NO.3 NOTES BY SYMBOL " "
NO.5 NOTES BY SYMBOL " " NO.7 NOTES BY SYMBOL " "
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING AND
PROVIDING ALL PULL BOXES AS REQUIRED BY THE NATIONAL
ELECTRICAL CODE.
2. ALL PULL BOXES SHALL BE AASHTO-HS-20 RATED.
GROUND ROD DETAIL
NOT TO SCALE
PULL BOX
NOT TO SCALE
CONCRETE ENCASED
DUCT BANK DETAIL
NOT TO SCALE
CEILING MOUNTED CONDUIT RACK
NOT TO SCALE
WATERTIGHT CONDUIT PENETRATION
NOT TO SCALE
CEILING OR WALL EXPOSED
CONDUIT INSTALLATION
NOT TO SCALE
UNDERGROUND TO ABOVE GRADE
CONDUIT TRANSITION
NOT TO SCALE
91/2"
4"
"M
IN
"M
IN
3'-0"MAX BETWEEN RODS
"M
IN
"M
IN
"M
IN
1"MIN
NO.2 GENERAL NOTES:
1"(TYP)
CONTINUOUS LOOP
GRADE
BROOKS OR
EQUAL
AASHTO HS-20
TRAFFIC RATED
COVER
SCHEDULE 40 PVC CONDUIT
(TYP)
#4 CONTINUOUS REBAR
@ EACH REBAR HOLE IN SPACER
(MIN OF 4, TYP)
#4 REBAR DRIVEN INTO SOLID
EARTH FOR ANCHOR (TYP)
#4 STIRRUP @ 18"C/C MAX
SPACERS @ 8'-0"C/C (TYP)
BACKFILL & COMPACT
W/SELECT MATERIAL
3000 PSI CONCRETE ENCASEMENT
FINISHED GRADE
LOCATION TAPE (12"
BELOW GRADE)
NO.5 GENERAL NOTES:
1. CONTRACTOR SHALL PROVIDE CHAIRS FOR REBAR ROUTED ALONG BOTTOM
OF DUCT BANK TO VERIFY THAT REBAR IS FULLY ENCASED WITH 4" OF
CONCRETE.
CONCRETE INSERT
PLASTIC END CAPS (TYP)
TYPE 304 SS 1/2" FULL
THREADED ROD
(TYP)
304 STAINLESS STEEL CHANNEL
UNISTRUT P1000 OR EQUAL
CONDUIT (TYP)
CONDUIT CLAMP, NUMBER &
SIZE AS REQUIRED (TYP)
CAULK ALL AROUND
W/SEALANT PRIOR TO
INSTALLING BUSHING
FILL VOID WITH
NON-SHRINK GROUT
AFTER INSTALLATION
CORE DRILLED HOLE
FLANGED TYPE
SEALING BUSHING
CONDUIT
MASONRY WALL
CONDUIT
(TYP)
COMPRESSIBLE
JOINT FILLER
EXISTING FOOTING OR
FOUNDATION
PVC COATED
ALUMINUM CONDUIT
PVC COATED ALUMINUM
OR FIBERGLASS LONG
SWEEP ELBOW
REFER TO APPLICABLE
WALL PENETRATION DETAILS
ALUMINUM EXPANSION FITTING
ALUMINUM CONDUIT
CONCRETE SLOPED AWAY
FROM BUILDING, 1"
CHAMFER ALL AROUND
CONCRETE ENCASEMENT AS
INDICATED ON PLANS
SCHEDULE 40 PVC
ALUMINUM ADAPTER
SCHEDULE 40 PVC
AASHTO HS-20 CAST IRON LID
W/ 1
2" LIFTING ROD
WELD CONDUCTORS TO ROD
EXOTHERMICALLY (2 PLACES)
BROOKS MODEL 3-RT OR
EQUAL
4"x10'-0" COPPER CLAD
GROUNDING ROD
1. ANCHORS SHALL BE 1
2"DIA STAINLESS STEEL KWIK BOLT III
WITH 31
2" EMBEDMENT. DO NOT DAMAGE EXISTING
STRUCTURE DURING ANCHOR INSTALLMENT.
304 STAINLESS STEEL
STRUT CHANNEL
2" 100MILS NEOPRENE
BUSHING (TYP)
CLAMP
(SIZE AS REQUIRED)
1. SELECT BACKFILL TO BE CLASS 4 EARTH FILL. FILL SHALL CONSIST OF MATERIALS
WHICH ARE CLASSIFIED AS SP, SM, SC, CL OR DUAL CLASSIFICATIONS THEREOF,
WHICH HAVE A LIQUID LIMIT LESS THAN OR EQUAL TO 35 AND A PLASTICITY
INDEX OF A MINIMUM OF 4 AND A MAXIMUM OF 15, WHICH ARE FREE OF
ORGANIC MATERIALS.
2. 24" FOR 600VAC AND BELOW, 26" FOR ABOVE 600VAC.
1. ALUMINUM CONDUIT TO EQUIPMENT AS REQUIRED. THE CONTRACTOR
SHALL SIZE AND PROVIDE PULL BOXES AS REQUIRED BY THE NATIONAL
ELECTRICAL CODE.
2. APPLY RUBBER ELECTRICAL TAPE TO ALL EXPOSED METAL CONDUIT OR
CONDUIT THREADS. EXTEND TAPE A MINIMUM 2" IN BOTH DIRECTIONS
BEYOND EXPOSED CONDUIT.
ALUMINUM LB & RISER MATERIAL
AS SPECIFIED MOUNT AS HIGH AS
POSSIBLE
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
H E
P U
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
A
T H
O R
IT
Y
O F
T E
X A
S N
O
N D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
E-501
D E
T A
IL
S
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
BACNET
SQUARE D
POWER
LOGIC PM
8000 SERIES
M D
P -0
208Y/120V, 3PH, 4W, 65KAIC, 1600A
225A 3P
1600/5
2PT'S
SPD
/0
G
/2
"C
M D
P -0
EQUIPMENT
PANEL "M1"
400A 3P
SPD
M D
P -0
100A 3P
SPD
M D
P -0
EXISTING COMPUTER ABD
RECEPTACLE
PANEL "B"
100A 3P
SPD
M D
P -0
P
EXISTING LIGHTING
PANEL "A"
100A 3P
SPD
M D
P -0
400A
SERVICE RATED DISTRIBUTION SWITCHBOARD "MDP"
UTILITY
XFMR
1600A 3P
(LSI)
30A 3P
COMPUTER ABD
RECEPTACLE
PANEL "B2"
SPD
HVAC
PANEL "D1"
U T
IL
-0
P
/0
G
-1 /2
"C
/0
G
-1 /2
"C
S
E T
S E
A C
H
(4 -4 k cm il
/0 G
"C
N G#3/0G.
M D
P -0
SPD
(2
/0
G
"C
SPD
HVAC
PANEL "D2"
M D
P -0
SPD
HVAC
PANEL "D3"
M
-0
50A
60A 2P
WELDER
DISCONNECT
BATTALION
STORAGE BUILDING
O G
"C
G
"C
20A 2P
OIL AND FLAMMABLE
STORAGE BUILDING
G
"C
M
-0
50A
O G
"C
M D
P -0
100A
SPD
TELECOM
PANEL "T"
40A 3P
SPD
WELDER
DISCONNECT
400A 3P
/0
G
"C
/0
G
"C
/0
G
"C
/0
G
-1 /2
"C
M
-0
M
-0
208Y/120V, 3PH, 4W, 42KAIC, 400A
EXISTING
CRANE
O
G
/4
"C
30A 3P
M
-0
NEW
CRANE
O G
/4 "C
M
-0
EQUIPMENT PANEL "M2"
SPARE
225A 3P
SPARE
(2
/0
G
"C
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
E-601
O N
E -L
IN
E
D
IA
G R
A M
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
NOT TO SCALE
1 ONE-LINE DIAGRAM
GENERAL NOTES:
1. PROVIDE PANELS WITH ARCH FLASH LABELS FROM THE MANUFACTURER.
GENERAL NOTES:NOTES BY SYMBOL " "
1. PROVIDE SQUARE D METER PM8000 SERIES (METSEPM8244) DIN RAIL MOUNTED
METER WITH REMOTE DISPLAY AND (METSEPM89M2600) I/O MODULE, 6
INPUTS/COUNTERS. PROVIDE BACNET CONVERTER FOR COMMUNICATION WITH
BACNET SYSTEM.
2. SERVICE RATED BREAKER.
3. BACNET CONTROLLER.
4. SUPPLY CAT6E CABLE IN 3/4" CONDUIT.
5. COORDINATE BREAKER SIZE WITH SPD MANUFACTURER.
6. CONCRETE ENCASED UNDERGROUND SERVICE ENTRANCE RATED CONDUCTOR AS
PER NEC ART 230.
7. REMOTE BUILDING PANEL.
8. REUSE EXISTING CONDUIT AND CONDUCTORS FEEDING PANELBOARD.
9. REUSE EXISTING PANELBOARD AND 20A/1P CIRCUIT BREAKERS ASSOCIATED
BREAKERS.
10. REROUTED & FED FROM NEW PANEL M4 VIA NEW HOMERUN. PROVIDE
NECESSARY CONDUCTOR & CONDUIT FOR A COMPLETE & OPERATIONAL SYSTEM.
M A
R K
D E
S C
R
IP
T
IO
N D
A
GRADE
20' MIN.20' MIN.
PROVIDE AN INSPECTION WELL FOR THE GROUND
ROD NEAREST THE ELECTRICAL SERVICE
(3) 3/4"x10' COPPER CLAD DRIVEN GROUND
RODS IN TRIANGULAR FORM
PANEL "T"
EGB
TMGB
BONDING JUMPERS TO
EQUIPMENT RACKS,
METALLIC PATHWAYS,
& VCT FLOOR
B O
N D
IN
G
J U
M P
E R
COMM1
#3/O (G) IN 1-1/4" C.
TBC
NOTE:
LABEL ALL GROUNDING/BONDING
CONDUCTORS AT ALL TERMINATION POINTS.
1000A
PANEL
"MDP"
NEUTRAL BUS
GROUND
BUS
#3/0
BONDING
JUMPER
#3/O (GROUNDING ELECTRODE
CONDUCTOR) IN 1-1/4" C.
#3/0 TELECOMM
BONDING CONDUCTOR
(TBC) IN 1-1/4"C.
BOND TO SPRINKLER
PIPING WITHIN 5'-0"
AFTER IT ENTERS THE
BUILDING. USE PIPE
GROUND CLAMP
1/4" X 4" X 24" COPPER GROUND BAR
MOUNTED INSIDE ELECTRICAL ROOM
BOND TO GAS PIPING WITHIN 10'-0"
AFTER IT ENTERS THE BUILDING. USE
PIPE GROUND CLAMP
BOND TO WATER PIPING WITHIN
5'-0" AFTER IT ENTERS THE
BUILDING. USE PIPE GROUND CLAMP
EXOTHERMIC WELD
REMOVABLE
MECHANICAL
CONNECTION
NOT TO SCALE
1 GROUNDING DIAGRAM
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
E-602
G R
O U
N D
IN
G
D
IA
G R
A M
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
M A
R K
D E
S C
R
IP
T
IO
N D
A
PLENUM RATED CAT 5-E (CLASS 2)
LINE VOLTAGE
0-10 VDC
WIRE LEGEND
LOW VOLTAGE (1A @ 40VDC/VAC)
ETHERNET LAN (CLASS 2)
15-24 VDC POWER
D
C
B
A
F
E nBRG1 nLIGHT
ENABLED
FIXTURE
nLIGHT
ENABLED
FIXTURE
OCCUPANCY SENSOR
CONTROL OR
DAYLIGHT SENSOR AS
SPECIFIED ON PLANS
LIGHT SWITCH AS
SPECIFIED ON PLANS
A
TO OTHER
BRIDGES
A
A
A
A nPANEL
RELAYS AS REQUIRED
nPANEL
BRIDGE
120V N
CAT5E
LIGHTING LOAD
"W2"CR1
CR2
CR3
CR4
A
LIGHTING LOAD
"W2"
LIGHTING LOAD
"W2"
LIGHTING LOAD
"W2"
NECY
PS
WHITE
BLACK
ORANGE
B
BRIDGE
B
LA
C K
W H
IT
E
LIGHTING
CONTROLLER
A
TO OTHER
BRIDGES
TO OTHER
BRIDGES
C B
SENSOR VIEW
D A
B
C
B B nBRG1 nLIGHT
ENABLED
FIXTURE
nLIGHT
ENABLED
FIXTURE
LIGHT SWITCH AS
SPECIFIED ON PLANS
A
TO OTHER
BRIDGES A
A
A nBRG1 nLIGHT
ENABLED
FIXTURE
nLIGHT
ENABLED
FIXTURE
OCCUPANCY SENSOR
CONTROL OR
DAYLIGHT SENSOR AS
SPECIFIED ON PLANS
LIGHT SWITCH AS
SPECIFIED ON PLANS
A
TO OTHER
BRIDGES
A
A
A
A
LIGHT SWITCH AS
SPECIFIED ON PLANS
A
NOT TO SCALE
TYPICAL nLIGHT ENABLED CEILING SENSOR
(W/DAYLIGHT HARVESTING) DIAGRAM
NOT TO SCALE
2 EXTERIOR LIGHTING CONTROL DIAGRAM
NOT TO SCALE
1 BUILDING NETWORK DIAGRAM
NOTES BY SYMBOL " "
1. PROVIDE 120V POWER IN 2 #12, #12G., 3/4"C.
2. PROVIDE 3/4"C.
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
E-603
L
IG
H T
IN
G
C O
N T
R O
L D
IA
G
R A
M S
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
NOT TO SCALE
4 TYPICAL nLIGHT ENABLED CONTROLS
NOT TO SCALE
TYPICAL nLIGHT ENABLED CEILING
SENSOR (W/DAYLIGHT HARVESTING)
DIAGRAM MULTIPLE SWITCHES
M A
R K
D E
S C
R
IP
T
IO
N D
A
SEQUENCE OF OPERATIONS FOR
LIGHTING SWITCHING / CONTROL
SPACE DESCRIPTION A B C D E
ELECTRICAL / MECHANICAL / TELECOM / FLUID DISTR.
STAIRWAY
STORAGE
RESTROOM
PRIVATE OFFICE
OPEN OFFICE
CORRIDORS
ARMS VAULT, COMSEC VAULT
LUMINAIRE CONTROL FUNCTIONS
VEHICLE MAINTENANCE AREA
WORKSHOPS - TOOL ROOM, CONSOLIDATED BENCH REPAIR
TRAINING / CLASSROOM / COMBAT SPARES / UNASSIGNED
F G H I J LK
BREAK ROOM
EXTERIOR PERIMETER BUILDING AREA
S C
H E
D U
LE
D
S H
U T
O F
F
R E
S T
R
IC
T E
D T
O M
A N
U A
L O
N
N O
N E
O F
T H
E L
IG
H
T
IN
G S
H A
LL
B E
A U
T O
M A
T
IC
A
LL
Y T
U R
N E
D O
N
R E
S T
R
IC
T E
D T
O P
A R
T
IA
L A
U T
O M
A T
IC
O
N
N O
M O
R E
T H
A N
O
F T
H E
L
IG
H T
IN
G
P O
W E
R S
H A
LL
B
E A
U T
O M
A T
IC
A
LL
Y
T U
R N
E D
O N
A N
D N
O N
E O
F T
H E
R E
M A
IN
IN
G L
IG
H
T
IN
G S
H A
LL
B E
A U
T O
M A
T
IC
A
LL
Y T
U R
N E
D O
N
B
IL
E V
E L
LI
G
H T
IN
G
C O
N T
R O
L
P R
O V
ID
E
O N
E I
N T
E R
M E
D
IA
T E
S T
E P
I N
L
IG
H T
IN
G
P O
W E
R O
R C
O N
T
IN
U O
U S
D
IM
M
IN
G
S T
E P
S H
A
LL
B E
B E
T W
E E
N
A N
D
O F
F U
LL
L
IG
H
T
IN
G P
O W
E R
A U
T O
M A
T
IC
D A
Y
LI
G H
T R
E S
P O
N S
IV
E
C O
N T
R O
L F
O R
S
ID
E
LI
G
H T
IN
G
A U
T O
M A
T
IC
D A
Y
LI
G H
T R
E S
P O
N S
IV
E
C O
N T
R O
L F
O R
T O
P
LI
G
H T
IN
G
A U
T O
M A
T
IC
P A
R T
IA
L
O F
F
L
IG
H T
IN
G
P O
W E
R S
H A
LL
B
E
A U
T O
M A
T
IC
A
LL
Y R
E D
U C
E D
B Y
A T
L E
A S
T
W
IT
H
IN
M
IN
U T
E S
O F
A
LL
O C
C U
P A
N T
S L
E A
V
IN
G T
H E
S P
A C
E
A U
T O
M A
T
IC
F U
LL
O
F F
L
IG
H
T
IN
G S
H A
LL
B
E A
U T
O M
A T
IC
A
LL
Y
S H
U T
O F
F W
IT
H
IN
M
IN
U
T E
S O
F A
LL
O
C C
U P
A N
T S
L E
A V
IN
G
T H
E S
P A
C E
A U
T O
M A
T
IC
A
LL
Y S
H U
T O
F F
B E
T W
E E
N M
ID
N
IG
H
T O
R B
U S
IN
E
S S
C
LO
S
IN
G
W H
IC
H
E V
E R
I S
L A
T E
R
A N
D
A .M
O
R B
U S
IN
E
S S
O P
E N
IN
G
W
H
IC
H E
V E
R C
O M
E S
F
IR
S T
O
R B
E T
W E
E N
T
IM
E S
E S
T A
B
LI
S H
E D
B Y
T H
E A
U T
H O
R
IT
Y H
A V
IN
G
J U
R
IS
D
IC
T
IO
N
A U
T O
M A
T
IC
A
LL
Y T
U R
N S
O F
F T
H E
L
IG
H T
IN
G
W H
E N
S U
F F
IC
IE
N T
D A
Y
LI
G H
T I
S A
V A
IL
A
B
LE
A U
T O
M A
T
IC
A
LL
Y R
E D
U C
E S
T H
E C
O N
N E
C T
E D
L
IG
H T
IN
G
P O
W E
R B
Y
A T
L E
A S
T
F R
O M
M
ID
N
IG
H T
O R
W
IT
H
IN
O N
E
H O
U R
O F
T H
E E
N D
O F
B U
S
IN
E S
S O
P E
R A
T
IO
N S
W
H
IC
H E
V E
R I
S L
A T
E R
LO
C
A L
C O
N T
R O
L
O N
E O
R M
O R
E M
A N
U A
L
LI
G H
T C
O N
T R
O
LS
IN
T
H E
S P
A C
E T
H A
T C
O N
T R
O
LS
A
LL
O F
T H
E L
IG
H
T
IN
G I
N T
H E
S P
A C
E
X X X X2
X X X X X X2
X X1 X X X
X X
X2
X X X
X X X
X X X X
X
X X
X X
X X X X XX1
X X X XX1 X2
X1 X
X1
X X X XX1 X
X1 X XX X
X X1 X X X X2
GENERAL NOTES:
1. X = REQUIRED TO EXECUTE.
2. X1 = REQUIRED TO EXECUTE.
3. X2 = REQUIRED TO EXECUTE.
X
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NO. VOLT. DESCRIPTION LAMPS WATTS
A1 LITHONIA 2BLT4-30L-ADP-MVOLT-EZ1-LP835-N100-USPO
M
120 LOW PROFILE VOLUMETRIC RECESSED LED LIGHTING 2'X4', 3000
LUMENS, CURVED LINEAR PRISMS DIFFUSER, MULTI VOLTAGE, 0-10
DIMMING 82 CRI, 3500K
LED 22.9
A1E LITHONIA 2BLT4-30L-ADP-MVOLT-EZ1-LP835-N100-EL14L-
USPOM
120 LOW PROFILE VOLUMETRIC RECESSED LED LIGHTING 2'X4', 3000
LUMENS, CURVED LINEAR PRISMS DIFFUSER, MULTI VOLTAGE, 0-10
DIMMING 82 CRI, 3500K WITH EMERGENCY BATTERY PACK
LED 22.9
A2 LITHONIA 2BLT4-40L-ADP-MVOLT-EZ1-LP835-N100-USPO
M
120 LOW PROFILE VOLUMETRIC RECESSED LED LIGHTING 2'X4', 4000
LUMENS, CURVED LINEAR PRISMS DIFFUSER, MULTI VOLTAGE, 0-10
DIMMING 82 CRI, 3500K
LED 31.7
A2E LITHONIA 2BLT4-40L-ADP-MVOLT-EZ1-LP835-N100-EL14L-
USPOM
120 LOW PROFILE VOLUMETRIC RECESSED LED LIGHTING 2'X4', 4000
LUMENS, CURVED LINEAR PRISMS DIFFUSER, MULTI VOLTAGE, 0-10
DIMMING 82 CRI, 3500K WITH EMERGENCY BATTERY PACK
LED 31.7
A3 LITHONIA 2BLT4-48L-ADP-MVOLT-EZ1-LP835-N100-USPO
M
120 LOW PROFILE VOLUMETRIC RECESSED LED LIGHTING 2'X4', 4800
LUMENS, CURVED LINEAR PRISMS DIFFUSER, MULTI VOLTAGE, 0-10
DIMMING 82 CRI, 3500K
LED 38
A3E LITHONIA 2BLT4-48L-ADP-MVOLT-EZ1-LP835-N100-EL14L-
USPOM
120 LOW PROFILE VOLUMETRIC RECESSED LED LIGHTING 2'X4', 4800
LUMENS, CURVED LINEAR PRISMS DIFFUSER, MULTI VOLTAGE, 0-10
DIMMING 82 CRI, 3500K WITH EMERGENCY BATTERY PACK
LED 38
B LITHONIA JCBL-18000LM-ACFR-MVOLT-GZ10-35K-80CRI-P
M-NPP16D-USPOM
120 LED DAMP RATED HIGH BAY, 18000 LUMENS, OPEN BOTTOM LENS,
FROSTED ACRYLIC REFLECTOR, MULTI-VOLTAGE, 3500K, 80 CRI,
PENDANT MOUNTING
LED 125
BE LITHONIA JCBL-18000LM-ACFR-MVOLT-GZ10-35K-80CRI-P
M-NPP16DER-USPOM
120 LED DAMP RATED HIGH BAY, 18000 LUMENS, OPEN BOTTOM LENS,
FROSTED ACRYLIC REFLECTOR, MULTI-VOLTAGE, 3500K, 80 CRI,
PENDANT MOUNTING WITH EMERGENCY BATTERY PACK
LED 125
C1 LITHONIA CLX-L48-FST-3000LM-HEF-WDL-WD-MVOLT-EZ1
-35K-90CRI-N100-WH-USPOM
120 LINEAR 48" LENGTH, 3000 LUMENS, HIGH EFFICIENCY
PREFORMANCE, LESS LOUVER, FLAT DIFFUSE LENS, WIDE
DISTRIBUTION, MULTI-VOLTAGE, 0-10 DIMMING, 3500K, 90CRI
LED 20.32
C1E LITHONIA CLX-L48-FST-3000LM-HEF-WDL-WD-120-EZ1-35
K-90CRI-N100-E10WLCP-WH-USPOM
120 LINEAR 48" LENGTH, 3000 LUMENS, HIGH EFFICIENCY
PREFORMANCE, LESS LOUVER, FLAT DIFFUSE LENS, WIDE
DISTRIBUTION, MULTI-VOLTAGE, 0-10 DIMMING, 3500K, 90CRI WITH
EMERGENCY BATTERY PACK
LED 20.32
C2 LITHONIA CLX-L48-FST-5000LM-HEF-WDL-WD-MVOLT-EZ1
-35K-90CRI-N100-WH-USPOM
120 LINEAR 48" LENGTH, 5000 LUMENS, HIGH EFFICIENCY
PREFORMANCE, LESS LOUVER, FLAT DIFFUSE LENS, WIDE
DISTRIBUTION, MULTI-VOLTAGE, 0-10 DIMMING, 3500K, 90CRI
LED 34.8
C2E LITHONIA CLX-L48-FST-5000LM-HEF-WDL-WD-120-EZ1-35
K-90CRI-N100-E10WLCP-WH-USPOM
120 LINEAR 48" LENGTH, 5000 LUMENS, HIGH EFFICIENCY
PREFORMANCE, LESS LOUVER, FLAT DIFFUSE LENS, WIDE
DISTRIBUTION, MULTI-VOLTAGE, 0-10 DIMMING, 3500K, 90CRI WITH
EMERGENCY BATTERY PACK
LED 34.8
C3 LITHONIA CLX-L48-FST-7000LM-HEF-WDL-WD-MVOLT-EZ1
-35K-90CRI-N100-WH-USPOM
120 LINEAR 48" LENGTH, 7000 LUMENS, HIGH EFFICIENCY
PREFORMANCE, LESS LOUVER, FLAT DIFFUSE LENS, WIDE
DISTRIBUTION, MULTI-VOLTAGE, 0-10 DIMMING, 3500K, 90CRI
LED 49.05
C3E LITHONIA CLX-L48-FST-7000LM-HEF-WDL-WD-120-EZ1-35
K-90CRI-N100-E10WLCP-WH-USPOM
120 LINEAR 48" LENGTH, 7000 LUMENS, HIGH EFFICIENCY
PREFORMANCE, LESS LOUVER, FLAT DIFFUSE LENS, WIDE
DISTRIBUTION, MULTI-VOLTAGE, 0-10 DIMMING, 3500K, 90CRI WITH
EMERGENCY BATTERY PACK
LED 49.05
D LITHONIA LDN6-35/15-L06-AR-LSS-MVOLT-GZ10-NPP16D-
USPOM
120 6" LED DOWNLIGHT, 3500K, 1500 LUMENS, CLEAR TRIM COLOR,
SEMI-SPECULAR FINISH, MULTI-VOTLAGE
LED 20.5
DE LITHONIA LDN6-35/15-L06-AR-LSS-MVOLT-GZ10-EL-NPP1
6D-USPOM
120 6" LED DOWNLIGHT, 3500K, 1500 LUMENS, CLEAR TRIM COLOR,
SEMI-SPECULAR FINISH, MULTI-VOTLAGE WITH EMERGENCY
BATTERY PACK
LED 20.5
F MARK LIGHTING SL4L-LOP-20FT-FLP-80CRI-35K-600LMF-NODIM-
120-NLIGHT-WL-USPOM
120 4" DIRECT LED TROFFER, WHITE FINISH. CONTRACTOR TO PROVIDE
WALL TO WALL WITHIN 6 INCHES.
LED 6W/FT
P SOLAS RAY HJGJJ1-020-40-U-HJWA-HJGU 120 MULTI-PURPOSE JELLY JAR FIXTURE, CLASS 1. DIVSION II RATED LED 20
W1E LITHONIA WST-LED-P2-40K-VW-120-PE-E7WC-DDBXD-US
POM
120 EMERGENCY ARCHITECTURAL WALL SCONCE LED 25
W2 LITHONIA DSXW2LED-30C-530-40K-T3M-MVOLT-PE-DBLX
D
120 LED WALLPACK, 30 LEDS 3 ENGINES, 530 MA DRIVER, 4000K, TYPE III
MEDIUM DISTRIBUTION, SURFACE MOUNTING BRACKET, BLACK
FINISH
LED 54
W3 LITHONIA DSXW2LED-30C-700-40K-T2M-MVOLT-PE-DBLX
D
120 LED WALLPACK, 30 LEDS 3 ENGINES, 700 MA DRIVER, 4000K, TYPE II
MEDIUM DISTRIBUTION, SURFACE MOUNTING BRACKET, BLACK
FINISH
LED 71
X PATHWAY L-D-EX-1C-R-SDT 120 CEILING MOUNTED SINGLE FACE EXIT LIGHT WITH DIE-CAST
ALUMINUM
HOUSING, BRUSHED ALUMINUM FINISH, RED LETTERS, AND NI-CAD
BATTERY BACK-UP, SELF DIAGNOSTIC.
LED 2
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
E-604
L
IG
H T
IN
G
F
IX
T U
R E
S C
H E
D U
L E
S
E Q
U E
N C
E O
F O
P E
R A
T
IO
N S
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
GENERAL NOTES:
1. LIGHT FIXTURES PROVIDED SHALL BE APPROVED EQUAL TO THE FIXTURE INDICATED IN THE SCHEDULE
ABOVE.
2. FIXTURE MODEL NUMBERS ARE USED TO ESTABLISH MINIMUM QUALITY AND PERFORMANCE
STANDARDSAND NOT TO ESTABLISH MOUNTING TYPE. MOUNTING REQUIREMENTS MAY VARY FOR THE
SAME TYPEOF FIXTURE THROUGHOUT THE PROJECT. CONTRACTOR SHALL VERIFY INSTALLATION LOCATION
ANDPROVIDE APPROPRIATE MOUNTING HARDWARE FIXTURE TYPE DESIGN FOR EACH LOCATION.
LIGHTING FIXTURE SCHEDULE NOTES:
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/2
/2
V
IS
H A
L R
B
H A
N P
.E
E-605
P A
N E
L S
C H
E D
U L E
S
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
Notes:
Equipment 2440 VA 100.00% 2440 VA
Lighting - Dwelling Unit 196 VA 100.00% 196 VA
Receptacle 64708 VA 57.73% 37354 VA
Power 50888 VA 100.00% 50888 VA
Other 21840 VA 100.00% 21840 VA
Motor 236072 VA 100.00% 236072 VA
Lighting 11273 VA 125.00% 14091 VA Total Est. Demand Current: 1364 A
Largest Motor 38337 VA 125.00% 47921 VA Total Conn. Current: 1405 A
Heating 34006 VA 100.00% 34006 VA Total Est. Demand: 491292 VA
HVAC 16160 VA 100.00% 16160 VA Total Conn. Load: 506265 VA
Cooling 30440 VA 100.00% 30440 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 1405 A
Total Conn. Load: 506265 VA
13 EXISTING PANEL "T" 3 100 A 100 A 14080 VA
12 PANEL "M2" 3 400 A 400 A 107436 VA
11 EXISTING PANEL "M" M1 3 400 A 400 A 104100 VA
10 PANEL "D3" 3 225 A 225 A 60865 VA
9 PANEL "D2" 3 225 A 225 A 69677 VA
8 EXISTING PANEL "D" 3 225 A 225 A 59308 VA
7 PANEL "B2" 3 225 A 225 A 9360 VA
6 EXISTING PANEL "A" 3 100 A 100 A 12498 VA
5 EXISTING PANEL "B" B1 3 225 A 225 A 26300 VA
4 NEW CRANE 3 100 A 80 A 22437 VA
3 EXISTING "MDP" BUILDING 47 2 100 A 20 A 3328 VA
2 EXISTING "MDP" BUILDING 46 2 100 A 50 A 8320 VA
1 EXISTING CRANE 3 400 A 30 A 8640 VA
CKT Circuit Description # of Poles Frame Size Trip Rating
Load
Remarks
A.I.C. Rating: Wires: 4 MCB Rating: 1600 A
Enclosure: Phases: 3 Frame Rating:
Mounting: Volts: 208Y/120V Mains Type: MCB
SWITCHBOARD: MDP
NOTES:
TOTAL DEMAND LOAD AMPS: 43 A
TOTAL DEMAND LOAD: 15316 VA
Equipment 1000 VA 100.00% 1000 VA NON COINCIDENT AMPS: 0 A Other 40 VA 100.00% 40 VA NON COINCIDENT LOAD: 0 VA Lighting - Dwelling Unit 196 VA 100.00% 196 VA TOTAL CONNECTED AMPS: 35 A Lighting 11273 VA 125.00% 14091 VA TOTAL CONNECTED LOAD: 12498 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 17 %
41 A 31 A 32 A
PHASE TOTALS
4882 VA 3747 VA 3879 VA
41 SPACE -- -- 0 0 -- -- SPACE 42
39 SPACE -- -- 0 0 -- -- SPACE 40
37 SPACE -- -- 0 0 -- -- SPACE 38
35 36
33 34
31 32
29 30
27 PIT LIGHTING 1 20 A 40 28
25 REPAIR RM 118 LTG. 1 20 A 500 500 20 A 1 REPAIR RM 118 LTG. 26
23 LIGHTING RELAY PANEL 1 20 A 500 500 20 A 1 REPAIR RM 118 EM. LTG. 24
21 1ST FLOOR EXTERIOR EM. EGRESS LIGHTS 1 20 A 350 500 20 A 1 NECY 22
19 2ND FLOOR EMERGENCY LIGHTS, COMM R... 1 20 A 261 490 20 A 1 2ND FLOOR LIGHTS 20
17 NE. EXTERIOR BAY LIGHTS 1 20 A 412 270 20 A 1 S. EXTERIOR BAY LIGHTS 18
15 NW. EXTERIOR BAY LIGHTS 1 20 A 358 216 20 A 1 NW. EXTERIOR BAY LIGHTS 16
13 RM 108 AND 109 1 20 A 165 261 20 A 1 RM 105, 106, AND 107 14
11 RM 114, 113, 112, 111, AND JAN LTG. 1 20 A 498 365 20 A 1 RM 101, 102, 103, AND 104 LTG. 12
9 EM. LTG. 1ST LEVEL 1 20 A 485 719 20 A 1 RM 115, 119, 120, AND 116 LTG. 10
7 MAINTENANCE AREA RM 117 LTG. 1 20 A 875 875 20 A 1 MAINTENANCE AREA RM 117 LTG. 8
5 REPAIR RM 118 LTG. 1 20 A 625 750 20 A 1 MAINTENANCE AREA RM 117 EM. LTG. 6
3 REPAIR RM 118 LTG. 1 20 A 500 625 20 A 1 REPAIR RM 118 LTG. 4
1 REPAIR RM 118 EM. LTG. 1 20 A 500 500 20 A 1 REPAIR RM 118 LTG. 2
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. 22,000 NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING 100 A FEED FROM MDP
PANEL NO. A MLO RATING 100 A LOCATION ELEC RM 106
NOTES:
TOTAL DEMAND LOAD AMPS: 54 A
TOTAL DEMAND LOAD: 19620 VA
NON COINCIDENT AMPS: 0 A
Equipment 1440 VA 100.00% 1440 VA NON COINCIDENT LOAD: 0 VA Receptacle 23360 VA 71.40% 16680 VA TOTAL CONNECTED AMPS: 73 A Power 1500 VA 100.00% 1500 VA TOTAL CONNECTED LOAD: 26300 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 9 %
76 A 66 A 80 A
PHASE TOTALS
8950 VA 7950 VA 9400 VA
41 42
39 40
37 RECP - ELEC 106 1 20 A 720 360 20 A 1 RECP - CORRIDOR 201 38
35 480 180 20 A 1 FACP 36
33 480 750 20 A 1 J-BOX FOR PROJECTOR 34
28 V DC RECTIFIER 1 3 30 A
480 750 20 A 1 J-BOX FOR PROJECTOR 32
29 VENDING CANDY 1 20 A 1000 1000 20 A 1 VENDING SODA 30
27 ASLMS CONTAINER 1 20 A 1920 1920 20 A 1 ASLMS CONTAINER 28
25 ASLMS CONTAINER 1 20 A 1920 1920 20 A 1 ASLMS CONTAINER 26
23 ASLMS CONTAINER 1 20 A 1920 1920 20 A 1 ASLMS CONTAINER 24
21 RECP - TOOL ROOM 108 1 20 A 180 540 20 A 1 RECP - COMBAT SPARE 115 22
19 RECP - OFFICE 1 103 1 20 A 180 180 20 A 1 RECP - NON-SENS S. STOR 109 20
17 RECP - OFFICE 104 1 20 A 180 180 20 A 1 RECP - OFFICE 1 103 18
15 RECP - ADMIN SHOP CONTROL 102 1 20 A 180 180 20 A 1 RECP - OFFICE 104 16
13 RECP - CORRIDOR 101 1 20 A 360 180 20 A 1 RECP - ADMIN SHOP CONTROL 102 14
11 RECP - FLUID DISTR. 114 1 20 A 180 360 20 A 1 RECP - DRINKING FOUNTAN 12
9 RECP - MENS 112 1 20 A 540 900 20 A 1 RECP - RR 111 10
7 REFRIGERATOR 1 20 A 1000 540 20 A 1 RECP - BREAK/TRAINING 113 8
5 RECP - MICROWAVE 1 20 A 1000 1000 20 A 1 RECP - COFFEE MAKER 6
3 RECP - COMSEC VAULT 120 1 20 A 180 180 20 A 1 RECP - COMSEC VAULT 120 4
1 RECP - ARMS VAULT 1 20 A 180 180 20 A 1 RECP - ARMS VAULT 2
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. 22,000 NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING 100 A FEED FROM MDP
PANEL NO. B MCB RATING 100 A LOCATION
NOTES:
TOTAL DEMAND LOAD AMPS: 26 A
TOTAL DEMAND LOAD: 9360 VA
NON COINCIDENT AMPS: 0 A
NON COINCIDENT LOAD: 0 VA
TOTAL CONNECTED AMPS: 26 A
Receptacle 9360 VA 100.00% 9360 VA TOTAL CONNECTED LOAD: 9360 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 8 %
27 A 27 A 24 A
PHASE TOTALS
3240 VA 3240 VA 2880 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 RECP - UNASSIGNED 203 1 20 A 540 1440 20 A 1 RECP - TRAINING ROOM 204 10
7 RECP - TRAINING ROOM 204 1 20 A 540 720 20 A 1 RECP - UNASSIGNED 203 8
5 RECP - TRAINING ROOM 204 1 20 A 1440 1440 20 A 1 RECP - TRAINING ROOM 204 6
3 RECP - TRAINING ROOM 204 1 20 A 720 540 20 A 1 RECP - TRAINING ROOM 204 4
1 RECP - TRAINING ROOM 204 1 20 A 1440 540 20 A 1 RECP - TRAINING ROOM 204 2
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. 22,000 NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING 100 A FEED FROM MDP
PANEL NO. B2 MLO RATING 100 A LOCATION
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
E-606
P A
N E
L S
C H
E D
U L E
S
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
NOTES:
Power 0 VA 0.00% 0 VA TOTAL DEMAND LOAD AMPS: 152 A Other 3816 VA 100.00% 3816 VA TOTAL DEMAND LOAD: 54732 VA Motor 24516 VA 100.00% 24516 VA NON COINCIDENT AMPS: 13 A
HVAC 7560 VA 100.00% 7560 VA NON COINCIDENT LOAD: 4576 VA
Heating 18840 VA 100.00% 18840 VA TOTAL CONNECTED AMPS: 165 A Cooling 4576 VA 100.00% 4576 VA TOTAL CONNECTED LOAD: 59308 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 2 %
161 A 168 A 167 A
PHASE TOTALS
19306 VA 20044 VA 19958 VA
41 416 1352 42
AHU-8 2 20 A
416 1352
20 A 2 CU-2
37 520 0 38
AHU-9 2 20 A
520 0 36
33 3036 0
35 A 3 HVU-1
31 3036 3036 32
VE-3 3 50 A
3036 3036 30
27 2592 3036
50 A 3 VE-2
25 2592 2100 26
HVU-2 3 20 A
2592 2100 24
21 GAS RADIANT HEATER 1 20 A 180 2100
35 A 3 VE-1
19 GAS RADIANT HEATER 1 20 A 180 576 20
17 576 576 18
15 576 576
20 A 3 EF-1
EF-2 3 20 A
576 2520 14
11 1362 2520 12
UH-3 2 20 A
1362 2520
35 A 3 CU-1
7 936 936 8
AHU-5 2 20 A
936 936
20 A 2 AHU-4
3 1362 936 4
UH-2 2 20 A
1362 936
20 A 2 AHU-1
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING FEED FROM
PANEL NO. D1 MLO RATING 225 A LOCATION
NOTES:
Power 17212 VA 100.00% 17212 VA TOTAL DEMAND LOAD AMPS: 164 A Other 2880 VA 100.00% 2880 VA TOTAL DEMAND LOAD: 59236 VA Motor 12600 VA 100.00% 12600 VA NON COINCIDENT AMPS: 29 A
HVAC 8600 VA 100.00% 8600 VA NON COINCIDENT LOAD: 10441 VA
Heating 10441 VA 100.00% 10441 VA TOTAL CONNECTED AMPS: 193 A Cooling 17944 VA 100.00% 17944 VA TOTAL CONNECTED LOAD: 69677 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 11 %
203 A 213 A 173 A
PHASE TOTALS
23843 VA 25121 VA 20714 VA
41 42
39 520 40
37 416 520
20 A 2 AHU-9
Power 2 20 A
416 2100 36
33 2100 2100 34
31 2100 2100
35 A 3 VE-6
VE-7 3 35 A
2100 1080 20 A 1 GAS FIRE HEATER 30
27 Other 1 20 A 1080 5460 28
25 3000 5460 26
23 3000 5460
70 A 3 DOAS-1
DOAS-2 3 35 A
3000 1363 22
19 1352 1363
20 A 2 UH-1
CU-7 2 20 A
1352 180 20 A 1 EF-3 18
15 1976 16
13 1976
20 A 2 CU-8
11 2520 1144 12
9 2520 1144
30 A 2 CU-3
CU-5 3 35 A
2520 180 20 A 1 EF-4, EF-5, EF-6 8
5 1362 0 6
CU-6 2 20 A
1362 2496 4
1 EF-7 1 20 A 360 2496
40 A 3 CU-4
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. 22,000 NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING 225 A FEED FROM MDP
PANEL NO. D2 MLO RATING 225 A LOCATION
NOTES:
TOTAL DEMAND LOAD AMPS: 161 A
TOTAL DEMAND LOAD: 58140 VA
Other 3456 VA 100.00% 3456 VA NON COINCIDENT AMPS: 8 A Motor 46764 VA 100.00% 46764 VA NON COINCIDENT LOAD: 2725 VA Heating 2725 VA 100.00% 2725 VA TOTAL CONNECTED AMPS: 169 A Cooling 7920 VA 100.00% 7920 VA TOTAL CONNECTED LOAD: 60865 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 4 %
175 A 175 A 162 A
PHASE TOTALS
20743 VA 20743 VA 19380 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 2640 28
25 2640 26
23 3708 2640
35 A 3 Cooling
21 3708 3036 22
HVU-3 3 50 A
3708 3036 20
17 3036 3036
50 A 3 VE-5
15 3036 576 16
VE-4 3 50 A
3036 576 14
11 3708 576
20 A 3 EF-10
9 3708 2100 10
HVU-4 3 50 A
3708 2100 8
5 576 2100
35 A 3 VE-8
3 576 1363 4
EF-9 3 20 A
576 1363
20 A 2 UH-4
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. 22,000 NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING 225 A FEED FROM MDP
PANEL NO. D3 MLO RATING 225 A LOCATION
NOTES:
TOTAL DEMAND LOAD AMPS: 287 A
TOTAL DEMAND LOAD: 103476 VA
Heating 2000 VA 100.00% 2000 VA NON COINCIDENT AMPS: 0 A Receptacle 11248 VA 94.45% 10624 VA NON COINCIDENT LOAD: 0 VA Power 10900 VA 100.00% 10900 VA TOTAL CONNECTED AMPS: 289 A Motor 79952 VA 100.00% 79952 VA TOTAL CONNECTED LOAD: 104100 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 7 %
297 A 308 A 270 A
PHASE TOTALS
35197 VA 36562 VA 32341 VA
41 SPARE 1 20 A 0 0 20 A 1 SPARE 42
39 SPARE 1 20 A 0 0 20 A 1 SPARE 40
37 SPARE 1 20 A 0 0 20 A 1 SPARE 38
35 1664 0 20 A 1 SPARE 36
SUMP PUMP 2 20 A
1664 1500 20 A 1 COMPRESSED AIR DRYER 34
31 RECP - MECH 107 1 20 A 720 9384 32
29 100 9384 30
27 100 9384
110 A 3 AIR COMPRESSOR
MOTORIZED DOOR 108 3 20 A
100 900 20 A 1 HOSE BIBB 10/11 26
23 4650 4650 24
21 4650 4650 22
WELDER REPAIR 118 3 50 A
4650 4650
50 A 3 WELDER REPAIR 118
17 RECP - CONSOLIDATED B. REPAIR 116 1 20 A 720 2000 20 A 1 EWH-2 18
15 2000 2000 16
TIRE CHANGE MACHINE 2 30 A
2000 2000
20 A 2 TIRE CHANGE MACHINE
11 RECP - CONSOLIDATED B. REPAIR 116 1 20 A 360 180 20 A 1 RECP - CONSOLIDATED B. REPAIR 116 12
9 1800 180 20 A 1 RECP - CONSOLIDATED B. REPAIR 116 10
RECP - SPECIAL RECEPT 2 20 A
1800 360 20 A 1 RECP - MAINTENANCE AREA 117 8
5 3333 5300 6
3 3334 5300 4
SATS CONTAINER 3 100 A
3333 5300
60 A 3 LIFT DOOR H
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. 22,000 NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING 400 A FEED FROM MDP
PANEL NO. M1 MCB RATING 400 A LOCATION
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
E-607
P A
N E
L S
C H
E D
U L E
S
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
NOTES:
TOTAL DEMAND LOAD AMPS: 309 A
TOTAL DEMAND LOAD: 111411 VA
NON COINCIDENT AMPS: 0 A
Receptacle 6660 VA 100.00% 6660 VA NON COINCIDENT LOAD: 0 VA Power 21276 VA 100.00% 21276 VA TOTAL CONNECTED AMPS: 298 A Motor 63600 VA 100.00% 63600 VA TOTAL CONNECTED LOAD: 107436 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 6 %
306 A 315 A 281 A
PHASE TOTALS
36352 VA 37408 VA 33676 VA
41 2496 42
39 4992 2496
30 A 2 OIL AND FLAMMABLE STORAGE BUILDING
BUILDING 38057 OIL & PAINT STORAGE 2 60 A
4992 180 20 A 1 COMPRESSED AIR PIT 38
35 HOSE BIBB 12/12 1 20 A 900 900 20 A 1 HOSE BIBB 10/11 36
33 RECP - MAINTENANCE AREA 117 1 20 A 720 360 20 A 1 RECP - MAINTENANCE AREA 117 34
31 RECP - EXTERIOR 1 20 A 540 720 20 A 1 RECP - MAINTENANCE AREA 117 32
29 HOSE BIBB -F 1 20 A 900 360 20 A 1 RECP - REPAIR AREA 118 30
27 COMPRESSED AIR -F 1 20 A 360 5300 28
25 5300 5300 26
23 5300 5300
60 A 3 LIFT DOOR -F
Motor 3 20 A
5300 360 20 A 1 COMPRESSED AIR - D 22
19 5300 900 20 A 1 HOSE BIBB -D 20
17 5300 360 20 A 1 COMPRESSED AIR - F 18
LIFT DOOR -F 3 60 A
5300 5300 16
13 HOSE BIBB -F 1 20 A 900 5300 14
11 HOSE BIBB - D 1 20 A 900 5300
20 A 3 LIFT DOOR D
9 5300 360 20 A 1 COMPRESSED AIR - D 10
7 5300 720 20 A 1 RECP - EXTERIOR 8
LIFT OHD 118.2 3 20 A
5300 360 20 A 1 COMPRESSED AIR H 6
3 COMPRESSED AIR H 1 20 A 360 900 20 A 1 HOSE BIBB - H 4
1 RECP - EXTERIOR 1 20 A 540 360 20 A 1 RECP - REPAIR AREA 118 2
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. NEUTRAL BUS 100% SECTIONS
SERVICE VOLTAGE 208Y/120V BUS RATING 400 A FEED FROM MDP
PANEL NO. M2 MLO RATING 400 A LOCATION
NOTES:
TOTAL DEMAND LOAD AMPS: 33 A
TOTAL DEMAND LOAD: 12040 VA
NON COINCIDENT AMPS: 0 A
NON COINCIDENT LOAD: 0 VA
TOTAL CONNECTED AMPS: 39 A
Receptacle 14080 VA 85.51% 12040 VA TOTAL CONNECTED LOAD: 14080 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
PANEL UNBALANCE 16 %
33 A 42 A 45 A
PHASE TOTALS
3960 VA 4880 VA 5240 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 QUAD - COMM 2 202 1 20 A 360 18
15 QUAD COMM2 202 1 20 A 360 360 20 A 1 QUAD - COMM 2 202 16
13 QUAD - COMM 2 202 1 20 A 360 180 14
11 1100 180
30 A 2 UPS
SERVER EQUIPMENT 2 30 A
1100 900 10
7 1800 900
20 A 2 SERVER EQUIPMENT
SERVER EQUIPMENT 2 30 A
1800 1800 6
3 REC - COMM 1 105 1 20 A 360 1800
30 A 2 SERVER EQUIPMENT
1 REC - COMM 1 105 1 20 A 360 360 20 A 1 REC - COMM 1 105 2
CK... DESCRIPTION POLE TRIP A B C TRIP POLE DESCRIPTION CK...
A.I.C. NEUTRAL BUS 100% SECTIONS 1
SERVICE VOLTAGE 208Y/120V BUS RATING FEED FROM
PANEL NO. T MLO RATING 200 A LOCATION
ABBREVIATIONS:
(ALL ABBREVIATIONS SHOWN ARE NOT
NECESSARILY
USED ON DRAWINGS)
A_______________________________________
ABOVE
ADJUSTABLE
ABOVE FINISHED FLOOR
AMERICAN NATIONAL
STANDARDS INSTITUTE
ACCESS POINT
ARCHITECT, ARCHITECTURAL
AMERICAN WIRE GAUGE
B
BUILDING
BUILDING MANAGEMENT
SYSTEM
C
CONDUIT
CONTRACTOR FURNISHED
CONTRACTOR INSTALLED
CEILING
CEILING LINE
COMMUNICATIONS
CONFERENCE
CORRIDOR
COMMUNICATIONS ROOM
D
DEMO
DIA
DN
E
EA
EF
EL
ELEC
EMT
ENCL
EXIST
F
FA
FACP
FOC
FMS
G
GA
GALV
G,GND
GUI
H
HH
I
ID
IEEE
IDF
J
J-BOX
K
KVA
KW
L
LB
LCD
LF
LTG
M
MATV
MAX
MDF
MECH
MT
N
N/A
NEC
NEMA
NIC
N.T.S
O
O.A.R.
OD
OFCI
OFOI
P
PDS PREMISE DISTRIBUTION
SYSTEM
PVC POLYVINYL CHLORIDE
PWR POWER
Q
QTY QUANTITY
R
RCP
REF:
REST
REQD
REV
RGS
RM
RMC
RU
S
SCS
SECT
SF
ST
STD
STOR
SUSP
SVC
T
TBD
TR
TEF
TER
TMD
TGB
THRU
TYP
U
UL
UNO
UTP
V
VERT
VEST
VIP
W
W/
WAO
W/O
WP
ABV
ADJ
AFF
ANSI
AP
ARCH
AWG
BLDG
BMS
C
CFCI
CLG
CL
COMM
CONF
CORR
CR
DEMOLISH
DIAMETER
DOWN
EACH
ENTRANCE FACILITY
ELEVATOR
ELECTRICAL
ELECTRICAL METALLIC
TUBING
ENCLOSURE
EXISTING
FIRE ALARM
FIRE ALARM CONTROL PANEL
FIBER OPTIC CABLE
FACILITIES MAINTENANCE
SHOP
GAUGE
GALVANIZED
GROUND
GRAPHIC USER INTERFACE
HAND HOLES
INSIDE DIAMETER
INSTITUTE OF ELECTRICAL
AND ELECTRONICS
ENGINEERS
INTERMEDIATE DISTRIBUTION
FRAME
JUNCTION BOX
KILO VOLT AMPERE
KILOWATTS
POUNDS
LIQUID CRYSTAL DISPLAY
LINEAR FEET
LIGHTING
MASTER ANTENNA TV
MAXIMUM
MAIN DISTRIBUTION FRAME
MECHANICAL
MOUNTED
NOT APPLICABLE
ELECTRIC CODE
NATIONAL ELECTRIC
MANUFACTURERS
ASSOCIATION
NOT IN CONTRACT
NOT TO SCALE
OWNER AUTHORIZED
REPRESENTATIVE
OUTSIDE DIAMETER
OWNER FURNISHED
CONTRACTOR
INSTALLED
OWNER FURNISHED OWNER
INSTALLED
REFLECTED CEILING PLAN
REFERENCE, REFER
RESTROOM
REQUIRED
REVISED, REVISION, REVISE
RIGID GALVANIZED STEEL
ROOM
RIGID METALLIC CONDUIT
RACK UNIT
STRUCTURED CABLING
SYSTEM
SECTION
SQUARE FEET
STAIR
STANDARD
STORAGE
SUSPEND
SERVICE
TO BE DETERMINED
TELECOMMUNICATIONS ROOM
TELECOM ENTRANCE
FACILITY
TELECOM EQUIPMENT ROOM
TEXAS MILITARY
DEPARTMENT
TELECOMMUNICATIONS
GROUND BUSBAR
THROUGH
TYPICAL
UNDERWRITERS
LABORATORIES, INC.
UNLESS NOTED OTHERWISE
UNSHIELDED TWISTED PAIR
VERTICAL
VESTIBULE
VERY IMPORTANT PERSON
WITH
WORK AREA OUTLET
WITHOUT
WEATHER-PROOF
TEMF TRANSPORTATION EQUIPMENT
MAINTENANCE FACILITY
GENERAL NOTES:
1. DRAWINGS ARE DRAWN TO SCALE UNLESS OTHERWISE NOTED.
CONTRACTOR IS RESPONSIBLE FOR COORDINATING EXACT ROUTING OF ALL
SERVICES WITH EXISTING CONDITIONS AND WITH ALL OTHER TRADES.
2. IN THE INSTALLATION OF THIS WORK, THE CONTRACTOR SHALL COMPLY IN
EVERY WAY WITH THE REQUIREMENTS OF LOCAL LAWS AND ORDINANCES,
THE LAWS OF THE STATE OF TEXAS, AND THE NATIONAL ELECTRICAL CODE.
3. CAREFULLY EXAMINE THE PREMISES TO DETERMINE THE EXTENT OF WORK
AND THE CONDITIONS UNDER WHICH IT MUST BE DONE. IF THERE ARE ANY
QUESTIONS REGARDING THE PROJECT, THE CONTRACTOR IS RESPONSIBLE
FOR OBTAINING CLARIFICATIONS FROM THE DESIGN CONSULTANT OR THEIR
DESIGNATED REPRESENTATIVE BEFORE PROCEEDING WITH WORK OR
RELATED WORK IN QUESTION.
4. ANY DISCREPANCIES BETWEEN THESE PLANS AND ACTUAL FIELD
CONDITIONS MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE
OAR FOR CLARIFICATION.
5. ALL WORK SHALL BE DONE IN A THOROUGH AND CONSCIENTIOUS MANNER
ACCORDING TO INDUSTRY STANDARDS AND SHALL BE SUBJECT TO
INSPECTION AND ACCEPTANCE. WORK THAT IS DEEMED SUBSTANDARD OR
NOT TO INDUSTRY STANDARD WILL BE SUBJECT TO REPLACEMENT OR
REPAIR AT NO ADDITIONAL COST TO THE OWNER OR GENERAL
CONTRACTOR.
6. CONTRACTOR TO COORDINATE ALL DEMOLITION ACTIVITIES WITH GENERAL
CONTRACTOR, OWNER AND SERVICE PROVIDERS PRIOR TO PERFORMANCE
OF ALL ACTIVITIES.
7. CONTRACTOR MUST RETURN ALL ACTIVE EQUIPMENT AND ELECTRONICS
REMOVED AS PART OF THE DEMOLITION SCOPE TO OWNER. ALL EQUIPMENT
MUST BE REMOVED, STORED, LOGGED AND LABELED CAREFULLY.
8. PRIOR TO DEMOLITION OF ANY COMMUNICATIONS COPPER OR FIBER
CABLES, CONTRACTOR SHALL VERIFY WITH DESIGN CONSULTANT AND
OWNER THAT ALL ACTIVE CIRCUITS HAVE BEEN CUT OVER OR
DEACTIVATED. DO NOT DEMO WITHOUT AUTHORIZATION FROM OWNER OR
TENANTS.
9. THE CONTRACTOR SHALL PROVIDE, INSTALL, TERMINATE, PATCH,
CROSS-CONNECT, LABEL, AND DOCUMENT COMMUNICATIONS CABLING
SYSTEMS BASED ON THE PROJECT SPECIFICATIONS AND ACCOMPANYING
DRAWINGS.
10. CONTRACTOR SHALL PROVIDE, INSTALL, TERMINATE, AND LABEL RACKS,
PATCH PANELS, WIRE MANAGEMENT AND CABLING AS DESCRIBED IN THE
DRAWINGS.
11. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER BONDING AND
GROUNDING OF THE SYSTEMS IN ACCORDANCE WITH APPLICABLE
ELECTRICAL CODES AND ANSI-J-STD-607-A.
12. ALL CONDUITS SHALL BE ROUTED TO ACCESSIBLE CEILING SPACE OR AN
ACCESS PANEL SHALL BE PROVIDED. ACCESS PANELS SHALL COMPLY WITH
FIRE CODE.
13. DIVISION 26 ELECTRICAL CONTRACTOR TO PROVIDE (1) - 4-11/16" X 4-11/16"
X 2-1/8"D BACKBOX AND SINGLE GANG DEVICE RING WITH (1) ONE-INCH
CONDUIT TO EITHER THE CABLE TRAY OR ABOVE ACCESSIBLE CEILING AS
REQUIRED FOR STANDARD, CEILING AND WALL MOUNTED TELEPHONE/DATA
COMMUNICATION WORK-AREA-OUTLETS (WAO), UNLESS NOTED OTHERWISE.
14. COORDINATE WORK AREA OUTLET PLACEMENT WITH THE PLACEMENT OF
ELECTRICAL OUTLETS WHEREVER POSSIBLE. IN ALL CASES THERE
SHALL BE A ELECTRICAL OUTLET NO FURTHER THAN ONE STUD BAY
DISTANCE FROM A LOW VOLTAGE WAO.
GENERAL:
1. CONDUITS SHALL HAVE A MAXIMUM 40% FILL RATIO. CABLE TRAY SHALL
HAVE A MAXIMUM 50% FILL RATIO.
2. NON-CONTINUOUS CABLE SUPPORT SYSTEMS (J-HOOKS) INSTALLATION AND
CONFIGURATION SHALL CONFORM TO THE REQUIREMENTS OF THE
CURRENT REVISION LEVELS OF ANSI/EIA/TIA STANDARDS 568 & 569, NFPA 70
(NATIONAL ELECTRICAL CODE), APPLICABLE LOCAL CODES, AND TO THE
MANUFACTURERS INSTALLATION INSTRUCTIONS AND THE NEMA VE-2
GUIDELINES.
3. REGARDLESS OF PATHWAY TYPE, ALL CABLING SHALL BE SUPPORTED AT A
5'-0" MAXIMUM INTERVAL.
4. UNLESS OTHERWISE NOTED, CABLE PATHWAY WITHIN ROOMS WILL RUN
PARALLEL TO WALLS.
5. UNLESS OTHERWISE NOTED ALL CONDUITS ARE ONE-INCH IN DIAMETER.
CONDUIT:
1. CONDUIT RUNS SHALL NOT CONTAIN 90° CONDUIT BODIES (OR LB'S).
2. MAINTAIN PROPER CONDUIT BEND RADIUS IN ACCORDANCE WITH
ANSI/EIA/TIA-569-B. FOR CONDUIT WITH AN INTERNAL DIAMETER OF 2" OR
LESS, MAINTAIN A BEND RADIUS OF AT LEAST 6 TIMES THE INTERNAL
CONDUIT DIAMETER. FOR CONDUIT WITH AN INTERNAL DIAMETER GREATER
THAN 2", MAINTAIN A BEND RADIUS OF AT LEAST 10 TIMES THE INTERNAL
CONDUIT DIAMETER.
3. DO NOT CONSIDER A PULL BOX AS A BEND. ALL CONDUITS MUST RUN
STRAIGHT THROUGH A PULL BOX WITH THE BEND EITHER BEFORE OR
AFTER THE PULL BOX.
4. REAM ALL CONDUIT ENDS. FIT STUBBED CONDUITS WITH AN INSULATED
BUSHING TO ELIMINATE SHARP EDGES THAT MAY DAMAGE CABLE
DURING INSTALLATION OR SERVICE. EQUIP ALL CONDUIT WITH PULL CORD
WITH A MINIMUM TEST RATING OF 200LBS.
5. ALL OUTLET BOX CONDUITS SHALL BE ROUTED TO NEAREST ACCESSIBLE
CEILING SPACE WHETHER OR NOT SHOWN AS SUCH ON DRAWINGS.
TELECOMM PATHWAY NOTES:
CONDUIT TURNING UP
CONDUIT TURNING DOWN
CONDUIT UP
CONDUIT DOWN
SYMBOL LEGEND (NOT ALL SYMBOLS MAY BE USED)
WIRE MESH CABLE TRAY, TYPICAL
CONDUIT TERMINATION (SLEEVE/STUB)
WALL MOUNT QUAD OUTLET - 5-20R
WALL MOUNTED L5-20R
W WALL MOUNTED PHONE AT 48" AFF. - (1) CAT6 VOICE CABLE
X WALL VOICE/DATA MOUNTED OUTLET - "X" DENOTES QTY OF DATA SERVICES
CAT6 CABLES, "Y" DENOTES QTY OF VOICE SERVICES CAT6 CABLES
WALL DATA MOUNTED OUTLET - "X" DENOTES QTY OF DATA SERVICES CAT6
CABLES
Y
X
DEMOLITION GENERAL NOTES:
1. CONTRACTOR TO COORDINATE ALL DEMOLITION ACTIVITIES WITH GENERAL
CONTRACTOR, OWNER AND SERVICE PROVIDERS PRIOR TO PERFORMANCE OF
ALL ACTIVITIES.
2. CONTRACTOR SHALL COORDINATE REMOVAL OF ALL DEVICES AND THEIR
REQUIREMENT TO BE DEMOLISHED, SALVAGED, REUSED OR RELOCATED WITH
THE GENERAL CONTRACTOR AND OWNER PRIOR TO DEMOLITION.
3. EXISTING HORIZONTAL OUTLET CONDUITS INSIDE WALLS ARE TO REMAIN.
INCLUDING THE BACKBOX AND CONDUIT UP TO ACCESSIBLE CEILING. THE
EXISTING DATA CABLING IS TO BE DEMOLISHED AS PART OF THIS WORK. THE
PATHWAY SHALL REMAIN AVAILABLE FOR FUTURE USE DURING CONSTRUCTION
WHERE APPROPRIATE AND APPROVED.
4. CONTRACTOR MUST RETURN ALL ACTIVE EQUIPMENT AND ELECTRONICS REMOVED
AS PART OF THE DEMOLITION SCOPE TO OWNER. ALL EQUIPMENT MUST BE
REMOVED, STORED, LOGGED AND LABELED CAREFULLY.
5. PRIOR TO DEMOLITION OF ANY COMMUNICATIONS COPPER OR FIBER CABLES,
CONTRACTOR SHALL VERIFY WITH DESIGN CONSULTANT AND OWNER THAT ALL
ACTIVE CIRCUITS HAVE BEEN CUT OVER OR DEACTIVATED. DO NOT DEMO
WITHOUT AUTHORIZATION FROM OWNER OR TENANTS.
6. CONTRACTOR SHALL PROTECT ANY EQUIPMENT IN THE DESIGNATED DEMOLITION
AND/OR CONSTRUCTION AREA FROM DAMAGE PRIOR TO COMMENCING WORK.
7. REMOVAL OF EQUIPMENT AND DEVICES SHALL INCLUDE BRACKETS, CABLING,
CONDUIT, JUNCTION BOXES, MOUNTING HARDWARE, TRIM PIECES AND RELATED
EQUIPMENT HARDWARE.
8. ITEMS SHOWN ON DRAWINGS MAY NOT BE DRAWN TO EXACT SCALE. CONTRACTOR
IS RESPONSIBLE FOR COORDINATING EXACT ROUTING OF ALL SERVICES WITH
EXISTING CONDITIONS AND WITH OTHER TRADES.
9. IN THE EXECUTION OF THIS WORK, THE CONTRACTOR SHALL COMPLY IN EVERY
WAY WITH THE REQUIREMENTS OF LOCAL LAWS AND ORDINANCES, THE LAWS
OF THE STATE OF TEXAS, THE NATIONAL BOARD OF FIRE UNDERWRITERS, AND
THE NATIONAL ELECTRICAL CODE.
10. CAREFULLY EXAMINE THE PREMISES TO DETERMINE THE EXTENT OF WORK AND
CONDITION UNDER WHICH IT MUST BE DONE. IF THERE ARE ANY QUESTIONS
REGARDING THE PROJECT, THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING
CLARIFICATIONS FROM THE DESIGN CONSULTANT, OR THEIR DESIGNATED
REPRESENTATIVE BEFORE PROCEEDING WITH WORK OR RELATED WORK IN
QUESTION.
11. ANY DISCREPANCIES BETWEEN THESE PLANS AND ACTUAL FIELD CONDITIONS
MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE OWNER AUTHORIZED
REPRESENTATIVE OR THEIR DESIGNATED REPRESENTATIVE FOR CLARIFICATION.
12. ALL WORK SHALL BE DONE IN A THOROUGH AND CONSCIENTIOUS MANNER
ACCORDING TO INDUSTRY STANDARDS AND SHALL BE SUBJECT TO INSPECTION
AND ACCEPTANCE. WORK THAT IS DEEMED SUB-STANDARD OR NOT TO
INDUSTRY STANDARD WILL BE SUBJECT TO REPLACEMENT OR REPAIR AT NO
ADDITIONAL COST TO THE OWNER OR GENERAL CONTRACTOR.
13. PRIOR TO STARTING THE INSTALLATION, THE ASSIGNED INSTALLATION SUPERVISOR
OR LEAD TECHNICIAN SHALL PARTICIPATE IN A WALK-THROUGH OF THE PROJECT
LOCATION WITH THE DESIGN CONSULTANT, OR THEIR DESIGNATED
REPRESENTATIVE, TO REVIEW THE INSTALLATION DOCUMENTATION.
14. THE CONTRACTOR IS REQUIRED TO PROPERLY FIRESTOP ANY CORES, UTILIZED
FOR THE PLACEMENT OF COMMUNICATIONS CABLING, WITH APPROVED
FIRESTOPPING COMPOUND AND ACCORDING TO LOCAL AND NATIONAL CODES.
15. COMPLETION OF THIS WORK MUST BE COORDINATED WITH WORK BEING
PERFORMED UNDER CONCURRENT, ADJACENT PROJECTS. CONTRACTOR SHALL
COORDINATE WITH OWNER AND OTHER CONTRACTORS AS REQUIRED
REGARDING SCHEDULE, PATHWAYS, LABELING, TESTING, ET AL.
16. COORDINATE TELECOM PATHWAYS WITH OTHER CONDUIT.
17. CONTRACTOR TO PERFORM DEMOLITION OF CABLING BEGINNING AT ENDS OF THE
CABLING RUN TO VERIFY CONNECTIVITY STATUS. REGARDLESS OF ANY CABLING
LABELS ATTACHED TO SUBJECT RUN.
IT SYSTEMS OVERVIEW:
TECHNOLOGY SYSTEMS OVERVIEW
THIS DRAWING PACKAGE CONSISTS OF TECHNOLOGY
SYSTEMS INFRASTRUCTURE REQUIRED IN THE DEMOLITION,
CONSTRUCTION AND RENOVATION OF THE EXISTING TEMF
FACILITY. THIS PACKAGE PROVIDES LOCATIONS OF DEVICE
AND CABLING TERMINATIONS, MAJOR CABLING PATHWAY
ACCOMMODATIONS AND COMMUNICATIONS ROOMS
REQUIREMENTS. THE TECHNOLOGY SYSTEMS INCLUDED IN
THIS PACKAGE ARE IDENTIFIED BELOW.
DEMOLITION
CONTRACTOR IS RESPONSIBLE FOR DEMOLITION OF ALL
VOICE/DATA SYSTEMS CABLING WITHIN THE SCOPE OF
WORK BOUNDARIES. CONTRACTOR MUST PROTECT AND
LABEL ALL INFRASTRUCTURE SHOWN ON DRAWINGS TO
REMAIN THROUGHOUT CONSTRUCTION. ALL PHONE,
NETWORK SWITCHGEAR AND AUDIO-VISUAL END
DEVICES SHALL BE REMOVED AND RETURNED TO THE
OWNER FOR FUTURE USE. CONTRACTOR SHALL RETURN
ANY ADDITIONAL NETWORK EQUIPMENT FOUND IN
DEMOLITION AREA TO OWNER FOR RE-USE OR
DISPOSAL.
BUSINESS CONTINUITY AND SELECTIVE DEMOLITION
THE CURRENT COPPER AND FIBER BACKBONE
INFRASTRUCTURE WILL BE REQUIRED TO BE PROTECTED,
OPERATIONAL AND MAINTAINED THROUGHOUT THE LIFECYCLE
OF THE PROJECT. SERVICE INTERRUPTIONS ARE NOT
PERMITTED AT ANY TIME. CONTRACTOR SHALL PROVIDE A
THOROUGH WRITTEN PLAN TO TEST, TAG, LABEL AND PROTECT
CRITICAL SYSTEM COMPONENTS. IN THE MAIN TELECOMM
EQUIPMENT ROOM (TER) SELECTIVE DEMOLITION WILL BE
REQUIRED TO REPLACE THE OLD DEMARC BACKBOARD,
DEMOLISH ALL EXISTING SYSTEMS. THOROUGH COORDINATION
BETWEEN THE OWNER AND CONTRACTOR IS REQUIRED.
COMMUNICATIONS ROOMS
CONTRACTOR SHALL INSTALL ALL NEW COMMUNICATIONS ROOM
INFRASTRUCTURE AS INDICATED ON DRAWINGS. THIS INCLUDES
WALL/FLOOR PENETRATIONS, WORK AREA OUTLETS, EQUIPMENT
CABINETS/RACKS, ETC. INDICATED ON PLANS UNLESS NOTED
OTHERWISE.
HORIZONTAL CABLING
CONTRACTOR SHALL INSTALL ALL HORIZONTAL CABLING
INFRASTRUCTURE, INCLUDING CONDUIT AND CABLE TRAY, AS
REQUIRED ON THE DRAWINGS AND SPECIFICATIONS. INSTALL TMD
PHONE AND DATA OUTLETS AND CABLE FROM THE NEAREST
COMMUNICATIONS ROOM, UNLESS NOTED OTHERWISE. PROVIDE
COPPER PATCH CABLES FOR ALL INSTALLED OUTLETS AS REQUIRED
IN SPECIFICATIONS.
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
M O
Y E
M O
Y E
M O
Y E
M o y e
I
T
C o n su lt in g
LL
C
T B
P E
R e g is tr a ti o n
F
-1
TN-100
S Y
S T
E M
S O
V E
R V
IE
W
N
O T
E S
A N
D S
Y M
B O
L S
C O
R P
S O
F E
N G
IN
E
E R
S
F O
R T
W O
R T
H
T E
X A
S
- W
G
-1 -D
-0
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S
B L
D G
M A
R K
D E
S C
R
IP
T
IO
N D
A
PLAN NORTH
B
KEY PLAN
A
4.1
B C D E F G H J
TND01
EXISTING
COMM
ROOM
NOTE:
DEMOLISH ALL WORK AREA OUTLETS, TELEPHONE JACKS, AND
RELATED SURFACE MOUNT RACEWAY AND CABLING BACK TO
THE POINT OF ORIGIN. REMOVE AND PROTECT THE EXISTING
COMMUNICATION CABINET, SWITCHES, POWER SUPPLIES,
PATCH PANELS AND ASSOCIATED MISCELLANEOUS EQUIPMENT
AND RETURN IT TO THE OWNER. PROTECT THE BACKBONE
FIBER AND COPPER AT THE MAIN POINT OF ENTRY.
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
M O
Y E
M O
Y E
M O
Y E
M o y e
I
T
C o n su lt in g
LL
C
T B
P E
R e g is tr a ti o
TND-101
D E
M O
L
IT
IO
N
P L
A N
F
IR
S
T F
L O
O R
C O
R P
S O
F E
N G
IN
E
E R
S
F O
R T
W O
R T
H
T E
X A
S
- W
G
-1 -D
-0
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S
B L
D G
3/32" = 1'-0"TND-101
1 DEMOLITION PLAN - FIRST FLOOR
Sheet Keynote Summary
Key Value Keynote Text
TND01 CONFIRM MAIN POINT OF
ENTRY FOR FIBER AND COPPER
BACKBONE. PROTECT IT IN
PLACE DURING
CONSTRUCTION.
M A
R K
D E
S C
R
IP
T
IO
N D
A
4.1
B C D E F G H J
OPEN TO BELOW
OPEN TO BELOW
ROOF BELOW
NOTE:
DEMOLISH ALL WORK AREA OUTLETS, TELEPHONE JACKS, AND
RELATED SURFACE MOUNT RACEWAY AND CABLING BACK TO
THE POINT OF ORIGIN. REMOVE AND PROTECT THE EXISTING
COMMUNICATION CABINET, SWITCHES, POWER SUPPLIES,
PATCH PANELS AND ASSOCIATED MISCELLANEOUS EQUIPMENT
AND RETURN IT TO THE OWNER. PROTECT THE BACKBONE
FIBER AND COPPER AT THE MAIN POINT OF ENTRY.
PLAN NORTH
A
B
KEY PLAN
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
M O
Y E
M O
Y E
M O
Y E
M o y e
I
T
C o n su lt in g
LL
C
T B
P E
R e g is tr a ti o
TND-102
D E
M O
L
IT
IO
N
P L
A N
S
E C
O N
D F
L O
O R
C O
R P
S O
F E
N G
IN
E
E R
S
F O
R T
W O
R T
H
T E
X A
S
- W
G
-1 -D
-0
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S
B L
D G
3/32" = 1'-0"TND-102
1 DEMOLITION PLAN - SECOND FLOOR
M A
R K
D E
S C
R
IP
T
IO
N D
A
4.1
B C D E F G H J
ELEC
TOOL ROOM
COMBAT SPARES
COMM 1
MENS
MAINTENANCE
AREA
CONSOLIDATED
BENCH REPAIR
WOMENS
NON-SENS
SECURE STOR
CORRIDOR
REPAIR AREA
MECH
FLUID DISTR
ARMS VAULT
BREAK / TRAINING
OFFICE 1
OFFICE 2
ADMIN SHOP
CONTROL
JAN
TN-103
PLAN NORTH
A
B
KEY PLAN
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
M O
Y E
M O
Y E
M O
Y E
M o y e
I
T
C o n su lt in g
LL
C
T B
P E
R e g is tr a ti o
TN-101
F
IR
S T
F L O
O R
O V
E R
A L
L
C O
R P
S O
F E
N G
IN
E
E R
S
F O
R T
W O
R T
H
T E
X A
S
- W
G
-1 -D
-0
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S
B L
D G
3/32" = 1'-0"TN-101
1 FIRST FLOOR OVERALL
M A
R K
D E
S C
R
IP
T
IO
N D
A
2D 2V
2D2V 2D2V 2D2V
2D 2V
2D2V
2D 2V
2D 2V
2D 2V
2D2V
2D 2V
2D2V
2D 2V
2D 2V
2D 2V 2D
2V
2D 2V
2D2V
2D 2V
2D 2V
2D2V 2D 2V
2D 2V
WW
W
2D 2V
W
A
4.1
B C D E F G H J
ELEC
TOOL ROOM
COMBAT SPARES
COMM 1
MENS
CONSOLIDATED
BENCH REPAIR
WOMENS
NON-SENS
SECURE STOR
CORRIDOR
REPAIR AREA
MECH
FLUID DISTR
ARMS VAULT
BREAK / TRAINING
OFFICE 1
OFFICE 2
ADMIN SHOP
CONTROL
JAN
TN01
TN21
TN21
TN-401
COMSEC VAULT
PLAN NORTH
A
B
KEY PLAN
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
M…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it.