ASCE-DRM-CO

27 July 2016

USMA PURCHASE DESCRIPTION

Air Conditioner, Portable, 60,000 Btu/Hr

This PD describes a portable air conditioner with programmable controls providing up to 60,000 Btu/Hr with a programmable controls.

Specifications

Cooling Capacity: Rating Conditions 95F at 60% RH 60,000 Btu/h

Electrical Characteristics: Voltage Requirement: 1 Phase, 208/230v Power Consumption: 6.6 kW Current Consumption 29 amps Recommended Fuse Size 50 amps NEMA Plug Configuration 6 – 50 Min. Max. Voltage 198 – 250

Fans: Motor Output 0.5 / 0.33 kW Evap.

1.2 / 0.93 kW Cond.

Evaporator: Fan Type Centrifugal Max Air Flow High/low 1940 / 1770 CFM Max External Static Pressure 0.9 IWG

Compressor: Type Hermetic Rotary Output 3.9 kW

Refrigerant: R-410A 3.97 Lb

Power Cord: Gauge 6 AWG (3-core) Minimum Length 6 Ft.

Condensate; Removal Collection tank With Auto pump

Operating Conditions: Min. Max (@ 50% RH) 650 – 1050F

Duct Length: Per Cold Duct Hose 40 Ft.

Hot Duct Hose 6 Ft.

Max Sound Level; With Condenser – Duct High/low 69/67 dB(A) Without Condenser – Duct High/low 71/69 dB(A)

Accessories

Each air conditioner unit shall also include:

One 24" x 24" sheet metal tile with 16" hole for warm air flexible duct.

One 16" diameter wire-reinforced, accordion-style duct in 25' length for condenser exhaust or evaporator intake.

Two Duct clamps for 16” diameter wire-reinforced accordion-style duct.

A condensate tank with float control of water level for automated relief pump.

Two replacement dust/air filters.

Four heavy duty casters of sufficient rating to support and move the air conditioner safely with a minimum of two casters swiveling and two locking.

Warranty

Each air conditioner unit shall be warranted against defect for a minimum of one year.

Delivery

Each unit shall be delivered to:

The United States Military Academy, West Point Cadet Uniform Factory 687 Hardee Place West Point, NY 10996.

This delivery address is equipped with a standard height loading dock and freight elevator for movement of unit(s) into any floor of the building.