AMMEND 0002
a. ANSWERS TO FAQ.
Q:
How many lighting circuits are at each panel?
A:
Building 750 Panel A - ckts: 1, 2, 3, 4, 5, 7, 8, 9, 10, 11
Panel B - ckts: 5, 9, 10, 11
Panel D - ckts: 1, 2, 3, 4, 5, 6, 7, 8, 9
Building 784 Panel D - ckts: 7, 8, 9, 11
Panel E - 7, 8, 9, 10, 11, 12, 13, 14, 15
Panel F - 2, 4, 6, 7, 9, 11, 13, 15
These circuits must be confirmed by the successful contractor prior to installation.
Q:
What is the total count of existing HPS Luminaires at Building 784?
A:
Seismic Zone Requirements:
INSTALL LOCAL FIXTURES FOR LOCAL SEISMIC ZONE. PENDANT FIXTURES SHALL HAVE SWIVEL HANGER ASSEMBLIES FITTED WITH A RESTRAINING DEVICE TO HOLD THE STEM AND/OR CEILING IN THE SUPPORT POSITION DURING EARTHQUAKE MOTIONS. BRACING SHALL BE THREE DIRECTIONAL, 120 DEGREES APART
b. The following drawing is added to provide a visual aid to offerors:
On a suspended fluorescent luminaire, each pendant shall the above restraining device, see drawing below.