1. We are reusing the existing Motor and Discharge Head
2. Information pertaining to existing pump bowl is as follows:
a. Equal or equivalent.
b. Original is a Fairbanks morse
i. 3 stage model 11 H
ii. 1500 GPM @ 118’ of head.
c. Driven by our existing motor.
i. 60 Hp
ii. 1765 RPM
d. The bowl assembly is
i. 50-3/4” long with the bowl stages being 11-1/4” wide
ii. The strainer at the bottom is 8” long by 12” wide ** this we need to stay under
12”
iii. Total length from pump threaded discharge to bottom of strainer is 62-3/4” long
iv. The pump shaft extends 11” beyond top of Threaded column adapter.