AMMEND 0002

a. ANSWERS TO FAQ.

Q:

How many lighting circuits are at each panel?

A:

Building 750 Panel A - ckts: 1, 2, 3, 4, 5, 7, 8, 9, 10, 11

Panel B - ckts: 5, 9, 10, 11

Panel D - ckts: 1, 2, 3, 4, 5, 6, 7, 8, 9

Building 784 Panel D - ckts: 7, 8, 9, 11

Panel E - 7, 8, 9, 10, 11, 12, 13, 14, 15

Panel F - 2, 4, 6, 7, 9, 11, 13, 15

These circuits must be confirmed by the successful contractor prior to installation.

Q:

What is the total count of existing HPS Luminaires at Building 784?

A:

Seismic Zone Requirements:

INSTALL LOCAL FIXTURES FOR LOCAL SEISMIC ZONE. PENDANT FIXTURES SHALL HAVE SWIVEL HANGER ASSEMBLIES FITTED WITH A RESTRAINING DEVICE TO HOLD THE STEM AND/OR CEILING IN THE SUPPORT POSITION DURING EARTHQUAKE MOTIONS. BRACING SHALL BE THREE DIRECTIONAL, 120 DEGREES APART

b. The following drawing is added to provide a visual aid to offerors:

On a suspended fluorescent luminaire, each pendant shall the above restraining device, see drawing below.