44026-E1
E1
SCALE OF FEET
030 30 60
N
1 SCALE: 30’ = 1’-0"
E1
M2
M2
M
M
M
M7 M
M
M
OVERALL ELECTRICAL SITE PLAN
LEGEND
SPECIAL ELECTRICAL KEYED NOTES:
OVERALL ELECTRICAL SITE PLAN
SIT (STATIONARY INFANTRY TARGET)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
SEE ELECTRICAL SCOPE OF WORK FOR MORE DETAILS.
ALL EXTERIOR MOUNTED LOAD CENTERS TO BE NEMA 3R.
MINIMIZED.
BIRD-NESTING SEASONS, 15 MARCH THROUGH 31 MAY, CLEARING AND GRUBBING OPERATIONS SHALL BE
CONTRACTOR MAY PERFORM CONSTRUCTION WORK WITHIN THE NON-CORE HABITAT AREA; HOWEVER, DURING
UXO AREA TO GAIN ACCESS TO OTHER CONSTRUCTION AREAS.
UNEXPLODED ORDANCE (UXO) AREA AT ANY TIME; HOWEVER, CONTRACTOR MAY USE EXISTING ROADS IN THE
CONTRACTOR SHALL NOT ENCROACH OR PERFORM ANT CONSTRUCTION OPERATIONS WITHIN THE LIMITS OF THE
NO SPLICING OF ELECTRICAL CABLES BETWEEN MANHOLES AND EMPLACEMENTS.
ROW OR LANE COMMON TRENCHING.
ALL RANGE AREA PRIMARY, SECONDARY ELECTRICAL AND COMMUNICATION CABLE SHALL BE INSTALLED IN
ENCASED DUCTS THREE (3) FEETS BEYOND ROAD ON EACH SIDE.
ALL CONDUITS CROSSING ROADS AND SERVICE DRIVES WILL BE CONCRETE ENCASED. EXTEND CONCRETE
FORT BENNING DIRECTORATE OF PUBLIC WORK (DPW).
ALL PRIMARY OUTAGE WILL BE COORDINATED WITH THE AREA OFFICE OF CORP. OF ENGINEERS AND
NO SPLICING OF CABLES BETWEEN THE EMPLACEMENTS IS ALLOWED.
PERCENT OF THE SUPPLYING TRANSFORMER’S SECONDARY VOLTAGE.
OPERATING VOLTAGE AT THE MOST DISTANT EMPLACEMENT OR TARGET SHOULD NOT BE LESS THAN 95
FROM THE EMPLACEMENT.
DIRECT BURIED CABLES SHALL FEED EMPLACEMENTS THROUGH CONDUIT THAT IS STUBBED OUT 5 FEET
PENETRATION.
ACTUAL DEPTH OF THE CABLES SHALL BE DEEP ENOUGH TO PREVENT DANAGE FROM THE PROJECTILE
CONCRETE ENCASED DUCT BANKS MUST BE USED WHENEVER TRENCHING UNDERNEATH ROAD SYSTEMS.
MUCH AS PRACTICAL TO MINIMUM DISTURBANCE.
DESIGNER SHOULD ROUTE THE TRENCHES ALONG THE ACCESS ROADS AND THE MAINTENANCE TRAILS AS
ROADS AND MAINTENANCE ROADS.
REDUCE THE AMOUNT OF TRENCHING ON DOWN RANGE BY PLACING ELECTRICAL TRENCHES ALONG COURSE
CENTER FEEDERS FROM ROC-TOWER POWER PANELS PRIOR TO DETERMINING THE FEEDER WIRE SIZE.
IT IS IMPORTANT THAT DETAILED VOLTAGE DROP CALCULATIONS BE PERFORMED ON ALL TARGET LOAD
RANGES.
CAN CARRY THE LOAD OF THE ENTIRE RANGE IF ONE FEEDER MUST BACK FEED TARGETS ON OTHER
PHASES TO RUN DOWN RANGE, AND THE PRIMARY FEEDERS SHOULD BE SIZED SUCH THAT EACH FEEDER
THE DESIGNER SHOULD CONSIDER PHASE IMBALANCE ON UTILITY SYSTEM WHEN SELECTING SELECTING
THE DESIGNER SHOULD CONSIDER THE MEANS TO BACK FEED TARGETS EVERYWHERE PRACTICAL.
BE CLEAR OF TREES, BUSHES, STUMPS, LEDGE, LARGE ROCKS AND OTHER IMPEDIMENTS.
ALL TRENCH LINES SHALL BE NOT LESS THAN TEN FEET FROM THE ROAD. THE TRENCH ROUTE MUST
REQUIREMENTS WITHOUT EXCEPTION.
ALL EXCAVATION AND ROADWAY WORK SHALL ADHERE TO OSHA, DOT, AND FLINT ELECTRIC SAFETY
BY THE LOCAL UTILITY.
THE MINIMUM CABLE DEPTHS FOR MEDIUM VOLTAGE POWER ARE 48-INCH OR THE DEPTHS DETERMINED
CODE HAS A MINIMUM REQUIREMENTS FOR TRENCHING DEPTHS. FOR DOWNRANGE PORTION OF RANGES
THE POWER AND DATA CABLES SHALL BE INSTALLED IN THE SAME TRENCH. THE NATIONAL ELECTRIC
THE OSCAR 5 (MORRIS RANGE). USE FIBER OPTIC COMMUNICATION DISTRIBUTION SYSTEM.
CONTRACTOR IS REQUIRED TO DESIGN THE DOWNGROUND POWER AND DATA DISTRIBUTION SYSTEMS FOR
ELECTRICAL DESIGN FOR THE GOVERNMENT APPROVAL BEFORE STARTING THEIR WORK.
THIS IS 1 35% DESIGN BID DOCUMENTS. CONTRACTOR IS REQUIRED TO SUBMIT THE 100%
S Y
M B
O L
D A
T E
B Y
R E
V I S I O
N S
DRAWN BY:
APPROVED BY:
D.SAYLOR
L&E NO:
DRAWING NUMBER: SCALE:
AS NOTED
DATE:
FORT BENNING, GEORGIA
FORT BENNING, GEORGIA
F I L
E N
A M
E
DIRECTORATE
OF PUBLIC WORKS
K. CHAN
15 FEB 2019
PISTOL QUALIFICATION COURSE RANGE
CONVERT OSCAR 5 RANGE TO COMBAT