Drawings_BLDG_34280_-_W911SG-18-R-0071.pdf
PDF 14 MB Posted
- Attached to
- BLDG 34280 INTERNAL WATER LINE REPLACEMENT
- Solicitation number
- W911SG-18-R-0071
About this file
Drawings BLDG 34280 - W911SG-18-R-0071
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 52.218-4201_UXO_POLICY.pdf | ||
| SOLICITATION_-_W911SG-18-R-0071.pdf | ||
| WSMR_Visitor_Control_Program.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S
ENGINEERING SERVICES DIVISION
DIRECTORATE OF PUBLIC WORKS
WHITE SANDS MISSILE RANGE, NEW MEXICO
DESIGN BRANCH
T
CIR
'A
EMA
FO
EC
AL
PH
TR
IB
I H
W
SDNAS
E R
ELISSIM
YTI
V
E G
ITCA
ECAPS&
N A
ELISSIM
SHEET INDEX
DRAWING NUMBER TITLE
WS-34280-2018-G-G1-01 Building 34280 Cover Sheet/Index Sheet
WS-34280-2018-P-P-02 Building 34280 Plumbing Demo Plan
WS-34280-2018-P-P-03 Building 34280 Plumbing Plan
WS-34280-2018-E-E-04 Building 34280 Electrical
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
ANSI D
DRAWING TITLE
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
RAFAEL ACOSTA
RAFAEL ACOSTA
WILLIAM R. RUCKER
RAFAEL H. ACOSTA
SAMUEL E. MORRIS, JR.
NTS
B34280 REPLACE ALL INTERNAL WATER LINES
WS-34200-2017-G-G1-01
COVER SHEET / INDEX SHEET
BUILDING 34200
ISSUED FOR CONSTRUCTION
MEN'S REST ROOM
WOMEN
ROOM
MECHANICAL
ROOM
CORRIDOR
ENTRY
FOYER
SUPPORT
SUPERVISOR CONFERENCE ROOM
RECEPTIONIST
TELEMETRY LABENTRY
FOYER
BREAK
ROOM
WATER HEATER
4 5
JANITOR
CLOSET
60'-0" 55'-6"
11'-2"
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
1/4" =1'
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34280-2018-P-EP-2
BUILDING 34280
PLUMBING DEMO PLAN
BUILDING 34280 PLUMBING PLAN
GENERAL NOTES
1. REFERENCE LEAD &ASBESTOS SURVEY IN STATEMENT OF WORK FOR IDENTIFIED HAZARDOUS
MATERIAL. IT IS THE CONTRACTORS RESPONIBILITY TO PERFORM ANY ABATEMENT AS SPECIFIED IN
THE STATEMENT OF WORK
KEYED NOTES
DEMO 2" INSULATED COPPER PIPE AND VALVES FROM POINT 4" ABOVE UNDER SLAB ENTRY TO
MECHANICAL NORTH WALL. CAP PIPE AND SEAL CMU OPENING WITH FOAM AND CEMENT FINISH AT
NORTH WALL. LEAVE STUB UP AT SLAB FOR NEW CONNECTION TO NEW WATER LINE.
2 DEMO THREE VERTICAL INSULATED COPPER LINES AND VALVES FROM HORIZONTAL PIPE TO CEILING.
COPPER LINES ARE APPROXIMATELY 1-1/4", 1" AND 12" IN DIA. CAP PIPE AT CEILING, CEILING HEIGHT IS 9
FEET.
3 DEMO VERTICAL AND HORIZONTAL 34" INULATED HOT WATER COPPERLINE ALONG NORTH WALL. CAP PIPE AND SEAL CMU OPENING WITH FOAM AND CEMENT FINISH. CAP PIPE AT CEILING HEIGHT.
4 DEMO 34"HOT AND 1"COLD INSULATED COPPER WATER LINES ABOVE CEILING. HARD CEILING MAY HAVE TO BE REMOVED TO ACCESS PIPING. REPAIR REMOVED CEILING WITH LIKE MATERIALS AND MATCH EXISTING FINISHES. ACCESS TO CEILING SPACE MAY BE ENTERED AT MECHANICAL ROOM.
Rafael Acosta
Rafael Acosta
Bill Rucker
Rafael Acosta
Samuel Morris
65% DESIGN SUBMISSION
65% DESIGN SUBMISSION65% DESIGN SUBMISSIONISSUED FOR CONSTRUCTION
02/06/17 ANSI D
5 DISCONNECT HOT AND COLD WATER PIPING AT PLUMBING FIXTURES AND REMOVE ALL PIPING AND
INSULATION IN CHASE .
2 4
ROOM
MECHANICAL
ROOM
CORRIDOR
ENTRY
FOYER
SUPPORT
SUPERVISOR CONFERENCE ROOM
RECEPTIONIST
TELEMETRY LABENTRY
FOYER
BREAK
ROOM
WATER HEATER
JANITOR
CLOSET
24' - 4" 60'-0" 11'-2"
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
1/4" =1'
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34200-2017-P/A-EP-X
BUILDING 34280
PLUMBING PLAN
BUILDING 34280 PLUMBING PLAN
GENERAL NOTES
1. REFERENCE LEAD &ASBESTOS SURVEY IN STATEMENT OF WORK FOR IDENTIFIED HAZARDOUS
MATERIAL. IT IS THE CONTRACTORS RESPONIBILITY TO PERFORM ABATEMENT AS SPECIFIED IN THE
STATEMENT OF WORK.
KEYED NOTES
INSTALL NEW 1-1/2" COPPER LINE RISER WHERE EXISTING PIPE WAS DEMOLISHED. INSTALL
REGULATING VALVE AT 1 FOOT HEIGHT WITH INLET AND OUTLET PRESSURE GAUGES. INSTALL 1-1/2"
COPPER LINE FROM RISER TO NORTH WALL AT SAME PREVIOUS HEIGHT BELOW ELECTRICAL.
SUPPORT RISER AND VALVE TO SLAB OR WALL. RECONNECT ELECTRICAL GROUNDING TO COPPER
PIPE. INSULATE WATER LINE WITH 1" FLEXIBLE ELASTOMERIC INSULATION.
INSTALL NEW TEE CONNECTION WITH 1" PEX PIPE AND LEVER BRASS BALL VALVE, CONNECTED TO EXISTING WATER HEATER. INSTALL 1" PEX PIPE TO CEILING HEIGHT AND TOP OF CHASE. ANCHOR
PIPING TO CMU WALL. INSULATE WATER LINE WITH 1" FLEXIBLE ELASTOMERIC INSULATION.
INSTALL NEW 1" PEX PIPE WITH LEVER BRASS VALVE UP TO CEILING HEIGHT AND TOP OF CHASE.
ANCHOR PIPING TO CMU WALL INSULATE WATER LINE WITH 1" FLEXIBLE ELASTOMERIC INSULATION.
INSTALL NEW 1" COLD AND HOT PEX WATER LINE TO PLUMBING FIXTURES ABOVE CHASE. DROP 12"
COLD AND HOT PEX WATER LINES TO FIXTURES AND CONNECT TO EXISTING VALVES AT EACH
PLUMBING FIXTURE. INSULATE WATER LINE WITH 1" FLEXIBLE ELASTOMERIC INSULATION.
DEMOLITION OF HARD CEILING MAY BE REQUIRED TO COMPLETE WORK. ANY CEILING REMOVED
SHALL BE REPLACED WITH LIKE MATERIALS AND FINISHES.
5 INSTALL NEW INSTANTANEOUS WATER HEATER UNDER THE LAVATORY MODEL CHRONOMITE
SR-20L/208. INSTALLATION SHALL BE PER MANUFACTURERS INSTRUCTIONS. SEE ELECTRICAL
DRAWING FOR ELECTRICAL REQUIREMENTS.
6 INSTALL NEW WATER HAMMER ARRESTERS (SIOUX CHIEF 653B) ON HOT AND COLD WATER LINES ABOVE CEILING. INSTALL ACCESS PANEL 18" X 18" METAL (ACUDOR) IN JANITOR CLOSET CEILING..
Rafael Acosta
Rafael Acosta
Bill Rucker
Rafael Acosta
Samuel Morris
65% DESIGN SUBMISSION
65% DESIGN SUBMISSION65% DESIGN SUBMISSIONISSUED FOR CONSTRUCTION
02/06/17 ANSI D
2. ALL PLUMBING WORK SHALL BE PERFORMED IN ACCORDANCE WITH IPC. ALL EXTERIOR COPPER PIPE AND RISER INTO BUILDING SHALL BE TYPE K, ALL INTERIOR PIPE 1" BELOW TO BE PEX CONFORMING TO ASTM F 877. PEX FITTINGS SHALL MEET ASTM F 1807, METAL-INSERT TYPE COPPER OR STAINLESS-STEELCRIMP RINGS AND MATCHING PEX TUBE DIMENSIONS. HYDROSTATIC TEST ALL NEW
PIPING TO 1-1/2 TIMES THE OPERATING PRESSURE FOR NOT LESS THAN 1 HOUR.
3 4
ROOM
MECHANICAL
ROOM
CORRIDOR
ENTRY
FOYER
SUPPORT
SUPERVISOR CONFERENCE ROOM
RECEPTIONIST
TELEMETRY LABENTRY
FOYER
BREAK
ROOM
INSTANTANEOUS
WATER HEATER
JANITOR
CLOSET
30 AMP DISCONNECT
SWITCH
CONDUIT
"WALL
MOUNTED"
J BOX
DESIGNED
CHIEF, ENGINEERING DIVISION
DATE
APPROVED
RECOMMENDED
BRANCH CHIEF
SUBMITTED
PROJECT MANAGER
CHECKED
DRAWN BY
NO. DATE
DRAWING NUMBER
SCALE
SHEET OF
SHEET
DESCRIPTION
REVISIONS
APPROVEDBY
SHEET SIZE
1/4" =1'
WHITE SANDS MISSILE RANGE, NEW MEXICO
DIRECTORATE OF PUBLIC WORKS
ENGINEERING SERVICES DIVISION
DRAWING TITLE
WS-34200-2017-EP-EP-4
BUILDING 34280
ELECTRICAL PLAN
BUILDING 34280 ELECTRICAL PLAN
GENERAL NOTES
1. REFERENCE LEAD &ASBESTOS SURVEY IN STATEMENT OF WORK FOR IDENTIFIED HAZARDOUS
MATERIAL. IT IS THE CONTRACTORS RESPONIBILITY TO PERFORM ABATEMENT AS SPECIFIED IN THE
STATEMENT OF WORK.
KEYED NOTES
ELECTRICAL REQUIREMENTS FOR LAVATORY MODEL CHRONOMITE SR-20L/208 AS SPECIFIED BY
MANUFACTURE'S INSTALLATION MANUAL.
1A) 2 CONDUCTORS (RED AND BLACK) -#12 AWG THHN, 600 V RATED, 30 AMP, COPPER, STRANDED, AND
90 DEG C
(CONDUCTOR IS SIZED AT 125% OF THE WATER HEATER RATING)
1B) DOUBLE POLE 30 AMP BREAKER TO BE RETROFITTED IN EXISTING DISTRIBUTION PANEL
(OVERCURRENT PROTECTION DEVICE SIZED NO MORE THAN 150% OF APPLIANCE
RATING)
1C) EQUIPMENT GROUND: 1 CONDUCTOR (GREEN)-#10 AWG THHN, 600 V RATED, COPPER, STRANDED, AND 90 DEG C
1D) RIGID GALVANIZED CONDUIT 1/2 INCH WITH JBOX
1E) TERMINATE CONDUCTORS TO EXISTING THREE PHASE DISTRIBUTION PANEL.
1D) 2 POLE HEAVY DUTY FUSE DISCONNECT SWITCH, 30 AMPS, 240 VOLTS, AND NEMA 3R.
Cesar Limon
Cesar Limon
Bill Rucker
Rafael Acosta
Samuel Morris
65% DESIGN SUBMISSION
65% DESIGN SUBMISSION65% DESIGN SUBMISSION
ISSUED FOR CONSTRUCTION
02/06/17 ANSI D
2. ALL PLUMBING WORK SHALL BE PERFORMED IN ACCORDANCE WITH IPC. ALL EXTERIOR COPPER PIPE AND RISER INTO BUILDING SHALL BE TYPE K, ALL INTERIOR PIPE 1" BELOW TO BE PEX CONFORMING TO ASTM F 877. PEX FITTINGS SHALL MEET ASTM F 1807, METAL-INSERT TYPE COPPER OR STAINLESS-STEELCRIMP RINGS AND MATCHING PEX TUBE DIMENSIONS. HYDROSTATIC TEST ALL NEW
PIPING TO 1-1/2 TIMES THE OPERATING PRESSURE FOR NOT LESS THAN 1 HOUR.
EXISTING 208 / 120 V, THREE PHASE PANEL, AND WIRE TROUGH.
3. CONDUIT:
A) FITTINGS REQUIRED TO COMPLETE ELECTRICAL CONDUIT SYSTEMS. INCLUDES CAPS, CONNECTORS, COUPLINGS
(EXCLUDING EXPANSION AND EXPANSION-DEFLECTION COUPLINGS), NIPPLES, REDUCERS, ELBOWS, PIPE, PLUGS LOCKNUTS, BOND NUTS, BUSHINGS, SEALS (EXCLUDING WALL PENETRATION AND ANY OTHER FITTINGS.)
B) DEVICES REQUIRED TO COMPLETE ELECTRICAL CONDUIT SYSTEMS AND TO FASTEN, CLAMP, ATTACH, AND
SUPPORT EACH CONDUIT IN PLACE.
1) INCLUDES THREADED JOINT COMPOUND; PROTECTIVE SEALANT; MATERIALS FOR SEALING ENDS OF CONDUITS
TERMINATING AT OUTDOOR BOXES, PANEL BOARDS OR CABINETS; SUPPORTS AND CLAMPS.
2) COMPLETE WITH BOLTS, WASHERS, AND NUTS.
A) JUNCTION BOX, JUNCTION BOX EXTENSIONS, AND JUNCTION BOX COVERS: STEEL, OR ZINC COATED.
B) EXPANSION COUPLINGS:
1) FURNISH FOR LONGITUDINAL MOVEMENT ONLY.
4. ALL ELECTRICAL CONNECTIONS MUST BE PROPERLY TORQUED TO PREVENT EXCESSIVE HEAT BUILDUP CAUSED BY A LOOSE CONNECTION OR DAMAGE OF THE CONDUCTOR All CAUSED BY OVERHEATING. TOO LOOSE A CONNECTION OR TOO TIGHT A CONNECTION CAN CAUSE PROBLEMS. CIRCUIT BREAKER TERMINALS DIFFER FROM SWITCH AND AND RECEPTACLE TERMINALS IN
TIGHTENING WITH PROPER TORQUE.
a) TERMINAL CONNECTORS:
1. HEAVY-DUTY, PRE INSULATED, PRESSURE-CRIMP TYPE WITH RING TONGUES.
2. TIN-PLATED COPPER.
3. SERRATED INNER BARREL.
4. 600-VOLT-RATED VOLT-RATED NYLON INSULATION.
5. INSULATION SUPPORT SLEEVE FOR VIBRATION RESISTANCE.
6. UL LISTED.
7. COMPATIBLE WITH CONDUCTOR SIZE AND TYPE OF CABLE FOR WHICH IT
USED.
5. MODEL SR-20L/208 SINGLE PHASE ELECTRICAL SPECS:
VOLTAGE: 208 V
WATTS: 4160 W
AMPERAGE CAPACITY: 20 A
6. CONTRACTOR SHALL INSTALL ALL ELECTRICAL EQUIPMENT TO FOLLOW THE NEC 2017.
7. DRILL HOLES AS NEEDED IN CONCRETE FOR INSTALLATION OF CONDUIT THRU WALLS. GROUT
CONDUIT IN PLACE IN ACCORDANCE NO SHRINK GROUT. CONTRACTOR SHALL
SUBMIT APPROVAL DATA (MANUFACTURER'S PRODUCT DATA) AND INSTRUCTIONS
(MANUFACTURER'S SURFACE PREPARATION, MIXING, INSTALLATION, AND CURING INSTRUCTIONS).
8. CONDUIT WALL/FLOOR PENETRATION SEALS:
-ELASTOMERIC MATERIAL TO PREVENT LIQUID OR LIQUID AND GAS SEEPAGE.
-DUST TIGHT.
-FIRE RETARDANT.
REMOVE BURRS AND SHARP CORNERS AT ENDS OF METAL CONDUIT.
4 4
| Sheets and Views |
| 34280RA-COVER SHEET |
| 34280RA-PLUMBING DEMO PLAN |
| 34280RA-PLUMBING PLAN) |