Draft - Technical Specs - Bettis 100 QC Specs.pdf
PDF 5 MB Posted
- Solicitation number
- W911WN27R0005
About this file
This is a Technical Specifications document for the AT Courtyard Construction & Site Utility Infrastructure project at Bettis Laboratory in West Mifflin, Pennsylvania, prepared for Fluor Marine Propulsion, LLC by Michael Baker International. The specifications are organized into division sections covering selective demolition, cast-in-place concrete, unit masonry, site clearing, earth moving, dewatering, concrete paving, and concrete paving joint sealants.
The selective demolition section requires removal of selected site elements with compliance to USACE hauling and disposal regulations and specifications for handling utilities, mechanical systems, and hazardous materials encountered during work. Cast-in-place concrete specifications mandate Portland cement Type I concrete with minimum 28-day compressive strength of 4,000 psi for wall footings and thrust blocking, 5,000 psi for pipe bollards, and 3,000 psi for miscellaneous non-structural concrete; concrete mixes must utilize ground granulated blast furnace slag or fly ash as cement substitute or additive with specific air entrainment and testing requirements per ASTM standards. Unit masonry specifications require concrete masonry units per ASTM C90, brick with minimum 2,200 psi compressive strength and no efflorescence per ASTM C67/C67M testing, and precast concrete caps for retaining walls; mortar must comply with ASTM C270 (Type M for below-grade, Type S for reinforced, Type N for above-grade applications) with grout minimum 2,000 psi compressive strength per ASTM C476. Earth moving and site clearing sections specify excavation to indicated elevations with rock excavation subject to unit pricing, backfill placement in layers not exceeding 6 inches with compaction to 95 percent maximum dry unit weight per ASTM D1557, dewatering system design and operation to maintain dry stable subgrades, and topsoil handling with 3.5 percent minimum organic material content. Concrete paving specifications require 4,000 psi minimum compressive strength concrete with air entrainment of 5-7 percent for deicing exposure, reinforcement per ASTM A615 Grade 60, and finishing with medium-to-fine-textured broom finish per ACI 301; concrete paving joint sealants must comply with ASTM C920 and include multi-component urethane, silicone, and bitumen-modified formulations with jet-fuel resistance where applicable. All work requires USACE inspection and testing verification, field quality control by independent testing agencies, and compliance with Pennsylvania Department of Transportation Publication 408, ACI standards, and CRSI manual requirements.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| UAA Information Form (1).pdf | ||
| Draft - Division 1 - Bettis 100 QC Specs.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AT COURTYARD
BETTIS LABORATORY, WEST MIFFLIN, PENNSYLVANIA
TOA-106
PO# 7019401
SPECIFICATIONS
Final Design SUBMISSION
September 3, 2026
Prepared for:
Fluor Marine Propulsion, LLC Bettis Laboratory PO Box 79 West Mifflin, Pennsylvania 15122-0079
Prepared by:
Michael Baker International 100 Airside Drive Moon Township, PA 15108
DRAFT
AT Courtyard Specifications Bettis Laboratory West Mifflin, PA Final Design Submission
TOA-106 PO 7019401 TABLE OF CONTENTS
TOC-1
TABLE OF CONTENTS
SPECIFICATION NUMBER SPECIFICATION TITLE
024119 SELECTIVE DEMOLITION
033000 CAST-IN-PLACE CONCRETE
042000 UNIT MASONRY
311000 SITE CLEARING
312000 EARTH MOVING
312319 DEWATERING
321313 CONCRETE PAVING
321373 CONCRETE PAVING JOINT SEALANTS
321501 DECOMPOSED GRANITE WITH STABILIZER
323300 SITE FURNISHINGS
329115 SOIL PREPARATION (PERFORMANCE SPECIFICATION)
329120 SOIL PREPARATION FOR CONTAINERS
329300 PLANTS
330513 SANITARY SEWERS
330700 UTILITY LINE REMOVAL
331116 SITE CITY WATER UTILITY DISTRIBUTION PIPING
334100 STORM UTILITY DRAINAGE PIPING
335111 SITE NATURAL-GAS DISTRIBUTION
NAVAL NUCLEAR LABORATORY
TASK ORDER #106 – AT COURTYARD
SELECTIVE DEMOLITION 024119 - 1
SECTION 024119 – SELECTIVE DEMOLITION
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes the following:
1. Demolition and removal of selected site elements.
1.2 RELATED DOCUMENTS
A. Contract Drawings and general provisions of the Contract, including General Condi-tions and Division 1 Specification Sections, apply to this Section.
1.3 SUBMITTALS
A. None required.
1.4 DEFINITIONS
A. Remove: Remove and dispose of items except those indicated to remain FMP/USACE property.
B. Remove and Reinstall: Remove items indicated; clean, service, and otherwise prepare them for reuse; store and protect against damage. Reinstall items in the same loca-tions or in locations indicated.
1.5 MATERIALS OWNERSHIP
A. Except for items or materials indicated to be reused and reinstalled, or otherwise indi-cated to remain FMP/USACE property, demolished materials shall be removed from the site and dispose of in accordance with the Special Conditions.
1.6 QUALITY ASSURANCE
A. Demolition Firm Qualifications: Shall be an experienced firm that has successfully completed selective demolition work similar to that indicated for this Project.
B. Regulatory Requirements: Comply with USACE hauling and disposal regulations.
SELECTIVE DEMOLITION 024119 - 2
1.7 PROJECT CONDITIONS
A. USACE and others will occupy portions of site adjacent to selective demolition area.
Conduct selective demolition so operations will not be disrupted.
B. Notify USACE of discrepancies between existing conditions and Contract Drawings be-fore proceeding with selective demolition.
C. Hazardous Materials: It is not expected that hazardous materials will be encountered in the majority of the Work.
1. If materials suspected of containing hazardous materials are encountered, do not disturb; immediately notify USACE. USACE will remove hazardous materials under a separate contract.
2. See General Conditions Addendum and Appendix A of the General Conditions for the procedure and coordination for any potential work near suspect soils.
PART 2 - PRODUCTS (Not Used)
PART 3 - EXECUTION
3.1 EXAMINATION
A. Verify that utilities have been disconnected and capped.
B. Survey existing conditions and correlate with requirements indicated to determine ex-tent of selective demolition required.
C. When unanticipated mechanical, electrical, or structural elements that conflict with in-tended function or design are encountered, investigate and measure the nature and extent of conflict.
3.2 UTILITY SERVICES AND MECHANICAL/ELECTRICAL SYSTEMS
A. Existing Services/Systems: Maintain services/systems indicated to remain and protect them against damage during selective demolition operations.
B. Service/System Requirements: Locate, identify, disconnect, and seal or cap off indi-cated utility services and mechanical/electrical systems serving areas to be selectively demolished.
1. USACE will arrange to shut off indicated utilities when requested by the Seller.
2. If services/systems are required to be removed, relocated, or abandoned, before proceeding with selective demolition provide temporary services/systems that bypass area of selective demolition and that maintain continuity of ser-vices/systems to other parts of building.
3. Cut off pipe or conduit in walls or partitions to be removed. Cap or plug and seal remaining portion of pipe or conduit after bypassing.
SELECTIVE DEMOLITION 024119 - 3
C. Where sections of underground utilities are being abandoned in place:
1. Fill open ends with concrete a minimum of 36 inches deep.
2. Provide survey locations of ends of pipe as part of record documents.
3.3 PREPARATION
A. Site Access and Temporary Controls: Conduct selective demolition and debris-removal operations to ensure minimum interference with roads, streets, walks, walk-ways, and other adjacent occupied and used facilities.
B. Temporary Facilities: Provide temporary barricades and other protection required to prevent injury to people and damage to adjacent buildings and facilities to remain.
C. Temporary Shoring: Provide and maintain shoring, bracing, and structural supports as required to preserve stability and prevent movement, settlement, or collapse of con-struction and finishes to remain, and to prevent unexpected or uncontrolled movement or collapse of construction being demolished.
3.4 SELECTIVE DEMOLITION
A. General: Demolish and remove existing construction only to the extent required by new construction and as indicated. Use methods required to complete the Work within limitations of governing regulations and as follows:
1. Neatly cut openings and holes plumb, square, and true to dimensions required.
Use cutting methods least likely to damage construction to remain or adjoining construction. Use hand tools or small power tools designed for sawing or grind-ing, not hammering and chopping, to minimize disturbance of adjacent surfaces.
Temporarily cover openings to remain.
2. Cut or drill from the exposed or finished side into concealed surfaces to avoid marring existing finished surfaces.
3. Do not use cutting torches until work area is cleared of flammable materials. At concealed spaces, such as duct and pipe interiors, verify condition and contents of hidden space before starting flame-cutting operations. Maintain fire watch and portable fire-suppression devices during flame-cutting operations.
4. Locate selective demolition equipment and remove debris and materials so as not to impose excessive loads on supporting walls, floors, or framing.
5. Dispose of demolished items and materials promptly.
B. Existing Items to Remain: Protect construction indicated to remain against damage and soiling during selective demolition. When permitted by USACE, items may be re-moved to a suitable, protected storage location during selective demolition and rein-stalled in their original locations after selective demolition operations are complete.
3.5 DISPOSAL OF DEMOLISHED MATERIALS
A. General: Remove demolished materials from Project site.
3.6 CLEANING
SELECTIVE DEMOLITION 024119 - 4
A. Clean adjacent structures and improvements of dust, dirt, and debris caused by selec-tive demolition operations. Return adjacent areas to condition existing before selective demolition operations began.
END OF SECTION 024119
CAST-IN-PLACE CONCRETE 033000 - 1
SECTION 033000 – CAST-IN-PLACE CONCRETE
PART 1 - GENERAL
1.1 SUMMARY
A. This Section includes:
1. The requirements for providing, forming, testing, placing, finishing and curing cast-in-place concrete including but not limited to concrete wall footings, concrete bollard footings, concrete thrust blocking, and concrete encasement.
2. Grout.
3. Concrete accessories.
4. Miscellaneous concrete.
1.2 RELATED DOCUMENTS
A. Contract Drawings and general provisions of the Contract, including General Conditions and Division 1 Specification Sections, apply to this Section.
1.3 SUBMITTALS
A. The Seller shall submit the following:
1. Shop Drawings:
a. Formwork.
b. Reinforcing Steel.
2. Product Data:
a. Welded Wire Fabric.
b. Cement.
c. Concrete.
d. Grout.
e. Concrete Curing.
f. Joint Fillers.
g. Joint Sealants.
h. Bonding Agent.
3. Design Data:
a. Concrete Mix for each type of Concrete.
4. Test Reports:
a. Concrete Compressive Strength Tests.
b. Aggregates.
c. Air Content.
d. Slump Tests.
DRAFT
H4ECDDCB
Highlight
1.3 SUBMITTALS
CAST-IN-PLACE CONCRETE 033000 - 2
5. Delivery slips for each truckload delivered.
1.4 QUALITY ASSURANCE
A. Comply with the following unless modified by requirements in the Contract Documents:
1. Pennsylvania Department of Transportation Publication 408
2. U.S. Department of Commerce Product Standard (PS) Publications.
3. American Society for Testing and Materials Standards.
4. ACI 117, “Specification for Tolerances for Concrete Construction and Materials.”
5. CRSI “Manual for Standard Practice.”
6. Corps of Engineers Specification CRD – C621 (588) Specification for Nonshrink
Grout.
B. Sampling
1. The seller shall sample materials at the construction site.
PART 2 - PRODUCTS
2.1 FORMWORK
A. Form material shall be as follows:
1. Metal forms shall be clean, free from rust, and free from dents.
2. Plywood shall comply with United States Product Standard PS-1 for Plyform
Class 1, Structural 1, Exterior Grade B-B or better.
3. Chamfer Strips: Wood, metal, PVC, or rubber; ¾-inch x ¾-inch.
B. Form coating compounds shall be of a commercial formulation that shall not bond with, stain or adversely affect the concrete surface. Confirm that any form coatings to be used are compatible with any concrete finish to be applied.
C. “Snap-tie” type form ties shall not leave an open hole through the concrete and shall permit permanent patching at every hole.
2.2 REINFORCING BARS
A. ASTM A615/A615M, Grade 60 or ASTM A996/A996M, Grade 60.
B. Reinforcement supports must conform to CRSI RB4.1. Submit description of reinforcement supports and materials for fastening coated reinforcement if not in conformance with CRSI RB4.1
2.3 WELDED WIRE FABRIC
A. Welded wire fabric shall conform to ASTM A185 flat sheets.
B. Tie wire shall be 16 gauge, soft annealed black steel.
C. Supports for welded wire fabric shall conform to CRSI Class 3.
DRAFT
H4ECDDCB
1.4 QUALITY ASSURANCE
CAST-IN-PLACE CONCRETE 033000 - 3
2.4 CONCRETE
A. Cement shall conform to:
1. Concrete: Portland cement ASTM C150 Type I.
B. Concrete aggregates shall conform to ASTM C33.
1. The coarse aggregate shall pass a 1 ½ -inch sieve and will be retained on a Number 4 sieve.
2. The fine aggregate shall be of a size that will pass a 3/8-inch sieve and will be retained on a Number 200 sieve.
C. Concrete shall conform to:
1. Concrete:
a. ASTM C94 for Ready Mix Concrete
b. Concrete for concrete wall footings and thrust blocking shall have a minimum 28-day compressive strength of 4000 psi. The slump shall be 4 inches (+0”, -2”).
c. Concrete for pipe bollards shall have a minimum 28-day compressive strength of 5000 psi.
d. Miscellaneous non-structural concrete including concrete encasement shall have a minimum 28-day compressive strength of 3000 psi.
D. Concrete Mix: Shall utilize ground granulated blast furnace slag or fly ash either as a cement substitute or as a concrete additive.
1. Fly Ash
a. The use of fly ash as a raw material in the production of Portland cement shall conform to ASTM Specification C150.
b. Fly ash as an admixture in concrete shall be Class C or Class F conforming to ASTM Specification C618 and shall be added at the rate of 10-30% by weight.
c. The amount of air-entrainment admixture shall be increased as necessary to obtain the same air content as that specified.
d. Exceptions to the use of fly ash are as follows and require written USACE consent:
1) Concrete to be poured in cold weather (i.e. ACI 306, Recommended Practices for Cold Weather Concreting).
2) Concrete to be placed under load prior to obtaining results of compression testing (i.e. seven days after placement).
3) Concrete containing Class F fly ash for exposed floor slabs or sidewalks. (Note: Poor finishing characteristics)
4) Other exceptions submitted by Seller.
2. Ground granulated blast furnace slag for use in concrete shall conform to the requirements of ASTM C989 and shall be Grade 100.
CAST-IN-PLACE CONCRETE 033000 - 4
a. Standard concrete for interior applications shall contain 50 percent, by weight of total cementitious materials, ground granulated blast furnace slag, and 50 percent Portland cement.
b. Standard concrete for exterior applications shall contain either 100 percent Portland cement for the cementitious materials or up to a maximum of 25 percent ground blast furnace slag and 75 percent Portland cement. All other requirements remain as specified.
E. Admixtures shall be compatible with other materials to be used and shall meet the following:
1. Air-entraining agent shall conform to ASTM C260. Air entrainment shall be between 5 and 7 percent in concrete exposed to freezing and thawing.
2. Chemical admixtures shall conform to ASTM C494, and must be agreed upon by USACE prior to their inclusion into any concrete. Calcium chloride shall not be used in any form.
3. Water reducers may be used for pumped concrete, in high temperatures, in low humidity, or as needed for placement and workability.
4. Other additives may be used if agreed upon by USACE.
5. Air-entraining agent shall not be used in concrete for interior floor slabs.
F. Bag mixes shall meet the requirements of ASTM C387, normal weight concrete.
2.5 GROUT
A. Cement-based grout shall have a minimum 28-day compressive strength of 5,000 psi and be non-shrink, non-metallic.
B. Materials shall be pre-measured and prepackaged, requiring only the addition of water, with manufacturer’s instructions printed on the outside of each container.
C. Cement based grout shall exhibit not shrinkage and a maximum of 0.2% expansion in the hardened state when tested in accordance with CRD-C621.
D. Cement based grout shall have an initial set time of a minimum of 1 hour.
2.6 CONCRETE CURING
A. Impervious Sheeting: Waterproof paper, polyethylene sheeting, or polyethylene coated burlap conforming to ASTM C171.
B. Liquid Membrane-Forming Compound: ASTM C309, white-pigmented, Type 2, free from paraffin or petroleum.
C. Liquid Chemical Compound: A suitable sealer-hardener designed for sealing and hardening in addition to curing of the concrete, applied by the method and at the rate recommended by the manufacturer. It shall not reduce the adhesion of tile, paint, roofing, waterproofing, or other material to be applied to the concrete. The chemical compound shall be free of petroleum resins or waxes.
CAST-IN-PLACE CONCRETE 033000 - 5
2.7 ACCESSORIES
A. Expansion Joint
1. ½-inch thick, closed cell structure plastic strip manufactured specifically for this purpose.
2. Other as identified on the Contract Drawings.
B. Joint Sealing Materials: ASTM D6690.
C. Preformed Joint Filler: ASTM D1751.
2.8 BONDING AGENT
A. Epoxy bonding agent shall be a 2-part, high modulus, moisture insensitive, polysulfide free, rigid epoxy containing 100 percent solids, and shall conform to ASTM C881, Type 2, Grade 2, Class B; ASTM C882; ASTM C883; ASTM D638 and ASTM D695.
2.9 PRODUCT HANDLING AND STORAGE
A. Cementitious materials shall be stored in a dry place and kept free from dirt and debris.
B. Packaged materials shall be stored in their original unbroken package or container.
C. Welded wire fabric shall be kept free of loose scale and rust.
PART 3 - EXECUTION
3.1 FORMWORK
A. Forms shall be constructed to conform to the required shapes, dimensions, lines, elevations and positions and shall be maintained sufficiently rigid to prevent deformation under load. Form surfaces shall be cleaned for each use.
B. Chamfer exposed joints, edges, and external corners of concrete ¾-inch x 45 degrees.
C. After removing forms, formed surfaces shall be filled and rubbed to correct honeycombing and blemishes. Finish shall be a smooth formed finish per ACI 301.
3.2 PLACING REINFORCEMENT
A. Place reinforcement in accordance with ACI 301.
B. Secure reinforcement, joint materials, and other embedded materials in position, inspected, and approved before start of concrete placing.
1. Shop fabricate reinforcing bars to conform to shapes and dimensions indicated for reinforcement, and as follows:
a. Provide fabrication tolerances that are in accordance with ACI 117.
CAST-IN-PLACE CONCRETE 033000 - 6
b. Provide hooks and bends that are in accordance with the Contract Documents.
C. Reinforcement must be bent cold to shapes as indicated. Bending must be done in the shop. Rebending of a reinforcing bar that has been bent incorrectly is not be permitted. Bending must be in accordance with standard approved practice and by approved machine methods.
D. Deliver reinforcing bars bundled, tagged, and marked. Tags must be metal with bar size, length, mark, and other information pressed in by machine. Marks must correspond with those used on the placing drawings.
E. Provide reinforcement that is supported and secured together to prevent displacement by construction loads or by placing of wet concrete, and as follows:
1. Provide supports for reinforcing bars that are sufficient in number and have sufficient strength to carry the reinforcement they support, and in accordance with ACI 301. Do not use supports to support runways for concrete conveying equipment and similar construction loads.
2. Equip supports on ground and similar surfaces with sand-plates.
3. Secure reinforcements to supports by means of tie wire.
4. Reinforcement must be accurately placed, securely tied at intersections, and held in position during placing of concrete by spacers, chairs, or other approved supports. Point wire-tie ends away from the form.
5. Bending of reinforcing bars partially embedded in concrete is permitted only as specified in the Contract Documents.
F. When concrete is placed, reinforcement must be free of materials deleterious to bond.
Reinforcement with rust, mill scale, or a combination of both will be considered satisfactory, provided minimum nominal dimensions, nominal weight, and minimum average height of deformations of a hand-wire-brushed test specimen are not less than applicable ASTM specification requirements.
G. Rinse placed reinforcing bars with fresh water to remove chloride contamination prior to placing concrete.
H. Replace defective reinforcement with new reinforcement having required shape, form, and cross-section area.
3.3 WELDED WIRE FABRIC
A. Welded wire fabric shall be placed as indicated on the Contract Drawings and securely supported and fastened to prevent displacement before or during placement of concrete.
B. Welded wire fabric shall be fully supported prior to placement of concrete. It shall not be positioned during placement.
CAST-IN-PLACE CONCRETE 033000 - 7
C. Embedded items shall be securely fastened and supported to prevent displacement during concrete placement.
D. USACE will inspect the forms, welded wire fabric, and embedded items and authorize placement of concrete.
E. Cover: Shall conform to ACI 301.
3.4 CONCRETE
A. Before placing concrete, equipment for mixing and transporting the concrete shall be cleaned, debris shall be removed from the places to be occupied by the concrete, forms shall be wetted or oiled, masonry units that will be contact with concrete shall be wetted.
B. Water, snow and ice shall be removed from place of deposit before concrete is placed.
C. Use of bag mix concrete shall be limited to the following non-structural conditions:
1. For quantities less than 0.5 cubic yards.
2. For applications not requiring aesthetic considerations.
D. Ready-mixed concrete shall be mixed and delivered in accordance with the requirements set forth in standard Specification for “Ready-Mixed Concrete”, ASTM C94.
E. Retempering of concrete is not permitted.
F. Concrete Placement
1. Concrete shall be placed immediately after arriving at the job site. On days when the air temperature is 70 degrees F or greater, concrete that has been mixing in a continuous manner or which has contained its mixing water for more than 90 minutes shall not be placed in the work. On days when the air temperature is less than 70 degrees F, this time limitation shall be increased to 120 minutes.
2. When placement of concrete is started, it shall be carried on as a continuous operation until the placement of the section is completed in such a manner that fresh concrete is not deposited on concrete placed earlier which has hardened sufficiently to cause formation of seams and planes of weakness within the section.
3. Work shall be compacted by mechanical internal-vibration equipment in accordance with ACI 309, supplemented by hand spading, rodding and tamping as required. Vibrators shall not be used to move or transport concrete inside the forms.
4. The use of form vibrators is not permitted.
5. The duration of vibration shall be limited to the time necessary to consolidate the placed concrete without causing segregation. The vibrators shall be operated by personnel experienced in their use and under experienced supervision.
6. Care shall be taken during concrete placement that embedded items are not moved or otherwise disturbed from their set position.
7. Concrete shall not be allowed a free fall of more than 5 feet.
CAST-IN-PLACE CONCRETE 033000 - 8
G. The placing or depositing of concrete shall be done in accordance with the requirements of the American Concrete Institute Building Code.
1. Cold Weather Concreting – Concrete should not be placed when the ambient temperature is below 40 degrees F or when the temperature is likely to go below 50 degrees F temperature before the expiration of the specified curing period. If it is necessary to place concrete under conditions of low temperatures, prior USACE consent shall be obtained and appropriate protection materials to adequately maintain curing temperatures shall be at the job site prior to initiating placement. This concrete shall be placed in accordance with the requirements of ACI 306, “Recommended Practice for Cold Weather Concreting”.
2. Hot Weather Concreting – During extremely hot weather, i.e., air temperatures in excess of 95 degrees F, every effort shall be made to keep the temperature of the concrete at the time of placement, well below 90 degrees F by methods described in ACI 305, “Recommended Practice for Hot Weather Concreting”.
3. Concrete shall be deposited as nearly as practicable to its final position to avoid segregation due to rehandling or flowing. No concrete that has partially hardened or been contaminated by foreign materials shall be deposited on the work, nor shall retempered concrete be used.
4. When concreting is started, it shall be carried on as a continuous operation until the placing of the panel or section is completed. The top surface shall be generally level.
5. Concrete shall be vibrated in accordance with ACI 309 by suitable means during the operation of placing, and shall be thoroughly worked around reinforcement, embedded fixtures, and into the corners of the forms.
6. Spare operable vibrators shall be available at the job site during concrete placement operations.
H. Conveying
1. Concrete shall be conveyed from the mixer to the place of final deposit by methods which will prevent the separation or loss of the materials.
2. Equipment for chuting, pumping, and pneumatically conveying concrete shall be of such size and design as to insure a practically continuous flow of concrete at the delivery and without separation of the materials.
I. Control joints shall be sawed within 24 hours of concrete placement.
1. Concrete shall be placed continuously so that each unit of operation will be monolithic in construction, and shall be compacted, screened to grade and prepared for the indicated or specified finish.
2. Crack control joints may be formed by crack control tool inserted into the plastic concrete or may be saw cut after the concrete has been placed. Joints shall be 1/8” wide and approximately ¾” deep unless otherwise indicated or directed by
USACE.
3. Crack control joints shall be deep tooled around existing adjoining foundations.
J. Protection
1. Curing
CAST-IN-PLACE CONCRETE 033000 - 9
a. Shall be accomplished by preventing loss of moisture, temperature change greater than 5 degrees F in one (1) hour or 50 degrees F in any 24 hours, mechanical injury, or injury from rain or flowing water for a period of not less than seven (7) days.
b. Curing compounds, if used shall be checked for compatibility with finish coats. Curing shall be started as soon as free water has disappeared from the concrete after placing and shall be accomplished by keeping the concrete surfaces damp.
c. Where formed surfaces are cured in the forms, the forms shall be kept continually wet. If the forms are removed before the end of the curing period, curing shall be continued as on unformed surfaces, using suitable materials.
2. Slabs
a. Shall remain undisturbed until at least 70 percent of the 28-day compression strength is achieved.
3. Removing forms that does not support the weight of concrete.
a. Formwork may be removed after cumulatively curing at not less than 50 degrees F ambient for 24-hours (not necessarily consecutive) after placing concrete providing concrete is hard enough to not be damaged by form removal and provided curing operations are maintained.
b. If ambient temperature is below 50 degrees F or if retarding agents are used, then the curing period prior to removing forms shall be increased at the discretion of USACE.
c. No forms may be removed until obtaining USACE consent.
K. Construction Joints
1. Shall be placed in slabs as shown on the Contract Drawings.
2. Other joints shall be reviewed by USACE.
3.5 GROUT
A. Cement-Based
1. Grout shall exhibit no shrinkage and a maximum of 0.2 percent expansion in the hardened state when tested in accordance with CRD-C-621.
2. Initial set time shall be a minimum of one (1) hour.
3.6 CONCRETE FINISHES
A. Formed surfaces shall receive a smooth rubbed finish. Finish imperfections using a cement-base grout. No aggregate shall be visible in exposed surfaces.
B. Horizontal surfaces at or above grade shall be true plane surfaces with no deviation in excess of ¼-inch when tested with a 10-foot straight edge. The dusting of a finish surface with dry material is not permitted.
CAST-IN-PLACE CONCRETE 033000 - 10
C. Concrete shall be screeded and floated with straight edge to bring the surface to the required finish level with no coarse aggregate visible. The concrete, while still green, shall be wood floated to a true, even plane with no coarse aggregate visible. Sufficient pressure shall be used on the wood floats to bring moisture to the surface. After the surface moisture has disappeared, the floated surfaces shall be given the following finish:
1. Interior Slabs: Steel trowel finish.
2. Exterior Slabs: Broom finish.
3.7 BONDING AGENTS
A. Concrete shall be chipped and routed to a sound surface free of laitance and the bonding agent shall be applied to this surface in accordance with the manufacturer’s instructions, prior to placing new concrete or grout patches.
3.8 SAMPLES AND TESTING
A. Furnish signed delivery slips to USACE for each truckload of concrete delivered.
Delivery slips shall certify design strength and include the following information:
1. Batch mix.
2. Air entrainment content.
3. Batch time.
B. Sampling shall be done in accordance with ASTM C172, except that concrete for slump tests and cylinders shall be taken several cubic feet into the truck.
C. Slump Tests
1. A minimum of one (1) test shall be made for each truckload of concrete used.
2. Excess slump will be cause for rejection of concrete.
3. Slump test shall be taken in accordance with ASTM C143 in the presence of
USACE.
4. Concrete used for slump tests shall not be placed into the pour.
D. Compression Testing
1. The number of test cylinders shall be as follows:
a. Six (6) test cylinders shall be made from one (1) truckload of each day’s total quantity of concrete placed from each concrete production facility used.
b. USACE reserves the right to select which truckload(s).
2. During the progress of the work, test cylinders shall be made in accordance with the “Method of Making and Curing Concrete Compression and Flexural Specimens in the Field” (ASTM C31).
CAST-IN-PLACE CONCRETE 033000 - 11
a. The Seller shall employ a test laboratory agreed upon by USACE to conduct compression tests to verify that the mix produces the strength of concrete as specified above.
1) Compression tests shall be carried out in accordance with the “Compressive Strength of Cylindrical Concrete Specimens” (ASTM C39).
2) Test results shall be reported to USACE.
b. Molds shall be plastic,
c. Cylinders shall be cured in accordance with ASTM C31.
d. One (1) 7-day and two (2) 28-day tests shall be conducted on the laboratory-cured cylinders. One (1) laboratory-cured cylinder shall be maintained for future testing as necessary.
e. Two (2) 7-day tests shall be conducted on the field-cured cylinders.
3. Protection of Cylinders
a. Tops of samples shall be trowel finished smooth.
b. Cylinders shall be covered and labeled.
c. Seller shall provide insulated boxes for storage of cylinders in the field during cold weather or an open tank during hot weather.
d. Care shall be taken during handling and transport to the testing agency to avoid unnecessary impacts to the cylinders.
4. If the average strength of the cylinders falls below the specified strength, USACE may order any of the following at the Seller’s expense:
a. Compression test on the sixth cylinder taken.
b. Compression tests made with specimens secured from the structure in accordance with ASTM Specification C42.
1) Cores shall be taken from the vertical center of the suspect placement.
2) Cores shall have a minimum l/D of unity.
c. Actual load tests of the structure made in accordance with ACI 318.
1) Load shall approximate ultimate design strength.
2) Deflection shall be measured during all load tests.
d. Removal and replacement of the concrete in question.
3.9 CLEANING
A. In-Progress Cleaning: Clean concrete as work progresses by dry scraping and brushing to remove fins and smears.
CAST-IN-PLACE CONCRETE 033000 - 12
B. Final Cleaning: After concrete is thoroughly set and cured, clean exposed surfaces as follows:
1. Wet surfaces with water.
2. Remove excess concrete with stiff non-metallic brushes.
3. Rinse with water.
END OF SECTION 033000
UNIT MASONRY 042000 - 1
SECTION 042000 - UNIT MASONRY
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Concrete masonry units.
2. Brick.
3. Precast Concrete Cap.
4. Mortar and grout materials.
5. Reinforcement.
6. Accessories.
7. Mortar mixes.
1.2 RELATED DOCUMENTS
A. Contract Drawings and general provisions of the Contract, including General Conditions and Division 1 Specification Sections, apply to this Section.
B. Related Requirements:
1. Section 033000 Cast-In-Place Concrete for concrete footers.
2. Section 312000 "Earth Moving for placement of backfill material.
1.3 DEFINITIONS
A. CMU(s): Concrete masonry unit(s).
B. Reinforced Masonry: Masonry containing reinforcing steel in grouted cells.
1.4 SUBMITTALS
A. The Seller shall submit the following:
1. Shop Drawings:
a. Masonry Units: Indicate sizes, profiles, and coursing.
b. Reinforcing Steel: Indicate bending, lap lengths, and placement of unit masonry reinforcing bars. Comply with ACI 315R. Indicate elevations of reinforced walls.
c. Brick: Show sizes, profiles, and coursing.
B. Product Data:
DRAFT
H4ECDDCB
1.4 SUBMITTALS
UNIT MASONRY 042000 - 2
a. Brick.
b. Precast Concrete Cap.
c. Cement.
d. Cementitious Materials
e. Concrete.
C. Material Certificates: For each type of the following:
1. Masonry units.
a. Include material test reports substantiating compliance with requirements.
b. For brick, include size-variation data verifying that actual range of sizes falls within specified tolerances.
c. For exposed brick, include test report for efflorescence in accordance with
ASTM C67/C67M.
2. Cementitious materials. Include name of manufacturer, brand name, and type.
3. Mortar admixtures.
4. Preblended, dry mortar mixes. Include description of type and proportions of ingredients.
5. Grout mixes. Include description of type and proportions of ingredients.
6. Reinforcing steel.
7. Anchors, ties, and metal accessories.
D. Qualification Statements: For testing agency.
E. Mix Designs: For each type of mortar and grout. Include description of type and proportions of ingredients.
1. Include test reports for mortar mixes required to comply with property specification. Test in accordance with ASTM C109/C109M for compressive strength, ASTM C1506 for water retention, and ASTM C91/C91M for air content.
2. Include test reports, in accordance with ASTM C1019, for grout mixes required to comply with compressive strength requirement.
F. Cold-Weather and Hot-Weather Procedures: Detailed description of methods, materials, and equipment to be used to comply with requirements.
1.5 QUALITY ASSURANCE
A. Qualifications:
1. Testing Agency Qualifications: Qualified in accordance with ASTM C1093 for testing indicated.
UNIT MASONRY 042000 - 3
1.6 DELIVERY, STORAGE, AND HANDLING
A. Store masonry units on elevated platforms in a dry location. If units are not stored in an enclosed location, cover tops and sides of stacks with waterproof sheeting, securely tied. If units become wet, do not install until they are dry.
B. Store cementitious materials on elevated platforms, under cover, and in a dry location.
Do not use cementitious materials that have become damp.
C. Store aggregates where grading and other required characteristics can be maintained and contamination avoided.
D. Deliver preblended, dry mortar mix in moisture-resistant containers. Store preblended, dry mortar mix in delivery containers on elevated platforms in a dry location or in covered weatherproof dispensing silos.
E. Store masonry accessories, including metal items, to prevent corrosion and accumulation of dirt and oil.
1.7 FIELD CONDITIONS
A. Protection of Masonry: During construction, cover tops of walls, projections, and sills with waterproof sheeting at end of each day's work. Cover partially completed masonry when construction is not in progress.
1. Extend cover a minimum of 24 inches down both sides of walls, and hold cover securely in place.
2. Where one wythe of multi-wythe masonry walls is completed in advance of other wythes, secure cover a minimum of 24 inches down face next to unconstructed wythe, and hold cover in place.
B. Do not apply uniform floor or roof loads for at least 12 hours and concentrated loads for at least three days after building masonry walls or columns.
C. Stain Prevention: Prevent grout, mortar, and soil from staining the face of masonry to be left exposed or painted. Immediately remove grout, mortar, and soil that come in contact with such masonry.
1. Protect base of walls from rain-splashed mud and from mortar splatter by spreading coverings on ground and over wall surface.
2. Protect sills, ledges, and projections from mortar droppings.
3. Turn scaffold boards near the wall on edge at the end of each day to prevent rain from splashing mortar and dirt onto completed masonry.
D. Cold-Weather Requirements: Do not use frozen materials or materials mixed or coated with ice or frost. Do not build on frozen substrates. Remove and replace unit masonry damaged by frost or by freezing conditions. Comply with cold-weather construction requirements contained in TMS 602.
UNIT MASONRY 042000 - 4
1. Cold-Weather Cleaning: Use liquid cleaning methods only when air temperature is 40 deg F and higher and will remain so until masonry has dried, but not less than seven days after completing cleaning.
E. Hot-Weather Requirements: Comply with hot-weather construction requirements contained in TMS 602.
PART 2 - PRODUCTS
2.1 UNIT MASONRY, GENERAL
A. Masonry Standard: Comply with TMS 602, except as modified by requirements in the Contract Documents.
B. Defective Units: Referenced masonry unit standards may allow a certain percentage of units to contain chips, cracks, or other defects exceeding limits stated.
2.2 CONCRETE MASONRY UNITS
A. Shapes: Provide shapes indicated and as follows, with exposed surfaces matching exposed faces of adjacent units unless otherwise indicated.
1. Provide square-edged units for outside corners unless otherwise indicated.
B. CMUs: ASTM C90, normal weight.
1. Size (Width): Manufactured to dimensions 3/8 inch less than nominal dimensions.
2.3 BRICK
A. General: Provide shapes indicated and as follows, with exposed surfaces matching finish and color of exposed faces of adjacent units:
1. For ends of sills and caps and for similar applications that would otherwise expose unfinished brick surfaces, provide units without cores or frogs and with exposed surfaces finished.
2. Unit Compressive Strength: Provide units with minimum average net-area compressive strength of 2200 psi.
3. Initial Rate of Absorption: Less than 30 g/30 sq. in. per minute when tested in accordance with ASTM C67/C67M.
4. Efflorescence: Provide brick that has been tested in accordance with ASTM C67/C67M and is rated "not effloresced."
5. Size (Actual Dimensions): 3-5/8 inches wide by 3-5/8 inches high by 7-5/8 inches long.
UNIT MASONRY 042000 - 5
2.4 PRECAST CONCRETE CAP
A. Provide precast concrete caps for retaining wall raised seating area to the dimensions shown on the Drawings.
2.5 MORTAR AND GROUT MATERIALS
A. Portland Cement: ASTM C150/C150M, Type I or II, except Type III may be used for cold-weather construction. Provide cement as required to produce light gray mortar.
1. Alkali content will not be more than 0.1 percent when tested in accordance with
ASTM C114.
B. Hydrated Lime: ASTM C207, Type S.
C. Portland Cement-Lime Mix: Packaged blend of portland cement and hydrated lime containing no other ingredients.
D. Masonry Cement: ASTM C91/C91M.
E. Mortar Cement: ASTM C1329/C1329M.
F. Preblended Dry Mortar Mix: Packaged blend made from portland cement and hydrated lime, sand, and admixtures and complying with ASTM C1714/C1714M.
G. Aggregate for Mortar: ASTM C144.
1. For mortar that is exposed to view, use washed aggregate consisting of natural sand or crushed stone.
H. Aggregate for Grout: ASTM C404.
2.6 REINFORCEMENT
A. Uncoated-Steel Reinforcing Bars: ASTM A615/A615M or ASTM A996/A996M, Grade 60.
B. Reinforcing Bar Positioners: Wire units designed to fit into mortar bed joints spanning masonry unit cells and to hold reinforcing bars in center of cells. Units are formed from 0.148-inch steel wire, hot-dip galvanized after fabrication. Provide units designed for number of bars indicated.
2.7 ACCESSORIES
A. Proprietary Acidic Masonry Cleaner: Manufacturer's standard-strength cleaner designed for removing mortar/grout stains, efflorescence, and other new construction stains from new masonry without discoloring or damaging masonry surfaces. Use product expressly approved for intended use by cleaner manufacturer and manufacturer of masonry units being cleaned.
UNIT MASONRY 042000 - 6
2.8 MORTAR AND GROUT MIXES
A. General: Do not use admixtures, including pigments, air-entraining agents, accelerators, retarders, water-repellent agents, antifreeze compounds, or other admixtures unless otherwise indicated.
1. Do not use calcium chloride in mortar or grout.
2. Use portland cement-lime mortar unless otherwise indicated.
3. Add cold-weather admixture (if used) at same rate for all mortar that will be exposed to view, regardless of weather conditions, to ensure that mortar color is consistent.
B. Preblended, Dry Mortar Mix: Furnish dry mortar ingredients in form of a preblended mix. Measure quantities by weight to ensure accurate proportions, and thoroughly blend ingredients before delivering to Project site.
C. Mortar for Unit Masonry: Comply with ASTM C270. Provide the following types of mortar for applications stated unless another type is indicated.
1. For masonry below grade or in contact with earth, use Type M.
2. For reinforced masonry, use Type S.
3. For exterior, above-grade, loadbearing, nonload-bearing walls, and parapet walls;
for interior load-bearing walls; for interior nonload-bearing partitions; and for other applications where another type is not indicated, use Type N.
D. Grout for Unit Masonry: Comply with ASTM C476.
1. Use grout of type indicated or, if not otherwise indicated, of type (fine or coarse) that will comply with TMS 602 for dimensions of grout spaces and pour height.
2. Proportion grout in accordance with ASTM C476, paragraph 4.2.1.2 for specified 28-day compressive strength indicated, but not less than 2000 psi.
3. Provide grout with a slump of 8 to 11 inches as measured in accordance with
ASTM C143/C143M.
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine conditions, with Installer present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.
1. For the record, prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.
2. Verify that foundations are within tolerances specified and reinforcement is properly placed. See Section 033000 Cast-In-Place Concrete.
3. Verify that substrates are free of substances that impair mortar bond.
B. Before installation, examine rough-in and built-in construction for piping systems to verify actual locations of piping connections.
UNIT MASONRY 042000 - 7
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 INSTALLATION, GENERAL
A. Thickness: Build cavity and composite walls and other masonry construction to full thickness shown. Build double -wythe grouted walls to actual widths of masonry units, using units of widths indicated.
B. Build chases and recesses to accommodate items specified in this and other Sections.
C. Use full-size units without cutting if possible. If cutting is required to provide a continuous pattern or to fit adjoining construction, cut units with motor-driven saws;
provide clean, sharp, unchipped edges. Allow units to dry before laying unless wetting of units is specified. Install cut units with cut surfaces and, where possible, cut edges concealed.
D. Select and arrange units for exposed unit masonry to produce a uniform blend of colors and textures. Mix units from several pallets or cubes as they are placed.
E. Wetting of Brick: Wet brick before laying if initial rate of absorption exceeds 30 g/30 sq.
in. per minute when tested in accordance with ASTM C67/C67M. Allow units to absorb water so they are damp but not wet at time of laying.
3.3 TOLERANCES
A. Dimensions and Locations of Elements:
1. For dimensions in cross section or elevation, do not vary by more than plus 1/2 inch or minus 1/4 inch.
2. For location of elements in plan, do not vary from that indicated by more than plus or minus 1/2 inch.
3. For location of elements in elevation, do not vary from that indicated by more than plus or minus 1/4 inch in a story height or 1/2 inch total.
B. Lines and Levels:
1. For bed joints and top surfaces of bearing walls, do not vary from level by more than 1/4 inch in 10 ft., or 1/2-inch maximum.
2. For conspicuous horizontal lines, such as lintels, sills, parapets, and reveals, do not vary from level by more than 1/8 inch in 10 ft., 1/4 inch in 20 ft., or 1/2-inch maximum.
3. For vertical lines and surfaces, do not vary from plumb by more than 1/4 inch in 10 ft., 3/8 inch in 20 ft., or 1/2-inch maximum.
4. For conspicuous vertical lines, such as external corners, door jambs, reveals, and expansion and control joints, do not vary from plumb by more than 1/8 inch in 10 ft., 1/4 inch in 20 ft., or 1/2-inch maximum.
5. For lines and surfaces, do not vary from straight by more than 1/4 inch in 10 ft., 3/8 inch in 20 ft., or 1/2-inch maximum.
UNIT MASONRY 042000 - 8
6. For vertical alignment of exposed head joints, do not vary from plumb by more than 1/4 inch in 10 ft., or 1/2-inch maximum.
7. For faces of adjacent exposed masonry units, do not vary from flush alignment by more than 1/4 inch except due to warpage of masonry units within tolerances specified for warpage of units.
C. Joints:
1. For bed joints, do not vary from thickness indicated by more than plus or minus 1/4 inch, with a maximum thickness limited to 1/2 inch.
2. For exposed bed joints, do not vary from bed-joint thickness of adjacent courses by more than 1/4 inch.
3. For head and collar joints, do not vary from thickness indicated by more than plus 3/8 inch or minus 1/4 inch.
3.4 LAYING MASONRY WALLS
A. Lay out walls in advance for accurate spacing of surface bond patterns with uniform joint thicknesses and for accurate location of openings, movement-type joints, returns, and offsets. Avoid using less-than-half-size units, particularly at corners, jambs, and, where possible, at other locations.
B. Bond Pattern for Exposed Masonry: Unless otherwise indicated, lay exposed masonry in running bond; do not use units with less-than-nominal 4-inch horizontal face dimensions at corners or jambs.
C. Lay concealed masonry with all units in a wythe in running bond or bonded by lapping not less than 4 inches. Bond and interlock each course of each wythe at corners. Do not use units with less-than-nominal 4-inch horizontal face dimensions at corners or jambs.
D. Stopping and Resuming Work: Stop work by stepping back units in each course from those in course below; do not tooth. When resuming work, clean masonry surfaces that are to receive mortar, remove loose masonry units and mortar, and wet brick if required before laying fresh masonry.
E. Built-in Work: As construction progresses, build in items specified in this and other Sections. Fill in solidly with masonry around built-in items.
3.5 MORTAR BEDDING AND JOINTING
A. Lay CMUs as follows:
1. Fully bed units and fill cells with mortar at anchors and ties as needed to fully embed anchors and ties in mortar.
B. Tool exposed joints slightly concave when thumbprint hard, using a jointer larger than joint thickness unless otherwise indicated.
UNIT MASONRY 042000 - 9
3.6 FIELD QUALITY CONTROL
A. USACE reserves the right to have an independent testing agency inspect and/or test any or all masonry materials provided and construction performed by the Seller.
1. Begin masonry construction only after inspectors have verified proportions of site-prepared mortar.
2. Place grout only after inspectors have verified compliance of grout spaces and of grades, sizes, and locations of reinforcement.
3. Place grout only after inspectors have verified proportions of site-prepared grout.
3.7 REPAIRING, POINTING, AND CLEANING
A. Remove and replace masonry units that are loose, chipped, broken, stained, or otherwise damaged or that do not match adjoining units. Install new units to match adjoining units; install in fresh mortar, pointed to eliminate evidence of replacement.
B. Pointing: During the tooling of joints, enlarge voids and holes, except weep holes, and completely fill with mortar. Point up joints, including corners, openings, and adjacent construction, to provide a neat, uniform appearance. Prepare joints for sealant application, where indicated.
C. In-Progress Cleaning: Clean unit masonry as work progresses by dry brushing to remove mortar fins and smears before tooling joints.
D. Final Cleaning: After mortar is thoroughly set and cured, clean exposed masonry as follows:
1. Remove large mortar particles by hand with wooden paddles and nonmetallic scrape hoes or chisels.
2. Test cleaning methods on sample wall panel; leave one-half of panel uncleaned for comparison purposes. Obtain Engineer’s approval of sample cleaning before proceeding with cleaning of masonry.
3. Protect adjacent stone and nonmasonry surfaces from contact with cleaner by covering them with liquid strippable masking agent or polyethylene film and waterproof masking tape.
4. Wet wall surfaces with water before applying cleaners; remove cleaners promptly by rinsing surfaces thoroughly with clear water.
5. Clean brick by bucket-and-brush hand-cleaning method described in BIA Technical Notes 20.
6. Clean concrete masonry by applicable cleaning methods indicated in
NCMA TEK 8-4A.
7. Clean masonry with a proprietary acidic masonry cleaner applied according to manufacturer's written instructions.
3.8 MASONRY WASTE DISPOSAL
A. Salvageable Materials: Unless otherwise indicated, excess masonry materials are Contractor's property. At completion of unit masonry work, remove from Project site.
UNIT MASONRY 042000 - 10
B. Waste Disposal as Fill Material: Dispose of clean masonry waste, including excess or soil-contaminated sand, waste mortar, and broken masonry units, by crushing and mixing with fill material as fill is placed.
1. Crush masonry waste to less than 4 inches in each dimension.
2. Mix masonry waste with at least two parts of specified fill material for each part of masonry waste. Fill material is specified in Section 312000 "Earth Moving."
3. Do not dispose of masonry waste as fill within 18 inches of finished grade.
C. Masonry Waste Recycling: Return broken CMUs not used as fill to manufacturer for recycling.
D. Excess Masonry Waste: Remove excess clean masonry waste that cannot be used as fill, as described above or recycled, and other masonry waste, and legally dispose of off Owner's property.
END OF SECTION 042000
SITE CLEARING 311000 - 1
SECTION 311000 – SITE CLEARING
1.1 SUMMARY
A. This Section includes the following:
1. Removing vegetation.
2. Clearing and grubbing.
3. Topsoil stripping.
4. Removing above-grade site improvements.
1.2 RELATED DOCUMENTS
A. Contract Drawings and general provisions of the Contract, including General Conditions and Division 1 Specification Sections, apply to this Section.
1.3 DEFINITIONS
A. Topsoil: Natural or cultivated surface-soil layer containing organic matter and sand, silt, and clay particles; friable, pervious, and black or a darker shade of brown, gray, or red than underlying subsoil; reasonably free of subsoil, clay lumps, gravel, and other objects more than 2 inches in diameter; and free of weeds, roots, and other deleterious materials.
1.4 MATERIALS OWNERSHIP
A. Except for materials indicated to be stockpiled or to remain FMP property, cleared materials shall be removed from the Site and disposed of in accordance with the General Conditions.
1.5 SUBMITTALS
A. None…