AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

EIE393 Renovate 8-Bay Weather Shelter, Eielson AFB, AK.

a. This amendment provides changes to the solicitation as indicated on the continuation pages of this document.

b. Proposal due date is now 29 January 2018 at 2:00 PM Alaska time.

c. YOU ARE REQUIRED TO ACKNOWLEDGE RECEIPT OF THIS AMENDMENT ON THE REVERSE SIDE OF THE STANDARD FORM 1442.

1. CONTRACT ID CODE PAGE OF PAGES

1 101

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 22-Jan-2018

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W911KB18R0020

X 9B. DATED (SEE ITEM 11)

22-Dec-2017

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

22-Jan-2018

CODE

U.S. ARMY ENGINEER DISTRICT, AK

CEPOA-CT (W911KB)

PO BOX 6898

JBER AK 99506-0898

W911KB 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

EIE393 – AM#3

SUMMARY OF CHANGES

A. The following drawings were included in the original solicitation and are substituted for the superseded documents:

1. EIE393 –A-002

2. EIE393 – A-122

3. EIE393 – A-132

4. EIE393 – A-202

5. EIE393 – A-204

6. EIE393 – A-206

7. EIE393 – A-501

8. EIE393 – A-504

9. EIE393 – A-507

10. EIE393 – A-601B

11. EIE393 – A-602

12. EIE393 – M-006

13. EIE393 – M-007

14. EIE393 – M-414

15. EIE393 – X-103

B. No additional drawings are added.

C. The following original specifications are revised as indicated:

1. 01 50 00.04 29 TEMPORARY CONSTRUCTION FACILITIES AND

CONTROLS FOR EIELSON AFB PROJECTS

a. Deleted paragraphs 3.4; 3.4.1; and 3.4.2.

1. 08 71 00 DOOR HARDWARE

a. Revised paragraph 3.5 HARDWARE SETS to add balanced magnetic switch to Door Hardware Set No. 23.

2. 09 29 00 GYPSUM BOARD

a. Revised paragraph 1.2 SUBMITTALS to add Glass Mat Covered or

Reinforced Gypsum Sheathing to SD-03 Product Data.

b. Added new paragraph 2.2.2 Type X (Special Fire-Resistant)

c. Added new paragraph 2.2.2.1 Glass Mat Covered or Reinforced Gypsum

Sheathing Sealant.

d. Revised paragraph 3.2.2 Glass Mat Covered or Fiber Reinforced Gypsum

Sheathing to add in accordance to gypsum association publication GA 253.

e. Added new paragraph 3.5.1 Sealing for Glass Mat or Reinforced Gypsum Board Sheathing.

3. 09 90 00 PAINTS AND COATINGS

a. Revised paragraph 1.2 SUBMITTALS to delete text in SD-03 Product Data and SD-11 Closeout Submittals.

b. Revised paragraph 1.12.1 to add Interior Painting Included and deleted text.

c. Revised paragraph 1.12.3.1 to delete text.

d. Revised paragraph 1.12.4.5 EPP to delete text.

e. Revised paragraph 1.12.4.11 MPI System Number to delete text.

f. Revised paragraph 1.12.4.12 Paint to delete text.

g. Revised paragraph 3.5.3 Coating Systems to add Division 4. Exterior

Concrete Masonry Units Paint Table and to delete text.

h. Revised paragraph 3.6 to delete text.

i. Revised paragraph 3.11 PAINT TABLES to delete text.

j. Revised paragraph 3.11.1 INTERIOR PAINT TABLES to add Division 4:

INTERIOR CONCRETE MASONRY UNITS PAINT TABLE; added C.

Galvanized Metal, Overhead Decking: added NON-HANGAR ROOMS.

4. 09 96 00

a. Revised paragraph 1.1 GENERAL to add SSPC SP 12/NACE No. 5.

b. Revised paragraph 1.2 SUBMITTALS to add Heat-Resistant Coatings.

c. Revised paragraph 2.1.1 to add Heat-Resistant Coatings

d. Added new paragraph 2.1.1.1 Category 2, 300 to 600 Degrees F.

e. Revised paragraph 2.2.1 Epoxy Coatings to delete text.

f. Revised paragraph 2.2.1.1 Masonry Surfaces Coatings to add Hangar Walls.

g. Revised paragraph 2.2.1.3 Gypsum Surfaces to add Hangar Walls

h. Revised paragraph 2.2.1.4 Exterior Ferrous and Galvanized Metal Surface

Coatings to add Paint interior and exterior side of exterior hollow metal doors and frames.

i. Revised paragraph 2.2.2.1 Aluminum Surface Coatings to add Exterior Windows.

j. Revised paragraph 3.1.1 Surface Preparation to add Presure wash all existing masonry and metal surfaces.

k. Revised paragraph 3.1.3 to add Masonry.

l. Revised paragraph 3.1.3.1 to add Masonry.

5. 10 11 00 VISUAL DISPLAY UNITS

a. Revised paragraph 1.4 SUBMITTALS to add Chain of Command Board to SD-03.

b. Added new paragraph 2.5 CHAIN OF COMMAND BOARD

6. 12 36 00 COUNTERTOPS

a. Revised paragraph 1.2 SUBMITTALS to add Stainless Steel to SD-03;

and to add Recycled Content for Stainless Steel Countertops to AD-11..

b. Added new paragraph 2.1.1 Recycled Content for Countertop Materials.

c. Revised paragraph 2.3.1 FABRICATION to add and Stainless steel; and to add Provide steel no lighter than 22-gage stainless steel.

d. Revised paragraph 3.1.2.1 Stainless Steel Surfacing to add Form counters and work surfaces with exposed edges returned.

D. The following new specification is added to the project:

1. Section 09 72 00 WALL COVERINGS

E. The following documents were included in the original solicitation and are substituted for the superseded documents:

1. EIE393 Project Table of Content

F. Other:

SECTION 00 11 00 – STANDARD FORM (SF) 1442

- The required response date/time has changed from 24-Jan-2017 02:00 PM to 29-Jan-2017 02:00 PM.

(End of Summary of Changes)

AM#3…F-35A Alter AMU/Weather Shelter W911KB-18-R-0020 (Squad #1) B1338 EIE393

PROJECT TABLE OF CONTENTS Page 1

READY TO ADVERTISE JANUARY 19, 2018

PROJECT TABLE OF CONTENTS

VOLUME I

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

00 11 00 SF1442

00 11 01 PROPOSAL SCHEDULE

00 21 00 INSTRUCTIONS, CONDITIONS, AND NOTICES TO OFFERORS

00 22 11 PROPOSAL SUBMISSION REQUIREMENTS (ONE STEP, DB)

ATTACHMENT 1 PROPOSAL DATA SHEET

ATTACHMENT 2 COMPANY SPECIALIZED EXPERIENCE-CONSTRUCTION

OR PRIME CONTRACTOR

ATTACHMENT 3 COMPANY SPECIALIZED EXPERIENCE-KEY

SUBCONTRACTOR

ATTACHMENT 4 PAST PERFORMANCE QUESTIONNAIRE

ATTACHMENT 5 LETTER OF COMMITMENT OF KEY SUBCONTRACTOR

00 45 00 REPRESENTATIONS AND CERTIFICATIONS

00 72 00 CONTRACT CLAUSES

00 73 00.00 29 SPECIAL CONTRACT REQUIREMENTS

00 73 46 WAGE DETERMINATION SCHEDULES

VOLUME II

DIVISION 01 - GENERAL REQUIREMENTS

01 19 30.02 29 SPECIAL ITEMS FOR EIELSON AFB PROJECTS

ATTACHMENT 1 Form AF592, HOT WORK PERMIT

ATTACHMENT 2 BASE CIVIL ENGINEERING WORK CLEARANCE REQUEST

ATTACHMENT 3 SAMPLE LETTER

ATTACHMENT 4 CY2017 UTILITY RATES

ATTACHMENT 5 POD LIGHTNING PROTECTION SYSTEMS MEMORANDUM

ATTACHMENT 6 AIRFIELD GEOTECHNICAL AND SURVEY

CONSTRUCTION FREE ZONE MAP

01 22 00.00 10 PRICE AND PAYMENT PROCEDURES

01 32 01.00 10 PROJECT SCHEDULE

01 33 00 SUBMITTAL PROCEDURES

ATTACHMENT 1 SUBMITTAL REGISTER

ATTACHMENT 2 SAMPLE FORM ENG 4025-R

01 33 29 SUSTAINABILITY REPORTING

ATTACHMENT 1 AF SUSTAINABILITY REQUIREMENTS SCORESHEET

01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS

01 36 00.00 29 RADIOACTIVE MATERIALS PROCEDURES

01 42 00 SOURCES FOR REFERENCE PUBLICATIONS

01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)

01 45 04.00 29 CONTRACTOR QUALITY CONTROL

ATTACHMENT 1 CONTRACTOR'S QUALITY CONTROL REPORT

01 45 35 SPECIAL INSPECTIONS

01 50 00.04 29 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS FOR

EIELSON AFB PROJECTS

PROJECT TABLE OF CONTENTS Page 2

READY TO ADVERTISE JANUARY 19, 2018

01 57 20.01 29 ENVIRONMENTAL PROTECTION

ATTACHMENT 1 2017 EIELSON AFB ENVIRONMENTAL SOP

ATTACHMENT 2 EIELSON DISPOSAL AREAS

ATTACHMENT 3 STOCKPILE DETAILS

ATTACHMENT 4 BUILDING 1307 HTRW REPORT

ATTACHMENT 5 BUILDING 1338 HTRW REPORT

ATTACHMENT 6 DRUM MARKING EXAMPLE

ATTACHMENT 7 EIELSON ASBESTOS MANAGEMENT AND OPERATIONS

PLAN

01 57 34.00 29 STORM WATER POLLUTION PREVENTION MEASURES

ATTACHMENT 1 DELEGATION OF AUTHORITY LETTER TEMPLATE

01 58 00 PROJECT IDENTIFICATION

ATTACHMENT 1 AIRFORCE PROJECT SIGN PLATE 6 AND PLATE 7

01 74 19.01 29 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT

01 78 00 CLOSEOUT SUBMITTALS

ATTACHMENT 1 DD FORM 1354 CHECKLIST

ATTACHMENT 2 EIELSON TECHNICAL REQUIREMENTS FOR GIS,

DRAFTING, AND SURVEYING DELIVERABLES

01 78 23 OPERATION AND MAINTENANCE DATA

01 91 00.15 TOTAL BUILDING COMMISSIONING

ATTACHMENT 1 OWNER’S PROJECT REQUIREMENTS

ATTACHMENT 2 BASIS OF DESIGN

ATTACHMENT 3 COMMISSIONING PLAN

ATTACHMENT 4 PRE-FUNCTIONAL CHECKLIST

ATTACHMENT 5 SAMPLE FUNCTIONAL PERFORMANCE TESTING

VOLUME III

DIVISION 02 - EXISTING CONDITIONS

02 41 00 DEMOLITION

02 61 13 EXCAVATION AND HANDLING OF CONTAMINATED MATERIAL

ATTACHMENT 1 DRAFT F-35 PROGRAMMATIC UFP-QAPP WORK PLAN

DIVISION 03 - CONCRETE

03 30 00 CAST-IN-PLACE CONCRETE

DIVISION 05 - METALS

05 05 23.16 STRUCTURAL WELDING

05 12 00 STRUCTURAL STEEL

05 40 00 COLD-FORMED METAL FRAMING

05 50 13 MISCELLANEOUS METAL FABRICATIONS

05 51 00 METAL STAIRS

05 51 33 METAL LADDERS

05 52 00 METAL RAILINGS

PROJECT TABLE OF CONTENTS Page 3

DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES

06 10 00 ROUGH CARPENTRY

06 20 00 FINISH CARPENTRY

06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS

06 61 16 SOLID SURFACING FABRICATIONS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

07 21 13 BOARD AND BLOCK INSULATION

07 21 16 MINERAL FIBER BLANKET INSULATION

07 22 00 ROOF AND DECK INSULATION

07 42 13 METAL WALL PANELS

07 42 63 FABRICATED WALL PANEL ASSEMBLIES

07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING

07 60 00 FLASHING AND SHEET METAL

07 84 00 FIRESTOPPING

07 92 00 JOINT SEALANTS

DIVISION 08 - OPENINGS

08 11 13 STEEL DOORS AND FRAMES

08 14 00 WOOD DOORS

08 31 00 ACCESS DOORS AND PANELS

08 33 13 COILING COUNTER DOORS

08 33 23 OVERHEAD COILING DOORS

AM#1...08 39 54 BLAST RESISTANT DOORS...AM#1

08 71 00 DOOR HARDWARE

08 71 13 AUTOMATIC DOOR OPERATORS

08 81 00 GLAZING

DIVISION 09 - FINISHES

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 GYPSUM BOARD

09 30 10 CERAMIC, QUARRY, AND GLASS TILING

09 51 00 ACOUSTICAL CEILINGS

09 62 38 STATIC-CONTROL FLOORING

09 65 00 RESILIENT FLOORING

09 67 23.16 FUEL RESISTIVE RESINOUS FLOORING, 5-COAT SYSTEM

09 68 00 CARPETING

AM#3...09 72 00 WALLCOVERINGS...AM#3

09 90 00 PAINTS AND COATINGS

09 96 00 HIGH-PERFORMANCE COATINGS

DIVISION 10 - SPECIALTIES

10 11 00 VISUAL DISPLAY UNITS

10 14 00.10 EXTERIOR SIGNAGE

10 14 00.20 INTERIOR SIGNAGE

10 21 13 TOILET COMPARTMENTS

10 26 00 WALL AND DOOR PROTECTION

PROJECT TABLE OF CONTENTS Page 4

10 28 13 TOILET ACCESSORIES

DIVISION 11 - EQUIPMENT

11 31 13 ELECTRIC KITCHEN EQUIPMENT

DIVISION 12 - FURNISHINGS

12 24 13 ROLLER WINDOW SHADES

AM#2...12 31 00 MANUFACTURED METAL CASEWORK...AM#2

12 36 00 COUNTERTOPS

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

DIVISION 13 - SPECIAL CONSTRUCTION

13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT

13 48 00.00 10 SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT

VOLUME IV

DIVISION 21 - FIRE SUPPRESSION

21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION

ATTACHMENT HANGAR ACCEPTANCE TEST PROCEDURES AFCEC

ATTACHMENT PAT-FAT CHECKLIST

21 13 17.00 10 DRY PIPE SPRINKLER SYSTEM, FIRE PROTECTION

21 13 18.00 10 PREACTION AND DELUGE SPRINKLER SYSTEMS, FIRE PROTECTION

21 13 20.00 20 LOW-LEVEL HIGH EXPANSION FOAM FIRE EXTINGUISHING FOR

AIRCRAFT HANGARS

DIVISION 22 - PLUMBING

22 00 00 PLUMBING, GENERAL PURPOSE

DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)

23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST

SYSTEMS

23 05 15 COMMON PIPING FOR HVAC

23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC

23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS

23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC

23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING

CONTROL SYSTEMS

23 57 10.00 10 FORCED HOT WATER HEATING SYSTEMS USING WATER AND STEAM

HEAT EXCHANGERS

DIVISION 25 - INTEGRATED AUTOMATION

25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END

AND INTEGRATION

PROJECT TABLE OF CONTENTS Page 5

DIVISION 26 - ELECTRICAL

26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT

26 08 00 APPARATUS INSPECTION AND TESTING

26 11 16 SECONDARY UNIT SUBSTATIONS

26 20 00 INTERIOR DISTRIBUTION SYSTEM

26 24 13 SWITCHBOARDS

26 27 14.00 20 ELECTRICITY METERING

26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION

26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS

26 35 44 270 VDC SOLID STATE GROUND POWER UNIT

26 36 00.00 10 AUTOMATIC TRANSFER SWITCH

26 51 00 INTERIOR LIGHTING

25 56 00 EXTERIOR LIGHTING

DIVISION 27 - COMMUNICATIONS

27 05 14.00 10 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM

27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM

DIVISION 28 - ELECTRONIC SAFETY AND SECURITY

28 08 10 ELECTRONIC SECURITY SYSTEM ACCEPTANCE TESTING

28 10 05 ELECTRONIC SECURITY SYSTEMS (ESS)

ATTACHMENT 1 NON-NUCLEAR IDS EQUIPMENT APPROVAL

28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM

DIVISION 31 - EARTHWORK

31 00 00 EARTHWORK

31 09 20.00 29 FIELD SCREEN TESTING OF SOILS FOR CHEMICAL CONTAMINATION

DIVISION 32 - EXTERIOR IMPROVEMENTS

32 01 19 FIELD MOLDED SEALANTS FOR SEALING JOINTS IN RIGID

PAVEMENTS

32 12 15.13 HOT-MIX ASPHALT AIRFIELD PAVING 32 12 16 HOT-MIX ASPHALT

(HMA) FOR ROADS

32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS

32 13 11 CONCRETE PAVEMENT FOR AIRFIELDS AND OTHER HEAVY-DUTY

PAVEMENTS

32 17 23 PAVEMENT MARKINGS

32 31 13 CHAIN LINK FENCES AND GATES

DIVISION 33 - UTILITIES

33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION

33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)

-- End of Project Table of Contents --

AM#3 F-35 RENOVATE AMU/WEATHER SHELTER (B1338) EIE393

EIELSON AFB, ALASKA

allowable load limit. Contractor is responsible for the repair of any damage to roads caused by construction operations.

3.3.3 Dust Control

Dust control methods and procedures must be approved by the Contracting Officer. Treat dust abatement on access roads with applications of calcium chloride, water sprinklers, or similar methods or treatment. See Section 01 19 30.02 29, SPECIAL ITEMS FOR EIELSON AFB PROJECTS, paragraph "DUST CONTROL" for additional requirements.

3.4 AM#3...DELETED TEXT...AM#3

3.4.1 AM#3...DELETED TEXT...AM#3

AM#3...DELETED TEXT...AM#3

3.4.2 AM#3...DELETED TEXT...AM#3

AM#3...DELETED TEXT...AM#3

-- End of Section --

Section 01 50 00.04 29 Page 5

AM#3...F-35A Alter AMU/Weather Shelter W911KB-18-R-0020

DOOR NO. 106A, 134B; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 6 EA A8112 652

LATCHSET 1 EA F01 626

CLOSER 2 EA C02021 ALUM

MANUAL FLUSH

BOLTS

1 P L04081 626

DUSTPROOF STRIKE 1 EA L04021 626

WALL STOP 1 EA L02101 626

GASKET 1 SET R3E165 628

DOOR HARDWARE SET NO. 04

DOOR NO. 106B; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 6 EA A8112 652

LOCKSET 1 EA F07 626

MANUAL FLUSH

BOLTS

1 PR L04081 626

WALL STOP 1 EA L02101 626

SILENCER 4 EA L03011 GREY

DOOR HARDWARE SET NO. 05

DOOR NO. AM#2...108A...AM#2; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A8111 652

EXIT DEVICE 1 EA TYPE 3, FUNCTION

CLOSER 1 EA C02011 ALUM

ARMOR PLATE 1 EA J101 630

WALL STOP 1 EA C02541 626

SECTION 08 71 00 Page 11

GASKET 1 SET R3E165 626

DOOR HARDWARE SET NO. 06

DOOR NO. 109, 110; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A8112 652

PUSH/PULL 1 PR J301/J405 630

CLOSER 1 EA C02011 ALUM.

KICK PLATE 1 EA J102 630

MOP PLATE 1 EA J103 630

WALL STOP 1 EA C02541 626

SILENCER 3 EA L03011 GREY

DOOR HARDWARE SET NO. 07

DOOR NO. 111, 113, 114; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A8112 652

LOCKSET 1 EA F04 626

KICK PLATE 1 EA J102 630

WALL STOP 1 EA L02101 626

GASKET 1 SET R3E165 628

DOOR HARDWARE SET NO. 08

DOOR NO. 117A; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 6 EA A8111 652

SECTION 08 71 00 Page 12

ELECT. EXIT

DEVICE (RHR)

1 EA L2-A156.3 TYPE 3,

FUNCTION 09 G1 -

E06

EXIT DEVICE (LHR) 1 EA TYPE 3, FUNCTION

CYLINDER 1 EA 626

POWER TRANSFER 1 EA ALUM

POWER

SUPPLY/CONTROLLER

1 EA

CARD READER 1 EA SEE SECURITY

KICK PLATE 1 EA J102 630

WALL STOP 1 EA L02101 626

GASKET 1 SET R3E165 628

PRESENTATION OF AN AUTHORIZED CARD TO UNLOCK DOOR FOR 15 SECONDS

DOOR HARDWARE SET NO. 09

DOOR NO. 121A; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

CAM HINGE 3 EA BY DOOR

MANUFACTURER

LOCKSET 1 EA FF-L-2740B ---

LOCKSET 1 EA F30 626

CYLINDER - HIGH

SECURITY

1 EA --- 626

ELECTRIC SPIKE 1 EA E09331 626

KEYPAD/CARD

READER

1 EA SEE SECURITY ---

KEYPAD 1 EA SEE SECURITY ---

CLOSER 1 EA C02011 ALUM

KICK PLATE 1 EA J102 630

SECTION 08 71 00 Page 13

WALL STOP 1 EA L02101 626

GASKET 1 SET BY DOOR

MANUFACTURER

BROWN

AUTO DOOR BOTTOM 1 EA R3C335 626

THRESHOLD 1 EA SEE SECURITY ---

BALANCED

MAGNETIC SWITCH

1 EA SEE SECURITY ---

POWER

SUPPLY/CONTROLLER

1 SET --- ---

ALARM HORN 1 EA SEE SECURITY

ALARM HORN SOUNDS WHEN BALANCED MAGNETIC SWITCH IS OPEN. PRESENTATION OF

VALID CARD AND KEYPAD CODE FROM EXTERIOR OR KEYPAD CODE FROM INTERIOR TO

SHUNT ALARM FOR 20 SECONDS.

DOOR HARDWARE SET NO. 10

DOOR NO. 121B; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

CAM HINGE 6 EA BY DOOR

MANUFACTURER

EXIT DEVICE 1 EA TYPE 11, FUNCTION

AUTO FLUSH BOLTS 1 PR A156.3, TYPE 25 626

KEYPAD 1 EA SEE SECURITY ---

CLOSER 2 EA C02021 ALUM

ASTRAGAL 1 ES R3E635 EXTRA

HEAVY DUTY

KICK PLATE 2 EA J101 630

OVERHEAD STOP 2 EA C02541 626

GASKET 1 SET BY DOOR

MANUFACTURER

BROWN

THRESHOLD 1 EA J32129 719

AUTO DOOR BOTTOM 2 EA R3C335 626

BALANCED

MAGNETIC SWITCH

2 EA SEE SECURITY ---

POWER

SUPPLY/CONTROLLER

1 EA --- ---

ALARM HORN 1 EA SEE SECURITY

SECTION 08 71 00 Page 14

ALARM HORN SOUNDS WHEN BALANCED MAGNETIC SWITCH IS OPEN. PRESENTATION OF

VALID KEYPAD CODE FROM INTERIOR TO SHUNT ALARM UNTIL RESET BY CODE.

DOOR HARDWARE SET NO. 11

DOOR NO. AM#2...122, 202A...AM#2; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

CONT. HINGE 2 EA A81021B 689

ELECT. EXIT

DEVICE (RHR)

1 EA L2-A156.3 TYPE 3,

FUNCTION 09 G1 -

E06 x 3

EXIT DEVICE (LHR) 1 EA TYPE 3, FUNCTION

CYLINDER 1 EA 626

AUTO OPERATOR 1 EA SEE 81 71 13 628

KEYPAD 2 EA SEE SECURITY ---

CLOSER 1 EA C02011 ALUM

ARMOR PLATE 2 EA J101 630

WALL STOP AM#2...2 EA...

AM#2

L02101 626

GASKET 2 EA R3E165 626

GASKET 1 EA R0E155 BROWN

DOOR HARDWARE SET NO. 12

DOOR NO. 123; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A8112 652

LOCKSET 1 EA F07 626

CLOSER 1 EA C02011 ALUM

KICK PLATE 1 EA J102 630

WALL STOP 1 EA L02101 626

SECTION 08 71 00 Page 15

SILENCER 3 EA L03011 GREY

DOOR HARDWARE SET NO. 13

DOOR NO. 127A; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A8112 652

LOCKSET 1 EA F07 626

CLOSER 1 EA C02011 ALUM

KICK PLATE 1 EA J102 630

WALL STOP 1 EA L02101 626

SILENCER 3 EA L03011 GREY

DOOR HARDWARE SET NO. 14

DOOR NO. AM#2...128A, 128F...AM#2; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 6 EA A5111 630

EXIT DEVICE

(RHR) X CDK

1 EA TYPE 3, FUNCTION

EXIT DEVICE

(LHR) X CDK

1 EA TYPE 3, FUNCTION

CYLINDER 3 EA 626

CLOSER 2 EA C02021 ALUM

ASTRAGAL 1 PR R3E635 628

KICK PLATE 2 EA AM#2...J102...AM#2 630

OVERHEAD STOP AM#2...2 EA...

AM#2

C02541 626

GASKET 2 EA R3E165 628

GASKET 1 EA R0E155 BROWN

THRESHOLD 1 EA J32129 719

SECTION 08 71 00 Page 16

AUTO DOOR BOTTOM 2 EA R3C335 626

DOOR HARDWARE SET NO. 15

DOOR NO. 128C; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 6 EA A5111 630

EXIT DEVICE X CDK 1 EA TYPE 3 FUNCTION 10 626

EXIT DEVICE X CDK 1 EA TYPE 3 FUNCTION 02 626

CYLINDER 3 EA 626

CLOSER 2 EA C02021 ALUM

ASTRAGAL 1 PR R3E635 628

KICK PLATE 2 EA J102 630

OVERHEAD STOP 2 EA

GASKET 2 EA R3E165 628

GASKET 1 EA R0E155 BROWN

THRESHOLD 1 EA J32129 719

AUTO DOOR BOTTOM 2 EA R3C335 628

DOOR HARDWARE SET NO. 16

DOOR NO. AM#2...128B...AM#2; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

CONT. HINGE 1 EA A51001B 630

CONT. ELECT.

HINGE

1 EA A51101B X 4 WIRE 630

ELECTRIC LOCKSET 1 EA SEE DESCRIPTION

BELOW

AUTO FLUSH BOLTS 1 PR A156.3, TYPE 25 626

SECTION 08 71 00 Page 17

AUTO OPERATOR 1 EA SEE 08 71 13 628

CLOSER 1 EA C02021 ALUM

COORDINATOR 1 EA A156.3, TYPE 21A 626

CARD READER 1 EA SEE SECURITY ---

BUTTON 1 EA SEE SECURITY ---

ASTRAGAL 1 PR R3E635 628

PROTECTION PLATES 2 EA SEE DETAILS 630

OVERHEAD STOP 2 EA C02541 626

GASKET 1 EA R0E155 BROWN

GASKET 1 EA R03E155 628

ARMOR PLATES 2 EA J101 630

THRESHOLD 1 EA J32129 719

AUTO DOOR BOTTOM 2 EA R3C335 626

BALANCED

MAGNETIC SWITCH

2 EA SEE SECURITY ---

DOOR ALARM 1 EA E0411 ---

DOOR LOCK IS FAIL SECURE FUNCTION ELECTRONIC LATCH RETRACTION WITH

3-POINT LATCH. ALARM HORN SOUNDS IF EITHER BALANCED MAGNETIC SWITCH IS

OPEN. PRESENTATION OF VALID BADGE AT INTERIOR TO SHUNT ALARM, RETRACT

LATCH, AND OPEN AUTO DOOR OPERATOR FOR 30 SECONDS. DEPRESSING OUTSIDE

BUTTON TO SHUNT ALARM, RETRACT LATCH, AND OPEN AUTO DOOR OPERATOR FOR 30

SECONDS

DOOR HARDWARE SET NO. 17

DOOR NO. 130, 131, 132, 141B, 142, 143; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

CONT. HINGE 2 EA A51021B 630

EXIT DEVICE 2 EA TYPE 3, FUNCTION

CLOSER 2 EA C02021 ALUM

ASTRAGAL 1 EA R3E634 626

ARMOR PLATE 2 EA J101 630

SECTION 08 71 00 Page 18

WALL STOP 2 EA L02101 626

GASKET 1 SET R0E155 BROWN

DOOR HARDWARE SET NO. 18

DOOR NO. 133, 141A; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

CONT. HINGE 1 EA A51021B 630

EXIT DEVICE 1 EA TYPE 3, FUNCTION

CLOSER 1 EA C02021 ALUM

ARMOR PLATE 1 EA J101 630

WALL STOP 1 EA L02101 626

GASKET 1 SET R0E155 BROWN

DOOR HARDWARE SET NO. 19

DOOR NO. AM#2...106F, 134A, 140, 145...AM#2; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 6 EA A5111 630

LOCKSET 1 EA F07 626

MANUAL FLUSH

BOLTS

1 PR L04081 626

ASTRAGAL 1 EA R3C615 628

CLOSER 2 EA C02021 ALUM

ARMOR PLATE 2 EA J101 630

OVERHEAD STOP 2 EA C02541 626

GASKET 2 EA R3E165 628

GASKET 1 EA R0E155 BROWN

THRESHOLD 1 EA J36329 719

SECTION 08 71 00 Page 19

AM#2...DOOR HARDWARE SET NO. 20

DOOR NO. 144; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A8111 630

EXIT DEVICE 1 EA TYPE 3, FUNCTION

630/626

CLOSER 1 EA C02021 ALUM.

ARMOR PLATE 1 EA J101 630

OVERHEAD STOP 1 EA C02541 626

GASKET 2 EA R3E165 628

GASKET 1 EA R0E155 BROWN

THRESHOLD 1 EA J32139 719

AUTO. DOOR BOTTOM 1 EA R3S335 628

BALANCED

MAGNETIC SWITCH

1 EA SEE SECURITY ---...AM#2

AM#2...DOOR HARDWARE Set No. 21

DOOR NO. 108B; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA 8111 652

ELECT. EXIT

DEVICE

1 EA L2-A156.3 TYPE 3,

FUNCTION 09 G1-E06

CYLINDER 1 EA --- 626

CARD READER 1 EA SEE SECURITY ---

CLOSER 1 EA C02011 ALUM.

KICK PLATE 1 EA J102 630

PROTECTION PLATE 4 EA SEE DETAIL 630

WALL STOP 2 EA L02101 626

SECTION 08 71 00 Page 20

GASKET 2 EA R3E165 626

PRESENTATION OF AN AUTHORIZED CARD TO UNLOCK DOOR FOR 15 SECONDS...AM#2

AM#2...DOOR HARDWARE SET NO. 22

DOOR NO. 203; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A8112 652

LOCKSET 1 EA F07 626

CLOSER 1 EA C02021 ALUM.

KICK PLATE 1 EA J102 630

WALL STOP 1 EA L02101 626

GASKET 1 EA R3E174 628...AM#2

AM#2...DOOR HARDWARE SET NO. 23

DOOR NO. 135, 204; EACH TO HAVE THE FOLLOWING:

ITEM NO. DESCRIPTION FINISH

HINGE 3 EA A5111 630

EXIT DEVICE X CDK 1 EA TYPE 3, FUNCTION

CYLINDER 2 EA --- 626

CLOSER 1 EA C02021 ALUM.

KICK PLATE 1 EA J101 630

OVERHEAD STOP 1 EA C02541 626

GASKET 2 EA R3E165 626

GASKET 1 EA R0E155 BROWN

THRESHOLD 1 EA J32129 719

AUTO DOOR BOTTOM 1 EA R3C335 626...AM#2

AM#3...BALANCED

MAGNETIC SWTICH

1 EA SEE SECURITY ---

SECTION 08 71 00 Page 21

CARD READER 1 EA SEE SECURITY ---

BUTTON 1 EA SEE SECURITY ---

DOOR ALARM 1 EA E0411 ---

ALARM HORN SOUNDS IF BALANCED MAGNETIC SWITCH IS OPEN. PRESENTATION OF

VALID BADGE AT INTERIOR TO SHUNT ALARM FOR 30 SECONDS. DEPRESSING

OUTSIDE BUTTON TO SHUNT ALARM FOR 30 SECONDS....AM#3

-- End of Section --

SECTION 08 71 00 Page 22

SECTION 09 29 00

GYPSUM BOARD

08/16

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ANSI A108.11 (1992; Reaffirmed 2005) Specifications for Interior Installation of Cementitious Backer Units

ASTM INTERNATIONAL (ASTM)

ASTM C1002 (2014) Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs

ASTM C1047 (2014a) Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base

ASTM C1177/C1177M (2013) Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing

ASTM C1396/C1396M (2014a) Standard Specification for Gypsum Board

ASTM C475/C475M (2015) Joint Compound and Joint Tape for Finishing Gypsum Board

ASTM C840 (2016) Standard Specification for Application and Finishing of Gypsum Board

ASTM C954 (2015) Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from

0.033 in. (0.84 mm) to 0.112 in. (2.84 mm) in Thickness

ASTM D1149 (2007; R 2012) Standard Test Method for Rubber Deterioration - Surface Ozone Cracking in a Chamber

ASTM D412 (2016) Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers - Tension

ASTM D624 (2000; R 2012) Tear Strength of

SECTION 09 29 00 Page 1

Conventional Vulcanized Rubber and Thermoplastic Elastomers

CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)

CDPH SECTION 01350 (2004; Add 2004-01) Standard Practice for the Testing Of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers

FM GLOBAL (FM)

FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/

GYPSUM ASSOCIATION (GA)

GA 214 (2010) Recommended Levels of Gypsum Board Finish

GA 216 (2010) Application and Finishing of Gypsum Panel Products

GA 253 (2012) Application of Gypsum Sheathing

GA 600 (2009) Fire Resistance Design Manual

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS SCS Global Services (SCS)Indoor Advantage

UNDERWRITERS LABORATORIES (UL)

UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

UL Fire Resistance (2014) Fire Resistance Directory

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-03 Product Data

Cementitious Backer Units

AM#3...Glass Mat Covered or Reinforced Gypsum Sheathing...AM#3

AM#3...Glass Mat Covered or Reinforced Gypsum Sheathing Sealant...

AM#3

Accessories

SECTION 09 29 00 Page 2

Submit for each type of gypsum board and for cementitious backer units.

Certifications

Gypsum Board

SD-07 Certificates

Asbestos Free Materials

Certify that gypsum board types, gypsum backing board types, cementitious backer units, and joint treating materials do not contain asbestos.

Indoor Air Quality

SD-08 Manufacturer's Instructions

Material Safety Data Sheets

SD-10 Operation and Maintenance Data

Manufacturer Maintenance Instructions

SD-11 Closeout Submittals

Recycled Content for Gypsum Board; S

Recycled Content for Paper Facing and Gypsum Cores; S

Indoor Air Quality for Gypsum Board; S

VOC Content of Joint Compound; S

1.3 CERTIFICATIONS

1.3.1 Indoor Air Quality Certifications

Submit required indoor air quality certifications in one submittal package.

1.3.1.1 Ceiling and Wall Systems

Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide validation by other third-party program that products meet the requirements of this paragraph. Provide current product certification documentation from certification body. Gypsum wall board and panels must meet the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type).

1.4 DELIVERY, STORAGE, AND HANDLING

1.4.1 Delivery

Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.

SECTION 09 29 00 Page 3

1.4.2 Storage

Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board and cementitious backer units outside, store off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions.

Provide adequate ventilation to prevent condensation. Store per manufacturer's recommendations for allowable temperature and humidity range.

Do not store gypsum wallboard with materials which have high emissions of volatile organic compounds (VOCs) or other contaminants, including paints and coatings. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives. Do not use materials that have visible moisture or biological growth.

1.4.3 Handling

Neatly stack gypsum board and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces.

1.5 QUALIFICATIONS

Furnish type of gypsum board work specialized by the installer with a minimum of 3 years of documented successful experience.

1.6 SCHEDULING

The gypsum wallboard must be taped, finished and primed before the installation of the highly-emitting materials, including epoxy floor coating.

Commence application only after the area scheduled for gypsum board work is completely weathertight. The heating, ventilating, and air-conditioning systems must be complete and in operation prior to application of the gypsum board. If the mechanical system cannot be activated before gypsum board is begun, the gypsum board work may proceed in accordance with an approved plan to maintain the environmental conditions specified below.

Apply gypsum board prior to the installation of finish flooring and acoustic ceiling.

1.7 ENVIRONMENTAL REQUIREMENTS

Do not expose the gypsum board to excessive sunlight prior to gypsum board application. Maintain a continuous uniform temperature of not less than 50 degrees F and not more than 80 degrees F for at least one week prior to the application of gypsum board work, while the gypsum board application is being done, and for at least one week after the gypsum board is set.

Shield air supply and distribution devices to prevent any uneven flow of air across the plastered surfaces. Provide ventilation to exhaust moist air to the outside during gypsum board application, set, and until gypsum board jointing is dry. Reduce openings in cold weather to prevent freezing of joint compound when applied. For enclosed areas lacking natural ventilation, provide temporary mechanical means for ventilation. In unglazed areas subjected to hot, dry winds or temperature differentials from day to night of 20 degrees F or more, screen openings with cheesecloth or similar materials. Avoid rapid drying. During periods of low indoor humidity, provide minimum air circulation following gypsum boarding and until gypsum board jointing complete and is dry.

SECTION 09 29 00 Page 4

1.8 FIRE RESISTIVE CONSTRUCTION

Comply with specified fire-rated assemblies for design numbers indicated per UL Fire Resistance or FM APP GUIDE.

PART 2 PRODUCTS

2.1 PRODUCT SUSTAINABILITY CRITERIA

For products in this section, where applicable and to extent allowed by performance criteria, provide and document the following:

2.1.1 Recycled Content for Gypsum Board Materials

Recycled content is identified for some products in this section; provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REPORTING paragraph RECYCLED CONTENT. Other products listed in this section may be available with recycled content; identify those products that meet project requirements for recycled content, and provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REPORTING paragraph RECYCLED CONTENT.

2.1.2 Reduce Volatile Organic Compounds (VOC) (LOW-EMITTING MATERIALS) for Products

Reduced VOC content is identified for some products in this section;

provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REPORTING paragraph REDUCE VOLATILE ORGANIC COMPOUNDS (VOC) (LOW-EMITTING MATERIALS). Other products listed in this section may be available with reduced VOC content; identify those products that meet project requirements for reduced VOC content, and provide documentation in accordance with Section 01 33 29 SUSTAINABILITY REPORTING paragraph REDUCE VOLATILE ORGANIC

COMPOUNDS (VOC) (LOW-EMITTING MATERIALS).

2.2 MATERIALS

Conform to specifications, standards and requirements specified. Provide gypsum board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only. Submit Material Safety Data Sheets and manufacturer maintenance instructions for gypsum materials.

2.2.1 Gypsum Board

ASTM C1396/C1396M. Gypsum board must contain a minimum of 20 percent post-consumer recycled content, or a minimum of 20 percent post-industrial recycled content. Provide data identifying percentage of recycled content for gypsum board. Paper facings must contain a minimum of 100 percent post-consumer recycled paper content. Provide data identifying percentage of recycled content for paper facing and gypsum cores. Provide certification of indoor air quality for gypsum board.

2.2.1.1 Type X (Special Fire-Resistant)

48 inch wide, 5/8 inch thick, tapered edges.

AM#3...2.2.2 Glass Mat Covered or Reinforced Gypsum Sheathing

Exceeds physical properties of ASTM C1396/C1396M and ASTM C1177/C1177M.

Provide 5/8 inch, gypsum sheathing. Provide gypsum board of with a

SECTION 09 29 00 Page 5 noncombustible water-resistant core, with glass mat surfaces embedded to the gypsum core or reinforcing embedded throughout the gypsum core. Warrant gypsum sheathing board for at least twelve months against delamination due to direct weather exposure. Seal all joints, seams, and penetrations with compatible sealant....AM#3

AM#3...2.2.2.1 Glass Mat Covered or Reinforced Gypsum Sheathing Sealant

Provide sealant compatible with glass mat covered or reinforced gypsum sheathing, rubber washers for masonry veneer anchors, and other associated cavity wall components such as anchors and through wall flashing. Provide sealants for glass mat covered or reinforced gypsum sheathing board edge seams and veneer anchor penetrations recommended by the glass mat covered or reinforced gypsum sheathing manufacturer and have the following performance requirements:

a. ASTM D412: Tensile Strength, 80 psi

b. ASTM D412: Ultimate Tensile Strength (maximum elongation), 170 psi

c. ASTM D624: Tear Strength, dieB, 27 ppi

d. ASTM D1149: Joint Movement Capability after 14 Days cure, plus or minus 50 percent....AM#3

2.2.3 Cementitious Backer Units

In accordance with the Tile Council of America (TCA) Handbook.

2.2.4 Joint Treatment Materials

ASTM C475/C475M. Product must be low emitting VOC types with VOC limits not exceeding 50 g/L. Provide data identifying VOC content of joint compound. Use all purpose joint and texturing compound containing inert fillers and natural binders, including lime compound. Pre-mixed compounds must be free of antifreeze, vinyl adhesives, preservatives, biocides and other slow releasing compounds.

2.2.4.1 Embedding Compound

Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.

2.2.4.2 Setting or Hardening Type Compound

Specifically formulated and manufactured for use with fiber glass mesh tape.

2.2.4.3 Joint Tape

Use cross-laminated, fiber glass mesh tape recommended by the manufacturer.

2.2.5 Fasteners

2.2.5.1 Screws

ASTM C1002, Type "G", Type "S" or Type "W" steel drill screws for fastening gypsum board to gypsum board, wood framing members and steel framing members less than 0.033 inch thick. ASTM C954 steel drill screws for fastening gypsum board to steel framing members 0.033 to 0.112 inch thick.

Provide cementitious backer unit screws with a polymer coating.

SECTION 09 29 00 Page 6

2.2.6 Accessories

ASTM C1047. Fabricate from corrosion protected steel designed for intended use. Accessories manufactured with paper flanges are not acceptable.

Flanges must be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials.

2.2.7 Water

Provide clean, fresh, and potable water.

PART 3 EXECUTION

3.1 EXAMINATION

3.1.1 Framing and Furring

Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.

3.1.2 Building Construction Materials

Do not install building construction materials that show visual evidence of biological growth.

3.2 APPLICATION OF GYPSUM BOARD

Apply gypsum board to framing and furring members in accordance with ASTM C840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints.

Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible. Surfaces of gypsum board and substrate members may be bonded together with an adhesive, except where prohibited by fire rating(s).

Treat edges of cutouts for plumbing pipes, screwheads, and joints with water-resistant compound as recommended by the gypsum board manufacturer.

Minimize framing by floating corners with single studs and drywall clips.

Install 5/8 inch gypsum over framing at 16 inch on center. Provide type of gypsum board for use in each system specified herein as indicated.

3.2.1 Application of Gypsum Board to Steel Framing and Furring

Apply in accordance with ASTM C840, System VIII or GA 216.

AM#3...3.2.2 Glass Mat Covered or Fiber Reinforced Gypsum Sheathing

Apply glass mat covered or fiber reinforced gypsum sheathing in accordance to gypsum association publications GA 253. Follow gypsum sheathing manufacturer's requirements of design details for joints and fasteners and

SECTION 09 29 00 Page 7 be properly installed to protect the substrate from moisture intrusion. Do not leave exposed surfaces of the glass mat covered or fiber reinforced gypsum sheathing beyond the manufacturer's recommendation without a weather barrier cladding. Properly flash the openings. Seal all joints, seams, and penetrations with a compatible silicone sealant....AM#3

3.2.3 Floating Interior Angles

Minimize framing by floating corners with single studs and drywall clips.

Locate the attachment fasteners adjacent to ceiling and wall intersections in accordance with ASTM C840, System XII or GA 216, for single-ply and two-ply applications of gypsum board to framing.

3.2.4 Control Joints

Install expansion and contraction joints in ceilings and walls in accordance with ASTM C840, System XIII or GA 216. Fill control joints between studs in fire-rated construction with firesafing insulation to match the fire-rating of construction.

3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS

3.3.1 Application

In wet areas (tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply cementitious backer units in accordance with ANSI A108.11.

3.3.2 Joint Treatment

ANSI A108.11.

3.4 FINISHING OF GYPSUM BOARD

Tape and finish gypsum board in accordance with ASTM C840, GA 214 and GA 216.

Finish plenum areas above ceilings to Level 1 in accordance with GA 214.

Finish walls and ceilings to receive a heavy-grade wall covering finish to Level 3 in accordance with GA 214. Finish walls and ceilings to receive paints, light textures, or wall coverings to Level 4 in accordance with GA 214. Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use self-adhering fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for water-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.

3.5 SEALING

Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00 JOINT SEALANTS. Apply material with exposed surface flush with gypsum board or cementitious backer units.

AM#3...3.5.1 Sealing for Glass Mat or Reinforced Gypsum Board Sheathing

Apply silicone sealant in a 3/8 inch bead to all joints and trowel flat.

Apply enough of the same sealant to all fasteners penetrating through the glass mat gypsum board surface to completely cover the penetration when troweled flat. Do not place construction and materials over sheathing

SECTION 09 29 00 Page 8 until a visual inspection of sealed joints during daylight hours has been completed by Contracting Officer....AM#3

3.6 FIRE-RESISTANT ASSEMBLIES

Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, and wall framing in accordance with the specifications contained in UL Fire Resistance for the Design Number(s) indicated, or GA 600 for the File Number(s) indicated. Joints of fire-rated gypsum board enclosures must be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.

3.7 PATCHING

Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.

-- End of Section --

SECTION 09 29 00 Page 9

SECTION 09 72 00

WALLCOVERINGS

08/17

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM E84 (2016) Standard Test Method for Surface Burning Characteristics of Building Materials

CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)

CDPH SECTION 01350 (2004; Add 2004-01) Standard Practice for the Testing Of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers

GREEN SEAL (GS)

GS-36 (2011) Commercial Adhesives

GYPSUM ASSOCIATION (GA)

GA 214 (2010) Recommended Levels of Gypsum Board Finish

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 286 (2015) Standard Methods of Fire Tests for Evaluating Contribution of Wall and Ceiling Interior Finish to Room Fire Growth

SCIENTIFIC CERTIFICATION SYSTEMS (SCS)

SCS SCS Global Services (SCS)Indoor Advantage

SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)

SCAQMD Rule 1168 (1989; R 2005) Adhesive and Sealant Applications

U.S. GENERAL SERVICES ADMINISTRATION (GSA)

FS CCC-W-408 (Rev D; Notices 1, 2) Wallcovering, Vinyl Coated

SECTION 09 72 00 Page 1

UNDERWRITERS LABORATORIES (UL)

UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings

UL 723 (2008; Reprint Aug 2013) Test for Surface Burning Characteristics of Building Materials

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-03 Product Data

Wallcoverings and Accessories; G

Primer and Adhesive

SD-04 Samples

Wallcoverings and Accessories; G

SD-07 Certificates

Indoor Air Quality

SD-08 Manufacturer's Instructions

Wallcoverings and Accessories

SD-10 Operation and Maintenance Data

Wallcoverings and Accessories; G

SD-11 Closeout Submittals

Indoor Air Quality for vinyl wallcovering; S

Indoor Air Quality for primer; S

Indoor Air Quality for adhesives; S

1.3 CERTIFICATIONS

1.3.1 Indoor Air Quality Certifications

1.3.1.1 Fabrics and Wallcoverings

Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that

SECTION 09 72 00 Page 2 products meet the requirements of this Section. Provide current product certification documentation from certification body.

1.3.1.2 Primers and Adhesives

Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body.

1.4 DELIVERY, STORAGE, AND HANDLING

Deliver the material to the site in manufacturer's original wrappings and packages and clearly label with the manufacturer's name, brand name, pattern and color name and number, dye lot number, size, and other related information. Store in a safe, dry, clean, and well-ventilated area at temperatures not less than 50 degrees F and within a relative humidity range of 30 to 60 percent. Store wallcovering material in a flat position and protected from damage, soiling, and moisture. Do not open containers until needed for installation, unless verification inspection is required.

1.5 ENVIRONMENTAL REQUIREMENTS

Comply with wallcovering manufacturer's printed installation instructions for minimum temperature of area to receive requirements for conditioning adhesive and wallcovering. Provide a minimum 50 degrees F area temperature, 72 hours prior to installation, during installation, and until the adhesive dries. Observe ventilation and safety procedures.

1.6 WARRANTY

Provide manufacturer's standard performance guarantees or warranties that extend beyond a one-year period.

PART 2 PRODUCTS

2.1 WALLCOVERINGS AND ACCESSORIES

Provide wall coverings and accessories material designed specifically for the specified use. Provide vinyl wallcovering and borders with a mercury, cadmium, lead, and chromium free base. Protect wallcoverings with bactericides and mildew inhibitors against microbiological and mildew growth.

2.1.1 Product Data

a. Wallcovering: Submit manufacturer's descriptive data, documenting physical characteristics, flame resistance, mildew and germicidal characteristics for wallcovering.

b. Primer and Adhesive: Submit manufacturer's descriptive data, documenting physical characteristics, mildew and germicidal characteristics.

SECTION 09 72 00 Page 3

2.1.2 Samples

2.1.2.1 Wallcovering

Submit three samples of each indicated type and example color of wallcovering. Provide minimum 5 by 7 inch samples of wallcovering.

2.1.3 Certificates

Submit manufacturer's statement attesting that the product furnished meets or exceeds specification requirements. Date the statement after the award of the contract, state Contractor's name and address, name the project and location, and list the requirements being certified. Include these certificates:

(1) Certified laboratory test reports of the physical properties for vinyl wallcovering, as specified.

(2) Certificates of Compliance for UL fire hazard classification listing, as specified.

(3) Certificates of Compliance for contact adhesive.

2.1.4 Manufacturer's Instructions

Submit preprinted installation instructions for wallcovering , adhesives and primers. Include substrate preparation and material application in the instructions.

2.2 VINYL WALLCOVERING TYPE A

Provide a vinyl coated woven or nonwoven wallcovering fabric. Conform to FS CCC-W-408 for vinyl wallcovering, Type II (Medium Duty) with a minimum total weight of 13 ounces/square yard and 20 ounces/linear yard. Provide width of 52/54 inch . Test vinyl wallcovering in accordance with NFPA 286 or meet the requirements of Class A when tested in accordance with ASTM E84 or UL 723.

Provide certification of indoor air quality for vinyl wallcovering.

2.3 PRIMER AND ADHESIVE

Provide a type primer and adhesive recommended by the wallcovering…