisfactorily at 5 percent overvoltage and 25 percent undervoltage for closing and opening.
vii. Must be open drip-proof (ODP).
viii. Must be capable for use with vertical pump described in CLIN 0001.
ix. Power factor must be above 0.8 at full load.
x. Service factor must be 1.00 or less.
xi. Efficiency must be above 92%.
i. Supply all drawings, including exploded views and dimensions, necessary to completely disassemble and reassemble the provided assembly.
j. Supply the operations and maintenance manuals that a minimum:
i. Describes the Operation of the pump and motor
ii. Lists the required maintenance of the pump and motor
iii. Contains a parts list
iv. Describes the repair/troubleshooting instructions for common problems
v. Contains safety warnings and instructions
vi. Documentation of Manufacturer's Standard Factory Test
k. Supply the pump performance curves
l. Supply the motor performance curves
m. Demonstrate that the proposed pump complies with the specified performance. Provide Factory pump test report consisting of the generated curves with test points, date of test, and test operator listed. The pump must be capable of operation without instability over the entire range of heads specified. Tolerances must be in accordance with HI requirements. Instability is defined, for this specification, as when one or more of the following conditions occur:
i. a. the pump has two or more flow rates at the same total head;
ii. b. The Head-capacity curve has a dip (region on curve where change in flow rate produces an abnormally low head);
iii. c. When any point in the usable range of head-capacity curve cannot be repeated within 3 percent.
iv. Includes Government Witnessed testing.
n. Rerun the test if this occurs. Test procedures, except as specified, must be in accordance with applicable provisions of HI ANSI/HI 14.6. The acceptance grade is 2B as described in HI ANSI/HI 14.6. Pumps are acceptable if they achieve the guarantee point requirements stated in this Statement of Work. Use water at approximately the same temperature for all tests run and record the temperature during test runs. Take vibration measurements in accordance with HI 9.6.4. If any vibration limits exceed those recommended by HI Figure 9.6.4.2.5.ab or if any deficiencies are revealed during any tests, correct such deficiencies and re-conduct the tests.
o. Manufacturers Standard Coating
0002. Furnish New 0.25 HP, 90 psi water pressure maintenance system (Jockey Pump System):
Provide new, water pressure maintenance system for the support of a 90 psi nominal piping system.
a. System must have an integrated control system with adjustable setpoint between 50 psi and 100 psi, for the control of a packaged water pump/motor assembly, and accumulator or bladder style gas buffer system.
b. Motors must be of the ball bearing type suitable for operation on 120 VAC and must operate the switch satisfactorily at 5 percent overvoltage and 25 percent undervoltage for closing and opening.
c. Protect the motor with overloads, sized as required by the motor, and have a molded case circuit breaker with magnetic trip unit for use as a disconnect means within the enclosure.
d. Supply all drawings, including exploded views and dimensions, necessary to completely disassemble and reassemble the provided assembly
e. Supply the operations and maintenance manuals that a minimum:
i. Describes the Operation of the pump and motor
ii. Lists the required maintenance of the pump and motor
iii. Contains a parts list
iv. Describes the repair/troubleshooting instructions for common problems
v. Contains safety warnings and instructions
0003. New Fire Pump Controller Panel:
a. Controller must be across the line starting type, rated 600 VAC, 3-phase, 3-wire, at 60-Hz.
b. Controller must be designed for a 50 HP motor at 480 VAC.
c. Controller must have a short circuit rating of 100,000 amps rms.
symmetrical at 480 VAC.
d. Controller must be the automatic type and UL listed and certified for fire pump service.
e. Controller must be completely wired, ready for field connections, and mounted in a free standing NEMA Type 12 or better enclosure arranged so that controller current carrying parts will not be less than 12 inches above the floor.
f. Fire pump controller must comply with NFPA 20, UL 218, and NFPA 70 /NEC standards to ensure reliable operation.
g. Fire pump controller must include automatic starting, manual electric shutdown, and have an overcurrent protective device designed to indefinitely carry locked-rotor current of a 50HP 480VAC fire pump without tripping.
h. Controller must monitor pump running, loss of a phase or line power, phase reversal and pump room temperature.
i. Controller must be equipped with terminals for remote monitoring of pump running, pump power supply trouble (loss of power or phase reversal), and pump room trouble (pump room temperature), and for remote start.
j. Controller must require the pump to run for ten minutes prior to automatic shutdown.
k. Provide a manual push button to shut down the pumps.
l. The controller must be equipped with an externally operable isolating switch which manually operates the motor circuit.
m. Means must be provided in the controller for measuring current for motor circuit conductors.
0004. New Manual Transfer Switch:
Contractor must furnish quantity one Manual Transfer Switch (for Dual-Purpose Pump Operation) A heavy-duty manual double-throw, transfer switch (MTS) is required to safely switch the pump's electrical connections and control signals between two distinct operational modes: "Fire Pump Mode" and "Unwatering Pump Mode." This switch acts as a selector, ensuring that the pump can only operate in one mode at a time and is completely isolated from the other mode's control system.
The Transfer Switch must be:
a. 3-Pole (for 3-Phase motor)
b. Manual
c. Double-Throw
d. Safety Switch
e. Break-Before-Make with a Center-OFF position
f. 600 VAC
g. Sized to handle the full load and locked-rotor current of the 50HP motor
h. Enclosure must be NEMA 3R rated and UL 1008 listed.
0005. New Overload Protection (for an existing 125A breaker):
a. Furnish one, three-phase NEMA Class 10 thermal overload relays with external manual reset rated for a 50HP, 3-phase motor protection.
b. The overload relay must be compatible with existing 125A, 600 VAC Westinghouse type AB DE-ION breaker and work with the existing NEMA size 3 starter.
c. Must be able to be installed in existing panel manufactured by "Continental".
d. The existing overload is an Allen-Bradley, type N43 with size 3 starter.
0006. 10 inch Dia sch 40 carbon steel pipe
a. Provide carbon steel pipe meeting the requirements of ASTM A53/A53M
b. Must be Grade A
c. Provide 10 foot standard sections.
0007. 10 inch Dia Slip Joint/Dresser Coupling
a. Provide carbon steel 10 inch diameter long bolted slip joints/dresser couplings that comply with AWWA 219.
b. Rated for Schedule 40 piping or 150 psi.
c. Rated Flow 650 GPM.
0008. 10 inch Dia sch 40 carbon steel flangesslip-on, raised face
a. Flanges must be:
i. Forged steel
ii. Slip-on
iii. ASTM A105/A105M rated faced and drilled to ASME B16.5 class 150 with a
0.0625 inch raised face
0009. 10 inch Dia sch 40 carbon steel 90 elbow - short radius flanged end
a. Fittings must be carbon steel flanged type.
b. Ensure the internal diameter bores of flanges and flanged fittings are the same as that of the associated pipe.
c. Drill cast steel backing flanges, ASTM A216/A216M in conformance with ASME B16.5 Class 150 with a 0.0625 inch raised face.
d. Where cast fittings are not available, provide segmental welded steel fittings, ASTM A53/A53M, Grade B, meeting the requirements of manufacturer's recommended wall thicknesses.
e. The flanges must be slip-on type.
f. Flanges for flanged fittings must be forged steel, ASTM A105/A105M, faced and drilled to ASME B16.5 Class 150 with a 0.0625 inch raised face.
0010. 10 inch Dia sch 40 carbon steel 45 elbow - short radius flanged end
a. Fittings must be carbon steel flanged type.
b. Ensure the internal diameter bores of flanges and flanged fittings are the same as that of the associated pipe.
c. Drill cast steel backing flanges, ASTM A216/A216M in conformance with ASME B16.5 Class 150 with a 0.0625 inch raised face.
d. Where cast fittings are not available, provide segmental welded steel fittings, ASTM A53/A53M, Grade B, meeting the requirements of manufacturer's recommended wall thicknesses.
e. The flanges must be slip-on type.
f. Flanges for flanged fittings must be forged steel, ASTM A105/A105M, faced and drilled to ASME B16.5 Class 150 with a 0.0625 inch raised face.
0011. 10 inch Dia sch 40 carbon steel tee flanged end
a. Fittings must be carbon steel flanged type.
b. Ensure the internal diameter bores of flanges and flanged fittings are the same as that of the associated pipe.
c. Drill cast steel backing flanges, ASTM A216/A216M in conformance with ASME B16.5 Class 150 with a 0.0625 inch raised face.
d. Where cast fittings are not available, provide segmental welded steel fittings, ASTM A53/A53M, Grade B, meeting the requirements of manufacturer's recommended wall thicknesses.
e. The flanges must be slip-on type. Flanges for flanged fittings must be forged steel, ASTM A105/A105M, faced and drilled to ASME B16.5 Class 150 with a 0.0625 inch raised face.
0012. 10 inch Dia sch 40 carbon steel gate valve, flanged end
a. Provide gate valves, with cast-iron bodies with bronze trim.
b. Provide valves meeting the requirements of AWWA C500 and have Class 150 flanged end connections.
c. Provide an OS&Y Bolted type bonnet.
d. Discs must be wedge type of bronze or bronze faced iron construction.
e. Use valves rated for 200 psig service.
f. Equip valves with handwheel operators.
g. Suitable for service with water temperatures from 33 to 120 degrees Fahrenheit, and ambient temperatures from -20 to 120 degrees Fahrenheit.
0013. 10 inch Dia sch 40 carbon steel three-way-valve
a. Provide three-way-valve valves meeting the requirements of AWWA C517 and have Class 150 flanged connections.
b. Use valves rated for 200 psig service.
c. Equip valves with handwheel operators.
d. T Configuration-three-way port arrangement
e. Suitable for service with water temperatures from 33 to 120 degrees Fahrenheit, and ambient temperatures from -20 to 120 degrees Fahrenheit.
0014. 10 inch Dia pressure relief valve - 100 psi service point
a. Provide pressure relief devices conforming to the requirements of ASME B31.3 and AWWA C530.
b. Pressure relief valves must be hydraulically operated, diaphragm actuated, pilot controlled globe or angle valves with externally mounted strainers and test cocks.
c. Provide bodies consisting of cast iron or forged steel and trim consisting of bronze.
d. Stem must be stainless steel.
e. Ensure end connections are flanged, faced and drilled to ASME B16.5 Class 150.
f. The valves must open when the upstream pressure reaches a maximum set point.
g. Valves must be adjustable to discharge 650 gpm of water between 50 psi and 100 psi. (Additional Range allowable, but the system needs to mitigate at approximately 200' head to protect downstream equipment).
h. Valve nominal size allowed to be 10 inch or 12 inch diameter.
i. Installation Orientation - Horizontal Service
j. Suitable for service with water temperatures from 33 to 120 degrees Fahrenheit, and ambient temperatures from -20 to 120 degrees Fahrenheit.
0015. Flange Gaskets Raised Face - for 10 inch flanges
a. Provide gaskets meeting the requirements of ASME B16.5.
b. Provide nonmetallic gaskets conforming to ASME B16.21 that are:
i. Maximum 0.125 inch thick
ii. Chloroprene rubber
iii. Durometer hardness No.80
iv. 1,500 psi minimum tensile strength
v. 125 percent minimum elongation
vi. Flat ring type for use with raised face flanges.
0016. Flange Bolts - for 10 inch flanges
a. Provide alloy-steel, ASTM A193/A193M, Grade B7, hex head bolts for the10 inch flanges specified in this SOW.
0017. Flange Nuts - for 10 inch flanges
a. Provide ASTM A194/A194M Grade 7 hex head nuts for bolts provided in
CLIN 0016.
0018. Flange Washers - for 10 inch flanges
a. Provide washers for the bolts provided in CLIN 0016 made of the same material as the bolts.
0019. 6 inch 150 psi capable pressure regulating valve
a. Provide pressure regulating devices conforming to the requirements of ASME B31.3 and AWWA C530.
b. Pressure relief valves must be
i. Hydraulically operated
ii. Diaphragm actuated
iii. Pilot controlled globe or angle valves
iv. With externally mounted strainers and test cocks
c. Provide bodies consisting of cast iron or forged steel and trim consisting of bronze. Stem must be stainless steel.
d. Ensure end connections are flanged, faced and drilled to ASME B16.5 Class 150.
e. The valves must proportionally close when the downstream pressure reaches a maximum set point.
f. Valves must be adjustable to discharge 300 gpm of water between 50 psi and 100 psi. (Additional Range allowable, but the system needs to mitigate at approximately 200' head to protect downstream equipment).
g. Valve nominal size allowed to be 6 inch or 8 inch diameter.
h. Required downstream pressure setpoint: 200' head/86.6psi
Installation Orientation - Horizontal Service
i. Suitable for service with water temperatures from 33 to 120 degrees Fahrenheit, and ambient temperatures from -20 to 120 degrees Fahrenheit.
0020. 6 inch Dia sch 40 carbon steel gate valve flanged end
a. Provide gate valves, with cast-iron bodies with bronze trim.
b. Provide valves meeting the requirements of AWWA C500 and have Class 150 flanged end connections.
c. Provide an OS&Y Bolted type bonnet.
d. Discs must be wedge type of bronze or bronze faced iron construction
e. Use valves rated for 200 psig service.
f. Equip valves with handwheel operators.
g. Suitable for service with water temperatures from 33 to 120 degrees Fahrenheit, and ambient temperatures from -20 to 120 degrees Fahrenheit.
0021. 6 inch Dia sch 40 carbon steel pipe
a. Provide carbon steel pipe meeting the requirements of ASTM A53/A53M, Grade A in 10 foot standard.
0022. 6 inch Dia sch 40 carbon steel 90 elbow - short radius flanged end
a. Fittings must be carbon steel flanged type.
b. Ensure the internal diameter bores of flanges and flanged fittings are the same as that of the associated pipe.
c. Drill cast steel backing flanges, ASTM A216/A216M in conformance with ASME B16.5 Class 150 with a 0.0625 inch raised face.
d. Where cast fittings are not available, provide segmental welded steel fittings, ASTM A53/A53M, Grade B, meeting the requirements of manufacturer's recommended wall thicknesses.
e. The flanges must be slip-on type.
f. Flanges for flanged fittings must be forged steel, ASTM A105/A105M, faced and drilled to ASME B16.5 Class 150 with a 0.0625 inch raised face.
0023. 6 inch Dia sch 40 carbon steel tee flanged end
a. Fittings must be carbon steel flanged type.
b. Ensure the internal diameter bores of flanges and flanged fittings are the same as that of the associated pipe.
c. Drill cast steel backing flanges, ASTM A216/A216M in conformance with ASME B16.5 Class 150 with a 0.0625 inch raised face.
d. Where cast fittings are not available, provide segmental welded steel fittings, ASTM A53/A53M, Grade B, meeting the requirements of manufacturer's recommended wall thicknesses.
e. The flanges must be slip-on type.
f. Flanges for flanged fittings must be forged steel, ASTM A105/A105M, faced and drilled to ASME B16.5 Class 150 with a 0.0625 inch raised face.
0024. 6 inch Dia sch 40 carbon steel slip-on, raised face flanges
a. Flanges must be forged steel, slip-on, ASTM A105/A105M, faced and drilled to ASME B16.5 Class 150 with a 0.0625 inch raised face.
0025. Flange Bolts - for 6 inch flanges
a. Provide alloy-steel, ASTM A193/A193M Grade B7 hex head bolts for 6 inch flanges provided under this contract.
0026. Flange Nuts - for 6 inch flanges
a. Provide ASTM A194/A194M Grade 7 hex head nuts for bolts provided in
CLIN 0025.
0027. Flange Washers - for 6 inch flanges
a. Provide washers for the bolts provided in CLIN 0025 made of the same material as the bolts.
0028. Flange Gaskets Raised Face - for 6 inch flanges
a. Provide gaskets meeting the requirements of ASME B16.5.
b. Gaskets must be:
i. Nonmetallic conforming to ASME B16.21
ii. Maximum thickness of 0.125 inch thick
iii. Made of chloroprene rubber
iv. With durometer hardness No.80
v. With 1,500 psi minimum tensile strength
vi. With 125 percent minimum elongation
vii. Flat ring type for use with raised face flanges.
0029. Waterflow Alarm Switch
a. Provide vane type waterflow switches for use on wet pipe sprinkler systems.
b. Flow switch must be UL listed and FM approved for use on a 6" steel pipe.
Flow switch must contain two single pole, double throw, snap action switches rated for 2 amps at 125VDC, and an adjustable, instantly recycling pneumatic retard.
c. Switches must be actuated at a flow of 6 GPM or greater.
d. Enclosure must be NEMA 4/IP54 rated, weatherproof, UV and flame resistant.
0030. Cold Cutting Split Frame Clamshell 4-8" with 110V Electric Motor
a. Must be a portable, split-frame ("clamshell") design, allowing the machine to split in half for mounting directly onto the outside diameter (OD) of an in-line pipe.
b. Must be capable of performing simultaneous cutting (parting) and beveling operations without removing the tool from the pipe.
c. Must be powered by a 110 VAC electric motor, suitable for use with standard industrial wall outlets or extension cords.
d. Cutting and Beveling must be done via a "cold cut" to prevent any heat-affected zones (HAZ) on the pipe material.
e. Must come with tooling sufficient to produce a standard 37.5-degree weld bevel. This requires two bits for the 37.5-degree bevel.
f. Must come as a kit including the main clamshell body, the electric drive motor assembly, the respective sets of parting and beveling tools, necessary operating hand tools, an operations and maintenance manual, and a durable storage/transport case post award.
g. The machine body shall be capable of mounting and machining piped with an outer diameter range that includes 4 inches to 8 inches.
h. The manufacturer's standard operations, maintenance, and safety manuals must be included post award.
i. Must be covered by the manufactures standard warranty, which must be for a minimum of 1 year against defects in material and workmanship.
j. Offeror must provide technical data sheets, dimensional drawings and other supporting documentation sufficient to demonstrate compliance with all salient characteristics listed above.
0031. Cold Cutting Split Frame Clamshell 6-12" with 110V Electric Motor
a. Must be a portable, split-frame ("clamshell") design, allowing the machine to split in half for mounting directly onto the outside diameter (OD) of an in-line pipe.
b. Must be capable of performing simultaneous cutting (parting) and beveling operations without removing the tool from the pipe.
c. Must be powered by a 110 VAC electric motor, suitable for use with standard industrial wall outlets or extension cords.
d. Cutting and Beveling must be done via a "cold cut" to prevent any heat-affected zones (HAZ) on the pipe material.
e. Must come with tooling sufficient to produce a standard 37.5-degree weld bevel. This requires two bits for the 37.5-degree bevel.
f. Must come as a kit including the main clamshell body, the electric drive motor assembly, the respective sets of parting and beveling tools, necessary operating hand tools, an operations and maintenance manual, and a durable storage/transport case.
g. The machine body shall be capable of mounting and machining piped with an outer diameter range that includes 6 inches to 12 inches.
h. The assembled machine, including the electric drive motor, shall require a maximum radial clearance of no more than 11.5 inches from the outer wall of the pipe to accommodate tight field-installation constraints.
i. The manufacturer's standard operations, maintenance, and safety manuals must be included.
j. Must be covered by the manufactures standard warranty, which must be for a minimum of 1 year against defects in material and workmanship.
k. Offeror must provide technical data sheets, dimensional drawings and other supporting documentation sufficient to demonstrate compliance with all salient characteristics listed above.
3. DETAILED REQUIREMENTS FOR SUPPLIES:
a. General
The equipment furnished and the work performed under this contract must be in conformance with the latest applicable provisions of standards listed bellow. All materials, components, and equipment must be new and conform to the requirements of these specifications.
b. References
i. ANSI C80.1: American National Standard for Electrical Rigid Steel Conduit (ERSC)
ii. ASME B16.21: Nonmetallic Flat Gaskets for Pipe Flanges
iii. ASME B16.34: Valves--Flanged, Threaded, and Welding End
iv. ASME B16.5: Pipe Flanges and Flanged Fittings
v. ASME B31.3: Process Piping
vi. ASTM A53/A53M: Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
vii. ASTM A105/A105M: Standard Specification for Carbon Steel Forgings for Piping Applications
viii. ASTM A193/A193M: Standard Specification for Alloy-Steel and Stainless Steel Bolting for High Temperature or High Pressure Service and Other Special Purpose Applications
ix. ASTM A194/A194M: Standard Specification for Carbon Steel, Alloy Steel, and Stainless Steel Nuts for Bolts for High Pressure or High Temperature Service, or Both
x. ASTM A216/A216M: Standard Specification for Steel Castings, Carbon, Suitable for Fusion Welding, for High-Temperature Service
xi. ASTM A1011/A1011M: Standard Specification for Steel, Sheet and Strip, Hot-Rolled, Carbon, Structural, High-Strength Low-Alloy, High-Strength Low- Alloy with Improved Formability, and Ultra-High Strength
xii. ASTM B3: Standard Specification for Soft or Annealed Copper Wire
xiii. ASTM B33: Standard Specification for Tin-Coated Soft or Annealed Copper Wire for Electrical Purposes
xiv. ASTM C882: Standard Test Method for Bond Strength of Epoxy- Resin Systems Used With Concrete By Slant Shear
xv. AWWA C219: Bolted, Sleeve-Type Couplings for Plain-End Pipe
xvi. AWWA C500: Metal-Seated Gate Valves for Waterworks Service
xvii. AWWA C517: Resilient-Seated Cast-Iron Eccentric Plug Valves
xviii. AWWA C520: Knife Gate Valves, 2 In.- 96 In. (50 mm - 2,400 mm)
xix. AWWA C530: Pilot-Operated Control Valves
xx. AWWA E103: Standard for Horizontal and Vertical Line-Shaft Pumps
xxi. HI 9.1-9.5: Pumps - General Guidelines
xxii. MSS SP-58: Pipe Hangers and Supports - Materials, Design, Manufacture, Selection, Application, and Installation
xxiii. NEMA AB 3: Molded Case Circuit Breakers and Molded Case Switches
xxiv. NEMA FB 1: Standard for Fittings, Cast Metal Boxes, and Conduit Bodies for Conduit, Electrical Metallic Tubing, and Cable
xxv. NEMA ICS 2: Industrial Control and Systems Controllers:
Contactors and Overload Relays Rated 600 Volts
xxvi. NEMA WC 57/ICEA S-73-532: Standard for Control, Thermocouple, and Instrumentation Cables
xxvii. NEMA WC 70/ICEA S-95-658: Power Cables Rated 2000 Volts or Less for the Distribution of Electrical Energy xxviii. NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection
xxix. NFPA 70: National Electrical Code (NEC)
xxx. UL 6: Electrical Rigid Metal Conduit-Steel
xxxi. UL 218: Standard for Fire Pump Controllers
xxxii. UL 489: Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Break
4. CERTIFICATES
Certifications of Equipment: Within 30 calendar days after date of award, a certified statement by the manufacturer of the equipment design tests in accordance with standards listed above have been previously made on this equipment as those provided in this SOW and that the results of the tests prove the equipment will operate satisfactorily under normal and short-circuit conditions when applied within their ratings. Contractor provides certification that the equipment furnished is compatible with the existing panel and with the circuit breaker and complies with the standards listed above. Certification will be required before the equipment is prepared for shipment.
5. DESCRIPTIVE DATA REQUIRED WITH QUOTE
The descriptive data and test results below (a. and b., below) must be submitted with your quote package and clearly demonstrate that the quoted products fully comply with all specifications and requirements identified in the Measurement and Payment section the Detailed Requirements for Supplies section above:
a. Descriptive Data on Equipment.
Cut-sheets, descriptive drawings, O&M manuals, and ordering information must be provided for the equipment listed above.
b. Test Results: Design and Production Tests Results.
6. COORDINATION
Delivery scheduling, offloading location and site access must be coordinated with the Contracting Officer.
7. LOOKOUT POINT ADDRESS
Deliveries must be made Monday - Thursday 0700 (7:00 am) - 1500 Pacific Time
Army Corps of Engineers
40386 W Boundary Rd
Lowell, OR 97452
8. WARRANTY
The Contractor shall effectuate the assignment to the Government all applicable standard manufacturer warranties for each component and packaged system furnished under this contract.
These warranties shall cover defects in design, manufacturing, and materials in accordance with each manufacturer's published warranty terms.
The Contractor shall provide all warranty documentation, certificates, and contact information necessary for the Government to pursue warranty claims directly with the original equipment manufacturer, without the need to contact the supply Contractor.
| IDCode: J |
| Page: 1 |
| Pages: 21 |
| AmendNo: 0002 |
| EffDate: 04 SEP 2026 |
| ReqNo: |
| ProjNo: |
| IssCode: W9127N |
| AdmCode: |
| IssuedBy: W071 ENDIST PORTLAND |
KO CONTRACTING DIVISION, 333 SW FIRST AVE
PORTLAND, OR 97204-3495
UNITED STATES
ARAGON LIEBZEIT, EMAIL: ARAGON.N.LIEBZEIT@USACE.ARMY.MIL TELEPHONE: (503) 808-4610 AdminBy:
SCD: PAS:
| ContractorNameAdd: |
| Code: |
| FacCode: |
| SolChg: 1 |
| SolNo: W9127N26QA155 |
| SolDate: 20 AUG 2026 |
| AwardChg: Off |
| AwardNo: |
| AwardDate: |
| Amended: 1 |
| OffrExt: 1 |
| OffrNoEx: Off |
| NoCopies: 1 |
| ApprData: SEE SECTION G - CONTRACT ADMINISTRATION DATA |
| ChgeOrd: Off |
| ChgeOrder: |
| Modify: Off |
| SuppAgre: Off |
| SuppAuth: |
| ModOthr: Off |
| OthrSpec: |
| NoReq: Off |
| Require: Off |
| Copies: |
| Descript: See Schedule |
| ContNameTitle: |
| CoNameTitle: CORY R. PFENNING |
| ContDate: |
| CODate: 04 SEP 2026 |
File details come from the government source that posted it. Updated .