Specs_Pt.4.pdf
PDF 317 KB Posted
- Attached to
- Renovation of TEMP Bldg 26041
- Solicitation number
- W91151-19-B-0016
About this file
Tech Exhibit A- Specification Part -4
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TEMF 26041 Fort Hood, Texas
CORRECTED FINAL
TIA/EIA-455-81 (2000b) FOTP-81 Compound Flow (Drip) Test for Filled Fiber Optic Cable
TIA/EIA-472DAAA (1993) Detail Specification for All Dielectric Fiber Optic Communications Cable for Outside Plant Use Containing Class 1a 62.5 Um Core Diameter/125 um Cladding Diameter/250 um Coating Diameter Fiber(s).
TIA/EIA-4750000-C (1996) Generic Specifications for Fiber Optic Connectors (ANSI)
TIA/EIA-598 (2014D; Add 2 2018) Optical Fiber Cable Color Coding
TIA/EIA-604-3 (2004b; R 2014) Fiber Optic Connector Intermateability Standard (FOCIS), Type SC and SC-APC, FOCIS-3
U.S. DEPARTMENT OF AGRICULTURE (USDA)
RUS Bull 1753F-601 (1994) Specifications for Filled Fiber Optic Cables (PE-90)
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-188-176 (1996; Notice 1) Standardized Profile for Asynchronous Transfer Mode (ATM)
1.2 DEFINITIONS
References in this section to cable refer to fiber optic ("FO") cable.
Fiber optic cable consists of optical fibers, strength member, and jacketing. Associated components include optical fiber connectors, optical patch panels, terminal bay cabinets, and splice closures as indicated.
1.3 ADMINISTRATIVE REQUIREMENTS
Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to work specified in this section.
1.3.1 Pre-Installation Meetings
Within 30 calendar days after date of receipt by him of notice of award, submit for the approval of the Contracting Officer six (6) copies of outline drawings of all equipment to be furnished under this contract, together with pre-construction and installation drawings and documents.
Ensure drawings show the general arrangement and overall dimensions of the cable installation, control centers, space requirements, details of any hidden floor supports or ceiling systems and provisions for conduits for external cables. Submit the following for review and approval:
a. Fiber Optic System Contract Drawings
b. Detailed Shop Drawings
c. Qualifications
SECTION 27 13 23.00 40 Page 3
d. Quality Assurance Plan
Submit a quality assurance plan for fiber optic cable systems consisting of detailed procedures defining methods to ensure compliance to contract drawings and specifications by drawing control, inspection and procurement records, and test plan showing when and how each system will be tested, material testing, and certification records. Submit test plan to the Technical Representative for approval at least 30 calendar days prior to the start of testing.
Submit manufacturer's product data for the following items. Ensure data includes a complete list of parts, special tools, and supplies with current unit prices and source of supply:.
a. Optical Fibers
b. Fiber Optic Cable Design
c. Splice Organizers
d. Pre-Connected Cable Assembly
e. Fiber Optic Terminal Cabinets
f. Optical Patch Panel Assemblies
g. Fiber Optic Media Types
h. Fiber Optic Terminations and Connectors
i. Fiber Optic Enclosures
j. Fiber Optic Cable Installer and Splicer Qualifications
k. Manufacturer's Qualifications
l. Fiber Optic System Instructions
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Qualifications; G
Quality Assurance Plan; G
SD-02 Shop Drawings
Fiber Optic System Contract Drawings; G
SECTION 27 13 23.00 40 Page 4
Detailed Shop Drawings; G
Record (As-Built) Drawings; G
SD-03 Product Data
Optical Fibers; G
Fiber Optic Cable Design; G
Splice Organizers; G
Fiber Optic Terminal Cabinets; G
Optical Patch Panel Assemblies; G
Fiber Optic Media Types; G
Fiber Optic Terminations and Connectors; G
Fiber Optic Enclosures; G
SD-06 Test Reports
Factory Test Certificates; G
Single and Multi-Mode OTDR Test; G
End-to-End Attenuation Tests; G
End-to-End Bandwidth TestsG
Fiber Optic Factory Test Plan; G
Fiber Optic Field Tests Plan; G
SD-07 Certificates
Fiber Optic Cable Installer and Splicer Qualifications; G
Manufacturer's Qualifications; G
SD-08 Manufacturer's Instructions
Fiber Optic System Instructions; G
1.5 QUALITY CONTROL
1.5.1 Fiber Optic Cable Installer and Splicer Qualifications
Provide technicians installing FO media, splices and performing system tests who are certified and trained in accordance with an approved manufacturers training program, with a minimum of 3 years FO experience in installing equivalent FO systems. Submit data for approval to the Contracting Officer. Submit FO technician qualifications for approval 30 days before splices are to be made on the cable. Certification includes the training, and experience of the individual on specific type and classification of FO media to be provided under this contract.
SECTION 27 13 23.00 40 Page 5
Contracting officer may require each person who is to perform fiber optic cable splicing to perform a minimum of one acceptable sample splice and termination. Do not incorporate sample splices and terminations in the job.
1.5.2 Quality Assurance Plan
Prepare a quality assurance plan which provides a detailed outline of all testing to be accomplished, addresses whether cladding modes have been stripped prior to testing, source wavelength (peak), spectral width full width/half maximum (FWHM), mode structure, fiber end preparation, and bandwidth measurements of fiber links both greater and less than 1 kilometer. Quality assurance plan includes, as a minimum, a schedule of when tests will be performed relative to installation milestones, specific test procedure that will be used, a list of test equipment that will be used including manufacturer, model number, range, resolution accuracy and conformance to the specified requirements.
1.5.3 Manufacturer's Qualifications
Ensure FO media manufacturer has a minimum of 3 years experience in the manufacturing, assembly, and factory testing of FO media which comply with RUS Bull 1753F-601. Ensure manufacturer provides a list of customers with 3 years of maintenance logs documenting experience with government customers.
1.5.4 Fiber Optic Factory Test Plan
Prepare and provide to the Government for review a test plan for factory and field tests of the FO media. Provide factory Optical Time Domain Reflectometer(OTDR) test data as part of the test report. Provide a list of factory test equipment. Include a FO link performance test plan.
Submit the plan at least 30 days prior to tests for government approval.
Refer to TIA-569 for performance measurement criteria. Conduct tests at all operating bandwidths. Provide calculations for optical power budget and bandwidth as required by RUS Bull 1753F-601 using test method TIA-455-78-B or TIA/EIA-455. Submit test plans and reports to the Government for review and approval.
1.5.5 Fiber Optic Field Tests Plan
Prepare and provide technicians and test equipment for field tests of FO media. Conduct OTDR reel tests at the job site prior to installation.
Perform OTDR and end to end tests of all installed media. Conduct tests on single mode fiber in accordance with TIA-526-7 for single mode fiber and EIA TIA/EIA-526-14A for multi mode fiber.
1.6 DELIVERY, STORAGE, AND HANDLING
Ship media to job site on factory reels in factory cartons. Provide a reel drum radius no smaller than the minimum bend radius recommended by the manufacturer for the media. Wind cable on the reel so that unwinding can be done without kinking the cable. Provide 6 1/2-feet pigtails of cable at each end of the reel readily accessible for testing. Attach a permanent label on each reel showing length, media, identification number, and date of manufacture. Provide water resistant label and ink on the labels.
Apply end seals to each end of the media after testing and before terminating to prevent moisture from entering the cable while stored at the job site. Ensure reels are suitable for outside storage conditions when temperature ranges from minus 40 degrees F to plus 150 degrees F, with
SECTION 27 13 23.00 40 Page 6 relative humidity from zero to 100 percent. Store equipment, other than FO media, delivered and placed in storage with protection from weather, humidity and temperature variation, dirt and dust, or other contaminants.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Protect existing incoming backbone fiber optic cable. Extend incoming fiber optic cable to the new communications room with new CPM fiber optic cable of matching strand count. Provide and install new fusion splice enclosure as shown.
Provide and install new 12 strand CMP fiber backbone to the new second floor communications room. Terminate all fiber on LC connectorsl
Provide detailed drawings for the fiber optic cable and pathway system.
Provide single line schematic details of the fiber optic and pathway media, splices, and associated construction materials. Ensure drawings are in AUTOCAD.DXF or compatible format. Provide Registered Communications Distribution Designer (RCDD) approved drawings of the fiber optic system.
Include drawing details of fiber optic terminations in equipment rooms.
Show final configuration, including location, fiber pair count, pathway innerduct arrangement, and pathway assignment of outside plant. Verify FO system is compatible with MIL-STD-188-176.
2.1.1 Fiber Optic Cable Design
2.1.1.1 Fiber Optic Media Types
Verify FO media meets all performance requirements of TIA-568-C.1, TIA-568-C.3 and the physical requirements of ICEA S-87-640 and TIA/EIA-598.
a. Multi Mode Fiber Media
Provide FO media with outer sheath jacket,ripcords, water blocking material, optional steel shield,core tube, and core fibers as installed in a permanent underground pathway system as shown on the construction drawings. Provide FO media with an all glass, graded index material with a nominal core diameter of 50 microns. Provide a cladding material for the fiber which is compatible with the core. Center media transmission window at 850 and 1300 nanometer wavelengths, with attenuation at 1300 nanometers less than 2.0 dB per kilometer, and minimum bandwidth of 500 mHz-Km.
b. Single Mode Fiber Media
Provide FO single mode media with outer sheath jacket, ripcords, water blocking material, optional steel shield, core tube, and core fibers as installed in a permanent underground pathway system as shown on the construction drawings. Provide media with all glass, dual window, graded index material with a core diameter of 8.7 microns. Coat fiber with a cladding material which is concentric with the core. Ensure fiber cladding diameter is a nominal 125 microns, and media has a transmission window centered at 1300 and 1550 nanometer wavelengths. Attenuation at 1550 nanometers is less than 0.5 dB per kilometer. Verify FO media complies with TIA/EIA-472DAAA,and TIA-758.
2.1.1.2 Cable Length
Ensure cable is manufactured continuous with no factory splices.
SECTION 27 13 23.00 40 Page 7
2.1.1.3 Construction
a. Number of Fibers Per Tube Per Cable
12-fiber cable cable are required as follows:
(1) Provide 12-fiber cable containing multimode and single mode fibers, with cable core configuration comprised of six loose buffer tubes, each containing six fibers. Color code six fibers in each loose buffer tube using the first colors of the standard Munsell color code, Blue, Orange, Green, Brown, Slate, and White.
Color code loose buffer tubes using the standard Munsell color code, Blue, Orange, Green, Brown and Slate. Ensure sixth buffer tube is Pink. Consider single mode fibers last in configuration.
b. Inner Jacket
Locate buffer tubes concentrically around the cable central core member and covered with a polyethylene inner jacket. Ensure inner jacket is high density polyethylene in accordance with ASTM D4976. Fill space between the buffer tubes and inner jacket with a gel compound to prevent air, moisture, or water intrusion in the inner jacket.
c. Pulling Strength Member
Use a ramid type material as pulling strength members in the cable to provide pulling strength of at least 400 pounds for the cable during installation.
d. Cable Outer Jacket
Apply black high density, high-molecular weight, polyethylene materials in accordance with ASTM D4976 longitudinally over all the inner jacket and sheathing strength member to form the cable outer jacket. Ensure outer jacket is smooth, concentric, non-nutrient to fungus, and free from holes, splits, blisters, or other imperfections. Overall outside cable diameter cannot exceed 0.75-inch.
e. Metallic Armor
Provide a metallic armor shield for direct buried cable for additional tensile strength, rodent protection, and high crush and moisture resistance. Provide metallic armoring of metallic tube or steel corrugation-coated with anti-corrosion material, sealed at the longitudinal overlap.
2.1.2 Cable Identification Symbol
First of three lines on the ID symbol employ 5 characters.
First and second characters, from left to right, denotes the number of active optical fibers in the cable.
Third character is a slash.
Fourth and fifth characters denote optical transmission windows which the optical fiber can support. These windows are defined herein as follows:
SECTION 27 13 23.00 40 Page 8
a. Fourth character is an "A" or an "O." The "A" denotes a window at a wavelength of 850 nanometers (nm) with an attenuation of 4 dB/kilometer
(km) and a bandwidth of 800 MHz-km. Use an "O" character if these requirements are not met.
b. Fifth character is a "B" or an "O." The "B" denotes a window at a wavelength of 1,300 nanometer (nm) with an attenuation of 1.0 dB/km and a bandwidth of 1,000 MHz-km. Use an "O" character if these requirements are not met.
Two lower lines of the cable ID symbol indicate multi-mode or single mode fibers, the cable number and the fiber count:
Example:
72/OB Identifies the number of optical fibers
(72) and the optical transmission window (OB - See preceding paragraph)
FM05 : 61-120 Identifies Multi-Mode Fiber Cable 05 with MM Fibers 61 through 120.
FS05 : 13-24 Identifies Single Mode Fiber Cable 05 with SM Fibers 13 through 24.
2.1.3 Temperature Environment
Provide fiber optical cable compliant with the mechanical performance requirements herein while used in duct applications where the temperature varies from 17.6 degrees F to 100 F. Ensure optical performance degradation is less than five percent of the optical performance requirements in the temperature range of minus 4 degrees F to 140 degrees F.
Do not damage fiber optical cable in storage where the temperature may vary from minus 40 degrees F to 149 degrees F.
2.1.4 Splice Compatibility Test
When the material of the optic fiber is different from Cornings' Class Code No. 1517 for multi-mode graded index fiber and No. 1528 for single-mode fiber, perform and document the Splice Compatibility Test with Vendor as follows:
a. Select fiber samples from a minimum of 3 different production lots of the fiber type proposed for the job.
b. Fabricate and measure a minimum of 10 fusion splices using fiber from the different production lots and a sample of Corning fiber, Class Code No. 1517 and No. 1528, supplied by the Government.
c. Measure fusion splices using an Optical Time Domain Reflectometer (OTDR) operating in the region of 1250 through 1350 nm. Ensure the insertion loss of the fusion splice equals the average of two OTDR measurements, one taken with the OTDR installed on the Corning fiber, and the other with the OTDR installed on the vendor's fiber. Verify Vendor's fiber and the Corning fiber are each a minimum of 1 Km in length throughout the testing.
d. Consider vendor's fiber compatible with the Corning fiber if the maximum splice insertion loss of each of 10 fusion splices tested
SECTION 27 13 23.00 40 Page 9 measures less than 0.2 dB.
Allow a maximum of three retries on any one splice to obtain a loss of
0.2 dB or less.
Perform these tests under Government supervision.
2.2 EQUIPMENT
2.2.1 Replacement Cable
Provide not less than a 0.5 kilometer reel of each size and type of the manufacturer's furnished cable in addition to cable sections indicated.
Deliver replacement cable reels to the Government as directed by the Contracting Officer.
2.2.2 Splice Organizers
Provide fusion spliced single mode or multi-mode fibers with a protective sleeve covering, stored in an organizer with a minimum of 18-inches spare coiled buffer tubing. Ensure single mode fibers are spliced last in the splice tray.
Complete a 12 fiber splice in an outer closure. Organizer assembly, with one tray containing 12 fusion splices each requires five extra trays, to form the section complete in the inner closure.
Fill space between the inner and outer closures with encapsulating fluid.
Factory drill end plates to fit the cable(s) outer diameter.
2.2.3 Optical Patch Panel Assemblies
Provide all cable terminations in optical patch panel assemblies, with patch panel assemblies of the pre-assembled chassis type with associated rack-mounting hardware.
To facilitate the transition between outside plant cable and the preconnectorized cable assemblies, ensure the fibers are fusion spliced and housed in a splice tray. Position splice tray in the optical patch panel assembly as indicated. Ensure splice attenuation does not exceed 0.2 db.
Cover splice with a protective sleeve.
2.2.4 Fiber Optic Enclosures
Provide metallic enclosures for fiber optic data transmission equipment.
NEMA 250, type 4 enclosure. Protect the spliced fibers from moisture and physical damage. Splice closure provides strain relief for the cable and the fibers at splice points. Provide full documentation citing conformance to structural parameters.
2.2.5 Fiber Optic Terminations And Connectors
FO connectors to comply with TIA/EIA-4750000-C and TIA/EIA-604-3.
2.2.6 Fiber Optic Pathway System
Provide an FO pathway system including raceway conduit, as shown on the drawings. Provide pathway materials compliant with TIA-569.
SECTION 27 13 23.00 40 Page 10
2.2.6.1 Conduit
Provide conduit as specified in Section 33 71 02 UNDERGROUND ELECTRICAL
DISTRIBUTION.
2.2.7 FO Media Tags
Provide stainless steel, 1 5/8-inches in diameter 1/16-inch thick, and circular in shape.
2.3 MATERIALS
Verify all materials used within a given cable are compatible with all other materials used in the same cable when such materials come into intimate contact. Ensure all cable components used have no adverse affect on optical transmission or on the mechanical integrity characteristics of the fiber placed in the cable, and all materials used are non-toxic, non-corrosive, and present no dermal hazard.
Minimum required material components applied to fiber optic cable construction are: central core member, color-coded optical fiber, color-coded loose tube buffer with gel-filling, gel-filling around loose tube, inner jacket, pulling strength members, and outer jacket. Variations in sequence and construction structural components will be considered when necessary.
2.3.1 Central Core Member
Include a central core member to serve as a cable core foundation to reduce strain on the fibers but not to serve as a pulling strength member. Ensure material of the central core member is non-metallic.
2.3.2 Optical Fibers
Provide two types of optical fibers, single-mode fiber and multi-mode fiber, within the cable as follows:
a. Provide Single-Mode (SM) fiber of equivalent graded index optical glass, with a fiber core diameter of approximately 8.7 micrometer.
Cladding diameter is 125 plus or minus 3 micrometer with core cladding offset less than 1 micrometer. Ensure minimum tensile strength of the fiber after primary protective coating is greater than 50,000 psi.
b. Provide multi--Mode (MM) fiber of the graded index optical glass type, with a core diameter of 50 plus or minus 3 micrometers. Cladding diameter is 125 plus or minus 3 micrometers. Ensure the core-cladding offset is less than 3 micrometer, and the minimum tensile strength of the fiber after primary protective coating is greater than 50,000 psi.
Softening point of the optical fiber clad material is 1630 degrees C plus or minus 50 degrees C in accordance with ASTM C338, or the optical fiber meets the requirements in paragraph SPLICE COMPATIBILITY TEST.
2.3.3 Fiber Primary Protective Coating
Coat optical fiber with suitable material to preserve the intrinsic high tensile strength of the glass fiber. Ensure outside diameter of the coated optical fiber is 250 (plus or minus 15) micrometer. Provide coating
SECTION 27 13 23.00 40 Page 11 material which is readily removable, mechanically or chemically, without damaging the optical fibers when the removal is desired.
2.3.4 Optical Fiber Color-Code Coating
Coat primary protective coated SM and MM fibers with a color-code coating for individual fiber identification. Maximum outside diameter of color-code coated fiber is less than 300 micrometer.
2.3.5 Colorants
Verify color concentrates or inks used to color code the optical fibers and the loose buffer tube are not susceptible to migration and chemical reaction with gel filling compound.
2.3.6 Filling Compound
Ensure inner jacket interior and loose tube buffer cavity contains a gel-type filling compound, of suitable viscosity so that it protects the optical fibers against the ingress of water and/or soluble chemicals, and not flow at the temperature of up to 149 degrees F. Verify gel filling compound is electrically non-conducting, inert gel-type, waterproof compound, non-toxic, with no dermal hazards, and compatible chemically and mechanically with all cable components and associated splice hardware materials to which it may make contact. Ensure gel filling compound is removable, as required, using commercially available products under field-type conditions.
2.4 TESTS, INSPECTIONS, AND VERIFICATIONS
2.4.1 Factory FO Quality Control
Provide conduit factory quality tests of FO media as required by TIA-472D000.
2.4.2 Factory Test Certificates
Provide fiber optical cable complying with the following optical and mechanical test requirements.
2.4.2.1 Optical Performance
a. Multi-Mode Fibers in the Cable
Verify optical attenuation of each optical fiber in the cable (reeled) is no greater than 1.0 dB/Km at 1300 plus or minus 50 nm optical spectrum window. Measure attenuation on completed cable reel length, and normalized linearly to 1 Km.
Verify bandwidth at minus 3 dB optical power of each optical fiber in the cable (reeled) is a bandwidth length product, gamma equals 1, greater than 1 GHz-Km at 1300 plus or minus 50 nm optical spectrum window.
Verify numerical aperture of each optical fiber is 0.2 plus or minus 0.015 at 1300 nm optical spectrum window. Ensure method of numerical aperture measurement is in accordance with TIA-455-177, at central wavelength 1300 nm nominal. When this requirement is not met, apply the fusion splice compatibility test.
b. Single-Mode Fibers in the Cable
SECTION 27 13 23.00 40 Page 12
Verify optical attenuation of each optical fiber in the cable (reeled) is no greater than 0.5 dB/Km at 1300 plus or minus 50 nm optical spectrum window. Measure attenuation on completed cable reel length, and normalized linearly to 1 Km. Ensure measurement method is in accordance with TIA-455-78-B, at central wavelength 1300 nm nominal.
Verify pulse dispersion of each optical fiber in the cable (reeled) is no greater than 3.5 picosecond/nm-Km within the emissive region of 1285-1330
nm. Ensure measurement method is in accordance with TIA-455-175.
Verify mode field diameter at 1300 nm optical spectrum window is within 10 plus or minus 1 micrometer. Ensure measurement method is in accordance with EIA/TIA 455-165A at central wavelength 1300 nm nominal. When this requirement is not met, apply the fusion splice compatibility test.
Verify cut-off wavelength for 1300 nm optical spectrum window is within 1200 plus or minus 70 nm. Ensure measurement method is in accordance with
ANSI/TIA-455-80C.
2.4.2.2 Mechanical Performance
a. Minimum Bend Radius
Provide cable which withstands bending to a minimum radius of 10 times the cable outer diameter without tensile load applied, and of 20 times the cable outer diameter with maximum tensile load applied (during installation), without damage to cable components or degradation of the optical fiber performance at room temperature.
b. Tensile Strength
Provide fiber optical cable which withstands a pull force of at least 400 pounds to be applied to the pulling strength member during the installation, and a tensile load of at least 300 newtons during operation without incurring any damage or detriment to fiber optical cable and optical performance. Ensure tensile strength test is in accordance with
TIA-455-33.
c. Flexing or Bending Cycles
Provide fiber optical cable which withstands at least 20 bending cycles at minimum bend radius without damage to the fiber optic cable components or degrading optical performance. Ensure cyclic flexing test is in accordance with TIA-455-104.
d. Crush Resistance
Provide minimum crush resistance of the fiber optical cable greater than 650 newton/centimeter (cm) without damage to cable components or degrading optical performance. Ensure crush resistance test is in accordance with
TIA/EIA 455-41-A.
e. Impact Resistance
Provide fiber optical cable capable of withstanding 20 impacts, at five newton-meters force, without damage to cable components, or degradation of optical performance. Ensure impact resistance test is in accordance with
TIA/EIA-455-25.
SECTION 27 13 23.00 40 Page 13
f. Gel Filling Compound Drip Test
Test optical cable for the ability of the gel filling compound in the interior of the inner jacket and loose tube buffer to resist flow at the temperature range of minus 40 degrees C to 60 degrees C in accordance with
TIA/EIA-455-81.
g. Fluid Penetration
Provide optical cable capable of preventing the entry and axial migration of pressurized water when subjected to fluid penetration testing in accordance with TIA-455-82.
2.4.3 Factory Reel Test
Test 100 percent OTDR test of FO media at the factory prior to shipment in accordance with TIA-568-C.1 and TIA-568-C.3. Use TIA-526-7 for single mode fiber and EIA TIA/EIA-526-14A Method B for multi mode fiber measurements.
Calibrate OTDR to show anomalies of 0.2 dB minimum. Provide digitized or photographic traces to the Contracting Officer.
PART 3 EXECUTION
3.1 INSTALLATION
Install and test the FO media in accordance with contract drawings, specifications, IEEE C2, NFPA 70, and TIA-590. Provide all necessary power, utility services, technicians, test equipment, calibration equipment as required to perform reel and final acceptance tests of the media.
Replace all media which fails the factory or reel tests or final acceptance field tests and re-test at the contractors expense.
3.1.1 Fiber Splices
Splices are not permitted unless shown on the construction drawings.
Field test splices within 24 hours after splice installation. Test splices to demonstrate a maximum 0.2 dB loss. Provide a minimum of 6 1/2-feet for routing and testing media. Provide fusion type outside plant fiber splices along the fiber route. Make all splice measurements at 1300 nm, plus or minus 5 nm. Mount all splices in trays. Do not increase number of splices.
Protect media ends of unspliced FO media during splicing operations. Cover completed splice with a protective sleeve heat shrink type to restore the protective properties of the fiber coating and buffering. Deviations to the splice, location and pulling plan will be permitted, upon approval by the Contracting Officer, at no additional cost to the Government.
Ensure all fiber colors are continuous from end to end. No switching or staggering of color scheme within the cable at splice points is allowed.
Splice fibers in order with multi-mode fibers identified first and single mode fibers at the end.
Bring cables out of the manhole in a controlled environment to perform the fiber fusion splice operation. Complete splice by returning the cable to the manhole such that the excess cable does not impede future entrance and utilization. Secure cable at regular intervals.
SECTION 27 13 23.00 40 Page 14
3.1.2 Contractor Damage
Promptly repair indicated utility and communications lines or systems damaged during site preparation and construction. When Contractor is advised in writing of the location of a non-indicated line or system, such notice provides that portion of the line or system with "indicated" status in determining liability for damages. In every event, immediately notify the Contracting Officer of damage.
3.1.3 Cable Installation in Cable Trays
Do not install communication cables in the same cable tray with ac power cables.
Install cables placed in cable trays in a neat and orderly manner and not crossed or interlaced with other cables except at breakout points.
Individually retain cables in vertical trays with straps at a maximum of 6-feet on center.
3.1.4 Grounding Systems
Ground cables at each termination point or as indicated.
3.1.5 Cable Pulling
3.1.5.1 FO Media Tensions
Install FO media as shown on construction drawings. Provide devices to monitor media tension during installation. Do not exceed manufacturers recommended maximum FO tensions and bending radii during installation.
3.1.5.2 Pulling Eyes
Equip media 1-1/4-inches in diameter and larger with cable manufacturer's factory installed pulling-in eyes. Provide media with diameter smaller than 1-1/4-inches with heat shrinkable type end caps or seals on cable ends when using cable pulling grips. Do not beat rings to prevent grip from slipping into the cable sheath. Use a swivel grip of 3/4-inch links between pulling-in eyes or grips and pulling strand.
3.1.6 Grounding
Ground exposed non current carrying metallic parts of telephone equipment, media sheaths, media splices, and terminals.
3.2 FIELD QUALITY CONTROL
3.2.1 Test Requirements
Ensure test equipment used for verifying installation testing is calibrated by a certified testing company within 3 weeks of use.
3.2.1.1 Single and Multi-Mode OTDR Test
Ensure the Optical Time Domain Reflectometer (OTDR) conforms to the following minimum requirements:
a. Operating wavelengths: 1,300 plus or minus 20 nanometers
SECTION 27 13 23.00 40 Page 15
b. Attenuation Range (one way): minimum 15 dB at 1,300 nm
c. Attenuation Resolution: 0.01 dB
d. Accuracy: plus 0.5 dB
Use OTDRs with digital readout capability and a means of providing a permanent record in the form of a strip chart.
3.2.1.2 End-to-End Attenuation Tests
An attenuation measurement test set consists of an optical power meter and an optical power source. Provide attenuation measurement test set in accordance with the applicable National Bureau of Standards (NBS) standards for a stable optical source. Meter may be analog or digital. Include end-to-end attenuation test reading on the test reference loss. Ensure measurement test set conforms to the following minimum requirements:
a. Operating wavelengths: 1,300 plus or minus 10 nanometers
b. Attenuation Range: at least 30 dB at 1,300 nm
c. Attenuation Resolution: 0.01 dB
d. Accuracy: The accuracy of the attenuation measurement test set is plus or minus 5 percent.
Ensure optical source is capable of coupling sufficient power into the fiber so that the light received at the meter is within the meter delectability limits.
3.2.1.3 End-to-End Bandwidth Tests
Ensure bandwidth test conforms to the following minimum requirements:
a. Operating wavelengths: 1,300 plus or minus 10 nanometers
b. Bandwidth range: minimum 1000 megahertz
c. Bandwidth Resolution: 1 megahertz
d. Accuracy: plus or minus 0.5 megahertz, Measurement Method: Swept Frequency
As a minimum, test each fiber cable before and after installation for any faults or attenuations using an Optical Time Domain Reflectometer (OTDR).
Conduct end-to-end attenuation tests after complete installation.
Clearly state all test equipment, test procedures, and testing techniques in the quality assurance plan. Conduct tests in accordance with the approved Quality Assurance Plan. Ensure all field tests are witnessed by the Contracting Officer. Give Contracting Officer at least 20 calendar days notice prior to performing each test.
Provide each test sheet with a sign-off blank for both Contractor and the Contracting Officer. Deliver copies of the completed test forms and test results as indicated.
SECTION 27 13 23.00 40 Page 16
Record sequential cable markings along the cable on the sequential cable form, prior to and after each end of splice point,and submit for approval.
Submit test results on all installed fiber cabling before and after each pre-connectorized cable assembly splice is completed.
Maintain an accurate test record during all field tests.
3.2.2 Field Reel Tests
Perform the following tests on FO media at the job site before it is removed from the cable reel. For cables with factory installed pulling eyes, perform these tests at the factory and submit certified test results with the media. Perform OTDR tests with media on reels and compare factory and field test data.
3.2.2.1 Reel Test Reports
Provide results of reel tests to the Contracting Officer within 5 working days before installation is to commence. Verify results indicate reel number of the media, manufacturer, type and number of fiber tested, and recorded readings in the report. When reel tests indicate that the media does not comply with factory reel test reports remove the media from the job site and replace with compliant media.
3.2.3 Final Acceptance Tests
Perform end-to-end tests including power meter light source and OTDR tests. Perform OTDR measurements as required by TIA-568-C.1 and TIA-568-C.3.
Test single mode fiber in accordance with TIA-526-7 (Optical Power Loss).
Test multi mode fiber in accordance with TIA-526-14(Optical Power Loss).
3.2.3.1 Test Results
Provide results of final acceptance tests (attenuation tests, OTDR traces, etc.), to the Contracting Officer within 5 working days after completion of tests.
3.3 CLOSEOUT ACTIVITIES
Submit 5 copies of the Record (As-Built) Drawings to the Contracting Officer.
-- End of Section --
SECTION 27 13 23.00 40 Page 17
SECTION 27 21 00.00 20
INTERCOMMUNICATION SYSTEM
04/06
-- End of Section --
SECTION 27 21 00.00 20 Page 1
SECTION 27 21 00.00 40
INTERCOMMUNICATION SYSTEM
02/16
-- End of Section --
SECTION 27 21 00.00 40 Page 1
SECTION 27 21 10.00 40
FIBER OPTIC DATA TRANSMISSION SYSTEM
05/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ELECTRONIC INDUSTRIES ALLIANCE (EIA)
ANSI/TIA-455-80C (2003) FOTP-80 - IEC 60793-1-144 Optical fibres Part 1-44: Measurement Methods and Test Procedures - Cut-off Wavelength
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2)
National Electrical Code
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-455-177 (2003b) FOTP-177 IEC-60793-1-43:
Measurement Methods and Test Procedures - Numerical Aperture
TIA-455-58 (2001b) FOTP-58 Core Diameter Measurement of Graded-Index Optical Fibers
TIA-455-78-B (2002) FOTP-78 Optical Fibres - Part 1-40: Measurement Methods and Test Procedures - Attenuation
TIA/EIA-455-204 (2000) Standard for Measurement of Bandwidth on Multimode Fiber
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
47 CFR 15 Radio Frequency Devices
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Fiber Optic System; G
SECTION 27 21 10.00 40 Page 1
Installation; G
SD-03 Product Data
Fiber Optic System; G
Spare Parts; G
Enclosures; G
Data Transmission Converters; G
SD-06 Test Reports
Test Procedures and Reports
Power Attenuation Test
Analog Video Signal Test
Digital Video Signal Test
Optical Time Domain Reflectometer Tests
SD-07 Certificates
Fiber Optic System
Optic Cable Assemblies
Labeling Format
SD-08 Manufacturer's Instructions
Manufacturer's Instructions
Manufacturer's Recommendations
SD-10 Operation and Maintenance Data
Operating Instructions
1.3 MAINTENANCE MATERIAL SUBMITTALS
1.3.1 Spare Parts
Submit spare parts data for each different item of material and equipment specified and furnished, after approval of detail drawings not later than 3 months prior to the date of beneficial occupancy. Include a list of parts and supplies, with current unit prices and source of supply, and a list of the parts recommended by the manufacturer to be replaced after 3 years of service.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide a fiber optics (FO) data transmission system (DTS). The data transmission system consists of FO transmission media, transmitter and
SECTION 27 21 10.00 40 Page 2 receiver modules, modems, transceiver modules, repeaters, cable and power line surge protection, terminal devices (such as connectors, patch panels and breakout boxes) and power supplies for operating active components.
Interconnect the data transmission system system components as shown.
Certify that computing devices comply with the requirements for Class A computing devices and are labeled as set forth in 47 CFR 15.
2.1.1 Environmental Requirements
Rate equipment and cable used indoors for continuous operation under ambient environmental conditions of 32 to 122 degrees F dry bulb and 10 to 95 percent relative humidity, non-condensing. Rate equipment and cables for continuous outdoor operation under ambient environmental conditions of minus 40 to plus 166 and humidity of up to 100 percent condensing or as normally encountered for the installed location. Rate all equipment and cable for continuous operation under the ambient environmental temperature, pressure, humidity, and vibration conditions specified or normally encountered for the installed location. Install cables in ducts, plenums, and other air-handling spaces per NFPA 70. Ensure cables installed in plenums are plenum-rated cables listed for the use. Ensure cables installed in risers are riser-rated cables listed for the use, unless the installed cable is identified as a permitted substitution for the required riser-rated cable type.
2.1.2 Hazardous Environment
Rate the system components and wiring located in areas where fire or explosion hazards may exist with the proper Classes, Divisions, and Groups.
Also rate the components and wiring for the operating temperatures.
Install according to Chapter 5 of NFPA 70 and as shown.
2.1.3 Electrical Requirements
Operate the equipment from a voltage source as shown, plus or minus 10 percent, and 60 Hz, plus or minus 2 percent.
2.1.4 Input Line Surge Protection
Protect inputs and outputs against surges induced on wiring and cables including wiring and cables installed outdoors. For components requiring protection, select surge protection devices based on voltages and current ratings of components to be protected. Protect communications equipment against surges induced on any communications circuit. Install surge protection circuits at each end of cables and conductors (except non-conductive FO cables which serve as communications circuits from consoles to field equipment and between field equipment). Furnish protection at equipment. Install additional triple electrode gas surge protectors rated for the application on each conductive wire line and coaxial circuit within 3-feet of the building cable entrance. Do not use fuses for surge protection. Test the inputs and outputs in both normal mode and common mode using the following two waveforms:
a. A 10 microsecond rise time by 1000 microsecond pulse width waveform with a peak voltage of 1500 volts and a peak current of 60 amperes.
b. An 8 microsecond rise time by 20 microsecond pulse width waveform with a peak voltage of 1000 volts and a peak current of 500 amperes.
SECTION 27 21 10.00 40 Page 3
2.2 COMPONENTS
2.2.1 Optical Fibers
2.2.1.1 General
Coat optical fibers with a suitable material to preserve the intrinsic strength of the glass. The outside diameter of the glass-cladded fiber is nominally 125 microns, and concentric with the fiber core. Ensure optical fibers meet TIA-455-78-B, and TIA-455-177.
2.2.1.2 50 Micron Multimode Fibers
Use conductors that are multimode, graded index, solid glass waveguides with a nominal core diameter of 50 microns. Ensure the fiber has transmission windows centered at 850 and 1300 nanometer wavelengths, with a numerical aperture minimum of 0.20. The attenuation at 850 nanometers is
3.5 dB/Km or less. The attenuation at 1300 nanometers is 1.5 dB/Km or less. For both transmission windows, the minimum bandwidth is 500 MHz-Km.
Certify the fibers to meet TIA/EIA-455-204 and TIA-455-58.
2.2.1.3 8.3 Micron Single-Mode Fibers
Use conductors that are single-mode, solid glass waveguides with a nominal core diameter of 8.3 microns. Ensure the fiber has a transmission windows centered at 1310 and 1550 nanometer wavelengths with a numerical aperture minimum of 0.10. The attenuation for inside cable at 1310 and 1550 nanometers is 1.0 dB/Km or less. The attenuation for outside cable at 1310 and 1550 nanometers is 0.5 dB/Km or less. Certify the fibers to meet
ANSI/TIA-455-80C.
2.2.2 Cross-Connects
2.2.2.1 Patch Panels
Install patch panels as a complete system of components by a single manufacturer; provide termination, splice storage, routing, radius limiting, cable fastening, storage, and cross-connection. Ensure patch panel connectors and couplers are the same type and configuration as used elsewhere in the system. Patch panels are a 19-inch rack mount type as shown.
2.2.2.2 Patch Cords
Provide patch cord cable assemblies consisting of factory connector-terminated flexible optical fiber cable with connectors of the same type as used elsewhere in the system. Optical fiber is the same type as used elsewhere in the system. Install patch cords as complete assemblies from manufacturer's standard products.
2.3 SYSTEM REQUIREMENTS
2.3.1 Receiver Dynamic Range
Ensure the dynamic range of receivers is large enough to accommodate both the worst-case, minimum receiver flux density, and the maximum possible receiver flux density, with a range of at least 15 dB. Where required, use optical attenuators to force the FO link power to fall within the receiver dynamic range.
SECTION 27 21 10.00 40 Page 4
2.4 ACCESSORIES
2.4.1 Fusion Splices
Use a portable, fully automatic, and compact fusion splicer, suitable for fusion splicing all types of telecommunication grade optical fibers and individual fibers as well as cables containing multiple optical fibers.
Ensure the fusion splicer is capable of operation under various environmental conditions (e.g., temperature, humidity, altitude, etc.) for all types of optical cable deployments. Start the automatic splicing process by pressing one button and can be interrupted at any time.
Alternatively, make available semi-automatic (step-by-step) or manual splicing by menu selection. Conduct communication with the fusion splicer through a language unspecific keyboard with universal symbols and display the dialogue with the splicer on the device screen.
2.4.2 Conduit, Fittings And Enclosures
Ensure conduit, fittings, and enclosures are as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM, and as shown.
2.4.3 Fan-Out Kits
For all loose-tube optical fibers, furnish and install fan-out kits using furcating tubes for connectorization. Incorporate strain relief for loose-tube optical fiber furcating tubes if the connectorization is not contained within a protective enclosure such as a patch panel. For tight-buffered optical fibers, furnish and install fan-out kits using furcating tubes and which incorporate strain relief, if the connectorization is not contained within a protective enclosure such as a patch panel. Furcating tubes required to incorporate strain relief also provide increased pullout protection. Tubes are comprised of an inner tube, surrounded by a layer of nonconductive strength members, then surrounded by an enclosing outer jacket layer. Color code fan-out kits to match the industry fiber color scheme. Length of furcating tube is 2436-inches minimum when installation is complete. Rate fan-out kits for the ambient conditions of the location as specified in paragraph ENVIRONMENTAL REQUIREMENTS. Provide terminations for each fiber, regardless whether fiber is active or spare.
2.5 CABLE CONSTRUCTION
2.5.1 Interior Cable
Loose buffer tube cable construction is such that the optical fibers are surrounded by a tube buffer, and contained in a channel or otherwise loosely packaged to provide clearance between the fibers and the inside of the container allowing for thermal expansions without constraining the fiber. Extrude the protective container from a material having a coefficient of friction sufficiently low to allow the fiber free movement.
Use fluorocopolymer (FCP) for the cable outer jacket, which complies with NFPA 70 for optical fiber nonconductive plenum (OFNP) applications. Do not exceed the manufacturers' recommended values for tensile strength, impact resistance, and crush resistance. Insulation and jacketing cable material cannot contain any polyvinyl chloride (PVC) compounds.
For tight buffer tube cable construction, use extrusion of plastic over each cladded fiber, with an outer jacket of FCP, which complies with NFPA 70
SECTION 27 21 10.00 40 Page 5 for optical fiber nonconductive riser (OFNR) requirements for riser cables and vertical shaft installations. Cover optical fibers in near contact with an extrusion tube and an intermediate soft buffer to allow for the thermal expansions and minor pressures. Do not exceed manufacturers' recommended values for tensile strength, impact resistance, and crush resistance. Insulation and jacketing cable material cannot contain any polyvinyl chloride (PVC) compounds.
2.5.2 Pigtail Cables
Use flexible fiber pigtail cables for connections to equipment having the same physical and operational characteristics as the parent cable. Ensure the cable jacket is FCP, which complies with NFPA 70 for OFNP applications. Maximum dB loss for pigtail cable is 3.5 dB/km at 850 nanometers, and 1.0 dB/km at 1300 nanometers, and .5 dB/Km at 1550 nanometers.
PART 3 EXECUTION
3.1 INSTALLATION
Install system components and appurtenances in accordance with the manufacturer's instructions and as shown. Provide interconnections, services, and adjustments required for a complete and operable data transmission system.
Where installation procedures, or any part thereof, are required to be in accordance with the manufacturer's recommendations of the material being installed, submit printed copies of these recommendations prior to installation. Installation of the item is not allowed to proceed until the recommendations are received and approved.
3.1.1 Interior Work
Install conduits, tubing and cable trays for interior FO cable as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM and as shown. Ensure cable installation and applications meet the requirements of NFPA 70, Article 770. Properly support and secure cables not installed in conduits or wireways. If installed in plenums or other spaces used for environmental air, comply with NFPA 70 requirements for this type of installation.
3.1.2 Service Loops
Ensure each FO cable has service loops of not less than 9.8-feet in length at each end. House the service loops in a service loop enclosure.
3.1.3 Metallic Sheath Grounding
Ground the FO cable with metallic sheath that enter buildings at a point as close as practivable to the building point of entrance. Ensure FO cable with metallic sheath routed in the trench with a power cable has the metallic sheath grounded at the cable termination points.
3.1.4 Splices
3.1.4.1 General
No splices are permitted unless the length of cable being installed exceeds
SECTION 27 21 10.00 40 Page 6 the maximum standard cable length available from a manufacturer or unless FO pigtails are used to connect transmitters, receivers, or other system components for terminations to the fiber. Make splices using the method recommended by the cable manufacturer. Place splices in a splice enclosure and encapsulate with an epoxy, ultraviolet light cured splice encapsulant or otherwise protected against infiltration of moisture or contaminants.
Field test FO splices at the time of splicing. Ensure fusion splices have a nominal splice loss of 0.15 dB for multimode and for single mode cable fusion splices and a maximum fusion splice loss not more than 0.3 dB loss.
3.1.5 Enclosure Sizing and Cable
Size termination enclosures to accommodate the FO equipment to be installed. Sizing includes sufficient space for service loops to be provided and to accommodate a neat layout of equipment and the bend radii of fibers and cables terminated inside the enclosure.
3.1.6 Enclosure Penetrations
Install enclosure penetrations from the bottom. Seal penetrations with rubber silicone sealant to preclude the entry of water. Internally seal conduits rising from underground.
3.2 FIELD QUALITY CONTROL
3.2.1 General
Provide personnel, equipment, instrumentation, and supplies necessary to perform testing.
3.2.2 Field Test
Verify the complete operation of the data transmission system in conjunction with field testing associated with systems supported by the fiber optic data transmission system as specified in Section prior to formal acceptance testing. Include a flux density test in field tests.
Perform these tests on each link and repeated from the opposite end of each link.
3.2.2.1 Optical Time Domain Reflectometer Tests
Perform optical time domain reflectometer tests using the FO test procedures of TIA-455-78-B. Perform an optical time domain reflectometer test on all fibers of the FO cable on the reel prior to installation.
Calibrate the optical time…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.