Specification_7Aug20.pdf

PDF 97 KB Posted

Attached to
Bonneville Pump and Motor Package
Solicitation number
W9127N-20-Q-0096
Issued by

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MPH1 – HW 6 Replacement Pump and Motor Requirements

3 Stage Vertical Pump / Motor

Mechanical Requirements

• Column Diameter ……............................................... 12”

• Discharge header ID………………………………………….….. 12”

• Driveshaft Diameter ………………………………………….… 1 3/16”

• Required Flow……………………………………………………..… 1500 US gpm

• Required Discharge pressure at well head……………………..……………………… 30 psig.

• Depth from well head to bottom of pump………………………………………………... 114 ft

• Design depth from well head to water surface………. 85ft

• Pump shall be constructed of 316SS, Bronze, or approved equal

• Line shaft bearings shall be suitable for water well service (Cutless rubber or approved equivalent)

See attached drawings for well cross section

Electrical Requirements

Driver Type Vertical Shaft Motor

Motor Power 100HP

Motor Speed 1800RPM

Phase/Frequency 3PH/ 60HZ

Voltage 460V

Frame 404TPA

Insulation: NEMA MG-1, Part 31