ECIP Solar Generation Installation, Presidio of Monterey, CA
Solicitation number
W91238-10-R-0050
Issued by

About this file

Amendment 0003 with Revised Section 01 10 10.

View the file

Other files

File Type Posted
10R0050 AM0006.pdf PDF
W91238-10-R-0050-0005.pdf PDF
AM-04_W91238-10-R-0050.pdf PDF
W91238-10-R-0050-0004.pdf PDF
Site Visit Sign-in Sheet 26 Aug.pdf PDF
Phase 2 Amendment.pdf PDF
Firms Selected for Phase 2.pdf PDF
POM Pricing Schedule.pdf PDF
CA29_dvb.pdf PDF
SPEC_W91238-10-R-0050.pdf PDF
Firms Selected for Phase 2.pdf PDF
AM0001.pdf PDF
W9123810R0050.pdf PDF
Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W62N6MORDPOM

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND T ITLE OF SIGNER (Type or print)

30-105-04EXCEPTION T O SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

ECIP Solar Generation Installation, Presidio of Monterey, CA

The purpose of this modif ication is to revise Section 01 10 10.

The Date for Receipt of Proposals remains unchanged.

1. CONTRACT ID CODE PAGE OF PAGES

J 1 2

16A. NAME AND T ITLE OF CONTRACTING OFFICER (Type or print)

16C. DAT E SIGNED

BY

16B. UNITED STATES OF AMERICA15C. DAT E SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W91238-10-R-0050

X 9B. DATED (SEE ITEM 11)

27-May-2010

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. T HIS ITEM ONLY APPLIES T O AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DAT A (If required)

13. T HIS ITEM APPLIES ONLY T O MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES T HE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. T HIS CHANGE ORDER IS ISSUED PURSUANT T O: (Specify authority) T HE CHANGES SET FORTH IN ITEM 14 ARE MADE IN T HE

CONTRACT ORDER NO. IN ITEM 10A.

B. T HE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED T O REFLECT T HE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT T O T HE AUT HORITY OF FAR 43.103(B).

C. T HIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT T O AUT HORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required t o sign t his document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

20-Aug-2010

CODE

USACE SACRAMENTO DISTRICT

ATTN: CONTRACTING DIVISION

1325 J STREET-ROOM 878

SACRAMENTO CA 95814-2922

W91238 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W91238-10-R-0050

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION 00010 - SOLICITATION CONTRACT FORM

TABLE OF CONTENTS

The Table of Contents has changed from:

Exhibit/Attachment Table of Contents

DOCUMENT TYPE DESCRIPTION PAGES DATE

Attachment 1 Specs w/drawings 18-AUG-2010 Attachment 2 Pricing Schedule 18-AUG-2010 Attachment 3 Wage Determination 13-AUG-2010 to:

Exhibit/Attachment Table of Contents

DOCUMENT TYPE DESCRIPTION PAGES DATE

Attachment 4 Section 01 10 10 20-AUG-2010

(End of Summary of Changes)

ECIP-Solar Generation Installation Presidio of Monterey (POM), CA

REQUEST FOR PROPOSAL DESIGN BUILD

SECTION 01 10 10

TABLE OF CONTENTS

GENERAL PROJECT DESCRIPTION AND GENERAL DESIGN REQUIREMENTS

1. DESIGN OBJECTIVES

1.1 Background

1.2 Project Description

1.3 Project Location

1.4 Applicable Criteria and Standards

1.5 Design Quality

1.6 Design Freedom

2. DESIGN STANDARDS AND SUMBITTAL REQUIREMENTS

2.1 Standards, Documents and Criteria

2.2 Design Standards

2.3 Codes

2.4 Design in English System

2.5 Drawings

2.6 Specifications

3. STRUCTURAL DESIGN

3.1 General

3.2 Design Standards, Codes and Criteria

3.3 Design Loads

3.4 Structural Components and Systems

4. ELECTRICAL DESIGN

4.1 System Description

4.2 Scope

4.3 Warranties

4.4 Quality Assurance

4.5 Delivery, Storage and Handling

4.6 Contractor Requirements

4.7 Manufactured Units

4.8 Array Mounting and Orientation

4.9 Wind Loading

4.10 System Electrical

4.11 PV Array Summary

4.12 Other Requirements

4.13 Monitoring

4.14 Testing and Training

4.15 Installation Plan

4.16 Installation Standards

4.17 600-800 Series Buildings Exterior Lighting Bollard Retrofits

4.18 Warehouse Building 235 Lighting Retrofits

4.19 MWR Equipment Storage Building 228 Lighting Retrofits

01 10 10-1

AM-03

CHAPTER 1.0 - DESIGN OBJECTIVES

1.1 BACKGROUND

As part of its ongoing drive to optimize efficiency and conserve natural resources, the Presidio of Monterey (POM) identified this project to install onsite solar generation at Building 842, Price Fitness Center’s rooftop, POM, CA. The site and location are shown on drawing G-002, Site Location Map. It is to provide roof mounted solar electric modules capable of generating 378 KW of electrical power as rated by California Energy Commission (CEC) criteria. Drawing sheet C-102 identifies two roof areas that are to be used for placement of photovoltaic modules, a primary area on the upper roof and a secondary area (if it is needed) on the lower roof. Roof area shall be provided with integrated walkways between PV module rows to allow easy access to modules for maintenance. See photos 1 through 13 that follow for various views of the roof areas. The location and direction of these photographs are shown on drawing C- 101, Overall Site Plan.

Photo 14 shows the existing 300 kVA transformer that serves the Fitness Center, the existing Square D 800 amp 480Y/277V switchboard with metering and 800 amp main circuit breaker that serves as the service entrance equipment for the facility, a Siemens 800 amp 600V rated heavy duty double throw safety switch, and a couple of handholes/pullboxes. Photo 15 shows the location of the Photovoltaic Array’s inverter and concrete pad. The photos also illustrate the varying roof levels of the structure.

Access to the roof is by fixed ladders from within the facility and on the roof between roof levels. The roofing system is described in Chapter 3, Structural Design, of this specification.

Photo 1 Photo 2

01 10 10-2

Photo 3 Photo 4

Photo 5 Photo 6

Photo 7 Photo 8

01 10 10-3

Photo 9 Photo 10

Photo 11 Photo 12

Photo 13 Photo 14 (Primary Junction Cabinet)

01 10 10-4

Photo 15 (300 kVA Transformer at right w/ Photo 16 (300 kVA Transformer, 800A Primary Junction Cabinet in Background Behind 480Y/277V Switchboard, 800A Double Throw Gate) Safety Switch)

Photo 17 (Transformer, Switchboard, Safety Switch Photo 18 (Door into Building along exterior showing wall and roof line above) wall to southeast of electrical equipment, room inside is Outdoor Recreation Room C138 on Lower Level-Area “C”, as-built drawing E-9, near column lines A and 11-12)

01 10 10-5

Photo 19 (Original Service Entrance Switchboard in Photo 20 (Central Inverter System, Data Rack, Electrical Room C134, see Main Level Plan-Area Telephone Terminal Board on Opposite Wall “C” on as-built drawing E-9 near column lines B from Switchboard in Elec Room C134, see Main and 11-12, Mechanical Room Electrical Plan in detail Plan-Area “C” on as-built drawing E-9 near 2 on as-built drawing E-11, and Electrical One Line column lines B and 11-12, Mech. Room Elec.

Diagram on as-built drawing E-2) Plan in detail 2 on as-built drawing E-11)

1.2 PROJECT DESCRIPTION

This design-build Request for Proposal (RFP) provides for the design and construction of a Solar Electricity Generation via the installation of a 378 kW CEC rated solar array photovoltaic system whose electrical generation shall be used to offset the fitness center’s 688,960 kWh/year electrical energy consumption. Sheet No. C-101 shows primary and secondary areas of the Price Fitness Center’s roof designated for photovoltaic modules. Contractor shall determine number, orientation, degree of tilt and/or tracking (if any), layout, means of support, electrical system connections, supporting equipment location and layout, etc. for the photovoltaic system to meet the system requirements. Photos 1 through 13 above show roof conditions corresponding to this layout’s roof location and areas adjacent to these locations including roof mounted equipment, drainage system and communications equipment. See Sheet No. C- 101 Site Plan for location and direction of photos.

If available at the time of design and construction, for this project’s array size, an optional mounting system to consider is UNIRAC’s ISYS Roof Mount. The ISYS Roof Mount is also a non-penetrating roof mounting solution which can accommodate a 0-30 degree module tilt and requires no ballast blocks or concrete – the System provides all of the weight necessary to satisfy 90-120 mph basic wind speeds while still maintaining a low distributed load to the roof. This system exceeds the rated basic wind speed of 85 miles per hour for this location.

The selected photovoltaic system shall incorporate state of the art high efficiency CEC-listed photovoltaic modules manufactured in the USA and be UL-listed as described in Chapter 4 Electrical Design. The modules shall be mounted to a non roof penetrating ballasted support system. If the ISYS Roof Mount is selected, ballast blocks are not required. The overall system shall be compatible with the existing roof system and not compromise its structural and moisture barrier capabilities. The overall system design is to be in accordance with the codes and criteria as described in Chapter 3 Structural Design.

01 10 10-6

Before any work is to proceed, a roof survey is to be conducted to verify dimensions, locate all roof penetrations, roof drainage system, roof mounted equipment, etc. A roof survey is also required to verify roof condition before the installation of the photovoltaic array. After work is complete, the condition of the roof shall be compared with before-work condition. Any damage to the roof due to construction shall be the responsibility of the contractor to repair. The roof installer is to be contacted to coordinate all repair and photovoltaic array installation work so as to not impact the roof warranty or the installation process.

Fixed ladder access is already present to accommodate access to the varying roof elevations. Also shown on C-101 is a possible staging area for the contractor and driveway access that may be used for a crane to lift materials onto the upper roof.

A concrete pad shall be provided in the area outside existing Outdoor Recreation Room C138 (outside Lower Level-Area “C”) as shown on Drawing C-101 for outside inverter support. The pad is to be located within the outside gated area shown in photos 15 through 18 above (no photo is currently available of the area opposite the transformer and electrical service entrance equipment). The concrete pad shall be minimum 4,000 psi concrete.

Additional scope items include three separate lighting retrofit requirements. The first retrofit is to change 243 each 70 watt high pressure sodium exterior lighting bollard fixtures in the 600 to 800 series buildings to 23 watt induction lighting fixtures. The second retrofit is to replace 27 each 150 watt HID industrial type lighting fixtures in Warehouse Building 235 with 32 watt equivalent induction type industrial lighting fixtures, with the addition of new occupancy sensor controls for 18 each of these new fixtures (the larger of the two rooms with the new fixtures). The third retrofit is to replace 57 each lighting fixtures rated from 400 watts to 40 watts in MWR Equipment Storage Building 228 with new induction lighting fixtures ranging in rating from 165 watts to 11 watts. See the last three paragraphs in this section for further description of these lighting retrofits. The purpose of these lighting retrofits is to improve the energy efficiency of the associated lighting and also reduce the labor required to maintain these fixtures since the induction lighting fixtures have a much longer lamp life than the current fixture types. See paragraphs 4.17 through 4.19 in this section for more detail on these lighting retrofit requirements.

1.3 PROJECT LOCATION

The Project is located at the Price Fitness Center, Building 842, Presidio of Monterey (POM), Monterey, CA. Major arteries and roads serving the installation are provided in the map below.

01 10 10-7

1.4 APPLICABLE CRITERIA AND STANDARDS

Applicable design and construction criteria references are listed in Chapter 2 and in other chapters within this Section 01 10 00 DESIGN REQUIREMENTS. Criteria shall be taken from the most current references as of the date of issue of the RFP except where noted. Referenced codes and standards are acceptable criteria. Administrative, contractual, and procedural features of the contract shall be as described in other sections of this RFP. Requirements of this RFP shall be deemed the controlling authority of any changes to the other referenced documents and criteria. Guide Specifications shall be used to provide all details not stated in this RFP, but in no way shall it result in a lower standard than stated in this RFP.

1.5 DESIGN QUALITY

The main objective of this solicitation is to provide a new solar electric roof mounted system with a CEC rated power capacity of 378 kW for the Price Fitness Center, building 842, as well as to provide designated exterior and interior lighting retrofits. Project shall be accomplished within the funds available while maximizing design and material quality. Photovoltaic system design and material quality shall be achieved through selection of new solar panels with appropriate mounting systems resulting in low-cost maintenance and operation, and an overall balance of increased efficiency within the parameters provided herein.

1.6 DESIGN FREEDOM

Requirements stated and illustrated in this RFP are minimums. Only the roof areas available for placement of the solar modules have been identified on Plan Sheet C-101. No specific layout of the modules has been dictated to allow for different design approaches as to number, ratings, layout, degree of tilt (if any), fixed vs. single-axis tracking or dual-axis tracking, etc. of the solar modules. Actual layout

01 10 10-8 of the solar modules shall take into consideration existing roof features to avoid conflict with existing roof penetrations/objects for HVAC system, antenna, skylight, etc. that impact available area for placement of the solar modules. Layout shall take into consideration the result of survey verification findings as noted in Section 1.2 above. Layout shall accommodate structural, building service, comply with codes, support constructability or specific solar array design features/requirements as may be identified during design and coordinated during the review process. It shall be understood that the location, selection, arrangement and size of solar panels shall be determined by the Design-Build contractor during the design process as necessary to best serve the needs of the facility, while maintaining the minimum level of service access and efficiency.

01 10 10-9

CHAPTER 2.0 - DESIGN STANDARDS AND SUBMITTAL REQUIREMENTS

2.1 STANDARDS, DOCUMENTS AND CRITERIA

The design requirements listed herein represent the minimum quality and quantity acceptable for the proposals and projects submittals. The Contractor shall be responsible for obtaining the latest edition of any documents not attached as part of this RFP, but referenced as criteria for the project. Requirements of this section may delete, revise, add to, or substitute for criteria contained in the referenced documents and this RFP shall be deemed the controlling authority of any changes to the other referenced documents and criteria.

Reference documents can be obtained from Construction Criteria Base published by the National Institute of Building Sciences Whole Building Design Guide http://www.wbdg.org or http://www.usace.army.mil/publications.

Design standards, reference documents and criteria applicable to the design of this project are referenced in the individual sections within this Section 01 10 10 to which they pertain. The latest edition of the following design standards, reference documents and criteria apply to all portions of the work whether or not they are referenced in the individual subsections of this RFP. Guide Specifications shall be used to provide all details not stated in this RFP, but in no way shall it result in a lower standard than stated in this RFP.

2.1.1 TI-800-01 - Technical Instructions - Design Criteria, U.S. Army Corps of Engineers

2.1.2 TI-800-03 - Technical Instructions - Technical Requirements for Design-Build, U.S. Army Corps of Engineers.

2.1.3 SPKP-1110-1-1 - Manual of Standard Procedures, U. S. Army Corps of Engineers.

2.1.4 ETL 1110-3-491, Sustainable Design for Military Facilities.

2.1.5 International Building Code (IBC), 2006 Edition (except as modified by UFC 1-200-1 and 3-301- 01).

2.1.6 NFPA 101 - Life Safety Code.

2.1.7 UFC 3-600-01 Unified Facilities Criteria – Design: Fire Protection Engineering for Facilities.

2.1.8 OCCUPATIONAL SAFETY AND HEALTH ACT (OSHA):

2.1.8.1 29 CFR Occupational Safety and Health Standards Part 1910

2.1.8.2 29 CFR 1926 Safety and Health Regulations for Construction

2.9 NFPA 70 – National Electrical Code

2.10 IEEE C2 – National Electrical Safety Code

2.11 UFC 3-550-01 – Exterior Electrical Power Distribution

01 10 10-10

2.12 UFC 3-520-01 Interior Electrical Systems

2.13 UFC 3-501-01 Electrical Engineering

2.14 Technical Criteria for the Installation Information Infrastructure Architecture (I3A)-Feb 2010

2.15 UFC 3-530-01 Design: Interior and Exterior Lighting and Controls

2.16 Illuminating Engineering Society-North America (IESNA) Lighting Handbook, Reference and Application, 9th Edition

2.17 EM 385-1-1 Safety and Health Requirements

2.2 DESIGN STANDARDS

Equipment, hardware, and materials shall be standard manufactured items unless otherwise specified.

Replacement parts shall be standard products and readily available through commercial means.

Discontinued products will not be accepted.

2.3 CODES

The design, materials, equipment, and installation shall be in accordance with the requirements of the listed codes and design manuals, with the requirements of this section, and with the listed specifications.

The building construction classification shall be in accordance with the International Building Code

(IBC).

2.4 DESIGN IN ENGLISH SYSTEM

This project shall be designed in the English system.

2.5 DRAWINGS

Attached drawings provide information to be used in the design of the system. All of the drawings are available in electronic file format (“Read Only”). AutoCAD 2009 drawings (.dwg format) will be available to the successful Offeror, however existing as-built drawings of the Price Fitness Center are available as scanned PDF files only. At the conclusion of project, Contractor shall provide complete electronic copies in AutoCAD of their completed design to the USACE and POM.

2.5.1 FIELD INFORMATION

The information provided on the drawings and reference drawings is provided to assist the Contractor during the design of this project. The Contractor is responsible for field-verifying all information given as noted in Section 1.2 above. The Contractor is responsible for obtaining all information during design.

Requests for information shall be coordinated through the Contracting Officer. Any survey providing utility locations, verification of existing features, etc. shall be the Contractor’s responsibility and shall tie into the project datum.

2.5.2 DESIGN DETAILS AND STANDARDS

01 10 10-11

The Contractor shall provide a design and construction package, which uses the design details given or referenced in this RFP. Additional details shall be created by the Contractor as required, but shall conform to the requirements of this RFP and are subject to approval by the Government.

2.6 SPECIFICATIONS

A minimum listing of specification sections to be utilized in the preparation of the design and construction package is as follows: PV Module, PV Module Support System, Miscellaneous Cast-in- Place Concrete – UFGS 03 30 53, Metal Ladders – UFGS 05 51 33, Seismic Protection for Electrical Equipment – UFGS 26 05 48.00 10, Basic Electrical Materials & Methods – UFGS 26 00 00.00 20, Interior Distribution System – UFGS 26 20 00, Switchboards and Switchgear – UFGS 26 23 00, Electrical Distribution System-Underground – UFGS 33 70 02.00 10, Exterior Lighting – UFGS 26 56 00, Interior Lighting – 26 51 00, Building Telecommunication System – UFGS 27 10 00. Technical specifications shall follow UFGS MasterFormat 2004 numbering standard..

01 10 10-12

CHAPTER 3.0 - STRUCTURAL DESIGN

3.1 General: All structural design is the contractor’s responsibility within the parameters given in this Section. The criteria established herein shall be used for the determination of structural loads, the analysis, design and construction of all structural systems related to the installation of the photovoltaic array. The photovoltaic array shall be mounted to a non-roof penetrating support system. Ballast blocks shall be used if it is required by the selected photovoltaic array system. Computation of all loads shall be required for the design of not only the mounting system itself but also for all loads transmitted to the existing structure. Verification is required to ascertain that the new installation will not impact the structural integrity of the existing roof and confirming the capacity of the existing roof structure to carry the additional loads as well as the redistribution of loading. If necessary, supplemental roof supporting members shall be designed to support the additional load. Also, verification is required to ascertain that all installations will not impact the roof’s moisture barrier capability and the existing drainage system.

All calculations shall be checked and initialed by a registered professional engineer other than the original Engineer of Record (EOR). The EOR shall stamp the final structural calculations and final structural drawings.

3.2 Design Standards, Codes and Criteria: Verification of roof capacity, design and construction of all structural systems shall comply with the latest editions (as of the issue date of this RFP) of the following standards, codes, and criteria unless otherwise noted. Where the criteria conflict, the most stringent requirement(s) shall apply.

3.2.1 ACI 318/318R: Building Code Requirements for Structural Concrete and Commentary.

3.2.2 AISC 325-05: Steel Construction Manual.

3.2.3 ASIC 360-05: Specifications for Structural Steel Buildings.

3.2.4 ASCE 7-05: Minimum Design Loads for Buildings and Other Structures.

3.2.5 ASCE 37: Design Loads on Structures during Construction.

3.2.6 AWS D1.1/D1.1M: Structural Welding Code – Steel.

3.2.7 AWS D1.3/D1.3M: Structural Welding Code – Sheet Steel.

3.2.8 UFC 1-200-01: General Building Requirements, with Change 2.

3.2.9 UFC 3-301-01: Structural Engineering.

3.2.10 UFC 3-310-04: Seismic Design for Buildings.

3.2.11 International Building Code, 2006 Edition (except as modified by UFC 1-200-1 and 3-301-01).

3.3 Design Loads: Design Loads shall be included in the structural notes on the contract drawings.

3.3.1 Building Occupancy Category: The building is a physical fitness center and shall be considered as an Occupancy Category II.

01 10 10-13

3.3.2 Minimum Live Load Requirements: The live loads shall be the maximum loads expected but in no case less than the minimum uniformly distributed unit loads required by Table 4-1 “Minimum Uniformly Distributed Live Loads and Minimum Concentrated Live Loads” of ASCE 7-05 and Table D-1 “Minimum Uniformly Distributed Live Loads and Minimum Concentrated Live Loads” of UFC 3-301-

01. If there is a conflict between the tables, the higher load value shall apply. The weight of actual equipment shall be used when greater.

3.3.3 Wind Loads: Wind pressures shall be calculated in accordance with ASCE 7-05 and Table E-1 “Structural Climatic Loading Data – United States, its Territories and Possessions” of UFC 3-301-01.

Basic Wind Speed 85 mph Exposure Category C Wind Importance Factor IW 1.00

3.3.4 Snow Loads and Frost Penetration: Snow loads and frost penetration shall be calculated in accordance with ASCE 7-05 and Table E-1 of UFC 3-301-01.

Ground Snow Load 0 psf Frost Penetration 4 inches Snow Importance Factor IS 1.00

3.3.5 Seismic Loads: Seismic loads shall be computed in accordance with ASCE 7-05 and Table E-2 “Earthquake Loading Data – United States, its Territories and Possessions of UFC 3-301-01. Table E-2 provides the following Ss and S1 values (based on Site Class B).

Short Period Spectral Acceleration Ss = 1.51 One Second Period Spectral Acceleration S1 = 0.63 Seismic Importance Factor IE 1.00

3.4 Structural Components and Systems: All structural components and systems shall comply with the requirements of current applicable standards, codes and criteria as well as industry standards. The structural as-built drawings for the building are found in Appendix 8.

3.4.1 Existing Building Roof and Roof Framing System: The existing building roof consists of a built up roof over insulation and steel roof deck. The steel roof deck is 3” 18 gauge steel. The roof framing plan for Area “A”, the primary location (upper roof), is shown on S-7 and uses rigid frames, K braced frames, and W beams. The roof framing plan for Area “B”, the secondary location (lower roof), is shown on S-8 and uses W beams, girders, and columns. The existing roof and roof framing drawings are found in Attachment 8.

The loading from the selected photovoltaic array system on the existing roof and roof framing system shall be verified for sufficient capacity by reviewing as-built drawings for the building, inspecting current site existing conditions, and performing design calculations following the codes and criteria specified above. The Contractor is responsible for evaluating the structural capacity of the roof under the new loading conditions and the design of supplemental roof support if necessary.

01 10 10-14

3.4.2 Existing Building Foundation: The existing building foundation drawings are found on sheets S- 2, S-3, S-4 and S-5 and foundation details are on sheets S-11, S-12, and S-13 in Attachment 8.

01 10 10-15

CHAPTER 4.0 - ELECTRICAL DESIGN

4.1 SYSTEM DESCRIPTION

A. The photovoltaic roof assembly shall be installed to deliver solar electrical power to Price Fitness Center (Building 842), Presidio of Monterey, CA as described herein. The lightweight system shall function as a solar power plant providing electricity to the fitness center as demanded and when available power exceeds fitness center needs, the system shall feed power onto the electrical grid for credit against consumption. System shall be installed to allow proper run off and drainage and avoid snow and ice accumulations and provide shading value to the roof area. The system shall be utility grid connected.

System shall be as shown in Section 4.11 PV Array Summary.

B. The system shall be specifically designed for installation on top of roof membrane built up roofs, ballasted and most other fully adhered roofing technology used for flat or low slope (2:12 slope or less) roofs, parts having contact with the roof shall not have sharp edges. The installation shall have NO penetrations of the roof membrane specified under other section within the document. Conduits shall be PVC supported by Rubber Blocks using NO penetrations of the roof membrane. The system shall include the capability to provide stand-alone, emergency PV power in conjunction with an emergency generator as described in PV Array Summary Section 4.11 B. Inverters. This capability is for future use only as there is no emergency generator at present. However, system should be compatible with future addition of an emergency generator for connection to the existing double throw safety switch pictured in photos 16 and 17 below paragraph 1.1 of this Section 01 10 00.

C. The contractor shall coordinate with Pacific Gas and Electric Utility (PG&E) revenue meters in building to meet all requirements for interfacing with the PG&E power grid and to obtain maximum credit for power fed onto the grid. The contractor shall provide building input to Main Distribution Switchboard (MDS, see photos 16 and 17 below paragraph 1.1 of this Section 01 10 00) as required. See paragraph 4.12B for more information about metering requirements.

D. Grounding in accordance with NFPA 70-2008.

E. The system shall be designed to prevent bird nesting (via sound, structure such as bird spikes, and/or sensor).

4.2 SCOPE

The system shall consist of an array of photovoltaic modules, each mounted on suitable support brackets, wind deflectors to minimize need for supplementary ballast, electrical terminal and combiner boxes, quick-connect electrical PV connectors, DC wiring, DC disconnect, grid-connected inverter and isolation transformer, AC disconnect, and a web-based data acquisition and monitoring system (DAS). The exterior pad mounted inverter shall be wired to the building electrical system in the Main Distribution Switchboard (MDS), rated at 800 Amps, 277/480 Volts, Three Phase.

A. Work shall include furnishing all labor, materials, and equipment necessary to complete installation of the system. Electrical and communications work shall comply with codes and criteria listed in paragraphs

2.9 through 2.16 of this section.

01 10 10-16

B. The array shall be installed on various roof areas as indicated and be suitably sized for the array output required. The system’s photovoltaic array shall provide a CEC rated 378 kW electrical power to feed the Price Fitness Center (Building 842) and back onto the utility grid.

4.3 WARRANTIES

A. The installer shall warrant the system in its entirety for a period of five years.

B. The photovoltaic panels shall be covered by the PV manufacturer’s limited warranty for a minimum of 25 years, and shall be passed through the PV array installer to the using agency.

C. The inverter shall be warranted by the manufacturer for a period of at least ten years.

4.4 QUALITY ASSURANCE

The PV Module assemblies and inverters shall be certified by Underwriters Laboratories.

4.5 DELIVERY, STORAGE AND HANDLING

A. Care shall be taken to protect the PV modules during delivery, storage, and installation.

B. Appropriate protective clothing shall be worn when handling the product. Such clothing shall include hard hats and steel-toe boots when lifting materials to structure also insulated gloves when working on an active system. Reference EM 385-1-1, Safety and Health Requirements, for complete coverage of safety and health requirements.

PRODUCT

4.6 CONTRACTOR REQUIREMENTS

A. The Contractor shall be required to provide documentation in their bid to demonstrate successful installation of a minimum of three systems similar in size and scope to the PV system of this project with aggregate capacity of at least 500 kilowatts. Bidders shall provide documentation of no more than five such systems. In addition, bidders shall submit firm references and experience as well as experience of staff members working on project.

B. The Contractor must be certified by the manufacturer of the system to install its product, and must be able to demonstrate successful experience as designer of record (architect or engineer) of system similar in size and scope to the PV system of this project, with aggregate capacity of at least 500 kilowatts.

C. The Contractor shall provide all necessary equipment and materials for a complete photovoltaic power system; shall provide turnkey installation of the photovoltaic system so as to make it operational and compliant with all applicable codes and standards and California Solar Initiative requirements; shall provide design services, including a complete permit set of drawings sealed by a California licensed professional engineer.

4.7 MANUFACTURED UNITS

PV modules shall have the following properties:

01 10 10-17

Attributes: Value: Test:

Wind Pressure Based On: 85 mph wind speed ASCE 7-05 Adhesive Testing Exceeds required bond strength UL 1703 Impact Resistance Safely withstands 2” diameter steel UL 1703 sphere dropped 51” Mechanical Loading 45 lb/ft, 30 minutes UL 1703 Humidity -40 C to 85 C, 85% RH 10 cycles UL 1703

4.8 ARRAY MOUNTING AND ORIENTATION

For flat roof area with tilt up installation, each framed module shall be mounted on an integrated system of support brackets that incline the modules at an angle above horizontal that is optimum for year round operations at the site location. The orientation of the modules shall be chosen by the Design/Build contractor, with the understanding that an orientation approximately toward the south direction is typically most efficient for most installations. Sheet No. C-101 shows that the building roof areas are not perpendicular or parallel to north-south orientation, so that may impact the orientation chosen for the modules. The mounting system shall utilize integrated wind deflectors to minimize the need for supplementary ballast and maintain structural loading at less than the loading requirements as specified under structural requirements and to be averaged over the area of the structure covered by the array. The mounting system shall have no sharp edges contained in the assembly, with No roof penetrations of the membrane. At the Design/Build contractor’s option, single-axis tracking or dual-axis tracking systems may be employed for the modules in order to enhance the energy production from the modules.

However, these approaches shall not be required as it adds complexity and cost to PV system per module, may not produce enough additional energy vs. a fixed angle installation to be economically justified, and may require additional roof area for the system and additional spacing between modules.

4.9 WIND LOADING

A. The system shall minimize wind loading by utilizing integrated wind deflectors.

B. The system design shall meet requirements of the system manufacturer for ability to meet the specified local standards for wind design speeds for the particular application.

4.10 SYSTEM ELECTRICAL

A. The modules shall be electrically connected by “quick connect” electrical connectors, which shall be UL listed for service in high-voltage photovoltaic systems to create electrical series-circuits (strings) according to the system specifications. The system shall have terminal boxes to provide the electrical circuit strings a secure entry to the conduit leading to the combiner boxes.

B. The system shall have combiner boxes, containing fuses and a bus to combine the outputs of the strings. A set of wires shall run from the combiner box to the inverter.

C. The system shall have an inverter as specified in the project documents.

D. An isolation transformer shall be part of the system for interfacing to the building’s electrical system.

01 10 10-18

E. Each system shall have A/C wiring running from the output of the inverter to a disconnect, then to an isolation transformer, then to building electrical service.

F. Grounding per NFPA 70 and US Army Corps of Engineers UFC 3-501-01.

H. All major components of the systems and the installation procedures shall meet the requirements of IEEE, National Electrical Safety Code (ANSI C2), NFPA 70 National Electrical Code, UL standards 1547 & 1741, IEEE Standard 929-2000 and all other applicable national, state, and local codes and standards.

I. System shall be designed to maximize annual energy production based on the stated system kW requirement and to maximize incentive payment for the system based on California Solar Initiative guidance for systems receiving power from investor-owned utilities in California (PG&E serves Presidio of Monterey and so this project qualifies for an incentive payment under that program). Design/Build Contractor shall be responsible for correctly filling out all paperwork and meeting all requirements for the system to qualify for the maximum incentive payment available for the design and orientation of the system. Incentive payment shall be made to the government and shall not be made to the Design/Build contractor.

4.11 PV ARRAY SUMMARY

A. PV Module Characteristics

PV modules shall be commercial off-the-shelf product, shall be UL listed, and shall be on the California Senate Bill 1 (SB1) compliant module list to be eligible for incentive in California (http://www.gosolarcalifornia.org/equipment/pv_modules.php). The Design/Build contractor may choose among the various type of PV modules in common use that will provide an efficient and economical installation and maximize power production at the POM. PV module types may incorporate polycrystalline silicon, monocrystalline silicon, amorphous silicon, cadmium telluride, polymeric, and copper indium gallium selenide solar cells. Ratings of PV modules shall be based on PTC (PVUSA Test Conditions of Photovoltaics for Utility Scale Applications Test Conditions) rather than the STC (Standard Test Conditions) that PV module manufacturers typically rate their modules with (see bottom of web page in URL link given above for a more detailed explanation of these rating considerations). PV module shall have durable tempered glass, EVA lamination and weatherproof back skin for long life protection.

Module shall have surface texturing to increase light absorption and improve efficiency.

Values for the following attributes shall be determined under PVUSA Test Conditions (PTC): Irradiance = 1,000 w/m, air temperature = 20 degrees C, wind speed of 1 meter per second at 10 meters above ground level and shall be submitted with bid.

B. Inverters

Inverters shall be commercial off-the-shelf product and shall be on the California Senate Bill 1 (SB1) compliant module list to be eligible for incentive in California (http://www.gosolarcalifornia.org/equipment/inverters.php).

01 10 10-19

Inverter to Utility Interface shall be 480V 3-Phase, 60 Hz. Inverters shall be listed by a recognized testing laboratory to Standard UL 1547 & 1741, and shall conform to all other application codes and standards.

Inverters shall be designed to be capable of stand-alone islanding type operation in conjunction with an emergency generator. Price Fitness Center does not currently have an emergency generator in place, but the double throw safety switch shown in photos 16 and 17 under paragraph 1.1 of Section 01 10 00 of this RFP allows for future connection of an emergency generator. The inverters shall be specifically designed to be capable of incorporating this mode of operation, and evidence of experience in this mode of operation shall be included with the inverters. The contractor shall provide DANGER WARNING LABELS for the future generator and at the building service and transformer to indicate the solar array is capable to back feed service, disconnect may be required for safety while performing maintenance.

4.12 OTHER REQUIREMENTS:

A. The contractor shall submit the following and other requirements indicated elsewhere in this document for review and approval; System design calculations for array and inverter sizing, CEC rated power production, all conductor and conduit sizing, voltage drop calculations, efficiencies, Array voltage & current sizing calculations, DC voltage drop, testing procedures, and manufacturer’s data and information for all equipment used on project. The following drawings shall be provided but not limited to: 1. Title sheet with index of drawings; Symbols and Abbreviations; Notes and Specifications; Staging and Access;

Electrical One Line Diagram and Tie in Locations; On Line Inverter system Diagram; Electrical Site Plan; Array Layout and total CEC power rating; Array Wiring Plan; Electrical layout, Equipment Elevations and pad details; General Array Arrangement and alignment details; System Structural and Civil drawings as specified elsewhere in this document with equipment shop drawings and manufacturer’s data. All the above shall be subject to government review and approval prior to implementation.

B. System shall be designed to comply with all performance based metering requirements and all eligible rebate/incentive program requirements for solar photovoltaic systems of this size and type to include Federal, State, PG&E Rebate through California Solar Initiative program (to include system capacity and performance based parts), and Green Tag program. Metering shall be on the California Senate Bill 1 (SB1) compliant List of Eligible System Performance Meters to be eligible for incentive in California (http://www.gosolarcalifornia.org/equipment/system_perf.php). Metering shall also comply with PG&E Net Zero Metering requirements as described at http://www.pge.com/mybusiness/energysavingsrebates/solar/install/netenergymetering/index.shtml.

Prepare and submit paperwork for eligible/rebate programs to the respective programs. Eligible rebates/incentives shall accrue to the government and not the contractor.

C. System shall be coordinated with California Solar Initiative (CSI) rebate/incentive requirements for customers in investor-owned utility (IOU) territories of PG&E since the Presidio of Monterey is served by that IOU. See http://www.pge.com/mybusiness/energysavingsrebates/solar/csi/howitworks/ for descriptions/links to various aspects of the California Solar Initiative and California Solar Initiative Handbook at http://www.gosolarcalifornia.ca.gov/documents/CSI_HANDBOOK.PDF for complete program guidelines and general reference for all CSI program questions.

01 10 10-20

D. System shall be designed to comply with requirements of all other eligible programs such as Renewable Energy Certificate (RECs), Green Tags, Renewable Energy Credits, and Tradable Renewable certificates (TRCs). These are interchangeable names for tradable, non-tangible energy commodities in the United States that represent proof that 1 megawatt-hour (MWh) of electricity was generated from an eligible renewable energy resource. Certification shall be accomplished through Green-e (http://www.green-e.org/getcert_re.shtml) and overseen through the Western Renewable Energy Generation Information System (http://www.wregis.org/).

E. Contractor’s proposal shall provide an estimate of electrical energy (in kilowatt-hours (kWh)) that the system shall produce over the course of a year based on the orientation, tilt angle, location, rating, efficiency, etc. of the photovoltaic modules and associated electrical equipment such as the inverter and transformer.

SYSTEM MONITORING AND TESTING

4.13 MONITORING

A. A Data Acquisition System (DAS) shall be installed as part of the system. The DAS shall allow measurement in English and metric units of:

• Ambient Temperature: (C degrees/ F degrees)

• Wind speed: (M/S, Miles/Hr)

• Solar irradiation: (W/m2) -Percent Efficiency - Logged every 15 Min

• System power: Output: AC (KW), DC Voltage (V), DC Amps (A) - Logged every 15 Min.

• Remote Access Capabilities via Internet Web Site and dial up.

• System Optimization and Improvement

Sensor Specifications & Accuracies:

Irradiance: 5% max 3% in natural day light Temperature: (C degrees/F degrees) +/- 1.0 C/F degrees Wind Speed within 0.1 m/s for range 5 m/s to 25 m/s

Data Processing Software:

System data shall be viewable on the web enabled data monitoring system and be able to be connected to a LAN.

The DAS shall include a data logger, network interface for data retrieval. NEMA 4 enclosure, dry bulb measuring device, anemometer, solar sensor and radiation shield, inverter performance. Monitoring system shall use the LonWorks protocol and shall be able to communicate with Garrison’s Utility Monitoring and Control System (UMCS) system.

Building Kiosk: Building shall be provided with a touch screen monitoring and display kiosk. The kiosk shall provide real time information showing exactly the power produced by the solar array (kW, kWH) for hourly, daily, weekly, monthly, yearly and over the system life time in tabular and graphic form. The system shall provide educational information about solar power energy and its benefits, the reduction of green house gases, reduction of fossil fuels, reduction of CO2 emissions and imported oils. The kiosk

01 10 10-21 shall be located by a LAN outlet in the Fitness Center lobby. The system data shall be stored and archived in a database. Provide a computer server, monitor, keyboard, and mouse at an available location within the Fitness Center to be determined that is in close proximity to the system electrical equipment, associated system controls, as well as a LAN outlet. Database shall reside on this server. Provide interconnection from the server to system controls for real-time and historical information regarding system parameters as well as connection to a LAN outlet to allow for external web access to the information. The format and display shall be submitted to the government for review and approval prior to implementation. Kiosk information shall be available via a created internet web site.

Web Access/Control:

Provide web access/control of the photovoltaic system to match that of the Sea Girt National Guard Training Center, New Jersey. See http://www.sunviewer.net/portals/SeaGirt/ web site for the information that shall be provided (to include system snapshot updated every 15 minutes, system performance and weather information parameters at current time and selectable by date/month/year, system information, and educationally related information and lessons. Submit sample data of web access/control system to government for review and approval prior to implementation. Provide web access/control capability within the server mentioned in previous subparagraph.

4.14 TESTING AND TRAINING:

A. Photovoltaic modules shall be tested in factory for design performance. All test results shall be furnished to Contracting Officer prior to system installation.

B. Inverter shall be factory tested for performance and results shall be included in the O&M manual. All test results shall be furnished to Contracting Officer prior to system installation.

C. System testing of installed photovoltaic array shall be performed on all system strings and recorded in the O&M manual. Submit test plan of installed photovoltaic system for review and approval prior to testing.

D. System start-up procedure shall be as outlined the PV system manufacturer’s Installation Manual and the Inverter Manual.

E. Contractor shall provide training of government personnel on the operation and maintenance of the photovoltaic system to include the monitoring and web access/controls as well.

INSTALLATION

4.15 INSTALLATION PLAN

A. The Roof installation shall be inspected for compliance with the manufacturer’s requirements. Minor repairs or service, if any, will be completed prior to installation.

B. An acceptance test and commissioning procedure shall be performed according to the manufacturer’s recommendations. The commissioning procedure shall include visual inspection of the array and of all system wiring and connections, and testing of each photovoltaic string for open circuit voltage, operating amperage, and isolation (megohm test).

C. All construction waste materials shall be removed from the site.

4.16 INSTALLATION STANDARDS

01 10 10-22

A. System installation shall conform to the manufacturer’s installation procedures and to the approved project drawings and specifications.

B. System installation shall conform to all applicable local, state, and National codes.

C. System installation shall conform to UL1547 & 1741 and other applicable UL standards for photovoltaic systems.

4.17 600-800 SERIES BUILDINGS EXTERIOR LIGHTING BOLLARD RETROFITS

There are 243 each existing exterior lighting bollards in the 600 to 800 series of buildings on the installation are 70 watt high pressure sodium. Retrofit these lighting bollards to change fixtures to 23 watt induction type fixtures using external inductor magnetic induction lamps. Lighting fixtures shall be UL listed. Replace 70 watt high pressure sodium lamp and ballast with 23 watt induction lamp and driver, replace existing reflector with new reflector sized and shaped to accommodate induction lamp size and orientation within the existing bollard opening, and redo associated wiring and mounting as required to complete retrofit of these fixtures. The City of Monterey has already had this retrofit performed on one of the existing lighting bollards and can identify its location and show the completed fixture retrofit to the Design/Build Contractor. Contact Don Neal with the City of Monterey at (831)760-2221 for the information on the identification number and location of this fixture. See Attachment 9 for PDF file of the Presidio of Monterey installation map with hand-written exterior lighting bollard locations and identification numbers. Also see following photos showing existing and retrofitted bollards.

01 10 10-23

Photo of typical existing 70 watt high pressure sodium (HPS) exterior lighting bollard

01 10 10-24

Photo of typical existing 70 watt HPS exterior lighting bollard w/refractor removed and lamp on

01 10 10-25

Photo of interior of exterior lighting bollard that has been retrofitted as an induction lighting fixture, refractor removed and reflector and lamp rotated below bollard opening

01 10 10-26

Photo of interior of exterior lighting bollard that has been retrofitted as an induction lighting fixture, refractor removed and retrofitted reflector and lamp in place within bollard opening

4.18 WAREHOUSE BUILDING 235 LIGHTING RETROFITS

There…