This document contains a drafted materials list and related federal contract opportunity solicitation for the Cole M. Rivers Power Feeder Electric Components project. The solicitation seeks commercial supplies and parts for a feeder power line repair project being conducted by the U.S. Army Corps of Engineers Portland District. The drafted materials list specifies various electrical components that must be delivered by set deadlines in September, October and December 2022 to the Corps' facility in Trail, Oregon. Responses to the solicitation are due by June 8th 2022, with the solicitation itself to be made available on June 10th. The opportunity is not set aside for small businesses. Interested parties should direct inquiries to the point of contact provided.

View the file

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

COLE M. RIVERS HATCHERY - POWER FEEDER REPAIR PROJECT - MATERIALS LIST
Dealines are inflexible dates. Deliveries are required to be arrived at Government facility on or before the deadlines.
No.Part #DeadlineDescriptionUnitQuantityVendor Notes
1312Px209/15/223-1/2" pvc schedule 40 conduit 20' lengthsfoot12400
2312PTA9/15/223-1/2" pvc male adapterea48
3312PIBU9/15/223-1/2" plastic bushingea48
4312PCPDSDB9/15/223-1/2" pvc Swedge coupling deep socket double bellea24
5312P90X36WBE9/15/223-1/2" Diameter, 90° sweep Elbow with Bell End, 36" Radius, Rigid Non-Metallic Conduit, Material: PVC, Schedule 40, Color: Gray.ea70
6312P45WBE9/15/223-1/2" PVC Elbow With 45 Degree Bend & Bell Endea14
7312PBE9/15/223-1/2" pvc bell endea96
8233-LA10/20/222'-8" X 3'-8" X 3'-6" precast concrete vault rated for traffic custom engraving on lid (HIGH VOLTAGE)ea10
9P1792B10/20/22P1790B 3” hole size one piece insulator made from a flame retardant, high hardness grade TPE polymer that is U.L. listed.ea72
10363-R-3X1000FTCaution-Buried High Voltage Cable Buried Below Underground Underground Tape, Dimensions: 3" x 1000', Color: Redea5
11G2036S9/15/22All Weather PVC Cement - Blue or Clear, 1-Quartea10
12P3582548MDB10/20/2248" x 80" Three Phase Sectionalizing Cabinet Height 48" Base width 80" Base Depth 46" Burial depth 24"ea5
13115-23-204512/1/2212 cuts at 1100 each and 3 cuts at 1250' each
2/0 1/C, 15 kV Okoguard Okoclear-TS, Copper Tape Shielded, Copper Conductor, 15 kV 100% and 133% Insulation Level, 105°C Rating, Type MV-105, For CT Use, Sun Res, Oil Res I & II, CSR FT4-ST1, HAL-FREE, SR, LTDD (-25C), TC-ER outside diameter .77"foot16,950
145810-B-1/012/1/2215kv-200a Industrial Loadbreak elbow kit connector insulation diameter range .700-.910"It is designed for use on tape shield, wire shield, UniShield® and JCN types of cables. The elbow is peroxide-cured EPDM. 3M™ 5810 Series Industrial Loadbreak Elbow Kit includes an elbow body, loadbreak probe, probe installation tool, silicone lubricant, cold shrink jacketing tube, mastic strips, ground braid assembly, constant force spring and CC-3 cable cleaning pads. This kit is rated for 5 to 15 kV, 200-amp applications. Meets ANSI/IEEE Standard 386.ea36
15845912/1/223M shield adapter kits. Kit includes 1 cold shrink sealing tube, 3 mastic sealing strips, 1 constant force spring, 1 pre formed, unique, integrated ground braid/bleeder wire, 1 strip semi conductive tape and 1 instruction sheet. It is compatible with semi conducting insulation shields and cable jacketsea10
16CC-212/1/22Cable cleaning preparation kit (3) Solvent Saturated Cleaning Pads in an Aluminum Lift Top Container, (1) 120 Grit, Non-Conductive Abrasive,ea20
17LPF215H12/1/22200A 15kv feedthru loadbreak bushing with continuous solid

current path of all copper alloy from finger contact

to finger contact, has an ablative arc interrupter with excellent de-ionizing properties. The body is molded of high quality peroxide cured EPDM insulation and has a molded on peroxide�cured semi-conductive EPDM shield.ea16
18ISB21512/1/22200 A, 15 kV Loadbreak Insulated Standoff Bushing, meets IEEE Std 386 standard Separable Insulated Connector Systems, and provides a single loadbreak interfaceea16
19LPC21512/1/22Loadbreak Protective Cap with copper ground wire and silicone lubricantea16
207622-T-11012/1/2215kv Cold shrink termination kit 2awg to 400MCMea4
214BCSTR9/15/22#4 Bare Stranded Copper wirefoot300
22128CGR9/15/221/2" x 8' Copper Ground rodsea10
23CEB19/15/221/2" Bronze Ground Rod Clamp 8 AWG solid to 2 AWG strandedea10