w911w4-16-t-0055.pdf
PDF 1 MB Posted
- Attached to
- Deluge Water System Federal contract opportunity
- Solicitation number
- w911w4-16-t-0055
About this file
The contractor shall do preventative maintenance and repairs as described in the Performance Work Statement on Deluge High Power System
View the file
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SEE ADDENDUM
(No Collect Calls)
W911W4-16-T-0055 30-Aug-2016
b. TELEPHONE NUMBER
586-282-5502
8. OFFER DUE DATE/LOCAL TIME
04:00 PM 01 Sep 2016
5. SOLICITATION NUMBER 6. SOLICITATION ISSUE DATE
AUTHORIZED FOR LOCAL REPRODUCTION
PREVIOUS EDITION IS NOT USABLE
STANDARD FORM 1449 (REV. 2/2012)
Prescribed by GSA – FAR (48 CFR) 53.212
(TYPE OR PRINT)
(SIGNATURE OF CONTRACTING OFFICER)
ADDENDA ARE
26. TOTAL AWARD AMOUNT (For Gov t. Use Only )
23.
CODE 10. THIS ACQUISITION IS
SUCH ADDRESS IN OFFER
17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT
BELOW IS CHECKED
TELEPHONE NO.
W911W49. ISSUED BY
18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a. UNLESS BLOCK
7. FOR SOLICITATION
INFORMATION CALL:
a. NAME
ADAM COLE
2. CONTRACT NO. 3. AWARD/EFFECTIVE DATE 4. ORDER NUMBER
(TYPE OR PRINT)
30b. NAME AND TITLE OF SIGNER 30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER
30a. SIGNATURE OF OFFEROR/CONTRACTOR 31a.UNITED STATES OF AMERICA
0 27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1. 52.212-4. FAR 52.212-3. 52.212-5 ARE ATTACHED.
25. ACCOUNTING AND APPROPRIATION DATA
1. REQUISITION NUMBER
20.
ADDITIONAL SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED.
OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, AND 30
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
W26MT961881001
ARE NOT ATTACHED
27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA ARE ARE NOT ATTACHED
(BLOCK 5), INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE
SET FORTH HEREIN, IS ACCEPTED AS TO ITEMS:
. YOUR OFFER ON SOLICITATION
28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN
% FOR:SET ASIDE:UNRESTRICTED ORX
SMALL BUSINESS
17a.CONTRACTOR/ CODE FACILITY
OFFEROR CODE
ARMY CONTRACTING COMMAND - WARREN
6501 E. 11 MILE RD
WARREN MI 48397-5000
18a. PAYMENT WILL BE MADE BY CODE
RATED ORDER UNDER
DPAS (15 CFR 700)
13a. THIS CONTRACT IS A
13b. RATING
CODE15. DELIVER TO CODE 16. ADMINISTERED BY
SEE SCHEDULE
12. DISCOUNT TERMS11. DELIVERY FOR FOB DESTINA-
TION UNLESS BLOCK IS
MARKED
SEE SCHEDULE
14. METHOD OF SOLICITATION
RFQ IFB RFPX
FAX:
TEL: SERVICE-DISABLED
VETERAN-OWNED
SMALL BUSINESS
8(A)
HUBZONE SMALL
BUSINESS
SIZE STANDARD:
$15,000,000
NAICS:
238220
X
OFFER DATED
29. AWARD OF CONTRACT: REF.
DELIVER ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY
COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND
EMAIL:
TEL:
31c. DATE SIGNED
SEE SCHEDULE
SCHEDULE OF SUPPLIES/ SERVICESITEM NO. QUANTITY UNIT UNIT PRICE AMOUNT
24.22.21.19.
WOMEN-OWNED SMALL BUSINESS (WOSB)
ELIGIBLE UNDER THE WOMEN-OWNED
SMALL BUSINESS PROGRAM
EDWOSB
32g. E-MAIL OF AUTHORIZED GOVERNMENT REPRESENTATIVE
SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS
(CONTINUED)
PAGE 2 OF256
ACCEPTED, AND CONFORMS TO THE CONTRACT, EXCEPT AS NOTED: ______________________________________________________
32a. QUANTITY IN COLUMN 21 HAS BEEN
RECEIVED INSPECTED
32b. SIGNATURE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32c. DATE 32d. PRINTED NAME AND TITLE OF AUTHORIZED GOVERNMENT
REPRESENTATIVE
32e. MAILING ADDRESS OF AUTHORIZED GOVERNMENT REPRESENTATIVE 32f . TELEPHONE NUMBER OF AUTHORIZED GOVERNMENT REPRESENTATIVE
37. CHECK NUMBER
FINALPARTIALCOMPLETE
36. PAYMENT35. AMOUNT VERIFIED
CORRECT FOR
34. VOUCHER NUMBER
FINAL
33. SHIP NUMBER
PARTIAL
38. S/R ACCOUNT NUMBER 39. S/R VOUCHER NUMBER 40. PAID BY
41a. I CERTIFY THIS ACCOUNT IS CORRECT AND PROPER FOR PAYMENT
41b. SIGNATURE AND TITLE OF CERTIFYING OFFICER 41c. DATE
42a. RECEIVED BY (Print)
42b. RECEIVED AT (Location)
42c. DATE REC'D (YY/MM/DD) 42d. TOTAL CONTAINERS
STANDARD FORM 1449 (REV. 2/2012) BACK
Prescribed by GSA – FAR (48 CFR) 53.212
AUTHORIZED FOR LOCAL REPRODUCTION
PREVIOUS EDITION IS NOT USABLE
SEE SCHEDULE
20.
SCHEDULE OF SUPPLIES/ SERVICES
21.
QUANTITY UNIT
22. 23.
UNIT PRICE
24.
AMOUNT
19.
ITEM NO.
UFC 3-601-02
8 September 2010
Section SF 1449 - CONTINUATION SHEET
ITEM NO SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT
0001 1 Test and replace Deluge System
FFP
See Performance Work Statement for specific details
Work must be completed prior to 10 September, 2016 FOB: Destination
PURCHASE REQUEST NUMBER: W26MT961881001
NET AMT
Contractor Manpower Report
FFP
FAR Clause 52.237-4000
1001 1 Option Year 1
FFP
See Performance Work Statement for specific details
Work must be completed week prior to 10 September, 2017
Contractor Manpower Report
FFP
2001 1 Option Year 2
FFP
See Performance Work Statement for specific details
Work must be completed week prior to 10 September, 2018
Contractor Manpower Report
FFP
3001 1 Option Year 3
FFP
See Performance Work Statement for specific details
Work must be completed week prior to 10 September, 2019
Contractor Manpower Report
FFP
3003 1 Option Year 4
FFP
See Performance Work Statement for specific details
Work must be completed week prior to 10 September, 2020
Contractor Manpower Report
FFP
DA PAM 385-64
Department of the Army Pamphlet 385–64 Safety
Ammunition and Explosives Safety Standards Headquarters Department of the Army Washington, DC 15 December 1999
UNCLASSIFIED
SUMMARY of CHANGE
DA PAM 385–64
Ammunition and Explosives Safety Standards This change 1--o Incorporates recent changes to explosives safety criteria of DOD 6055.9-
STD,
DOD Ammunition and Explosives Safety Standards.
o Incorporates requirements previously only contained in TM 206-1300-9 (rescinded) (para 2-6).
o Adds requirements for underground facilities (para3-23, para 5-13, figure 5- 10, and para 6-3c).
o Adds requirements for plans to provide safety, security, and environmental protection in emergency response (para 3-24).
o Adopts DOD revisions to criteria for hazard division 1.2 (app I).
o Provides corrections to quantity-distance requirements for public highways (para 5-6).
o Provides corrections to unbarricaded intraline distance requirements (para 5-6d(3)).
o Provides corrections to facilities siting criteria (chap 5).
o Provides corrections to magazine siting criteria (chap 5).
o Corrects/updates quantity-distance tables (chap 5) o Adds requirements for surge suppression for incoming conductors to include suppression at the entrance to the building from each wire to ground (para 6- 5b).
o Corrects qualification requirements for personnel responsible for electrical maintenance, inspection and testing (para 6-13c(1)).
o Clarifies lighting protection electrical test requirements for earth covered magazines (table 6-1).
o Corrects DD Form 626 inspection requirements motor vehicles loaded with explosives, ammunition, or other hazardous material (para 7-7a and 7-8).
o Adds information on DOD explosives safety surveys (para 8-1f).
o Changes construction requirements for explosives buildings (para 8-5).
o Provides changes to requirements for barricaded open storage modules and barricades and earth cover for magazines (para 8-29c, 8-29d(3), and 8-30).
o Provides quantity-distance requirements for maritime prepositioning ships (para 11-6d(7)) and table 11-13).
o Provides changes to lightning protection requirements (chap 12) o Adds requirements from the Munitions Rule (para 13-29 and chap 19).
o Changes safety requirements for contingency deployment ammunition operations in a less than wartime environment (chap 14).
o Changes safety requirements for wartime operations (chap 15).
o Changes earth covered magazine criteria (app G).
o Adds explosives safety program management requirements (app J).
o This new Department of the Army pamphlet--o Implements and amplifies the explosives safety criteria depicted in DOD 6055.9-STD, DOD Ammunition and Explosives Safety Standards (chap 1).
o Defines general safety standards for Army operations involving ammunition and/or explosives (chap 2).
o Establishes management controls for fire prevention, suppression and protection as applicable to Army ammunition and explosives (chap 3).
o Provides an overview of the Joint Hazard Classification System (JHCS) and establishes storage principles for the various compatibility groupings of ammunition and explosives (chap 4).
o Establishes quantities of explosives material and distance separation requirements that provide defined levels of protection (chap 5).
o Establishes requirements for the installation and use of electrical service and equipment in Army explosives facilities (chap 6).
o Defines regulations and guidance regarding shipment of Army explosives and other dangerous articles (chap 7).
o Establishes requirements and provides definitive material on the preparation and submittal of explosives and toxic chemical site plans (chap 8).
o Explains the purpose, denotes minimum requirements and defines responsibilities of the Army explosives licensing program (chap 9).
o Provides guidance on the appropriate usage of material handling equipment (MHE) for ammunition and/or explosives operations (chap 10).
o Establishes requirements for the movement of Army units to ports during times of war, peace, or national emergency (chap 11).
o Provides the minimum technical criteria for lightning protection of explosives areas and facilities (chap 12).
o Sets forth requirements for storage of ammunition and explosives within the Army (chap 13).
o Establishes peacetime operational requirements concerning CONUS and OCONUS ammunition and explosives activities, training operations, contingency force operations and airfields used by military aircraft in the theater of operations (chap 14).
o Provides guidance for the safe handling, transportation, and storage of ammunition during wartime and contingency operations (chap 15).
o Defines the Army criteria pertaining to the storage and handling of commercial explosives (chap 16).
o Provides guidance on the requirements and procedures for the disposal of ammunition, explosives and propellants (chap 17).
o Establishes requirements and criteria relative to operations involving maintenance and/or the restoration of ammunition and explosives to a serviceable condition (chap 18).
Headquarters Department of the Army Washington, DC 15 December 1999 Safety Ammunition and Explosives Safety Standards Department of the Army Pamphlet 385–64 H i s t o r y . T h i s p u b l i c a t i o n w a s o r i g i n a l l y p r i n t e d o n 2 8 N o v e m b e r 1 9 9 7 . I t w a s a u t h e n t i c a t e d b y D e n n i s J . R e i m e r , G e n e r a l , U n i t e d S t a t e s A r m y , C h i e f o f Staff and Joel B. Hudson, Administrative A s s i s t a n t t o t h e S e c r e t a r y o f t h e A r m y .
This electronic edition publishes the basic 1 9 9 7 e d i t i o n a n d i n c o r p o r a t e s c h a n g e 1 .
C h a n g e 1 w a s p r i n t e d o n 1 5 D e c e m b e r 1 9 9 9 a n d w a s a u t h e n t i c a t e d b y E r i c K .
S h i n s e k i , G e n e r a l , U n i t e d S t a t e s A r m y , C h i e f o f S t a f f a n d J o e l B . H u d s o n , A d m i n i s t r a t i v e A s s i s t a n t t o t h e S e c r e t a r y o f t h e A r m y . C h a n g e s a r e s h o w n w i t h underscore and tint.
Summary. This pamphlet provides force protection guidance for commanders with an ammunition or explosives mission. It p r o v i d e s p r o c e d u r e s t o p r o t e c t m i l i t a r y and civilian Army employees, the public, a n d t h e e n v i r o n m e n t . I t a l s o s e t s f o r t h procedures for use when transporting amm u n i t i o n o r e x p l o s i v e s o v e r t h e p u b l i c highway.
A p p l i c a b i l i t y . T h e p r o v i s i o n s o f t h i s pamphlet apply to all Army installations and activities, the Army National Guard ( A R N G ) , t h e U . S . A r m y R e s e r v e (USAR), Government-owned, contractoroperated (GOCO) facilities, and contractor operations on Government property.
Ammunition and explosives under U.S. title, even though stored in a host country, remain the responsibility of the U.S. commander.
Storage must conform with Army standards for explosives safety unless the use of other criteria (such as North Atlantic Treaty Organization (NATO) or host nation has been agreed to or is mandatory.
A copy of all agreement documents will b e p r o v i d e d m a j o r A r m y c o m m a n d s (MACOMs) involved and two will be sent t o t h e D i r e c t o r , U . S . A r m y T e c h n i c a l C e n t e r f o r E x p l o s i v e s S a f e t y (USATCES). A copy of all agreements will also be made a permanent part of the real property records. Provisions of this p a m p h l e t a p p l y i n w a r t i m e , p e a c e t i m e , and in contingency situations.
Proponent and exception authority.
T h e p r o p o n e n t o f t h i s p a m p h l e t i s t h e Under Secretary of the Army. The Under Secretary of the Army has the authority to approve exceptions to this pamphlet that a r e c o n s i s t e n t w i t h c o n t r o l l i n g l a w a n d r e g u l a t i o n . T h e U n d e r S e c r e t a r y o f t h e Army may delegate this authority, in writing, to a division chief within the propon e n t a g e n c y w h o h o l d s t h e g r a d e o f colonel or the civilian equivalent.
Suggested Improvements. Users are invited to send comments and suggested improvements on DA Form 2028 (Recomm e n d e d C h a n g e s t o P u b l i c a t i o n s a n d Blank Forms) directly to Director, U.S.
A r m y T e c h n i c a l C e n t e r f o r E x p l o s i v e s Safety.
Distribution. Distribution of this publication is made in accorance with initial d i s t r i b u t i o n n u m b e r ( I D N ) 0 9 5 4 6 6 , f o r command levels D and E for the Active Army, the Army National Guard, and the U.S. Army Reserve.
Contents (Listed by paragraph and page number)
Chapter 1 Introduction, page 1 Purpose • 1–1, page 1
References • 1–2, page 1 Explanation of abbreviations and terms • 1–3, page 1 Implementation • 1–4, page 1 Policy on existing explosives facilities • 1–5, page 1 Chapter 2 General Safety Precautions, page 1 Hazard analysis and risk assessment • 2–1, page 1 Personnel qualifications • 2–2, page 2 Use of written standards • 2–3, page 2 DA PAM 385–64 • 15 December 1999 i
UNCLASSIFIED
Contents—Continued Personnel and explosives limits • 2–4, page 2 Handling and movement precautions • 2–5, page 2 Housekeeping • 2–6, page 3 Testing, disassembly, and modification of explosives items • 2–7, page 4 Explosive ordnance disposal training aids • 2–8, page 4 Field safety • 2–9, page 5 Accident reporting • 2–10, page 5 Rod and gun clubs • 2–11, page 5 Public demonstrations, exhibitions, and celebrations • 2–12, page 5 Static or public display • 2–13, page 6 Explosives training aids for military working dogs • 2–14, page 6 Hunting • 2–15, page 6 Chapter 3 Fire Prevention, Protection, and Suppression, page 9 Fire prevention management • 3–1, page 9 Smoking • 3–2, page 9 Training • 3–3, page 10 Fire drills • 3–4, page 10 Fire exit drills • 3–5, page 10 Alarms • 3–6, page 10 Fire prevention requirements • 3–7, page 10 Auxiliary firefighting equipment • 3–8, page 12 Storage of water for firefighting • 3–9, page 13 Access to fire hose • 3–10, page 13 Limitation of fire areas • 3–11, page 13 Reciprocal agreements for fire fighting support • 3–12, page 13 Public withdrawal distances • 3–13, page 13 Firefighting guidance symbols • 3–14, page 14 Posting fire symbols • 3–15, page 14 Exceptions on posting fire symbols • 3–16, page 14 Posting chemical hazard symbols • 3–17, page 15 Procedures for chemical agents and other toxic substances • 3–18, page 15 Firefighting at railheads • 3–19, page 15 Automatic sprinkler systems • 3–20, page 15 Deluge systems for explosives operations • 3–21, page 15 Instructions for fighting fires involving ammunition or explosives • 3–22, page 17 Reentry of underground facilities • 3–23, page 18 Emergency planning • 3–24, page 18 Chapter 4 Hazard Classification and Compatibility Groups, page 29 Explosives hazard classification procedures • 4–1, page 29 EIDS and EIDS ammunition • 4–2, page 29 Storage principles • 4–3, page 30
Mixed storage • 4–4, page 30 Storage compatibility groups • 4–5, page 30 Class 1 or 6 chemical agent hazards or combined chemical agent and explosives hazards • 4–6, page 31 Underground storage • 4–7, page 31 Chapter 5 Quantity-Distance, page 33 Explosives quantity-distance • 5–1, page 33 Quantity of explosives • 5–2, page 33 Measuring distance • 5–3, page 34 ii DA PAM 385–64 • 15 December 1999 Contents—Continued Q-D computations and determinations • 5–4, page 34 Fragments • 5–5, page 35 Quantity-distance: expected effects and permissible exposures • 5–6, page 36 Facilities siting criteria • 5–7, page 40 Magazine siting requirements • 5–8, page 53 Quantity-distance tables • 5–9, page 54 Airfields, heliports, and seadromes • 5–10, page 55 Pier and wharf facilities • 5–11, page 56 Liquid propellants • 5–12, page 56 Underground storage • 5–13, page 58 Chapter 6 Electrical Hazards, page 99 Section I Electrical Service and Equipment, page 99 Overview • 6–1, page 99 Hazardous locations • 6–2, page 99 Approved equipment • 6–3, page 100 Maintenance of electrical equipment • 6–4, page 101 Electrical service lines in explosives areas • 6–5, page 101 Electrical motors for hazardous locations • 6–6, page 101 Portable lighting systems • 6–7, page 101 Permanent lighting for storage magazines • 6–8, page 101 Flexible cords • 6–9, page 101 Section II Static electricity, page 102 Static electricity charge dissipation subsystem • 6–10, page 102 Ordnance grounds (static grounds) • 6–11, page 106 Instrument grounds • 6–12, page 106 Section III Grounding, page 106 Explosives facility grounding • 6–13, page 106 Earth electrode subsystem • 6–14, page 106 Section IV Electromagnetic Radiation, page 108 Hazards of electromagnetic radiation to electro-explosive devices (EEDs) • 6–15, page 108 Chapter 7 Transportation, page 119 Section I General requirements, page 119 General information • 7–1, page 119 Certification of personnel involved with transportation • 7–2, page 119 Hazard classification • 7–3, page 119 Preparation for shipment • 7–4, page 120 Compatibility of explosives in transportation • 7–5, page 120 Section II
Motor Vehicles, page 120 Vehicle general safety requirements • 7–6, page 120 Inbound motor shipment of ammunition and explosives • 7–7, page 121 DA PAM 385–64 • 15 December 1999 iii Contents—Continued Outbound motor vehicle shipments of explosives • 7–8, page 121 Safe haven for explosive shipments • 7–9, page 122 On-post explosive movements • 7–10, page 122 Passengers in or on Government vehicles transporting explosives • 7–11, page 122 Section III Rail, Air, and Water Transport, page 122 Railroad transportation • 7–12, page 123 Air transportation • 7–13, page 124 Water transportation • 7–14, page 125 Chapter 8 Safety Site Planning, Construction, and Utilities, page 125 Section I Explosives/Toxic Chemical Safety Site Plans, page 125 Explosives/Toxic Chemical Safety Site Plan Submittals • 8–1, page 125 Explosives safety site plan contents • 8–2, page 126 Review and approval of explosives safety site plans • 8–3, page 127 Section II Construction Considerations, page 127 Construction considerations • 8–4, page 127 Buildings • 8–5, page 128 Interior finishes and floors • 8–6, page 128 Firewalls • 8–7, page 129 Substantial dividing walls • 8–8, page 129 Building exits • 8–9, page 129 Safety chutes • 8–10, page 129 Emergency exits and fire escapes • 8–11, page 129 Stairways • 8–12, page 129 Fixed ladders • 8–13, page 129 Platforms, runways, and railings • 8–14, page 129 Passageways • 8–15, page 129 Roads, walks, and gates • 8–16, page 129 Windows and skylights • 8–17, page 130 Drains and sumps • 8–18, page 130 Hardware • 8–19, page 130 Tunnels • 8–20, page 130 Powerhouse equipment • 8–21, page 130 Refrigeration • 8–22, page 130 Laundries • 8–23, page 130 Steam for processing and heating • 8–24, page 130 Ventilation • 8–25, page 131 Electrical equipment • 8–26, page 131 Collection of explosives dusts • 8–27, page 131 Automatic sprinkler systems • 8–28, page 132 Section III Open Storage Modules, Barricades, and Protective Construction, page 132 Barricaded open storage modules • 8–29, page 132 Barricades and earth cover for magazines • 8–30, page 133 Policy on protective construction • 8–31, page 134 Strengthening (hardening of buildings) • 8–32, page 135 iv DA PAM 385–64 • 15 December 1999 Contents—Continued
Chapter 9 Explosives Licensing, page 140 Procedures • 9–1, page 140 Required information • 9–2, page 140 Chapter 10 Materials Handling Equipment (MHE), page 140 General requirements • 10–1, page 140 Battery-powered materials handling equipment • 10–2, page 140 Gasoline and diesel powered equipment • 10–3, page 141 LP-gas-powered equipment • 10–4, page 141 Gasoline, diesel-powered and LP-gas-powered equipment for handling explosives materials • 10–5, page 141 Storage • 10–6, page 142 Chapter 11 Port Operations, page 142 Background information • 11–1, page 142 Loading of vehicles • 11–2, page 142 Vehicle holding site • 11–3, page 143 Railhead operations • 11–4, page 143 Road movement • 11–5, page 143 Port safety • 11–6, page 143 Chapter 12 Lightning Protection, page 148 General information • 12–1, page 148 Fundamental principles of lightning protection • 12–2, page 149 Locations requiring an LPS • 12–3, page 149 Locations not requiring lightning protection • 12–4, page 149 Requirements for lightning protection systems • 12–5, page 150 Types of lightning protection systems • 12–6, page 151 General prohibitions • 12–7, page 151 Bonding • 12–8, page 152 Lightning warning systems • 12–9, page 152 Structural grounds • 12–10, page 152 Grounding • 12–11, page 152 Surge protection • 12–12, page 152 Visual inspection requirements • 12–13, page 153 Electrical testing requirements • 12–14, page 153 Records • 12–15, page 153 Truck holding areas • 12–16, page 153 Lightning protection for empty facilities • 12–17, page 153 Chapter 13 Explosives Storage Requirements, page 155 General requirements • 13–1, page 155 Magazine storage of explosives and ammunition • 13–2, page 156 Outdoor storage • 13–3, page 159 Holding yard • 13–4, page 159 Storage of specific types of ammunition and explosives • 13–5, page 159 Inert ammunition • 13–6, page 161 Unserviceable ammunition • 13–7, page 162 Storage of captured enemy ammunition • 13–8, page 162 Chemical munitions • 13–9, page 162 Chemical Group B agents • 13–10, page 163 DA PAM 385–64 • 15 December 1999 v Contents—Continued Storage of Chemical Group B agent munitions • 13–11, page 163 Special protective equipment for Chemical Group B agent munitions • 13–12, page 163 First aid for Group B chemical agents • 13–13, page 164
Leaking Chemical Group B agent munitions • 13–14, page 164 Removal of spilled Chemical Group B fillers • 13–15, page 164 Fire in Chemical Group B agent munitions magazines • 13–16, page 164 Chemical Group C agents • 13–17, page 164 Storage for Chemical Group C munitions • 13–18, page 164 First aid and special equipment for Chemical Group C munitions • 13–19, page 164 Leaking Group C chemical munitions • 13–20, page 165 Removal of Chemical Group C contamination • 13–21, page 165 Fire in Chemical Group C munitions magazines • 13–22, page 165 Chemical Group D fillers • 13–23, page 166 Storage of Chemical Group D munitions • 13–24, page 166 Special protective equipment for Chemical Group D munitions • 13–25, page 166 First aid for Chemical Group D munitions • 13–26, page 166 Leaking Chemical Group D munitions • 13–27, page 166 Fire in Chemical Group D munitions magazines • 13–28, page 166 Termination of use of facilities storing ammunition and explosives • 13–29, page 166 Chapter 14 General • 14–1, page 167 Site plan process • 14–2, page 167 Asset Preservation Distances. • 14–3, page 168 Basic load ammunition holding areas • 14–4, page 168 Basic load storage in other than BLAHAs • 14–5, page 170 Vehicle and equipment maintenance • 14–6, page 170 Fire prevention • 14–7, page 170 Surveillance • 14–8, page 171 Storage • 14–9, page 171 Basic load storage ammunition holding areas in the United States • 14–10, page 171 General requirements for training operations • 14–11, page 171 Upload exercises • 14–12, page 171 Combat configured loads • 14–13, page 172 Aviation operations at BLAHAs • 14–14, page 172 Forward area rearm/refuel points (FARP) • 14–15, page 172 Airfield Operations • 14–16, page 173 Ports • 14–17, page 174 Static missile battery separation • 14–18, page 174 Separation from fuel • 14–19, page 175 Chapter 15 Wartime Operations, page 183 General requirements • 15–1, page 183 Theater and corps ammunition storage areas • 15–2, page 184 Storage at the ASP and ATP • 15–3, page 185 Short-term ATP storage • 15–4, page 185 Field storage and handling areas. • 15–5, page 185 Transportation within the theater of operations • 15–6, page 186 Modular storage • 15–7, page 186 Ammunition turn-in at the cessation of hostilities • 15–8, page 187 Emergency destruction of ammunition • 15–9, page 187 vi DA PAM 385–64 • 15 December 1999 Contents—Continued Chapter 16 Storage and handling of commercial explosives, page 189 Background • 16–1, page 189 Use • 16–2, page 189 Procedures • 16–3, page 189 Commercial dynamite • 16–4, page 189 Chapter 17
Demilitarization, page 190 Demilitarization • 17–1, page 190 Methods • 17–2, page 190 Safety precautions • 17–3, page 190 Site selection for burning or demolition grounds • 17–4, page 191 Burning sites • 17–5, page 191 New demilitarization technologies • 17–6, page 191 Chapter 18 Maintenance, page 192 General information • 18–1, page 192 Safety requirements • 18–2, page 192 Operational shields • 18–3, page 193 Equipment for shielded operations • 18–4, page 195 Tools, equipment and supplies • 18–5, page 195 Protection of primers • 18–6, page 195 Cleaning ammunition • 18–7, page 195 Spray painting • 18–8, page 195 Electrostatic paint spraying and detearing of inert items in non-hazardous locations • 18–9, page 196 Infrared ray drying • 18–10, page 196 Drying freshly painted loaded ammunition • 18–11, page 197 Heat sealing equipment • 18–12, page 197 Soldering containers • 18–13, page 197 Thread cleaning • 18–14, page 197 Inert scrap components and packaging materials • 18–15, page 198 Sand or shotblasting operations • 18–16, page 198 Location of sand or shotblasting operations in explosives storage areas • 18–17, page 198 Sand or shotblasting operations within a building in an operating line • 18–18, page 199 Electrical testing of ammunition and ammunition components • 18–19, page 199 Profile and alignment gaging operations • 18–20, page 199 Collection of explosives dusts • 18–21, page 200 Location of collection chambers • 18–22, page 200 Design and operation of collection systems • 18–23, page 200 Solid propellant collection • 18–24, page 201 Destruction of solid wastes • 18–25, page 201 Assembly and crimping of complete rounds • 18–26, page 201 Rotational speeds for equipment used in field ammunition operations • 18–27, page 202 Machining of explosives • 18–28, page 202 Operational shields for munitions loading • 18–29, page 203 Chapter 19 Special storage procedures for waste military munitions, page 203 Scope and applicability • 19–1, page 203 Waivers and exemptions • 19–2, page 203 Requirements for Storage of Waste Military Munitions under CE • 19–3, page 204 Other storage standards • 19–4, page 204 Reporting • 19–5, page 204 DA PAM 385–64 • 15 December 1999 vii Contents—Continued Closure of facilities storing waste munitions under CE • 19–6, page 205 Closure of facilities storing waste military munitions under RCRA • 19–7, page 205 Appendixes A. References, page 206 B. Earth Electrode Subsystem Test and Inspection, page 210 C. Inspection and Test of Static Electricity Charge Dissipation Subsystem, page 217 D. Inspection and Test of Lightning Protection Subsystems, page 219 E. Field Expedient Grounding Techniques, page 222 F. Safe Conveyor Separation for Ammunition/Explosives, page 222
G. Standard designs for explosives facilities, page 229 H. The 100–Foot Zone of Protection, page 230 I. Revised Hazard Division 1.2 criteria, page 238 J. Explosives Safety Program Management, page 244 K. Investigating and Reporting Unpermitted or Uncontrolled Detonation, Release, Discharge, or migration of Waste Military Munitions, page 250 Table List Table 3–1: Extinguishing agents for fires, page 18 Table 3–2: Fire symbol hazards and actions, page 18 Table 3–3: Chemical hazard symbols and actions, page 19 Table 3–4: Emergency withdrawal distances for nonessential personnel, page 20 Table 3–5: Fire divisions hazards, page 20 Table 3–6: Fire division symbols, page 21 Table 3–7: Chemical agents and fillers contained in ammunition and the chemical hazard symbols required in storage, page 21 Table 4–1: EIDS and EIDS ammunition hazard divisions, page 32 Table 4–2: QD criteria for configuration of HD 1.6 components and assemblies with other HD components, page 32 Table 4–3: Storage Compatibility Mixing Chart, page 32 Table 5–1: HD 1.1 inhabited building and public traffic route distances, page 43 Table 5–2: Minimum primary fragment protection distance expressed in feet for selected HD 1.1 Items, page 45 Table 5–3: HC/D 1.1 intraline distances in feet from PESs other than earth-covered magazines3, page 46 Table 5–4: HD 1.1 intraline distances from earth-covered magazines (type of distance protection to be provided to ES), page 47 Table 5–5: HC/D 1.1 intermagazine hazard factors and distances, page 48 Table 5–6: HC/D 1.1 Guide for Intermagazine Distance 1,8,9, page 50 Table 5–7: Personnel protection distances from aboveground detonations, page 50 Table 5–8: Required blast overpressure protection distance in feet for nonessential personnel at ranges used for detonating ammunition for demilitarization, demonstration, or explosives ordnance disposal, page 51 Table 5–9: Thermal flux calculations, page 51 Table 5–10: Impulse noise protection decision table, page 63 Table 5–11: Impulse noise zones measured in feet from intentional detonations, page 63 Table 5–12: Impulse noise B-duration (estimated for various NEWs and distances), page 64 Table 5–13: Impulse noise zones and required protections with maximum permissable number of detonations per day, Table 5–14: Q-D for unprotected aboveground service tanks supporting explosives storage or operating complexes, Table 5–15: HD 1.2 distances, page 68 Table 5–16: HD 1.3 QD, page 69 viii DA PAM 385–64 • 15 December 1999 Contents—Continued Table 5–17: HC/D 1.4 quantity-distance, page 71 Table 5–18: QD criteria for HD 1.6 ammunition, page 71 Table 5–19: HD 1.1.QD for military aircraft parking areas, page 72 Table 5–20: Application of ammunition and explosives safety distances between various types of facilities, page 73 Table 5–21: Liquid propellant HE (TNT) equivalents 2,3,4,5,6,7, page 74 Table 5–22: Factors for converting gallons of propellant into pounds1, page 75 Table 5–23: Liquid propellants hazard and compatibility groups, page 75 Table 5–24 (PAGE 1): QD for propellants, page 77 Table 5–24 (PAGE 2): QD for propellants—Continued, page 77 Table 5–24 (PAGE 3): QD for propellants—Continued, page 78 Table 5–25: Hazard group IV separation distances, page 78 Table 5–26: Chamber separation, page 78 Table 5–27: Distance to protect against ground shock, page 80 Table 5–28: Distance to protect against hard rock debris, page 81
Table 5–29: Distance to protect against soft rock debris, page 82 Table 5–30: Functions of loading density, page 82 Table 5–31: Values for Ratio DHYD/VE 1/2.8, page 85 Table 5–32: Scaled IBD for airblast without mitigating, page 86 Table 5–33: Distance versus overpressure along the centerline, page 86 Table 5–34: Effective overpressure at the opening, page 87 Table 5–35: Allowable overpressure at IBD, page 87 Table 5–36: IBD distances to protect against airblast, page 88 Table 6–1: Grounding system inspection and test requirements, page 110 Table 6–2: Ground rod quantity requirements, page 110 Table 6–3: Minimum safe distance from transmitter antennas, page 111 Table 6–4 (PAGE 1): Safe separation distance equations, page 113 Table 6–4 (PAGE 2): Safe separation distance equations, page 113 Table 8–1: Intermagazine separation for barricaded storage modules for mass detonating explosives, page 136 Table 11–1: Mixed class/division for QD computations, page 147 Table 11–2 (PAGE 1): Quantity-distance separations for pier and wharf facilities, page 148 Table 11–2 (PAGE 2): Quantity-distance separations for pier and wharf facilities--Continued, page 148 Table 11–3: Variation of MPS QD factors with loadout, page 148 Table 12–1: Lightning protection systems, page 154 Table 14–1: Quantity-distance table for basic load ammunition holding areas, page 177 Table 14–1A: Quantity-distance for armored vehicles, page 177 Table 14–2: Minimum Quantity-Distance for hardened aircraft shelters (HAS) for propagation prevention, page 179 Table 14–3: Minimum Quantity Distance for Hardened Aircraft Shelters for Asset Preservation, page 180 Table 14–3A: Quantity-distance from a U.S. third-generation hardened aircraft shelter PES to an unhardened exposed site1,2, page 180 Table 14–4: Quantity-distance for assets preservation at airfields, page 181 Table 15–1: Wartime compatibility chart, page 188 Table 15–2: Q-D for field storage and handling areas., page 189 Table 16–1: Turning of commercial dynamite, page 190 Table B–1: Test probe C and P distances, page 213 Table F–1: Safe conveyor spacing, page 222 Table I–1A: Hazard subdivision 1.2.1 QD for munitions with NEWQD > 1.60 pounds, page 241 Table I–1B: Minimum fragment distances for HD 1.2.1 items stored in structures, which can contribute to the debris hazard, page 242 Table I–2: Hazard subdivision 1.2.2 Quantity-Distances (IBD, PTR, and ILD) for munitions with NEWQD 1.60 pounds, page 243 Table I–3: Summary of hazard subdivisions 1.2.1, 1.2.2, and 1.2.3 quantity-distances (NOTE: all distances shown are in feet), page 244 Table I–4: Hazard subdivision 1.2.1, 1.2.2, and 1.2.3 mixing rules, page 244 DA PAM 385–64 • 15 December 1999 ix Contents—Continued Table J–1: Army Explosives Safety Courses, page 249 Figure List Figure 2–1 (PAGE 1): Risk management, page 7 Figure 2–1 (PAGE 2): Risk management, page 8 Figure 3–1: Fire symbol 1 — mass detonation, page 22 Figure 3–2: Fire symbol 2 — explosion with fragments, page 23 Figure 3–3: Fire symbol 3 — mass fire, page 24 Figure 3–4: Fire symbol 4 — moderate fire, page 25 Figure 3–5: Chemical hazard symbol 1, page 26 Figure 3–6: Chemical hazard symbol 2, page 27 Figure 3–7: Chemical hazard symbol 3, page 28 Figure 5–1: Impulse noise zones for various B-durations and peak sound pressures, page 89
Figure 5–2: Impulse noise zones from intentional detonations, page 90 Figure 5–3: Intermagazine hazard factors, page 91 Figure 5–4: Intermagazine hazard factors, page 92 Figure 5–5: Intermagazine hazard factors, page 92 Figure 5–6: Intermagazine hazard factors, page 93 Figure 5–7: Intermagazine hazard factors, page 93 Figure 5–8: Intermagazine hazard factors, page 94 Figure 5–9: Intermagazine hazard factors, page 95 Figure 5–10: Typical Underground Facilities, page 96 Figure 5–11: Constant Pressure Contour, page 97 Figure 5–12: Debris Dispersal Functions, page 98 Figure 6–1: Typical Ground Rod Installation, page 114 Figure 6–2: Typical multiple ground rod installation, page 114 Figure 6–3: Typical ground loop installation, page 115 Figure 6–4: U.S. Navy designed earth electrode subsystem, page 116 Figure 6–5: Typical grid installation, page 117 Figure 6–6: Typical radial installation, page 118 Figure 6–7: Typical buried plates or cones installation, page 119 Figure 8–1: Typical 8–cell module, page 136 Figure 8–2: Determination of barricade height, page 137 Figure 8–3: Determination of barrricade length, page 138 Figure 8–4: Barricade locations, page 139 Figure 14–1: Hardened aircraft shelter an as exposed site, page 181 Figure 14–2: Hardened aircraft shelter as a PES, page 182 Figure 14–3: Igloo Q-D angles, page 183 Figure B–1: Measurement of soil resistivity, page 214 Figure B–2: Resistivity determination of a small site, page 215 Figure B–3: Fall of potential method for measuring the resistance of earth electrodes, page 216 Figure B–4: Fall of potential resistance to earth test, page 217 Figure D–1: Testing lightning protection system, page 221 Figure H–1: Zone of protection test, page 232 Figure H–2: Zone of protection for integral systems, page 233 Figure H–3: Illustrated zone of protection, page 234 Figure H–4: Zone of protection geometric concept, page 235 Figure H–5: Adequate protection not penetrating earth cover, page 236 Figure H–6: Adequate protection penetrating earth cover, page 237 Figure H–7: Inadequate protection penetrating earth cover, page 237 Glossary Index x DA PAM 385–64 • 15 December 1999 Chapter 1 Introduction 1–1. Purpose This pamphlet explains the Army’s safety criteria and standards for operations involving ammunition and explosives prescribed by AR 385–64, for the United States Army, GOCO facilities, and contractor operations on Government property.
1–2. References Required and related publications are listed in appendix A.
1–3. Explanation of abbreviations and terms Abbreviations and special terms used in this pamphlet are explained in the glossary.
1–4. Implementation
a. This pamphlet provides the guidance to implement AR 385–64. Adhering to its procedures will ensure safe and proper storage and handling of ammunition and explosives. Mandatory requirements are those in which the term “shall,” “will,” or “must” is used and no deviation is permitted without specific written authority in the form of a waiver or exemption as detailed in AR 385–64. Advisory provisions are those in which the term “may” or “should” is used, and no deviation is permitted unless local waivers are authorized in writing by local commander or his or her designee. In new construction or building modification, advisory standards be come mandatory.
b. Some of the procedures used in carrying out the U.S. Army Explosives Safety Program are outlined in publications that are not published by the Army and are not available through standard supply channels. For example, several are published by the National Fire Protection Association (NFPA) and some by the American National Standards Institute (ANSI).
1–5. Policy on existing explosives facilities A program should be locally developed to correct deficiencies if such deficiencies exist where previously constructed explosives facilities do not comply with current safety standards. The program priority items should be based on a hazard analysis and risk assessment of each violation.
Chapter 2 General Safety Precautions 2–1. Hazard analysis and risk assessment All operations involving ammunition and explosives will be reviewed to identify and manage the risk associated with the operation (see fig 2–1).
a. A risk assessment shall be performed on all new or modified industrial operations and facilities involving ammunition and explosives. Based upon this assessment, engineering design criteria for the facility and/or operation will be developed to select appropriate equipment, shielding, engineering controls, and protective clothing for personnel.
The assessment will review such factors as—
(1) Initiation sensitivity;
(2) Quantity of materials;
(3) Heat output;
(4) Rate of burning;
(5) Potential ignition and initiation sources;
(6) Protection capabilities of shields, various types of clothing, and fire protection systems; and,
(7) The acute and chronic health hazards of hot vapors and combustion products on exposed personnel.
b. Ammunition and explosives operations will require an operational or task hazard analysis prior to writing a new standing operating procedure (SOP) for an ammunition or explosives operation or before the biannual review of an existing ammunition or explosives operation.
c. Personnel conducting the hazard analysis will be knowledgeable—
(1) In ammunition and explosives safety;
(2) In the task to be performed; and,
(3) In the methods used to conduct a hazard analysis.
DA PAM 385–64 • 15 December 1999 1 2–2. Personnel qualifications Personnel working with explosives will be trained in the tasks to be performed. They must understand the hazards, standards, procedures, and precautions that apply to their work.
2–3. Use of written standards Written standards must be developed and used for each explosives operation. These standards may be based on standards found in Army publications such as regulations or technical manuals, or in higher headquarters standard publications.
a. SOPs for all explosives operations ensure workers have the information necessary to perform their tasks safely.
Each worker will read the SOP or have the SOP read aloud before starting the operation. SOPs must be readily available at the work site. Applicable parts of the SOP will be clearly posted at all workstations in the operation, such as bays within a building. When posting within the work site is not practical, the SOP will be posted at the entrance to the site.
b. All SOPs for explosives operations will identify potentially hazardous items or conditions. Explosives workers observing hazardous or potentially hazardous conditions will notify their supervisor immediately. Supervisors will correct the operations or practices which, if allowed to continue, could reasonably be expected to cause death or serious physical harm to personnel or major system damage, or endanger the installation’s capacity to accomplish its mission.
c. Procedures will be written in English and in the language workers understand if they do not understand English.
d. Written procedures are not required for explosives ordnance disposal (EOD) emergency operations in connection with an approved render-safe procedure.
2–4. Personnel and explosives limits Operations must be conducted in a manner which exposes the minimum number of people to the smallest quantity of explosives for the shortest period of time consistent with conducting the operation. Examples are as follows:
a. Tasks not necessary to the operation will be prohibited within the immediate area of the hazard produced by the operation.
b. Personnel limits must be clearly posted for each operation and must not be exceeded during the operation. Limits for explosives operations will be included in the SOP.
c. Where concurrent operations must be performed in a single building, the layout will be planned to protect from blast overpressure and to provide separation of dissimilar explosives hazards by using substantial dividing walls, barricades, or other means to ensure maximum personnel protection.
d. Personnel not needed for the operation will be prohibited from visiting. This does not prohibit official visits by safety, quality control (QC), management, or inspection personnel, up to established personnel limits.
e. Each worker will ensure explosives limits for the work area are not exceeded. Limits will be expressed in total net explosive weight (NEW), number of units, or the number of trays, boxes, pallets, or other units which are more easily controlled.
f. Explosives limits will be based on the minimum quantity of explosives sufficient for the operation. Limits will not exceed the quantity used during half a work shift, and will be consistent with quantity-distance (Q-D) separation criteria.
g. The maximum amount of explosives of each hazard division (HD) allowed will be clearly posted in each room, cubicle, magazine, or building used for storing explosives. For operating locations, post the explosives limits for the operation being conducted. Material limits need only be posted in storage magazines if the limit is not the same as that for other magazines in the block or if the limit would not be readily apparent due to some unusual circumstances.
2–5. Handling and movement precautions Munitions and/or explosives will be handled only by trained personnel who understand the hazards and risks involved in the operation. Supervisors will be trained to recognize and abate hazards associated with their operations.
a. Detonators, initiators, squibs, blasting caps (electrical and nonelectrical), and other initiating devices will be 2 DA PAM 385–64 • 15 December 1999 carried in protective containers. The containers must prevent item-to-item contact and be marked to identify the contents.
b. Bale hooks will not be used to handle explosives.
c. Nails may be used to secure covers or repair explosives containers only if there is no hazard to the explosive item or of penetrating protective coverings.
d. Nails and other packing materials will comply with technical packing orders, military specifications, or Department of Transportation (DOT) specifications applicable to the item.
e. Munitions will not be tumbled, dragged, dropped, thrown, rolled, or walked. Containers designed with skids may be pushed or pulled for positioning, unless otherwise marked on the container.
f. Conveyors, chutes, hand trucks, and forklifts may be used in atmospheres and locations where they will not create hazards.
g. Sectionalized roller conveyors moving munitions or explosives will be supported and the sections interlocked or secured. Boxes of explosives will not be used to support conveyors.
h. Safety handtools will be constructed of wood or other nonsparking or spark-resistant materials such as bronze which, under normal conditions of use, will not produce sparks. Only properly maintained safety handtools will be used for locations having hazardous concentrations of flammable dusts, gases, vapors, or exposed explosives.
(1) Handtools or other implements used near hazardous materials must be handled carefully and kept clean. All tools will be checked for damage at the start and on completion of work.
(2) If it is necessary to use ferrous metal handtools because of their strength, the immediate area should be free from exposed explosives and other highly combustible materials except in specific operations approved by the installation safety officer.
(3) Safety handtools containing copper or zinc, such as brass or bronze, will not be used in proximity to lead azide or residuals from the treatment of lead azide.
2–6. Housekeeping Ammunition storage, handling, and operating facilities and areas will be maintained free of debris and rubbish and accumulation of oily rags or other material subject to spontaneous ignition.
a. Waste materials.
(1) Waste materials, such as oily rags, hazardous materials, such as explosives scrap, and wood, paper, and combustible packing materials, will not be mixed. Each of these categories of waste will be carefully controlled and placed in separate approved, properly marked containers. The containers will be placed outside the facilities, except for containers required at the work location during operations. Working location containers will be emptied, as needed but at least once each shift.
(2) Containers for explosive waste will have covers, preferably self-closing. Explosives hazardous waste includes scrap powder, initiating or sensitive explosives, sweepings from open explosive areas, and rags contaminated with these explosives.
(a) Receptacles should have enough liquid, normally water or oil, to cover the scraps or rags if this does not add to the hazard.
(b) No. 10 mineral oil is useful for covering white phosphorous (WP), pyrotechnic, tracer, flare, and similar mixtures. If water is used to cover such materials, scrap should be put in so it is immediately immersed to reduce any production of dangerous gases.
(3) Hazardous waste material will be removed from operating buildings to the disposal area (or an isolated, temporary collection point) at frequent intervals and before leaving at the end of the duty day or shift. When isolated collection points are used, time and quantity limits, which comply with environmental regulations, will be set up to ensure timely movement of the material to the disposal area. Hazardous material should not be “stored” in the disposal area but disposed of as soon as possible after arrival.
(4) Hazardous wastes will be disposed of in authorized facilities. A SOP will cover disposal operations. The DA PAM 385–64 • 15 December 1999 3 organization responsible for hazardous waste disposal will include disposal facilities on waste disposal permits, as required by the Environmental Protection Agency (EPA).
b. Cleaning. A regular cleaning program will be established. To ensure safety, frequency, especially in operating buildings, will depend on local conditions.
(1) General cleaning will not be done during an explosives operation or while explosives are in operating buildings.
(2) Where there are exposed explosives or a risk from accumulating explosives, structural members, radiators, heating coils, pipes, and electrical fixtures will be kept clean.
c. Sweeping compounds.
(1) Sweeping compounds containing wax or oil will not be used on conductive floors.
(2) Cleaning agents that include caustic alkalis must not be used in locations containing exposed explosives because sensitive explosive compounds may form.
(3) Where there may be exposed explosives on the floor, hot water or steam is the preferred cleaning method. When sweeping compounds must be used, they will be nonabrasive.
(4) Sweeping compounds may be combustible but will not be volatile (closed cup flashpoint will not be less than 230 degrees Fahrenheit).
d. Explosives recovery and re-use. All loose explosives recovered as sweepings will be destroyed.
2–7. Testing, disassembly, and modification of explosives items This paragraph gives precautions to take during testing, disassembly, and modification of explosives items.
a. All testing, disassembly, and modification operations will be done by qualified technicians according to approved SOPs. The supervisor will provide any necessary drawings and sketches.
b. Modification, testing, or disassembly of explosives items is permitted for any one of the following circumstances:
(1) When authorized by approved publications.
(2) When approval has been granted by the MACOM and the item manager or system program office.
(3) When EOD personnel require disassembly for technical intelligence or emergency render-safe operations.
(4) When conducted as part of an approved organization mission that includes research, development, or test of explosives items or explosive equipment.
c. Operational…