AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
PROJECT TITLE: John Day Adult Fish Ladder PIT Tag Antenna Installation - Phase 2
1. The purpose of this amendment is to; (a) add the site visit roster, (b) change draw ing ES601to read "interior fixture" and to (c) change Specification 26 05 00.00 25, paragraph 2.10 to identify indicate outdoor transformers must have NEMA 3R enclosure and indoor transformers can have NEMA 1 enclosures. See attached specifications.
2. All other terms and conditions remain unchanged.
POC: Derek Caputi Email: derek.caputi@usace.army.mil
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 05-May-2017
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W9127N-17-B-0006
X 9B. DATED (SEE ITEM 11)
14-Apr-2017
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
05-May-2017
CODE
USACE PORTLAND DISTRICT
333 SW 1ST AVE
PORTLAND OR 97204-3440
W9127N 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W9127N-17-B-0006
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
(End of Summary of Changes)
E L.
D A
M S
E R
V
IC
E G
A
LL
E R
Y
S O
U T H N
O N -O
V E R F
LO
W
D Q
PCQ3
DOMESTIC WATER PUMPHOUSE #2
SEE NOTE 2
SEE NOTE 3
SEE NOTE 4
ON SHEET E-701
SEE PANEL SCHEDULE
B U
S
B U
S
400A
480V.
125 250 30 50 125 250
T R
A S H R
A K E
F .T . P
E N S T O
C K
S P A R E
T R
A N S F O
R M
E R D
R
0V . R
E C E P T
208Y/120
480V
30 90
SQ01
FED FROM
DQ1
45 KVA
5 1/21.3
EL. 185
SERVICE GALLERY
DAM MONOLITH 14
IN SOUTH NON-OVERFLOW
IFLIFR
FR3
PANEL
LTG
30 20202020 25 20
FQ3, 480V, 3-PHASE
0V . R
E C E P T
208Y/120
480V
30 90
45 KVA
5 1/21.3
IFLIFR
FR3
PANEL
LTG
40 20202020 25 20
FQ3, 480V, 3-PHASE
MECH ROOM, EL. 188.0
SOUTH LADDER VISITORS CENTER
SOUTH LADDER VISITORS CENTER - MECH ROOM, EL. 188.0
S01
S02
S19
H E
A T
E R
K
W D
U C
T
M O
T O
R C
O M
P R
E S
S O
R
M O
T O
R D
U C
T F
A N
H O
IS
T
N E
W
J
IB
C
R A
N E
U N
U S
E D
U N
U S
E D
U N
U S
E D
480V
208Y/120V
FR3.2
PANEL
LTG
NEW
H E
A T
E R
K
W D
U C
T
M O
T O
R C
O M
P R
E S
S O
R
M O
T O
R D
U C
T F
A N
H O
IS
T
N E
W
J
IB
C
R A
N E
U N
U S
E D
U N
U S
E D
NEW ADULT PIT TAG ROOM
LED LIGHT FIXT.
NEW EXTERIOR
(TYP. OF 3)
LED LIGHT FIXT.
NEW INTERIOR
LIGHT SWITCHES
NEW 1-POLE
J O
H N D
A Y L
O C
K A
N D D
A M
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
P O
R T
L A
N D
O R
E G
O N
P O
R T
L A
N D D
IS
T R
IC
T
W
IL
L
IA
M F
O R
T U
N Y P .E
A N
S I
D
G E
C D
B D
B
:1
/1
/2
ES601
G E
C D
W B
F
A D
U L T F
IS
H L
A D
D E
R S
J D
F .1
E
S
X X
X .d g n
IN
S
T A
L L
A T
IO
N
P
IT
T
A G D
E T
E C
T
IO
N S
Y S
T E
M
O N
E -L
IN
E D
IA
G R
A M
S
N O
R T
H F
IS
H L
A D
D
R
N -1
-B -0
B
B A
N N
IS
T
R
B F
T E
X T R
E V
IS
IO
N
C H
A N
G E E
X T
E R
IO
R T
O I
N T
E R
IO
R /0
/1
A -1
EXISTING ONE-LINE DIAGRAM
NOTES:
6. SEE SHEET EN701 FOR CONDUIT AND CABLE SCHEDULE.
5. SEE SHEET E-001 FOR SYMBOL LEGEND.
PANEL SCHEDULE ON SHEET E-701.
NEW LIGHTING CIRCUIT TO NEW ADULT PIT TAG ROOM. SEE FR3
4. USE EXISTING SPARE 20A, 1-POLE CIRCUIT BREAKER (CKT 8) FOR
3. PROVIDE NEW 40A, 3-POLE CIRCUIT BREAKER IN COMPARTMENT 2B.
2. REMOVE CIRCUIT BREAKER IN COMPARATMENT 2B.
1. ALL ITEMS SHOWN ARE EXISTING UNLESS INDICATED OTHERWISE.
REVISED PARTIAL ONE-LINE DIAGRAM
REFERENCE DRAWINGS:
SOUTH FISH LADDER -- VISITOR CENTER PLANES401
XFMR TR3
SHIELDED ISOLATION
NEW 15KV, 3-PHASE
NEW
NEWNEW
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N M
A R
K
D A
T E
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
C O
N T
R A
C T N
O
IDENTIFICATION
SHEET
D A
T E
A P
P R
D R
A W
IN
G N
U M
B E
R of Engineers
US Army Corps
P L
O T D
A T
E
54321
D
C
B
A
D R
A W
N B
Y
C H
E C
K E
D B
Y
PORTLAND DISTRICT
John Day Adult Fish Ladder PIT Tag Antenna Installation - Phase 2
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 10 00.00 25 CONTRACT ADMINISTRATION DATA
01 10 10.00 25 CONTRACTOR'S OPERATIONS AND REQUIREMENTS
01 11 00.00 25 SUMMARY OF WORK
01 22 00.00 25 MEASUREMENT AND PAYMENT
01 32 01.00 25 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 35 26.00 25 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 25 QUALITY CONTROL
01 45 00.10 25 QUALITY CONTROL SYSTEM (QCS)
01 57 19.00 25 TEMPORARY ENVIRONMENTAL CONTROLS
01 78 23.00 25 OPERATION AND MAINTENANCE DATA
01 78 39.00 25 PROJECT RECORD DOCUMENTS
DIVISION 03 - CONCRETE
03 62 16.00 25 NON-SHRINK GROUTING
DIVISION 05 - METALS
05 52 00.00 25 METAL RAILINGS
DIVISION 08 - OPENINGS
08 11 13.00 25 STEEL DOORS AND FRAMES
08 71 00.00 25 DOOR HARDWARE
DIVISION 09 - FINISHES
09 22 00.00 25 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00.00 25 GYPSUM BOARD
09 90 00.00 25 PAINTS AND COATINGS
DIVISION 13 - SPECIAL CONSTRUCTION
13 34 23.00 28 PREFABRICATED STRUCTURES (PRECAST CONCRETE)
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 74 33.00 25 PACKAGED, OUTDOOR, HEATING AND COOLING MAKEUP
AIR-CONDITIONERS
DIVISION 26 - ELECTRICAL
26 05 00.00 25 COMMON WORK RESULTS FOR ELECTRICAL
26 05 19.00 25 INSULATED WIRE AND CABLE
26 05 48.00 25 SEISMIC PROTECTION FOR ELECTRICAL AND MECHANICAL EQUIPMENT
26 08 00.00 25 APPARATUS INSPECTION AND TESTING
DIVISION 31 - EARTHWORK
31 00 00.00 25 EARTHWORK FOR ELECTRICAL CONDUIT
DIVISION 32 - EXTERIOR IMPROVEMENTS
PROJECT TABLE OF CONTENTS Page 1
32 16 13.00 25 CONCRETE SIDEWALKS AND CURBS AND GUTTERS
DIVISION 40 - PROCESS INTERCONNECTIONS
40 95 33.00 25 FIBER OPTIC DATA TRANSMISSION SYSTEM
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 2
SECTION TABLE OF CONTENTS
DIVISION 26 - ELECTRICAL
SECTION 26 05 00.00 25
COMMON WORK RESULTS FOR ELECTRICAL
PART 1 GENERAL
1.1 REFERENCES
1.2 PREVENTION OF CORROSION
1.2.1 General
1.2.2 Fastenings and Fittings
1.2.3 Corrosion-Resisting Materials
1.2.4 Corrosion-Resisting Treatments
1.3 DEFINITIONS
1.4 SUBMITTALS
1.5 GENERAL REQUIREMENTS
1.6 EQUIPMENT LABELING
1.7 SPARE PARTS
PART 2 PRODUCTS
2.1 MATERIAL REQUIREMENTS
2.2 CONDUITS, RACEWAYS, AND DUCTS
2.2.1 Rigid Steel Conduit
2.2.2 Electrical Metallic Tubing (EMT)
2.2.3 Liquidtight Flexible Metallic Conduit
2.2.4 Non-Metallic Wiring Duct (Channel)
2.2.5 Duct Seal
2.2.6 Multichannel Surface Raceway and Fittings
2.2.7 Conduit ID Tags
2.3 CONDUIT DEVICE BOXES AND FITTINGS
2.3.1 Outlet and Switch Boxes
2.3.2 Fittings for Conduit and Outlet Boxes
2.3.3 Cast Junction Boxes
2.3.4 Expansion Fittings
2.3.5 Watertight Cord Connectors
2.3.6 Watertight Hubs
2.3.7 Eye Nut Conduit Plugs
2.4 SPECIAL BOXES, ENCLOSURES, AND CABINETS
2.4.1 General
2.4.2 Junction and Outlet Boxes
2.4.3 Vent Drain
2.4.4 Steel Cabinets and Boxes
2.5 WIRE AND CABLE
2.6 SAFETY SWITCHES
2.6.1 General
2.6.2 Disconnects
2.7 MOLDED CASE CIRCUIT BREAKERS
2.7.1 General
2.7.2 Trip Units
2.7.3 480-Volt AC Circuits
SECTION 26 05 00.00 25 Page 1
2.7.4 120/240-Volt AC Circuits
2.7.5 Ground Fault Circuit Interrupters
2.8 PANELBOARDS
2.8.1 General
2.8.2 Enclosures
2.8.3 Components
2.9 CONTROL EQUIPMENT
2.9.1 Control Accessories
2.9.2 Fuses
2.9.3 Fuseholders
2.9.4 Miniature Circuit Breakers
2.9.5 Supplementary Protectors
2.9.6 Termination Points
2.9.6.1 Terminal Blocks
2.9.6.2 Distribution Block
2.9.6.3 Marking Strips
2.9.6.4 Designations
2.9.7 Component Nameplates
2.10 LIGHTING TRANSFORMERS
2.11 WIRING DEVICES
2.11.1 General
2.11.2 Toggle Switches
2.11.3 Receptacles
2.11.3.1 General Use
2.11.3.2 Isolated-Ground
2.11.3.3 Ground Fault Circuit Interrupter
2.11.3.4 Cover Plates
2.11.4 Insulating Tapes
2.12 HANDHOLES
2.12.1 General
2.12.2 Grounding
2.13 LIGHTING FIXTURES
2.13.1 General
2.13.2 Interior
2.13.3 Exterior
2.13.4 LED Lamps
2.14 ELECTRICAL GROUNDING AND BONDING EQUIPMENT
2.14.1 Conductors
2.14.2 Ground Bus
2.14.3 Driven Ground Rods
2.14.4 Ground Inspection Wells
PART 3 EXECUTION
3.1 GENERAL
3.2 REMOVAL OF EXISTING ELECTRICAL EQUIPMENT
3.3 GROUNDING
3.3.1 Ground Connections
3.3.2 Grounding Conductors
3.3.3 Bonding of Exposed Steel
3.3.4 Driven Ground Rods
3.4 CONDUIT INSTALLATION
3.4.1 General
3.4.2 Exposed Conduit
3.4.3 Buried Conduit
3.4.4 Cutting and Threading
3.4.4.1 General
3.4.4.2 Thread Compound
3.4.5 Bends
SECTION 26 05 00.00 25 Page 2 g2ct9dc9 Highlight
3.4.6 Drains
3.4.7 Coordination
3.4.8 Termination of Conduit
3.4.9 Grounding of Conduit
3.4.10 Conduit Inspection
3.4.11 Pull Wires
3.4.12 Changes in Directions of Runs
3.4.13 Expansions Fittings
3.4.14 Supports
3.4.15 Liquidtight Flexible Metallic Conduit
3.4.16 Surface Metal Raceway
3.5 BOX AND ENCLOSURE INSTALLATION
3.5.1 General
3.5.2 Installation
3.5.3 Contractor-Designed Equipment Mounting
3.6 WIRE AND CABLE
3.7 SAFETY SWITCHES
3.8 WIRING DEVICES
3.8.1 Toggle Switches and Receptacles
3.8.2 Device Plates
3.9 BOXES AND FITTINGS
3.10 IDENTIFICATION PLATES AND WARNINGS
3.11 ELECTRICAL EQUIPMENT MOUNTING
3.11.1 General
3.11.2 Concrete Anchors
3.12 FIELD QUALITY CONTROL
3.12.1 Performance of Field Acceptance Checks and Tests
3.12.1.1 General
3.12.1.2 Safety
3.12.1.3 Phase-rotation tests
3.12.1.4 Exceptions
3.12.2 Follow-Up Verification
-- End of Section Table of Contents --
SECTION 26 05 00.00 25 Page 3 change due to age or contact with insulating materials. Wire identification must be as shown on the Contractor's drawings.
2.9.7 Component Nameplates
Each item of equipment mounted in each control cabinet must be provided with an engraved nameplate, device label, or with other suitable means of identification. Nameplates must be made of laminated sheet plastic or of anodized aluminum approximately 1/16-inch thick, engraved to provide white letters on a black background. Equipment of the withdrawal type must be provided with nameplates mounted on the removable equipment in locations visible when the equipment is in place. The nameplates must be fastened to the panels in proper position. Lettering must be 3/16-inch high. Samples of engraved nameplates with a schedule of nameplate sizes and lettering must be submitted for approval. The Contractor will be permitted to supply and attach to each control cabinet assembly a nameplate or trademark.
2.10 LIGHTING TRANSFORMERS
Transformers must be shielded, isolation, dry-type transformers rated 15kVA, three-phase, 480V delta to 208Y/120V grounded wye, 60 hertz, ventilated with NEMA 250, type 1 enclosure for indoor installation and NEMA 250, type 3R enclosure for outdoor instatllation. Windings must be copper and have two windings per phase. Windings have a minimum of two 2-1/2-percent taps above and below nominal voltage. Transformer must have h 220 degrees C insulation system with temperature rise not exceeding 115 degrees C under full-rated load in maximum ambient temperature of 40 degrees C. Efficiencies must meet levels defined (where applicable) in DOE 2016 Low Voltage Energy Efficiency Levels as per DOE 10 CFR Part 431.
2.11 WIRING DEVICES
2.11.1 General
Wiring devices must conform to NEMA WD 1. Dimensional requirements of wiring devices must conform with and NEMA WD 6.
2.11.2 Toggle Switches
Toggle switches must be in accordance with EIA 480, and must control LED lighting fixtures and must be of the heavy duty, general purpose, noninterchangeable flush-type. Toggle switches must be industrial grade toggle typerated 20 amperes at 277 volts, 60 hertz alternating current (ac) only. Switch must have poles as required. Wiring terminals must be of the screw type or of the solderless pressure type having suitable conductor-release arrangement. All toggle switches must be products of the same manufacturer.
2.11.3 Receptacles
2.11.3.1 General Use
Receptacles must be hospital grade, 20A, 125V AC, 2-pole, 3-wire duplex (NEMA 5-20R). Wiring terminals must be screw type, side or back wired with two screws per terminal, with a green grounding screw connected directly to the receptacle yoke. Not more than one receptacle must be installed in a single gang box.
SECTION 26 05 00.00 25 Page 17 g2ct9dc9 Highlight
| A.07.24 W9127N-17-B-0006 Amendment 0002 |
| PUBLISH |
| PROJECT TABLE OF CONTENTS |
| DIVISION 26 - ELECTRICAL |
| 26 05 00.00 25 - COMMON WORK RESULTS FOR ELECTRICAL |
| 26 05 00.00 25 - COMMON WORK RESULTS FOR ELECTRICAL |
| PART 2 PRODUCTS |
| 2.9 CONTROL EQUIPMENT |
| 2.9.7 Component Nameplates |
| 2.10 LIGHTING TRANSFORMERS |
| 2.11 WIRING DEVICES |
| 2.11.1 General |
| 2.11.2 Toggle Switches |
| 2.11.3 Receptacles |
| 2.11.3.1 General Use |
| [2]: [2] |
| Amd0002: AMD #0002 |