Amendment 2.pdf
PDF 3 MB Posted
- Attached to
- WSMR Special Weapons Assembly Facility (SWAF) 4
- Solicitation number
- W9126G20B0008
About this file
This document describes a federal contract opportunity for the renovation of Special Weapons Assembly Facility 4 at White Sands Missile Range in New Mexico. The solicitation number is W9126G20B0008 and is set aside for small businesses only. The contract value is estimated between $5-10 million. The work includes abatement of asbestos and lead paint, replacement of cranes and electrical systems, and renovation of interior walls, floors, ceilings and mechanical systems. Bids are due by 13 July 2020 and award is anticipated around 31 July 2020. The contract will be fixed-price and awarded by the Army Corps of Engineers. Plans and specifications will be available electronically only on SAM.gov where contractors must also register to receive amendments and submit bids.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Bid Abstract_20B0008.pdf | ||
| Amendment 3.pdf | ||
| Amendment 1.pdf | ||
| SWAF 4_SITE VISIT_SIGN- IN SHEETS 25-06-2020.pdf | ||
| WMSR_SWAF_4_Drawings.pdf | ||
| W9126G20B0008.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
The Solicitation for White Sands Missile Range Special Weapons Assembly Facility (SWAF) 4; WSMR, NM is amended as follows.
See SF30 Continuation Sheet(s)
NOTE: The Bid Receipt date will be 24 July 2020; at 10:00 a.m.,CT.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY
16B. UNITED STATES OF AMERICA 15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer) (Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X 9A. AMENDMENT OF SOLICITATION NO.
W9126G20B0008
X 9B. DATED (SEE ITEM 11)
10-July-2020
10B. DATED (SEE ITEM 13)
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
20 -July-2020
CODE
US ARMY ENGINEER DISTRICT, FORT WORTH
ATTN: CESWF-CT
819 TAYLOR ST, ROOM 2A19
P.O. BOX 17300
FORT WORTH TX 76102-0300
W9126G 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W9126G20B0008
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
CHANGES TO SOLICITATION W9126G20B0008
CHANGES TO THE SPECIFICATIONS
1. Replacement Sections: Replace the following section with the accompanying new section of the same number and title bearing the notation W9126G20B0008- 0002:
06 20 00 FINISH CARPENTRY
41 22 23.19 MONORAIL HOISTS
CHANGES TO THE DRAWINGS
2. Replacement Drawings.- Replace the drawings listed below with the attached new drawings(s) of the same number, each page bearing the notation W9126G20B0008- 0002.
CE100 - EXISTING SITE CONDITIONS
CD100 - DEMOLITION PLAN
CP100 - PAVING PLAN
CU100 - OVERALLUTILITY PLAN
End of Summary of Changes
WSMR SWAF 4 Renovation WS19S4RENO
SECTION 06 20 00
FINISH CARPENTRY
<AMENDMENT NO. 0002>
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN HARDBOARD ASSOCIATION (AHA)
AHA A135.4 (1995; R 2004) Basic Hardboard
AMERICAN LUMBER STANDARDS COMMITTEE (ALSC)
ALSC PS 20 (2015) American Softwood Lumber Standard
AMERICAN WOOD PROTECTION ASSOCIATION (AWPA)
AWPA M4 (2015) Standard for the Care of Preservative-Treated Wood Products
AWPA U1 (2017) Use Category System: User Specification for Treated Wood
APA - THE ENGINEERED WOOD ASSOCIATION (APA)
APA L870 (2010) Voluntary Product Standard, PS 1-09, Structural Plywood
ASME INTERNATIONAL (ASME)
ASME B18.2.1 (2012; Errata 2013) Square and Hex Bolts and Screws (Inch Series)
ASME B18.2.2 (2015) Nuts for General Applications:
Machine Screw Nuts, Hex, Square, Hex Flange, and Coupling Nuts (Inch Series)
ASME B18.6.1 (2016) Wood Screws (Inch Series)
ASTM INTERNATIONAL (ASTM)
ASTM D2898 (2010; R 2017) Standard Practice for Accelerated Weathering of Fire-Retardant-Treated Wood for Fire Testing
ASTM F547 (2017) Standard Terminology of Nails for Use with Wood and Wood-Base Materials
SECTION 06 20 00 Page 1
W9126G20B0008- 0002
BUILDERS HARDWARE MANUFACTURERS ASSOCIATION (BHMA)
ANSI/BHMA A156.9 (2015) Cabinet Hardware
CALIFORNIA AIR RESOURCES BOARD (CARB)
CARB 93120 (2007) Airborne Toxic Control Measure (ATCM) to Reduce Formaldehyde Emissions from Composite Wood Products
COMPOSITE PANEL ASSOCIATION (CPA)
CPA A208.1 (2016) Particleboard
HARDWOOD PLYWOOD AND VENEER ASSOCIATION (HPVA)
HPVA HP-1 (2016) American National Standard for Hardwood and Decorative Plywood
NATIONAL HARDWOOD LUMBER ASSOCIATION (NHLA)
NHLA Rules (2015) Rules for the Measurement & Inspection of Hardwood & Cypress
NORTHEASTERN LUMBER MANUFACTURERS ASSOCIATION (NELMA)
NELMA Grading Rules (2013) Standard Grading Rules for Northeastern Lumber
REDWOOD INSPECTION SERVICE (RIS) OF THE CALIFORNIA REDWOOD
ASSOCIATION (CRA)
RIS Grade Use (1998) Redwood Lumber Grades and Uses
SOUTHERN PINE INSPECTION BUREAU (SPIB)
SPIB 1003 (2014) Standard Grading Rules for Southern Pine Lumber
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
40 CFR 770 Formaldehyde Standards for Composite Wood Products
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
WEST COAST LUMBER INSPECTION BUREAU (WCLIB)
WCLIB 17 (2015) Standard Grading Rules
WESTERN WOOD PRODUCTS ASSOCIATION (WWPA)
WWPA G-5 (2017) Western Lumber Grading Rules
SECTION 06 20 00 Page 2
WINDOW AND DOOR MANUFACTURERS ASSOCIATION (WDMA)
WDMA I.S.4 (2015A) Preservative Treatment for Millwork
WOOD MOULDING AND MILLWORK PRODUCERS ASSOCIATION (WMMPA)
WMMPA WM 6 (2007) Quality Industry Standards Booklet
WOODWORK INSTITUTE (WI)
NAAWS 3.1 (2017; 2018 Errata Edition) North American Architectural Woodwork Standards
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are [for Contractor Quality Control approval.][for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section
01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Detail Drawings Indicating All Wood Assemblies; G[, [_____]]
SD-03 Product Data
Wood Products; G[, [_____]]
Countertops; G[, [_____]]
Engineered Wood Products; G[, [_____]]
Treated Wood Products; G[, [_____]]
Soffits; G[, [_____]]
Fascias and Trim; G[, [_____]]
Hardware and Accessories; G[, [_____]]
[ VOC Content for Siding; S
][ Recycled Content for MDF/Particleboard; S
] SD-04 Samples
Samples; G[, [_____]]
SD-07 Certificates
Certificates of Grade; G[, [_____]]
[ Certified Sustainably Harvested Wood for Trim and Frames; S
][ Certified Sustainably Harvested Softwood Plywood; S
SECTION 06 20 00 Page 3
][ Certified Sustainably Harvested Hardwood Plywood; S
][ Certified Sustainably Harvested Hardboard; S
][ Certified Sustainably Harvested Siding; S
][ Indoor Air Quality for Hardwood Plywood; S
][ Indoor Air Quality for MDF and Particleboard; S
][ Indoor Air Quality for Non-aerosol Adhesives; S
][ Indoor Air Quality for Aerosol Adhesives; S
]1.3 DETAIL DRAWINGS
Submit detail drawings indicating all wood assemblies proposed for use in the project. Indicate materials, species, grade, density, grain, finish details of construction, location of use in the project, finishes, types, method and arrangement of fasteners, and installation details. This includes all fabricated assemblies.
1.4 PRODUCT DATA
Submit Manufacturers printed data including proposed species, grade, density grain, and finish as applicable; sufficient to demonstrate compliance with this specification for each type of wood product specified. For treated wood products also provide documentation of environmentally safe preservatives for each type of wood product specified.
Provide Manufacturers printed data for hardware and all wood accessories including but not limited to edge banding, adhesives, and sealers.
1.5 SAMPLES
Samples indicating proposed species, grade, density grain, and finish for each type of wood product specified. Provide samples of sufficient size to show pattern and color ranges of proposed products.
1.6 DELIVERY, STORAGE, AND HANDLING
Deliver wood products to the jobsite in an undamaged condition. Stack materials to ensure ventilation and drainage. Protect against dampness before and after delivery. Store materials under cover in a well ventilated enclosure and protect against extreme changes in temperature and humidity. Keep materials wrapped and separated from off-gassing materials (such as drying paints and adhesives). Do not use materials that have visible moisture or biological growth. Do not store products in building until wet trade materials are dry and humidity of the space is within wood manufacturer's tolerance limits for storage.
1.7 QUALITY ASSURANCE
1.7.1 Certifications
1.7.1.1 Certified Wood Grades
Provide certificates of grade from the grading agency on graded but
SECTION 06 20 00 Page 4 unmarked lumber or plywood attesting that materials meet the grade requirements specified herein.
[1.7.1.2 Certified Sustainably Harvested Wood
Provide wood certified as sustainably harvested by FSC STD 01 001[, ATFS STANDARDS, CSA Z809-08, SFI 2015-2019, or other third party program certified by PEFC ST 2002:2013]. Provide a letter of Certification of Sustainably Harvested Wood signed by the wood supplier. Identify certifying organization and their third party program name and indicate compliance with chain-of-custody program requirements. Submit sustainable wood certification data; identify each certified product on a line item basis. Submit copies of invoices bearing certification numbers.
][1.7.1.2 Indoor Air Quality Certifications
1.7.1.2.1 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.7.1.2.2 Composite Wood Products
For purposes of this specification, composite wood products include hardwood plywood, particleboard, medium density fiberboard (MDF), panel substrates, and door cores. Provide products certified to meet requirements of both 40 CFR 770 and CARB 93120. Provide current product certification documentation from certification body.
]1.7.2 Lumber
Identify each piece or each bundle of lumber, millwork, and trim by the grade mark of a recognized association or independent inspection agency certified by the Board of Review of the ALSC to grade the species.
1.7.3 Plywood
Provide each sheet of plywood with the mark of a recognized association or independent inspection agency that maintains continuing control over the quality of the plywood. Marks must identify plywood by species group or span rating, exposure durability classification, grade, and compliance with
APA L870.
1.7.4 Hardboard [and Particleboard]
Provide materials marks or written documentation identifying the producer and the applicable standard.
1.7.5 Pressure Treated Lumber and Plywood
Inspect each treated piece in accordance with AWPA U1.
SECTION 06 20 00 Page 5
1.7.6 Non-Pressure Treated Woodwork and Millwork
Mark, stamp, or label to indicate compliance with WDMA I.S.4.
1.7.7 Fire-Retardant Treated Lumber
Each piece must bear an Underwriters Laboratories fire resistance label or comparable label of another nationally recognized independent fire retardant materials testing laboratory.
PART 2 PRODUCTS
2.1 WOOD PRODUCTS
2.1.1 Sizes and Patterns of Wood Products
Provide yard and board lumber sizes in accordance with ALSC PS 20. Provide shaped lumber and millwork in the patterns indicated and in standard patterns of the association covering the species. Size references, unless otherwise specified, are nominal sizes. Provide actual sizes within manufacturing tolerances allowed by the applicable standard.
2.1.2 Species and Grades
Provide in accordance with AWPA U1 Use Category System Tables unless otherwise specified herein.
2.1.3 Trim, Finish, and Frames
Provide species and grades listed in the table below for wood materials that must be painted. For materials that must be stained, have a natural, or a transparent finish, provide materials one grade higher than those listed in the table below. Provide trim, except window stools and aprons with hollow backs.[ Provide certified sustainably harvested wood for trim and frames.]
SECTION 06 20 00 Page 6
TABLE OF GRADES FOR WOOD TO RECEIVE PAINT FINISH
Grading Rules Species Exterior and Interior Trim, Finish, and Frames
WWPA G-5 standard grading rules
Aspen, Douglas Fir-Larch, Douglas Fir South, Engelmann Spruce-Lodgepole Pine, Engelmann Spruce, Hem-Fir, Idaho White Pine, Lodgepole Pine, Mountain Hemlock, Mountain Hemlock-Hem-Fir, Ponderosa Pine-Sugar Pine, (Ponderosa Pine-Lodgepole Pine,) White Woods, (Western Woods,) Western Cedars, Western Hemlock
All Species: C & BTR.
Select (Choice & BTR Idaho White Pine) or Superior Finish. Western Red Cedar may be graded C & BTR. Select or A & BTR in accordance with Special Western Red Cedar Rules.
WCLIB 17 standard grading rules
Douglas Fir-Larch, Hem-Fir, Mountain Hemlock, Sitka Spruce, Western Cedars, Western Hemlock
All Species: C & BTR VG, except A for Western Red Cedar
SPIB 1003
standard grading rules
Southern Pine C & BTR
NHLA Rules Cypress C-Select
NELMA Grading Rules standard grading rules **
Balsam Fir, Eastern Hemlock-Tamarack, Eastern Spruce, Eastern White Pine, Northern Pine, Northern Pine, Northern White Cedar
All Species: C-Select except C & BTR for Eastern White Pine and Norway Pine
RIS Grade Use standard specifications
Redwood Clear, Clear All Heart
NHLA Rules Cypress B Finish
Red Gum, Soft Elm, Birch Select or BTR (for interior use only)
Note: ** http://www.nelma.org/library/2013-standard-grading-rules-for-northeastern-lumber/
SECTION 06 20 00 Page 7
2.1.4 Utility Shelving
Provide utility shelving in a suitable species equal to or exceeding the requirements of No. 3 common white fir under WWPA G-5, 1 inch thick; or plywood, interior type, Grade A-B, 1/2 inch thick, any species group.
2.1.5 Softwood Plywood
Provide in accordance with APA L870.[ Provide certified sustainably harvested softwood plywood.][ When located on the interior of buildings, provide products with no added urea-formaldehyde resins.]
a. Plywood for Soffits: Exterior type, B-B medium density overlay.
b. Plywood for Shelving: Interior type, [A-B] [B-B] Grade, any species group.
c. Plywood for Countertops: Exterior type, A-C Grade.
2.1.6 Hardwood Plywood
HPVA HP-1, Type [Technical (Exterior)] [I (Exterior)] [II (Interior)] [III (Interior)], [Premium (A)] [Good (1)] [Sound (2)] [Utility (3)] [Backing (4)] [Specialty (SP)] Grade, [hardwood veneer core construction,] [lumber core construction,] face veneers of [_____]White Oak, of thickness indicated.[ Provide certified sustainably harvested hardwood plywood.][ When located on the interior of buildings, provide products with no added urea-formaldehyde resins. For products located on the interior of the building (inside of the weatherproofing system), provide certification of indoor air quality for hardwood plywood.]
2.1.7 Hardboard
AHA A135.4, [standard] [tempered] [service] type, [1/8] [1/4] inch thick.[ Provide certified sustainably harvested hardboard.]
[2.1.8 Medium Density Fiberboard (MDF) and Particleboard
CPA A208.1, Grade 1-M-2 or 2-M-2 or better.[ For products located on the interior of the building (inside of the weatherproofing system), provide certification of indoor air quality for MDF and particleboard.]
Provide products with 80 percent total recovered materials content.
Provide data identifying percentage of recycled content for MDF/particleboard.
]2.1.9 Stairs
Treads 1-1/4 inches thickness, clear red or white oak. Risers 1 inch nominal finish lumber.
2.1.9 Shoe Mould
Clear red or white oak, 1/2 by 5/8 inch unless otherwise indicated.
2.1.10 Wood Seats
Clear maple, oak, or other suitable hardwood, not less than 1-5/8 inches thick, with rounded edges. Provide stainless steel stanchions or brackets.
SECTION 06 20 00 Page 8
2.1.11 Wood Bumpers
Clear oak[, maple] [, birch] [or] [_____], dressed to size indicated and with outer edges beveled.
2.1.12 Catwalks
Boards, 1 by 6 inches nominal, species and grade equal to or exceeding 3 Common Hem-Fir under WWPA G-5.
2.1.13 Siding
Provide hardboard, plywood, or wood for horizontal siding. Provide hardboard or plywood for panel siding.[ Provide certified sustainably harvested siding.][ When located on the interior of buildings, provide products with no added urea-formaldehyde resins. Provide data identifying VOC content for siding.]
2.1.13.1 Horizontal Hardboard Siding
AHA A135.6, factory primed face and longitudinal edges, factory sealed back, lap type, [8] [9] [10] [12] inches wide, maximum practicable lengths, 3/8 or 7/16 inch thick, [smooth] [embossed] [textured] face.
2.1.13.2 Panel Hardboard Siding
AHA A135.6, factory primed face and longitudinal edges, factory sealed back, 4 feet wide, maximum practicable lengths, 3/8 or 7/16 inch thick, [smooth] [embossed] face [, and grooved as selected from manufacturer's standard patterns].
2.1.13.3 Horizontal Plywood Siding
APA L870, exterior, [medium density overlay] lap type, [6] [8] [12] inches wide, maximum practicable lengths, [3/8] [7/16] [15/32] [1/2] inch thick, [smooth] [embossed] [rough sawn texture] [embossed] face.
2.1.13.4 Panel Plywood Siding
APA L870, exterior, [medium density overlay,] 4 feet wide, maximum practicable lengths, span rating of [16] [24] inches on center, [smooth] [embossed] [rough sawn texture] [striated] face, [and grooved] as selected from manufacturer's standard patterns.
2.1.13.5 Horizontal Rated Siding
Qualified under APA E445, exterior type [medium density overlay], lap types, [6] [8] [10] [12] inches wide, maximum practicable lengths, [7/16] [15/32] [1/2] inch thick, [smooth] [embossed] [rough sawn texture] face.
2.1.13.6 Panel Rated Siding
Qualified under APA E445, exterior type, [medium density overlay] 4 feet wide, maximum practicable lengths, [span rated at 16 inch] [span rated at 24 inch,] [smooth] [embossed] [striated] face [, and grooves] as selected from manufacturer's standard patterns.
SECTION 06 20 00 Page 9
2.1.13.7 Wood Siding
Provide [horizontal bevel type, minimum 3/16 inch thin edge by minimum 7/16 inch thick edge,] [horizontal plain lap type] [horizontal drop type] [vertical board, tongue and groove or shiplap on long edges,] [vertical board and batten type,] 1 inch thick, [6] [8] [10] inches wide, maximum practicable lengths, [smooth] [rough sawn texture].
2.1.13.8 Engineered Wood Structural Panels
Comply with ICC IBC, Chapter 23 Wood, and with APA S350, exterior, exposure [1] [2], [single-faced] [double-faced], 4 feet wide, maximum practicable lengths, selected from manufacturer's standard patterns to satisfy the wind load for the specified span.
2.1.13.9 Epoxy Coated Wood Panels
Provide prefinished epoxy coated wood panels consisting of an asbestos-free cement board base sheet with a factory applied surface of epoxy resin and decorative natural stone chips. Provide factory applied finish in a minimum 20 mils thickness consisting of 100 percent solids, with a two component epoxy resin based coating followed by an application of inert aggregate.
Provide stone color(s) and accessory colors as selected by Contracting Officer's Representative from manufacturer's full color and pattern ranges. Provide cement board base sheets in a minimum thickness of 1/4 inch thick. Dimensionally stable finished panels are required. Water absorption on the surfaced side of panels cannot exceed 0.20 percent after 24 hours of submergence in water. Provide accessories in manufacturer's standard extruded aluminum. Provide mouldings for meeting strips, end caps, inside corners, outside corners. Provide non-corrosive, self-tapping screw type fasteners finished to match the color of the panel surface.
Provide caulking compounds that are color compatible, low modulus silicone or urethane types.
2.2 SOFFITS
2.2.1 Hardboard and Plywood
Provide hardboard and plywood soffits in siding grade hardboard, 3/8 or 7/16 inch thick; plywood, APA L870, exterior type, [Grade A-C] [plywood panel siding] [rated siding],[11/32 inch thick for 24 inches on center] [ 15/32 inch thick for 32 inches on center] [19/32 inches thick for 48 inches on center] maximum span with all edges supported.
2.3 FASCIAS AND TRIM
2.3.1 Wood
Provide species and grades for all fascia and trim, including exterior door and window casings, in accordance with AWPA U1 Use Category System Tables.
Provide sizes indicated. Metal corners may be provided in lieu of wood corner boards for horizontal siding. If metal corners are used, provide galvanized steel or aluminum, completely coated with primer compatible for the specific metal substrate.
SECTION 06 20 00 Page 10
2.2 COUNTERTOPS
2.2.1 Laminated Plastic-faced Countertops
ANSI/NEMA LD 3.
2.2.1.1 Countertop Finishes
High pressure plastic laminate, Grade GP 50 or PF 42, satin or textured finish. Provide color and pattern [_____] [as selected by Contracting Officer's Representative from manufacturer's full color and pattern ranges].
2.2.1.2 Backing Sheet
Heavy gauge, BK 20.
2.2.1 Solid Surface
For solid surface countertops refer to Section 06 61 16, SOLID POLYMER
(SOLID SURFACING) FABRICATIONS.
2.3 MOISTURE CONTENT OF WOOD PRODUCTS
Air dry or kiln dry lumber. Kiln dry treated lumber after treatment.
Maximum moisture content of wood products at time of delivery to the jobsite, and when installed, must be as follows:
a. Interior Paneling: [6] [12] percent.
b. Interior Finish Lumber, Trim, and Millwork: 1-1/4 Inches Nominal or Less in Thickness: [6] [12] percent on 85 percent of the pieces and [8 ] [15] percent on remainder.
c. Exterior Treated and Untreated Finish Lumber and Trim: 4 inches Nominal or Less in Thickness: 19 percent.
d. Exterior Wood Siding: 15 percent.
e. Provide moisture content of other materials in accordance with the applicable standards.
2.4 PRESERVATIVE TREATMENT OF WOOD PRODUCTS
2.4.1 Non-Pressure Treatment
Treat woodwork and millwork, such as [cabinets, ]exterior trim, door trim, and window trim, in accordance with WDMA I.S.4, with either 2 percent copper napthenate, 3 percent zinc napthenate, or 1.8 percent copper-8-quinolinolate. Provide a liberal brush coat of preservative treatment to field cuts and holes.
2.4.2 Pressure Treatment
Treat lumber and plywood used on the exterior of buildings [or in contact with masonry or concrete] with a waterborne preservative listed in AWPA U1 (P series is included therein by reference) as applicable, and inspected in accordance with AWPA U1. Identify treatment on each piece of material by the quality mark of an agency accredited by the Board of Review of the American Lumber Standards Committee. Provide treated plywood to a
SECTION 06 20 00 Page 11 reflection level as follows:
Preservative treat exterior wood moulding and millwork that will be within 18 inches of soil or in contact with water or concrete in accordance with WMMPA WM 6. Provide a field treatment in accordance with AWPA M4 of exposed areas of treated wood that have been cut or drilled. Items of all-heart material of cedar, cypress, or redwood do not require preservative treatment except when in direct contact with soil.
2.5 FIRE-RETARDANT TREATMENT
2.5.1 Wood Products
Pressure treat fire-retardant treated lumber and plywood in accordance with AWPA U1. Comply with material use as defined in AWPA U1 for Interior Type [ A] [and] [B] and Exterior Type. Treatment and performance inspection must be conducted by a qualified independent testing agency that establishes performance ratings. Each piece or bundle of treated material must bear identification of the testing agency to indicate performance with such rating. Subject treated materials that will be exposed to rain wetting to an accelerated weathering technique in accordance with ASTM D2898, Method A, prior to being tested for compliance with AWPA U1.
Treat the following items:
2.6 HARDWARE AND ACCESSORIES
Provide sizes, types, and spacings of hardware and accessories as recommended in writing by the wood product manufacturer, except as otherwise specified.
2.6.1 Wood Screws
ASME B18.6.1.
2.6.2 Bolts, Nuts, Lag Screws, and Studs
ASME B18.2.1 and ASME B18.2.2.
2.6.3 Nails
Use nails of a size and type best suited for each application and in accordance with ASTM F547. Use hot-dipped galvanized or aluminum nails for exterior applications. For siding, provide nails of sufficient length to extend 1-1/2 inches into supports, including wood sheathing over framing.
Where nailing is impractical, provide screws of a size and type best suited for each application.
2.6.4 Adjustable Shelf Standards
ANSI/BHMA A156.9, Type B04071 mortised[_____], with shelf rests Type B04081
2.6.5 Vertical Slotted Shelf Standards
ANSI/BHMA A156.9, Type B04102[_____], with shelf brackets Type B04112[_____].
SECTION 06 20 00 Page 12
2.6.6 Closet Hanger Rods
Chromium plated steel rods, not less than 1 inch diameter by 18 gage. Rods may be adjustable with integral mounting brackets if smaller tube is 1 inch by 18 gage. Provide intermediate support brackets for rods more than 48 inches long.
2.7 FABRICATION
2.7.1 Quality Standards (QS)
2.7.1.1 Grades
The terms "Premium," "Custom," and "Economy" refer to the quality grades defined in NAAWS 3.1. Provide items not otherwise specified in a specific grade as "Custom" grade.
2.7.1.2 Adhesives
Select adhesives for durability and permanent bonding. Address factors such as materials that must be bonded, expansion and contraction, bond strength, fire rating, moisture resistance, and manufacturer's recommendations.
[ Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168. Provide aerosol adhesives used on the interior of the building meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for non-aerosol adhesives applied on the interior of the building (inside of the weatherproofing system). Provide certification or validation of indoor air quality for aerosol adhesives used on the interior of the building.
]2.7.2 Countertops
Fabricate with lumber and a core of [exterior plywood] [or] [particleboard], glued and screwed to form an integral unit. Bond laminated plastic under pressure to exposed surfaces, using adhesive as recommended by the plastic manufacturer [, and bond a backing sheet under pressure to underside of countertop]. Provide countertop units as post-formed type, no-drip nose, cove mouldings, Style A backsplash, and surfaced with ANSI/NEMA LD 3, Grade PF 42 plastic. Provide backsplashes not less than 3-1/2 inches nor more than 4-1/2 inches high.
2.7.2 Cabinets
Unless specified otherwise, provide wall and base cabinets of the same construction, materials, and finishes as countertops. Fabricate cabinets with solid ends and frame fronts, or with frames all around. Provide frames of solid hardwood not less than 3/4 by 1-1/2 inches. Provide ends, bottoms, backs, partitions, and doors as hardwood plywood. Mortise and tenon, dovetail, or dowel and glue joints to produce a rigid unit. Cover exposed edges of plywood with hardwood strips. Provide cabinet doors, frames, and solid exposed ends 3/4 inch thick minimum. Provide cabinet bottoms, partitions, and framed ends to be 1/2 inch minimum. Provide
SECTION 06 20 00 Page 13 shelves to be 5/8 inch thick minimum. Provide cabinet backs 1/4 inch thick minimum.
2.7.2.1 Cabinet Hardware
ANSI/BHMA A156.9. Provide cabinet hardware including two self, closing hinges for each door, two side mounted metal drawer slides for each drawer, and pulls for all doors and drawers as follows. Provide hardware exposed to view [as bright chromium plated][_____]. Comply with the following requirements for all cabinet hardware:
a. Provide frameless concealed European style, back mounted hinges with 165 degree opening and a self closing feature when at less than 90 degrees open.
b. Provide drawer slides having a static rating capacity of [100 lbs.
][_____]. Slides to have a self closing/stay closed action, zinc or epoxy coated steel finish, ball bearing rollers, and positive stop with lift out design.
c. Provide drawer pulls as similar to those shown on the drawings,[wire type pulls with center-to-center dimension of not less than 3-1/2 inches and a cross sectional diameter of 5/16 inch]. Provide handle projections not less than[ 1-5/16 inches]. [_____].
d. Provide heavy duty magnetic drawer catches.
2.7.2.2 Finish
Provide a clear factory finish on wood surfaces after fabrication. Provide fabricator's standard natural finish equivalent to one coat of sealer, one coat of varnish on all surfaces and a second coat of varnish on surfaces exposed to view. Provide spar varnish in exterior or wet area applications. Sand lightly and wipe clean between coats.
2.7.3 Workbenches
Dovetail and glue drawer corners. Fasten frames with suitable wood screws or bolts. Sand exposed surfaces smooth, and ease exposed edges. Provide two side mounted, metal, ball bearing drawer slides [ANSI/BHMA A156.9, Type [_____],] for each drawer, and at least two surface mounted hinges[, Type [_____],] and a magnetic catch[, Type [_____],] for each door.
2.7.3 Casework with Transparent Finish (CTF)
2.7.3.1 AWI Quality Grade
[Premium] [Custom] [Economy] grade.
2.7.3.2 Construction
Provide [reveal overlay] [flush overlay] [exposed face frame] design details.
<AM#0002>2.7.3.3 Exposed Parts
White Oak or Red Oak specie, Plain cut.
SECTION 06 20 00 Page 14
<AM#0002>2.7.3.4 Semi-Exposed Parts
As specified in the NAAWS 3.1 for the grade selected.
2.7.4 Casework with High Pressure Laminate Finish
2.7.4.1 AWI Quality Grade
[Premium] [Custom] grade.
2.7.4.2 Construction
Provide [reveal overlay] [flush overlay] [exposed face frame] design details.
2.7.4.3 Exposed Surfaces
High pressure plastic laminate, color and pattern [_____][as selected by Contracting Officer's Representative from manufacturer's full range].
2.7.4.4 Semi-Exposed Surfaces
As specified in the NAAWS 3.1 for the grade selected.
[2.7.4.5 Edge Banding
Provide edge banding for casework doors and drawer fronts in PVC vinyl Veneer Edge Banding [0.020 inch] [0.125 inch] [_____] thick. Provide width [15/16 inches] [_____].[ Match color and pattern to exposed door and drawer front laminateveneer pattern and color.][ Provide color and pattern
]PART 3 EXECUTION
Do not install building construction materials that show visual evidence of biological growth.
3.1 FINISH WORK
Apply primer to finish work before installing. Where practicable, shop assemble and finish millwork items. Construct joints tight and in a manner to conceal shrinkage but to avoid cupping, twisting and warping after installation. Miter trim and mouldings at exterior angles; cope at interior angles and at returns. Provide millwork and trim in maximum practical lengths. Fasten finish work with finish nails. Provide blind nailing where practicable. Set face nails for putty stopping.
3.1.1 Exterior Finish Work
Machine sand exposed flat members and square edges. Machine finish semi-exposed surfaces. Construct joints to exclude water. In addition to nailing, glue joints with waterproof glue as necessary for weather resistant construction. Evenly distribute end joints in built-up members.
Provide shoulder joints in flat work. Reinforce backs of wide-faced miters with metal rings and waterproof glue. Unless otherwise indicated, provide fascia and other flat members 3/4 inch thick minimum. Provide door and window trim in single lengths. Provide braced, blocked, and rigidly anchored cornices for support and protection of vertical joints. Provide soffits in largest practical size. Align joints of plywood over
SECTION 06 20 00 Page 15 centerlines of supports. Fasten soffits with aluminum or stainless steel nails. Back prime all concealed surfaces of exterior trim.
3.1.2 Interior Finish Work
After installation, sand exposed surfaces smooth. Provide window and door trim in single lengths.
3.1.3 Door Frames
Set plumb and square. Provide solid blocking at not more than 16 inches on center for each jamb. Position blocking to occur behind hinges and lock strikes. Double wedge frames and fasten with finish nails. Set nails for putty stopping.
3.1.4 Thresholds
Unless otherwise indicated, provide thresholds [5/8 inch thick by 2-5/8 inches wide with beveled sides] and cut to fit at jambs. Fasten thresholds with casing nails. Set nails for putty stopping.
3.1.5 Window Stools and Aprons
Provide stools with rabbets over window sills. Provide aprons with returns cut accurately to profile of member.
3.1.6 Bases
Provide flat member with a moulded top [and oak shoe mould]. Fasten base to framing or to grounds.[ Nail shoe mould to base.] Set [shoe mould] [one-piece wood base] after finish flooring is in place.
3.1.7 Finish Stair Work
Fit, nail, screw, bolt, and glue stair work together to form a strong, rigid structure without squeaks or vibrations. Anchor newels and posts securely to stair framing. Cut newels, posts, and drops accurately around floor construction to make a tight fit. Embed balusters into treads and landings and secure with glue. Provide railings with straight runs that follow the slope of the stairs and have smooth curved turns. Return railing profile at ends and secure joints with bolts and nuts in accordance with structural load requirements for railings. Secure railing to posts and newels with concealed anchors. Support wall rails on metal brackets spaced near ends and at not more than 5 feet on center.
3.2 SHELVING
Support 1 inch nominal thick wood shelf material or 3/4 or 23/32 inch thick plywood shelf material with end and intermediate supports arranged to prevent buckling and sagging.[ Provide hook strips 1 by 4 inches nominal and cleats 1 by 2 inches nominal.] Provide cleats except where hook strips are specified or indicated.[ Where adjustable shelving is indicated, provide standards and brackets or shelf rests for each shelf.][ Anchor standards to wall at not more than 2 feet on center.]
3.2.1 Linen Closets
Unless indicated otherwise, provide linen closets with a counter shelf 20 inches wide located 36 inches above the floor, a lower shelf approximately
SECTION 06 20 00 Page 16
18 inches wide and 18 inches above the floor, and three upper shelves 11-1/4 inches wide located 14 inches above the counter shelf and 14 inches apart.
3.2.2 Storage Rooms
Unless otherwise indicated, provide storage rooms with shelves 11-1/4 inches wide, bottom shelf 18 inches above the floor, top shelf 18 inches below the ceiling, and intermediate shelves approximately 18 inches apart.
3.2.3 Room Closets
Provide two shelves 11-1/4 inches wide. Support lower shelf by hook strips at back and ends, and provide full length wood or metal clothes hanger rods unless indicated otherwise.
3.2.4 Cleaning Gear Closets
Provide [shelves of size and arrangement indicated] [two shelves 14 inches wide].
3.3 CLOTHES HANGER RODS
Provide clothes hanger rods where indicated and in closets having hook strips. Set rods parallel with front edges of shelves and support by sockets at each end and intermediate brackets spaced not more than 4 feet on center.
3.2 MISCELLANEOUS
3.2.1 Countertops
Conceal fastenings where practicable. Fit counters tight to adjoining surfaces and scribe where necessary. Provide scribed joints neat and flush. Provide counter sections in longest lengths practicable with a minimum number of joints. Where joints are necessary, provide tight joints drawn up with concealed type heavy pull-up bolts. Glue joints with water resistant glue and make rigid with screws, bolts, or other approved fastenings.
3.2.1 Cabinets
Provide cabinets level, plumb, true, and tight to adjacent walls. Secure cabinets to walls with concealed toggle bolts. Secure top to cabinet with concealed screws.[ Make cutouts for fixtures from templates supplied by fixture manufacturer. Locate cutouts for pipes so that edges of holes are covered by escutcheons after installation.]
3.2.2 Workbenches
Provide level, plumb, and tight to adjacent construction. Fasten workbenches to walls with screws or toggle bolts and to floors with expansion bolts.
3.2.3 Wood Seats
Support seats [on brackets spiked to the studs] [on stanchions]. Secure seats to supports with [screws] [bolts] as required; countersink heads of [screws] [bolts] and fill holes with hardwood filler, finished flush with
SECTION 06 20 00 Page 17 tops of seats.
3.2.4 Wood Bumpers
Bore, countersink, and bolt wood bumpers in place where indicated.
3.2.5 Catwalks in Attic Spaces
Lay boards with 1 inch spaces between. Stagger end joints, with each joint on a support.
3.3 SIDING
3.3.1 Installation of Siding
Fit and position siding without springing or otherwise forcing panels into place.[ For siding to have a stain finish, set nails and stop with nonstaining putty to match finished siding.][ For siding to have a paint finish, drive nails flush.]
3.3.2 Horizontal Siding
Locate end joints over framing members and alternate such that there are a minimum of two boards between joints on the same support. Evenly distribute shorter pieces throughout the installation. Provide starter strips to establish proper cant for siding. Predrill ends of siding as necessary to prevent splitting when nailed.[ Horizontal bevel or plain lap siding: Overlap and nail into each support in accordance with recommendations of siding manufacturer.][ Horizontal drop siding: Work each course into top edge of previous course. Nail into each support with [two nails, one near lower edge to clear top of previous course, and one just above mid-height of course.] [one nail just above mid-height of course.]]
3.3.3 Vertical Board Siding
Apply siding with horizontal joints only at locations indicated. Work each board into edge of previous course. Nail into supports at 24 inches on center with [two nails, one blind if possible at or near joint with previous board, and one just outside board centerline.] [one nail just outside board center line.]
3.3.4 Vertical Board and Batten Siding
Apply with horizontal joints only at locations indicated. Install each board with 1/2 inch of space between boards. Nail at center of board and into supports at 24 inches on center. Center battens over space between boards and nail down center at 16 inches on center.
3.3.5 Panel Siding
Apply panels with edges at joints spaced in accordance with manufacturer's recommendations. Provide shiplapped edges or square edges that will be covered by battens in a [primed for paint finish,] [sealed for stain finish]. Back all edges with framing members. Nail panels at edges 6 inches on center and at intermediate supports 12 inches on center. Locate edge nailing 3/8 inch from edges. For shiplap joints, nail 3/8 inch from visible joint and at a location to penetrate lap with previous panel. When panel siding is part of an engineered shear wall or used as wall bracing, SECTION 06 20 00 Page 18 nail shiplap joints to supports with double rows of nails. Space battens at [12] [16] inches on center and nail down center at 24 inches on center.
3.3.6 Epoxy Coated Panels
Provide panels where indicated and install in accordance with panel manufacturer's written installation instructions.
3.4 SOFFITS
3.4.1 Wood
Provide panels with edges at joints spaced in accordance with manufacturer's written instructions and with all edges backed by framing members. Nail panels 3/8 inch from edges at 6 inches on center and at intermediate supports at 12 inches on center. Provide panels in maximum practicable lengths.
3.5 FASCIA AND EXTERIOR TRIM
Construct, caulk, and machine sand exposed surfaces and edges to exclude water. In addition to nailing, glue joints as necessary for weather resistance. Evenly distribute end joints in built-up members. Shoulder joints in flat work. Reinforce backs of wide-faced miters with metal rings and glue. Provide fascia and other flat members in maximum practicable lengths. Braced, block, and rigidly anchor cornices for support and protection of vertical joints.
3.3 MOULDING AND INTERIOR TRIM
Install mouldings and interior trim straight, plumb, level and with closely fitted joints. Provide exposed surfaces machine sanded at the shop. Cope returns and interior angles at moulded items and miter external corners.
Shoulder intersections of flatwork to ease any inherent changes in plane.
Provide window and door trim in single lengths. Blind nail to the extent practicable. Set and stop face nailing with a nonstaining putty to match the applied finish. Use screws for attachment to metal; set and stop screws in accordance with the same quality requirements for nails.
-- End of Section --
SECTION 06 20 00 Page 19
SECTION 41 22 23.19
MONORAIL HOISTS
AMENDMENT NO. 0002
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ASME INTERNATIONAL (ASME)
ASME B30.11 (2010) Monorails and Underhung Cranes - Safety Standard for Cableways, Cranes, Derricks, Hoists, Hooks, Jacks, and Slings
ASME B30.16 (2017) Overhead Underhung and Stationary Hoists
ASME HST-1 (2012) Performance Standard for Electric Chain Hoists
ASTM INTERNATIONAL (ASTM)
ASTM A275/A275M (2018) Standard Practice for Magnetic Particle Examination of Steel Forgings
ASTM E543 (2015) Standard Practice for Agencies Performing Non-Destructive Testing
ASTM E709 (2015) Standard Guide for Magnetic Particle Examination
CRANE MANUFACTURERS ASSOCIATION OF AMERICA (CMAA)
CMAA 74 (2015) Specifications for Single Girder Cranes
MATERIAL HANDLING INDUSTRY OF AMERICA (MHI)
MHI MH27.1 (2009) Specifications for Underhung Cranes and Monorail Systems
MHI MH27.2 (2009) Specifications for Enclosed Track Underhung Cranes and Monorail Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA ESPG (2009-2010) Electrical Standards and Product Guide (ESPG)
NEMA ICS 8 (2011) Crane and Hoist Controllers
NEMA MG 1 (2016; SUPP 2016) Motors and Generators
SECTION 41 22 23.19 Page 1
NEMA MG 2 (2014) Safety Standard for Construction and Guide for Selection, Installation and Use of Electric Motors and Generators
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.179 Overhead and Gantry Cranes
1.2 SYSTEM DESCRIPTION
Provide an electric powered hoist and electric poweredtrolley complete, tested and ready for operation for the existing monorail track. Hoist, trolley, equipment, materials, installation, examination, inspection, and workmanship shall conform to the applicable requirements of NFPA 70, ASME B30.11, ASME B30.16, ASME HST-1,, MHI MH27.1 and MHI MH27.2, as modified and supplemented by this specification. Reference in these publications to the "authority having jurisdiction" means the "Contracting Officer."
1.2.1 Design Data: Structural Design Calculations
Submit structural design calculations verifying the size of structural members, structural supports (fittings, rods, brackets, and components), and lifting beams for the track beam system. Include stress and loading diagrams. Submit calculations with monorail drawings. Submit additional product data for commercially procured items, including as a minimum, the following items:
Festoon System Runway Electrification System Variable Frequency Drives Bumpers End Stops
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Monorail system, including attachments to existing building structure; G Complete schematic wiring diagram with description of operation; G
SECTION 41 22 23.19 Page 2
SD-03 Product Data
Monorail Track System; G
Electric Chain Hoist; G
Trolley; G Pendant Pushbutton Station; G
Hook Proof Test; G Festoon System; G Runway Electrification System; G Variable Frequency Drives; G Bumpers; G End Stops; G Manufacturer's Published Tables
Manufacturer's descriptive data and technical literature, performance charts and curves, catalog cuts, and installation instructions, and parts list.
SD-05 Design Data
Structural Design calculations; G Structural and Load Capacity calculations; G
Load and sizing calculations as specified.
SD-06 Test Reports
125 percent Rated Load test No-Load Test Post-Erection Inspection Operational Tests Rated Load Speed Test Load Chain Proof Test Hook NDT Report Hook Tram Measurement
Tests and inspections reports. Magnetic particle inspection of hook and hook nut results.
SD-07 Certificates
Compliance with all listed Standards Semi-Annual Overload/Safe for Testing Hazardous Material Brake Settings Runway Straightness/Levelness Loss of Power Test Hook Proof Test
SD-10 Operation and Maintenance Data
Monorail with hoist system, all components, Data Package 3; G
Submit Data Package 3 as specified in Section 01 78 23 OPERATION
AND MAINTENANCE DATA.
SECTION 41 22 23.19 Page 3
1.4 QUALITY ASSURANCE
1.4.1 Certificates: Load Chain
a. Certification of minimum Load Chain Proof Test, clearly indicating load chain breaking strength for each hoist, and clearly identified for traceability. Submit factory certification of load chain rated capacity.
b. Certification that the hoist, hook, and trolley system contains no hazardous material, asbestos, cadmium, lead, elemental mercury, or PCBs.
c. Semi-Annual Overload/Safe for Testing certification that the hoist, hook, and trolley system is safe to test on a semi-annual overload basis with a test load of 131.25 percent of rated capacity with no detrimental effects.
d. Certification that testing may be performed in which hoist, hook, and trolley system is subjected to a Loss of Power Test during operation with no detrimental effects.
e. Certification that the hoist, hook, and trolley system design and fabrication is in compliance with all listed standards.
f. Hook Proof Test certification that the hoist hook was subjected to a minimum static load of 200 percent of rated capacity for at least 10 minutes without deformation.
g. Runway Straightness/Levelness certification that the straightness, levelness, and elevation of the monorail system meet MH27.1 requirements.
h. Certification of brake settings, including the allowable range of adjustment for hoist and trolley brakes and the initial setting of each.
1.4.2 Pre-Erection Inspection
Before erection, the Contractor and the manufacturer's representative shall inspect the monorail and hoist systems and components at the job site to determine compliance with specifications and manufacturer's data and shop drawings as approved. Notify the Contracting Officer 28 days before the inspection.
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Delivery and Storage
Inspect materials delivered to site for damage; unload and store with minimum handling. Store materials on-site in enclosures or under protective coverings. Protect materials not suitable for outdoor storage to prevent damage or corrosion during periods of inclement weather, including subfreezing temperatures, precipitation, and high winds. Store materials susceptible to deterioration by direct sunlight under cover and avoid damage due to high temperatures. Do not store materials directly on ground. When special precautions are required, prominently and legibly stencil instructions for such precautions on outside of equipment or its crating.
SECTION 41 22 23.19 Page 4
1.5.2 Handling
Handle materials in such a manner as to ensure delivery to final location in undamaged condition.