Drawing_85-96_pages.pdf
PDF 4 MB Posted
- Attached to
- Renovation of TEMP Bldg 26041
- Solicitation number
- W91151-19-B-0016
About this file
Drawing pages 85-96
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT TO SCALE
NOT TO SCALE
- NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
NOT TO SCALE
CONSTRUCTION OF 90 DEGREE ELBOWS CONSTRUCTION OF 45 DEGREE ELBOWS ROUND BRANCH TAKEOFF
TYPICAL RECTANGULAR
TRANSITION
TYPICAL RECTANGULAR TO
ROUND TRANSITION
TYPICAL SPLITTER DAMPER
TYPICAL TURNING VANES
RECTANGULAR BRANCH TAKE OFF
TYPICAL VOLUME DAMPER
1 1/2W
ROUND 90° ELBOW
CL
LC
"W"
SQUARE 90° ELBOW
CL
LC
SQUARE 45° ELBOWROUND 45° ELBOW
AIR
FLOW
"W"
"W"
BRANCH
MAIN
BRANCH
ROUND DUCT
MAINSPLITTER DAMPER
BRANCH
DAMPER ADJUSTMENT
ROD & LOCK SCREW
1"R
2" R
ADIU
S
HINGE
POINT
USE THIS DESIGN WHERE
SQUARE 90° ELBOWS ARE
SHOWN ON PLANS OR IF
SPACE CONDITIONS DO
NOT PERMIT INSTALLATION
OF ROUND 90° ELBOWS
USE THIS DESIGN WHERE
ROUND 90° ELBOWS ARE
SHOWN ON PLANS
TURN VANES-SEE
DETAIL THIS SHEET
"W
"W"
"W
TURN VANES-SEE DETAIL
THIS SHEET
1 1/2W
"W
"W" "W"
"W
USE THIS DESIGN
WHERE ROUND 45°
ELBOWS ARE SHOWN
ON PLANS
USE THIS DESIGN
WHERE RECTANGULAR
45° ELBOWS ARE
SHOWN ON PLANS
TURN VANES -SEE
DETAIL THIS SHEET
FLOW
AIR
MAIN
SLOPE NOT TO
EXCEED 1" IN 4"
RECTANGULAR
DUCT
SLOPE NOT TO
EXCEED 1" IN 4"
1"1"
AIR
FLOW
TURN
VANES
CONNECTION
LINKAGE
DOUBLE ACTING
BLADES
OPERATING SHAFT
FOR QUADRANT
OR MOTOR.
GENERAL INSTALLATION NOTES:
1. ALL DUCTS SHALL BE CONSTRUCTED AND ERECTED IN A NEAT
AND WORKMANLIKE MANNER.
2. DUCTS SHALL BE CONSTRUCTED OF THE WEIGHTS, GAUGES, AND
MATERIAL SHOWN IN THE SCHEDULE OF THESE DRAWINGS.
3. THE DIMENSION SHOWN FOR ALL DUCTS SHOWN IN PLAN GIVE
THE NET INSIDE CLEAR WIDTH FIRST AND THEN THE NET INSIDE CLEAR
HEIGHT.
4. AIR TURNING VANES SHALL BE INSTALLED IN ALL ABRUPT
ELBOWS TO PREVENT TURBULENCE.
5. DUCTS SHALL BE SECURELY ATTACHED TO THE BUILDING
CONSTRUCTION IN AN APPROVED MANNER.
6. DIVERGING TRANSITION PIECE SHALL BE MADE AS GRADUAL AS
POSSIBLE.
7. INSTALL FIRE/SMOKE DAMPERS IN ACCORDANCE WITH UL 555.
8. ACCESS PANELS SHOULD BE PLACED BEFORE AND/OR AFTER
EQUIPMENT INSTALLED IN THE DUCT.
9. DUCT AREA SHOULD NOT BE DECREASED MORE THAN 10
PERCENT WHEN OBSTRUCTIONS CANNOT BE AVOIDED, AND THEN
A STREAMLINED FITTING SHOULD BE USED.
10. FLEXIBLE FABRIC CONNECTIONS (OR EQUAL) SHOULD BE USED
ON BOTH INLETS AND OUTLETS OF ALL FAN COIL UNITS.
11. JOINTS AND SEAMS OF SUPPLY DUCTS SHALL BE FASTENED
SECURELY AND MADE AIR TIGHT.
USE SPLITTER
DAMPERS ON
DUCT TEES.
WEIGHT
HORIZONTAL VERTICAL
FLOW
AIR
AIR FLOW
FLOWAIR
ANGLE STOP
SPRING
CATCH
SPRING
CATCH
FUSIBLE
LINK
ACCESS PANEL
DETERMINE SIZE
& LOCATED IN
THE FIELD
ANGLE
STOP
HINGE
POINT
FUSIBLE
LINK
NOT TO SCALE
TYPICAL FIRE DAMPER
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
H E
P U
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
A
T H
O R
IT
Y
O F
T E
X A
S N
O
N D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C P
B
C P
B
D W
L
/4
/2
V A
N C
A S
H E
N P
.E
M-503
M E
C H
A N
IC
A
L D
E T
A
IL
S I
II
/4
/1
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F
R E
N O
V A
T
IO
N S
B L
D G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C P
B
C P
B
D W
L
/4
/2
V A
N C
A S
H E
N P
.E
M-601
M E
C H
A N
IC
A
L S
C H
E D
U L E
S
/4
/1
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F
R E
N O
V A
T
IO
N S
B L
D G
NOTES:
NOTES:
REMARKS:
REMARKS:
1. PROVIDE WITH UNIT MOUNTED DISCONNECT.
2. FAN TO BE VARIBEL VOLUME.
AIR COOLED CONDENSING UNIT SCHEDULE
MARK
ASSOCIATED
AHU EER [SEER]
TOTAL CAP
(MBH)
AMBIENT
AIR (°F)
UNIT ELECTRICAL
MANUFACTURER/MODELMCA MOCP VOLT/PH
CU-1 AHU-1 12.5 48.5 105 37 60 208/1 TRANE/4TWR706A1
CU-2 AHU-2 [15.3] 20.5 105 13 20 208/1 TRANE/PUZ-A18NHA4
CU-3 AHU-3 [20.8] 11.7 105 11 28 208/1 TRANE/PUZ-A12NKA7
CU-4 AHU-4 12.5 41.2 105 24 40 208/1 TRANE/4TWR5048H1
CU-5 AHU-5 12.5 53.2 105 32 50 208/1 TRANE/4TWR4060G1
CU-6 AHU-6 [15.3] 20.5 105 13 20 208/1 TRANE/PUY-A18NHA6
CU-7 AHU-7 [15.2] 13.7 105 13 15 208/1 TRANE/PUY-A12NHA4
CU-8 AHU-8 12.0 19.7 105 14 25 208/1 TRANE/4TWR4024G1
CU-9 AHU-9 12.0 35.9 105 22 35 208/3 TRANE/4TWR5042H1
GAS FIRED RADIANT HEATER SCHEDULE
MARK SERVES CAPACITY (MBH) MOUNTING HEIGHT VOLT/PH MANUFACTURER/MODEL
GRH-1 THRU 8 MAINTENANCE AREA 30 13 120/1 REZNOR/RIHN30
GRH-9 THRU 20 REPAIR AREA 30 13 120/1 REZNOR/RIHN30
1. ESP DOES NOT INCLUDE UNIT OR FILTER LOSSES.
2. PROVIDE WITH FIELD-INSTALLED CONDENSATE LIFT PUMP AND UL-APPROVED FLOAT SWITCH IN DRAIN PAN.
3. POWERED BY AIR-COOLED CONDENSING UNIT.
1. PROVIDE WITH APPROPRIATE ACCESSORIES TO SUPPORT HEATER FROM WALL.
2. PROVIDE WITH FACTORY THERMOSTAT. SET TO 55°F (ADJUSTABLE).
3. PROVIDE WITH UNIT MOUNTED DISCONNECT.
DEDICATED OUTSIDE AIR SYSTEM SCHEDULE
MARK
SUPPLY FAN
EER
COOLING GAS HEATING UNIT ELECTRIC
OPERATING
WEIGHT
(LB) MANUFACTURER/MODELCFM
FAN
HP/QTY
BHP
(HP)
EXT S.P.
(IN WG)
TOTAL
NOM CAP
(MBH)
TOTAL
SEN CAP
(MBH)
AMBIENT
AIR (°F)
EAT
DB/WB
(°F)
LAT
DB/WB
(F)
HEATING
INPUT
(MBH)
HEATING
OUTPUT
(MBH) EAT (°F)
LAT
(°F) VOLT/PH MCA MFS
DOAS-1 1,000 2.5/1 0.47 1.0 9.9 89.8 58.3 105 105/78 51.4/51.4 75 60 24 79.6 208/3 45.5 70 1409 TRANE/OABD108D3
DOAS-2 500 2.5/1 0.24 1.0 12.0 38.5 26.5 105 105/78 56.1/56.1 50 40 24 98.1 208/3 25.0 35 1305 TRANE/OABD036D3
EXHAUST FAN SCHEDULE
MARK LOCATION SERVES CFM
EXT S.P.
(IN WG)
MAX.
SONES
MOTOR
MANUFACTURER/MODEL NOTES
ENCLOSURE
TYPE
POWER
(HP) RPM VOLTS PH
EF-1 SIDEWALL MOUNTED MAINTENANCE AREA 4,000 0.40 16.9 EXP 1.0 1725 208 3 GREENHECK/CWB-180-10 1, 2
EF-3 SIDEWALL MOUNTED FLUID DISTRIBUTION 100 0.18 2.5 ODP 1/100 1300 120 1 GREENHECK/CW-060-G 1, 3
EF-4 CEILING MOUNTED MENS RESTROOM 260 0.40 3.5 ODP 121W - 120 1 GREENHECK/SP-A410 1
EF-5 CEILING MOUNTED WOMENS RESTROOM 260 0.40 3.5 ODP 121W - 120 1 GREENHECK/SP-A410 1
EF-6 CEILING MOUNTED JANITOR 60 0.25 1.0 ODP 17W - 120 1 GREENHECK/SP-B80 1
EF-7, 8 SIDEWALL MOUNTED MECHANICAL/ELECTRICAL 200 0.40 6.5 ODP 1/20 1550 120 1 GREENHECK/CW-080-D 1, 3
EF-9, 10 SIDEWALL MOUNTED REPAIR AREA 6,800 0.40 23 EXP 2.0 1725 208 3 GREENHECK/CWB-220-20 1, 2
HEATING VENTILATOR UNIT
MARK SERVES CFM
FAN
HP/QTY BHP (HP) HEATING TYPE
HEATING
INPUT
(MBH)
HEATING
OUTPUT
(MBH) EAT (°F) TEMP RISE VOLT/PH MCA MOCP
OPERATING
WEIGHT MANUFACTURER/MODEL
HVU-1, 2 MAINTENANCE AREA 3,700 5.0/1 2.4 DIRECT GAS-FIRED 134.7 123.9 24 31.0 208/3 21.6 35 685 GREENHECK/DG-112-H10
HVU-3, 4 REPAIR AREA 6,700 7.5/1 5.25 DIRECT GAS-FIRED 243.8 224.3 24 31.0 208/3 30.9 50 882 GREENHECK/DG-115-H20
REMARKS:
1. PROVIDE WITH UNIT MOUNTED DISCONNECT.
2. PROVIDE WITH MODULATING HOT GAS REHEAT COIL.
3. PROVIDE WITH GAS HEAT EXCHANGER WITH MODULATING CAPACITY CONTROL AND HIGH TURNDOWN KIT.
4. PROVIDE WITH FACTORY FURNISHED ONBOARD BACNET CONTROLLER.
REMARKS:
1. PROVIDE WITH UNIT MOUNTED DISCONNECT.
2. FAN TO BE VARIABLE VOLUME.
3. PROVIDE WITH FACTORY SPEED CONTROLLER.
DX SPLIT - SYSTEM INDOOR UNIT SCHEDULE
MARK
NOM
SIZE
(TONS) CFM
OUTSIDE
(CFM)
EXT S.P.
(IN WG)
COOLING HEATING UNIT ELECTRIC
MANUFACTURER/MODEL NOTES
TOTAL
NOM CAP
(MBH)
TOTAL
SEN CAP
(MBH)
AMBIENT
AIR (°F)
EAT
DB/WB
(°F)
LAT
DB/WB
(F)
HTG CAP
(MBH)
AMBIENT
AIR (°F)
EAT
(°F)
LAT
(°F)
FAN
POWER
(HP) VOLT/PH MCA MOCP
AHU-1 5.0 1,850 400 0.67 47.7 38.5 105 73.8/61.3 53.8/51.8 38.4 24 70 89.2 0.75 208/1 9.0 15.0 TRANE/TEM6A0D60H51 1
AHU-2 1.5 425 - - 20.5 13.3 105 80.0/67.0 49.3 19.9 24 70 115.1 208/1 - - TRANE/PKA-A18HA4 2,3
AHU-3 1.0 425 - - 11.7 9.6 105 80.0/67.0 57.9 8.6 24 70 89.4 208/1 - - TRANE/PKA-A12HA7 2,3
AHU-4 4.0 1,600 450 0.48 41.2 30.2 105 72.0/60.5 53.9/50.9 30.4 24 70 87.6 0.75 208/1 9.0 15 TRANE/TEM6A0C48H41 1
AHU-5 5.0 1,900 150 0.41 53.2 45.7 105 77.7/63.0 55.2/53.1 40.1 24 70 89.5 0.75 208/1 9.0 15.0 TRANE/TEM6A0C60H51 1
AHU-6 1.5 425 - - 20.5 13.3 105 80.0/67.0 49.3 - - - - 208/1 - - TRANE/PKA-A18HA4 2,3
AHU-7 1.0 425 - - 13.7 10.4 105 80.0/67.0 56.1 - - - - 208/1 - - TRANE/PKA-A12HA4 2,3
AHU-8 2.0 700 170 .43 19.7 15.6 105 73.1/60.9 52.2/50.5 15.2 24 70 90.1 0.33 208/1 4.0 15.0 TRANE/TEM6A0B24H21 1
AHU-9 3.5 1,300 330 .37 35.9 29.1 105 72.1/60.5 51.4/50.3 26.7 24 70 89.0 0.5 208/1 5.0 15.0 TRANE/TEM6A0C42H41 1
1. PROVIDE WITH FACTORY HAILGUARD.
2. SIZE, ROUTE, INSULATE AND PROVIDE APPURTENANCES FOR DX REFRIGERANT PIPING SYSTEMS, AS PER MANUFACTURER RECOMMENDATIONS.
3. PROVIDE WITH LOW AMBIENT OPERATION.
VEHICLE EXHAUST FAN SCHEDULE
MARK SERVES CFM
EXT S.P.
(IN WG)
MOTOR
MANUFACTURER/MODEL
POWER
(HP) VOLTS PH
VE-1, 6 THRU 8 MAINTENANCE/REPAIR AREA 4,000 5 5.0 208 3 CAR-MON/CMB-30
VE-2 THRU 5 MAINTENANCE/REPAIR AREA 5,600 5 7.5 208 3 CAR-MON/CMB-32
REMARKS:
1. PROVIDE WITH UNIT MOUNTED DISCONNECT.
2. PROVIDE WITH STAND ALONE CO / NOX WALL-MOUNTED DETECTION SYSTEM (ONE BETWEEN EACH WORK BAY).
ELECTRIC PROPELLER UNIT HEATER SCHEDULE
MARK SERVES TYPE
CAPACITY
(KW)
AIRFLOW
(CFM)
THROW
(FT)
MOUNTING
HEIGHT (FT)
UNIT ELECTRICAL
MANUFACTURER/MODELVOLT/PH AMPS
UH-1 FLUID DISTRIBUTION 2.8 410 12 8 208/1 13.1 CHROMALOX/HVH-02-81-00
UH-2 MECHANICAL 2.8 410 12 8 208/1 13.1 CHROMALOX/HVH-02-81-00
UH-3 ELECTRICAL 2.8 410 12 8 208/1 13.1 CHROMALOX/HVH-02-81-00
UH-4 NONSENS SECURE STORAGE 2.8 410 12 8 208/1 13.1 CHROMALOX/HVH-02-81-00
5. PROVIDE WITH MERV-8 PLEATED FILTER.
6. FACTORY RUNISHED HAIL GUARD.
DIFFUSER, REGISTER AND GRILLE SCHEDULE
MARK TYPE
FACE SIZE
INCHES
NECK SIZE
INCHES MANUFACTURER/MODEL NOTES
A SQUARE CEILING SUPPLY DIFFUSER 24" X 24" 8" TITUS/TMS
B SQUARE CEILING SUPPLY DIFFUSER 24" X 24" 10" TITUS/TMS
C SQUARE CEILING SUPPLY DIFFUSER 24" X 24" 12" TITUS/TMS
D SQUARE CEILING RETURN DIFFUSER 24" X 24" 10" X 10" TITUS/PAR
E SQUARE CEILING RETURN DIFFUSER 24" X 24" 12" X 12" TITUS/PAR
F SQUARE CEILING RETURN DIFFUSER 24" X 24" 15" X 15" TITUS/PAR
G SQUARE CEILING RETURN DIFFUSER 24" X 24" 18" X 18" TITUS/PAR
REMARKS:
1. PROVIDE WITH APPROPRIATE ACCESSORIES TO SUPPORT HEATER FROM WALL.
2. PROVIDE WITH INTEGRAL THERMOSTAT SET TO 55°F (ADJ.)
3. PROVIDE INTEGRAL DISCONNECT.
REMARKS:
1. UNITS SHALL BE FURNISHED WITH APPROPRIATE FRAMES, ETC. FOR MOUNTING IN RESPECTIVE CEILING OR WALL TYPES.
2. SOUND VALUES SHALL NOT EXCEED 30 NC (ROOM).
M A
R K
D E
S C
R
IP
T
IO
N D
A
HVUOA
CONTROLLER
HARDWIRED TO
EMERGENCY
SHUTDOWN SWITCH
1 10
H
C
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
OUTSIDE AIR TEMPERATURE (GLOBAL)
EMERGENCY SHUTDOWN (GLOBAL)
DIRECT FIRED HEATING VENTILATOR CONTROL SEQUENCE
1. THE HVU SHALL BE CONTROLLED BY THE BAS AND REMAIN ENABLED 24/7. THE BAS CONTRACTOR
SHALL PROVIDE THE HVU SYSTEM WITH A BACNET CONTROLLER. THE UNIT SHALL START AND STOP
BASED ON THE FOLLOWING CRITERIA: OCCUPANCY SCHEDULE, CARBON MONOXIDE AND NITROUS
OXIDE SENSORS, OR MANUAL/REMOTE OVERRIDE THROUGH THE BAS.
2. THE HVU SHALL BE CONTROLLED AS FOLLOWS WHEN THE SPACE IS OCCUPIED (AS DETERMINED BY
OCCUPANCY SCHEDULE):
2.1.SUPPLY FAN: THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY WHEN THE SPACE IS OCCUPIED.
2.1.1. WHEN THE AMBIENT TEMPERATURE IS BELOW 55°F THE HVU SHALL PROVIDE 100% OUTSIDE
AIR TEMPERED TO 55°F TO THE SPACE.
2.1.2. WHEN THE AMBIENT TEMPERATURE IS ABOVE 55°F THE HVU SHALL PROVIDE 100% OUTSIDE
AIR TO THE SPACE.
2.1.3. COORDINATE HIGH/LOW LEVEL VFD SETPOINTS WITH TAB CONTRACTOR.
2.1.4. DURING NORMAL OPERATIONS THE HVU SHALL OPERATE AT OPERATING CFM AS SPECIFIED
ON SCHEDULE.
2.1.5. AT THE LOW LEVEL OF THE CO AND NOx SETPOINT THE SUPPLY FAN SHALL RAMP UP TO
PROVIDE FULL CFM AS SPECIFIED ON SCHEDULE.
2.1.6. ONCE THE CO AND NOx LEVELS HAVE FALLEN BELOW THE LOW LEVEL SET POINT, THE HVU
SHALL FALL BACK DOWN TO NORMAL OPERATING CONDITIONS.
3. THE HVU SHALL BE CONTROLLED AS FOLLOWS WHEN THE SPACE IS UNOCCUPIED (AS DETERMINED
BY OCCUPANCY SCHEDULE):
3.1.SUPPLY FAN: THE SUPPLY FAN SHALL NOT OPERATE UNLESS MANUALLY OVERRIDDEN FROM THE
BAS OR FROM CARBON MONOXIDE AND NITROUS OXIDE SENSORS.
3.2.DAMPER POSITION: THE OUTSIDE AIR DAMPER SHALL BE FULLY CLOSED.
4. EMERGENCY SHUTDOWN: THE UNIT FAN SHALL STOP, THE GAS CONTROL VALVE SHALL CLOSE AND
THE OUTSIDE AIR DAMPER SHALL BE MOVED TO THE CLOSED POSITION IN THE EVENT THAT AN
EMERGENCY SHUTDOWN BUTTON IS TRIGGERED IN THE FACILITY. NORMAL OPERATIONS SHALL
RESUME ONLY AFTER A MANUAL SYSTEM RESET AT THE BAS.
5. THE HVU SHALL BE PROVIDED WITH THE FOLLOWING ALARMS:
5.1.SIGNAL FROM VFD INSTALLED ON THE SUPPLY FAN CIRCUIT SHALL SEND AN ALARM TO THE BAS IF
THE FAN IS COMMANDED ON AND NO CURRENT IS DETECTED.
5.2.THE BAS SHALL MONITOR THE SPACE CO AND NOx SENSORS AND SEND AN ALARM IF THE SPACE
LEVELS RISE ABOVE THE LOW LEVEL SETPOINT (ADJ.)
5.3.A SMOKE DETECTOR LOCATED IN THE SUPPLY AIR DUCTWORK SHALL BE HARD WIRED INTO THE
MOTOR CONTROL CIRCUIT TO SHUT DOWN THE FAN AND SEND AN ALARM TO THE BAS IF SMOKE IS
DETECTED.
5.4.THE CONTROLLER WILL ACTIVATE AN ALARM WHEN THE FILTER PRESSURE LOSS ACROSS THE FILTER
EXCEEDS THE HIGH LIMIT SETPOINT OF 0.7 INCHES STATIC PRESSURE (ADJ.)
5.5.THE CONTROLLER WILL ACTIVATE AN ALARM WHEN AN EMERGENCY SYSTEM SHUTDOWN IS
TRIGGERED.
14 X
SUPPLY FAN ON/OFF
SUPPLY FAN FAILURE
SUPPLY FAN STATUS (VFD)
VFD SPEED SIGNAL
GAS CONTROL VALVE
LEAVING AIR TEMPERATURE SENSOR
SMOKE DETECTOR
FILTER ALARM
SYSTEM ENABLE
X
X
X X
X
X X
X X
X
OUTDOOR AIR DAMPER X
FILTER DIFFERENTIAL PRESSURE
SPACE AIR TEMPERATURE X
X
3 46
M
T
VFD
T
DP
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
FAN STATUS (VFD)
FAN FAILURE
EXHAUST FAN CONTROL SEQUENCE
1. THE EXHAUST FANS IN THE WORKBAYS SHALL BE CONTROLLED BY THE BAS AND REMAIN ENABLED 24/7. THE BAS CONTRACTOR
SHALL PROVIDE THE EXHAUST FAN SYSTEM WITH A BACNET CONTROLLER. THE UNIT SHALL START AND STOP BASED ON THE
FOLLOWING CRITERIA: OCCUPANCY SCHEDULE, CARBON MONOXIDE AND NITROUS OXIDE SENSORS, OR MANUAL/REMOTE
OVERRIDE THROUGH THE BAS.
2. THE EXHAUST FANS SHALL BE CONTROLLED AS FOLLOWS WHEN THE SPACE IS OCCUPIED (AS DETERMINED BY OCCUPANCY
SCHEDULE):
2.1. THE FAN SHALL OPERATE CONTINUOUSLY WHEN THE SPACE IS OCCUPIED.
2.1.1. COORDINATE HIGH/LOW LEVEL VFD SETPOINTS WITH TAB CONTRACTOR.
2.1.2. DURING NORMAL OPERATIONS THE EXHAUST FAN SHALL OPERATE AT OPERATING CFM AS SPECIFIED ON SCHEDULE.
2.1.3. AT THE LOW LEVEL OF THE CO AND NOx SETPOINT THE EXHAUST FAN SHALL RAMP UP TO PROVIDE FULL CFM AS
SPECIFIED ON SCHEDULE.
2.1.4. ONCE THE CO AND NOx LEVELS HAVE FALLEN BELOW THE LOW LEVEL SET POINT, THE EXHAUST FAN SHALL FALL BACK
DOWN TO NORMAL OPERATING CONDITIONS.
3. THE EXHAUST FAN SHALL BE CONTROLLED AS FOLLOWS WHEN THE SPACE IS UNOCCUPIED (AS DETERMINED BY OCCUPANCY
SCHEDULE):
3.1. THE EXHAUST FAN SHALL NOT OPERATE UNLESS MANUALLY OVERRIDDEN FROM THE BAS OR FROM CARBON MONOXIDE AND
NITROUS OXIDE SENSORS.
4. EMERGENCY SHUTDOWN: THE UNIT FAN SHALL STOP IN THE EVENT THAT AN EMERGENCY SHUTDOWN BUTTON IS TRIGGERED
IN THE FACILITY. NORMAL OPERATIONS SHALL RESUME ONLY AFTER A MANUAL SYSTEM RESET AT THE BAS.
5. THE EXHAUST FAN SHALL BE PROVIDED WITH THE FOLLOWING ALARMS:
5.1.A CURRENT TRANSFORMER INSTALLED ON THE EXHAUST FAN CIRCUIT SHALL SEND AN ALARM TO THE BAS IF THE FAN IS
COMMANDED ON AND NO CURRENT IS DETECTED.
5.2.THE BAS SHALL MONITOR THE SPACE CO AND NOx SENSORS AND SEND AN ALARM IF THE SPACE LEVELS RISE ABOVE THE LOW
LEVEL SETPOINT (ADJ.)
5.3.THE CONTROLLER WILL ACTIVATE AN ALARM WHEN AN EMERGENCY SYSTEM SHUTDOWN IS TRIGGERED.
X
FAN ON/OFF (OCCUPANCY SCHEDULE)
VFD SPEED SIGNAL
SYSTEM ENABLE
X
X X
X
EA OUT
BUILDINGEF
EA
FROM
SPACE
HARDWIRED TO
EMERGENCY
SHUTDOWN SWITCH
6 EMERGENCY SHUTDOWN (GLOBAL) X
CONTROLLER
VFD4
ELECTRIC UNIT HEATER START/STOP:
THE HEATER SHALL NORMALLY BE CONTROLLED BY THE SPACE MOUNTED
DEDICATED THERMOSTAT, THE DDC SYSTEM SHALL MONITOR THE SPACE
TEMERATURE. IF AT ANY TIME THE SPACE TEMPERATURE DROPS BELOW 55°F, AN
ALARM SHALL BE SENT TO THE BAS.
THE UNIT SHALL NOT BE AFFECTED DURING OCCUPANCY SCHEDULE.
ELECTRIC UNIT HEATER:
55° F
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
2 TEMPERATURE SENSOR
X
X
HEATER START/STOP
X
CARBON MONOXIDE / NITROUS OXIDE DETECTORS ARE FOR MONITORING AND ALARM
ONLY. THERE SHALL BE TWO SET POINT LEVELS (ADJ). WHEN LEVELS EXCEED THE FIRST
SETPOINT (ADJ), A SIGNAL SHALL BE SENT TO THE HVU'S VIA BAS. WHEN LEVELS EXCEED
THE SECOND SETPOINT (ADJ), ALARM IS TO BE VISUALLY DISPLAYED AND AUDIBLY
ALARMED IN SPACE AND AN ALARM SENT TO BAS.
CARBON MONOXIDE / NITROUS OXIDE DETECTORS:
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
2 HIGH LEVEL SETPOINT
X X
LOW LEVEL SETPOINT
CO NOx
CONTROLLER
ALARM
INFRARED UNIT HEATER START/STOP:
THE DDC SYSTEM SHALL ENABLE/DISABLE THE INFRARED UNIT HEATERS.
THE DDC SHALL ENABLE THE UNIT HEATERS WHEN THE OUTSIDE AIR TEMPERATURE IS
LESS THAN 75 DEGREES F.
HEATING SPACE TEMPERATURE SETPOINTS:
WHEN ENABLED, THE UNIT HEATER SHALL BE CONTROLLED BY A WALL THERMOSTAT TO
MAINTAIN 55 DEGREES F SETPOINT.
UNOCCUPIED SETBACK:
ON A PROGRAMMED TIME SCHEDULE (ADJUSTABLE), THE UNIT SHALL SWITCH TO AN
UNOCCUPIED MODE OF OPERATION. IN UNOCCUPIED MODE, THE UNIT SHALL NOT BE
ALLOWED TO START.
INFRARED UNIT HEATER:
EXHAUST FAN START/STOP:
THE FAN SHALL START/STOP BY A LOCAL SWITCH LOCATED IN THE WORK BAYS.
HOSE REEL START/STOP:
THE HOSE REEL SHALL START/STOP BY A LOCAL SWITCH LOCATED IN THE WORK BAYS.
VEHICLE EXHAUST SYSTEM:
THERE SHALL BE AN EMERGENCY SHUTOFF SWITCH LOCATED IN ALL BUILDINGS (REFER TO
MECHANICAL PLANS FOR LOCATIONS). IF AN EMERGENCY SWITCH IS ACTIVATED, THE
FOLLOWING MECHANICAL EQUIPMENT SHALL BE SHUTDOWN AND AN ALARM SHALL BE
SENT TO THE BUILDING AUTOMATION SYSTEM:
ALL FAN COIL UNITS EXCLUDING COILS SERVING IT OR TELECOM ROOMS.
ALL EXHAUST FANS.
ALL HEATING AND VENTILATING UNITS.
IF AN EMERGENCY SWITCH IS ACTIVATED, THE FOLLOWING MECHANICAL EQUIPMENT
SHALL OPERATE NORMALLY:
ALL ELECTRIC UNIT HEATERS.
HEAT PUMP SERVING IT AND TELECOM ROOM FAN COIL UNITS.
ONCE AN EMERGENCY SWITCH IS ACTIVAED, USER INTERVENTION AT THE BUILDING
AUTOMATION SYSTEM SHALL BE REQUIRED TO RESTART THE MECHANICAL EQUIPMENT.
EMERGENCY SHUTDOWN OF HVAC EQUIPMENT:
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C P
B
C P
B
D W
L
/4
/2
V A
N C
A S
H E
N P
.E
M-602
P
ID
S
C H
E M
A T
IC
I
/4
/1
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F
R E
N O
V A
T
IO
N S
B L
D G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
NOT TO SCALE
HEATING VENTILATOR UNIT P&ID
CONTROL SCHEMATIC
NOT TO SCALE
EXHAUST FAN FOR WORKBAYS P&ID
CONTROL SCHEMATIC
NOT TO SCALE
ELECTRIC UNIT HEATERS P&ID
CONTROL SCHEMATIC
NOT TO SCALE
INFRARED UNIT HEATERS P&ID
CONTROL SCHEMATIC
DOASOA SA
INTEGRAL
CONTROLLER
HARDWIRED TO
EMERGENCY SHUTDOWN
SWITCH
2 3
P
C
R
C
7 6 5
(TYPICAL)
DEDICATED OUTSIDE AIR SYSTEM CONTROL SEQUENCE
1. THE DOAS SHALL BE CONTROLLED BY THE BAS AND REMAIN ENABLED DURING OCCUPIED HOURS. REFER TO THIS SHEET FOR MORE
INFORMATION ON OCCUPANCY SCHEDULE.
2. DOAS CONTROL: THE DOAS SYSTEM SHALL BE PROVIDED WITH A FACTORY FURNISHED ON-BOARD BACNET CONTROLLER. THE MANUFACTURER
SHALL USE ITS PREFERRED SEQUENCE TO MEET THE FOLLOWING REQUIREMENTS: IN COOLING, THE CONTROLLER SHALL MONITOR THE
PRIMARY COIL LEAVING AIR TEMPERATURE AND MODULATE REFRIGERANT FLOW TO MAINTAIN THE PRIMARY COIL LEAVING AIR
TEMPERATURE SET POINT OF 55°F. THE DOAS SYSTEM SHALL THEN MODULATE THE REHEAT COIL TO REHEAT THE AIR TO THE SUPPLY AIR
TEMPERATURE SETPOINT OF 75°F. IN HEATING, THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE AND MODULATE
REFRIGERANT FLOW TO MAINTAIN THE SUPPLY AIR TEMPERATURE SETPOINT OF 70°F.
3. EMERGENCY SHUTDOWN: UPON ACTIVATION OF PUSHBUTTONS INSTALLED IN THE SPACE, OR UPON SIGNAL FROM THE FACP, DE-ENERGIZE
ALL HVAC EQUIPMENT AND CLOSE ALL MOTORIZED DAMPERS.
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
OUTSIDE AIR TEMPERATURE
FILTER DIFFERENTIAL PRESSURE
SUPPLY AIR TEMPERATURE
X
X
X X
EMERGENCY SHUTDOWN (GLOBAL)
SUPPLY FAN FAILURE X
X
SUPPLY FAN ON/OFF
SUPPLY FAN STATUS
X
CONDENSATE OVERFLOW X
SUPPLY AIR FLOW X
SUPPLY AIR TEMPERATURE SETPOINT X
PRIMARY COIL LEAVING AIR TEMPERATURE X
PRIMARY COIL LEAVING AIR TEMP. SETPOINT X
XSYSTEM ENABLE13 X
X
X
EA OUT
BUILDINGEF
EA
FROM
SPACE
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
FAN STATUS (CT SENSOR)
FAN FAILURE
EMERGENCY SHUTDOWN (GLOBAL) X
FAN ON/OFF (OCCUPANCY SCHEDULE) X
X
X
HARDWIRED TO
EMERGENCY
SHUTDOWN SWITCH
EXHAUST FAN CONTROL SEQUENCE
1. THE EXHAUST FANS SHALL BE ENABLED AND ENERGIZED DURING OCCUPIED HOURS. REFER TO THIS SHEET
FOR MORE INFORMATION ON OCCUPANCY SCHEDULE.
2. BAS TO MONITOR CT FOR STATUS, PROVIDE ALARM IF FAN IS COMMANDED ON BUT FAN IS NOT
OPERATING.
3. EMERGENCY SHUTDOWN: UPON ACTIVATION OF PUSHBUTTONS INSTALLED IN THE SPACE, OR UPON
SIGNAL FROM THE FACP, DE-ENERGIZE ALL HVAC EQUIPMENT AND CLOSE ALL MOTORIZED DAMPERS.
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
FILTER DIFFERENTIAL PRESSURE
RETURN AIR TEMPERATURE
X X
XEMERGENCY SHUTDOWN (GLOBAL)
SUPPLY FAN FAILURE X
XSUPPLY FAN STATUS
CONDENSATE OVERFLOW X
MINI-SPLIT CONTROL SEQUENCE
1. THE MINI-SPLIT SYSTEM SHALL REMAIN ENABLED DURING ALL HOURS.
2. MINI-SPLIT CONTROL: THE MINI-SPLIT SYSTEM SHALL BE PROVIDED WITH A FACTORY FURNISHED ON-BOARD BACNET CONTROLLER. THE
MANUFACTURER SHALL USE ITS PREFERRED SEQUENCE TO MEET THE FOLLOWING REQUIREMENTS: THE SPACE AIR TEMPERATURE SETPOINT
SHALL BE MONITORED AND THE SYSTEM SHALL BE ENERGIZED TO MAINTAIN THE SETPOINTS 72°F.
3. THE ONBOARD BACNET CONTROLLER SHALL COMMUNICATE WITH THE BAS TO ALLOW THE MONITORING AND CONTROL OF I/O POINTS LISTED
HERE. THE SYSTEM SHALL BE ENABLED 24/7.
4. ALARMS: THE ONBOARD BACNET CONTROLLER SHALL TRANSMIT SYSTEM ALARMS TO THE GUI. THE ONBOARD CONTROLLER SHALL, AT A
MINIMUM, TRACK ALARMS LISTED IN THE I/O POINTS LIST.
SPACE AIR TEMPERATURE X
SPACE AIR TEMPERATURE SETPOINT X
COMPRESSOR FAILURE X
XCOMPRESSOR STATUS
ACCU FAN FAILURE X
XACCU FAN STATUS11
ACCU
RA SA
INTEGRAL
CONTROLLER
HARDWIRED TO
EMERGENCY
SHUTDOWN SWITCH
6 7
MS
72° F
ACCU
RA SA
INTEGRAL
CONTROLLER
HARDWIRED TO
EMERGENCY
SHUTDOWN SWITCH
6 7
FCU
75° F
POINT NAMETAG
BAS INPUT/OUTPUT POINT LIST
AI AO DI DO ALARM
FILTER DIFFERENTIAL PRESSURE
RETURN AIR TEMPERATURE
X X
XEMERGENCY SHUTDOWN (GLOBAL)
SUPPLY FAN FAILURE X
XSUPPLY FAN STATUS
CONDENSATE OVERFLOW X
MINI-SPLIT CONTROL SEQUENCE
1. THE MINI-SPLIT SYSTEM SHALL REMAIN ENABLED DURING ALL HOURS.
2. MINI-SPLIT CONTROL: THE MINI-SPLIT SYSTEM SHALL BE PROVIDED WITH A FACTORY FURNISHED ON-BOARD BACNET CONTROLLER. THE
MANUFACTURER SHALL USE ITS PREFERRED SEQUENCE TO MEET THE FOLLOWING REQUIREMENTS: THE SPACE AIR TEMPERATURE SETPOINT SHALL
BE MONITORED AND THE SYSTEM SHALL BE ENERGIZED TO MAINTAIN THE SETPOINTS 75°F (COOLING) & 70°F (HEATING).
3. THE ONBOARD BACNET CONTROLLER SHALL COMMUNICATE WITH THE BAS TO ALLOW THE MONITORING AND CONTROL OF I/O POINTS LISTED HERE.
THE SYSTEM SHALL BE ENABLED 24/7.
4. ALARMS: THE ONBOARD BACNET CONTROLLER SHALL TRANSMIT SYSTEM ALARMS TO THE GUI. THE ONBOARD CONTROLLER SHALL, AT A MINIMUM, TRACK ALARMS LISTED IN THE I/O POINTS LIST.
SPACE AIR TEMPERATURE X
SPACE AIR TEMPERATURE SETPOINT X
COMPRESSOR FAILURE X
XCOMPRESSOR STATUS
ACCU FAN FAILURE X
XACCU FAN STATUS11
SCHEDULE OF OPERATION: PROVIDE 7-DAY SCHEDULES
OCCUPIED: FROM 8 AM (ADJ) - 6 PM (ADJ).
UNOCCUPIED: 6 PM (ADJ) - 8 AM (ADJ).
OCCUPANCY SCHEDULE:
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C P
B
C P
B
D W
L
/4
/2
V A
N C
A S
H E
N P
.E
M-603
P
ID
S
C H
E M
A T
IC
I
I
/4
/1
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F
R E
N O
V A
T
IO
N S
B L
D G
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
NOT TO SCALE
1 DOAS P&ID CONTROL SCHEMATIC
NOT TO SCALE
EXHAUST FAN P&ID CONTROL
SCHEMATIC
NOT TO SCALE
MINI-SPLIT (COOLING ONLY) P&ID
CONTROL SCHEMATIC
NOT TO SCALE
MINI-SPLIT (WITH HEATING) P&ID
CONTROL SCHEMATIC
REMARKSMANUFACTURER AND MODEL NO.
ELEMENT DATA
W
MARK LOCATION
INSTANTANEOUS GAS WATER HEATER SCHEDULE
MAX BTU/HR.
INPUT
GWH-1 199,900 350 NAVIEN, NPE-240-NG
MIN BTU/HR.
19,900
V PH
120 1
HZ
FLOW RATE
TEMP RISE F FLOW GPM
6.5JANITOR CLOSET SINGLE WATER HEATER60
NOTES :
1. SET OUTLET TEMPERATURE TO 120 MAX.
2. EXTERNAL HOT WATER CIRCULATION PUMP.
3. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
PLAN/DETAIL
SHEET WHERE RISER
DIAGRAM IS SHOWN
NOTE: ALL SYMBOLS AND ABBREVIATIONS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS.
NUMBER
RE: X/PX
PLUMBING RISER LOCATOR
DRAWING/DETAIL REFERENCE
RISER
NUMBER
X
TEE OUT OF TOP OF PIPE
CAP ON END OF PIPE
BELOW FINISHED GRADE
BELOW FINISHED FLOOR
1/8" PER FOOT SLOPE
1/4" PER FOOT SLOPE
ABOVE FINISHED GRADE
ABOVE FINISHED FLOOR
TEE OUT OF BOTTOM OF PIPE
AMERICANS WITH DISABILITIES ACT
GALLONS PER HOUR
GALLONS PER MINUTE
VENT THROUGH ROOF
TEXAS ACCESSIBILITY STANDARD
DOUBLE CHECK BACKFLOW PREVENTER
TEXAS COMMISSION ON ENVIRONMENTAL QUALITY
POINT OF NEW TO EXISTING CONNECTION
DRAINAGE WASTE AND VENT
RECOVERY
HORSE POWER
TEMPERATURE
REFER TO:
TYPICAL
WITH
RD
1/4"/FT
1/8"/FT
OFD OVERFLOW DRAIN
ROOF DRAIN
FLOOR SINK
FLOOR DRAIN
BFG
DCBFP
TAS
TEMP
TCEQ
RE:
REC
GPH
HP
GPM
TYP
VTR
W/
DWV
BFF
FS
RD
ADA
AFG
AFF
OFD
FD
HW(140°)
SS
ABBREVIATION
NFWH or HB
ENGINE OIL
WASTE OIL OUT OF SPEC
DOUBLE GRADE CLEANOUT
DIRECTION OF FLOW
DIRECTION OF PITCH DOWN (SLOPE)
VALVE IN RISER (TYPE AS SPECIFIED OR NOTED)
SHUT-OFF VALVE (SEE SPECIFICATIONS FOR TYPE)
NON-FREEZE WALL HYDRANT or HOSE BIBB
EXISTING PIPING TO BE REMOVED (DEMO PLAN ONLY) (INDICATE SERVICE TYPE)
PIPE TURNING AND RISING UP
PIPE TURNING AND DROPPING DOWN
PCO
WCO
GCO
DGCO
FCO
NFWH or HB
PLUG CLEANOUT
WALL CLEANOUT
GRADE CLEANOUT
RELIEF VALVE
FLOOR CLEANOUT
UNION
GR
A T
G
GO
O
AF
UAF
WOS
OW
WO
TRANSMISSION FLUID
NATURAL GAS
COMPRESSED AIR
GREASE
ANTIFREEZE
GEAR OIL
USED ANTIFREEZE
OIL/WATER WASTE
EXISTING PIPING (INDICATE SERVICE TYPE)
WASTE OIL
PCO
WCO
GCO
FCO
DGCO
A G
AF
GR
T
O
GO
UAF
WOS
OW
WO
PLUMBING LEGEND
SYMBOL
OFD
RD
COLD WATER
ROOF DRAIN
VENT
SANITARY SEWER
OVERFLOW DRAIN
HOT WATER (140°)
DESCRIPTION
V
CW
RD
OFD
COLD WATER FIXTURE UNITS CWFU'S
SWFU'SSANITARY WASTE FIXTURE UNITS
NOT TO SCALE NTS
INVERT ELEVATION OR FLOW LINE I.E.
HWHOT WATER
140HW
HOT WATER RETURN HWR
UNDERFLOOR U/F
REDUCER OR INCREASER FITTING
FIXTURE UNIT F.U.
REDUCED PRESSURE BACKFLOW PREVENTER RPBFP
140HW
RD
OFD
G A T
GR
GO
AF
O
WO
WOS
UAF
OW
X
X
WATER HAMMER ARRESTOR WHA
XX
XX XX
XX
GENERAL NOTES:
1. THIS PROJECT IS DESIGNED BASED ON THE FOLLOWING CODES: INTERNATIONAL PLUMBING CODE 2015. UFC-3-420-01 PLUMBING SYSTEMS, UFC 4-010-01 DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, UFC-4-024-01 PROCEDURES FOR DESIGNING AIRBORNE CHEMICAL PROTECTION FOR BUILDINGS.
2. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR THE EXACT LOCATION OF ALL CEILING MOUNTED DEVICES.
3. REFER TO ARCHITECTURAL INTERIOR ELEVATION DRAWINGS, WHERE THE ARCHITECT HAS DRAWN SUCH ELEVATIONS, FOR THE LOCATIONS OF ALL WALL MOUNTED DEVICES. OTHERWISE INSTALL PER INDUSTRY
STANDARDS, CODES AND/OR ORDINANCES OF THE AUTHORITY HAVING JURISDICTION.
4. COORDINATE ALL SLAB PENETRATIONS AND SLEEVES PRIOR TO EACH CONCRETE POUR. VERIFY EXACT LOCATION OF CONCRETE FLOOR "LEAVE-OUTS" FOR PLUMBING FIXTURE ROUGH-INS.
5. PROVIDE ACCESS DOORS FOR INSTALLATION IN WALLS AND CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED PLUMBING EQUIPMENT, VALVES, CONTROLS AND OTHER DEVICES.
6. INSTALL PIPING TO PROVIDE THE MAXIMUM POSSIBLE CLEAR HEIGHT UNDERNEATH. MAINTAIN A MINIMUM OF 10 INCHES ABOVE FINISHED CEILING TO PROVIDE CLEARANCE FOR LIGHTING FIXTURES.
7. COORDINATE THE EXACT LOCATION OF FLOOR DRAINS WITH THE ARCHITECTURAL DRAWINGS AND MECHANICAL EQUIPMENT LOCATIONS PRIOR TO INSTALLATION OF DRAINS.
8. COORDINATE WORK WITH ARCHITECTURAL FEATURES, PIPING, EQUIPMENT, MECHANICAL WORK, ELECTRICAL WORK, AND BUILDING STRUCTURE TO AVOID INTERFERENCES.
9. PROVIDE RATED INTUMESCENT CAULK OR PUTTY AT ALL FIRE RATED PENETRATION LOCATIONS, INCLUDING BUT NOT LIMITED TO STAIRWELLS, CORRIDORS, AND MECHANICAL OR ELECTRICAL EQUIPMENT ROOMS.
ESCUTCHEONS ARE NOT REQUIRED, EXCEPT IN EXPOSED LOCATIONS. HOWEVER THE CAULK OR PUTTY SHALL BE INSTALLED SMOOTH AND FLUSH TO THE SURROUNDING SURFACE.
10. MINIMUM SLOPE FOR DRAINAGE PIPE WITHIN 5'-0" OF BUILDING IS 1/4" PER FOOT FOR 2-1/2" DIAMETER AND LESS AND 1/8" PER FOOT FOR 3" DIAMETER AND GREATER. MINIMUM SLOPE FOR DRAINAGE PIPE BEYOND
5'-0" OF BUILDING IS 1%.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION, ACCEPTABLE MANUFACTURER AND MODEL NUMBER ON PLUMBING FIXTURES.
ROUGH-IN (INCHES)
1/2"
NOTE:
SSK1 SERVICE SINK 3" 2"
DESCRIPTION
URINALUR1
MARK
2"2"
W V
30"x30" FLOOR MOUNTED, CORNER, 5-SIDED, TERRAZO OR MOLDED STONE1/2"
WALL MOUNTED, MANUAL FLUSH VALVE TYPE, ADA/TAS ACCESSIBLE3/4"-
HW CW
REMARKS
WC1 WATER CLOSET 2"4" -
WC2 WATER CLOSET 4" 2" WALL MOUNTED, MANUAL FLUSH VALVE TYPE, ADA/TAS ACCESSIBLE
WALL MOUNTED, MANUAL FLUSH VALVE TYPE1"
- 1"
1/2"S1 SINK 2" 2" COUNTER-TOP MOUNTED, DOUBLE COMPARTMENT, GOOESNECK FAUCET, STAINLESS STEEL, ADA/TAS ACACCESSIBLE, WITH HAND SPRAYER1/2"
PLUMBING FIXTURE ROUGH-IN SCHEDULE
1/2"L1 LAVATORY 2" 2" 1/2" WALL MOUNTED, RECTANGULAR, ADA/TAS ACCESSIBLE
1/2"SH1 SHOWER 2"FD 2" 1/2"
1/2"SH2 SHOWER 2"FD 2"
BUILT-UP TYPE ENCLOSURE, WITH MIXING VALVE, HAND HELD SPRAYER, SHOWER ARM, 5'-0" FLEXIBLE HOSE, IN-LINE VACUUM
BREAKER, SLIDE BAR, ADA/TAS ACCESSIBLE
1/2" BUILT-UP TYPE ENCLOSURE, WITH MIXING VALVE, IN-LINE VACUUM BREAKER, SHOWER HEAD
PETROLEUM, OIL AND LUBRICANTS POL
ELECTRIC WATER COOLEREWC1 2" 2" WALL MOUNTED, DUAL, HI-LO TYPE W/APRON ON HIGH UNIT AND WITH BOTTLE FILLER, ADA/TAS ACCESSIBLE1/2"
ESE1
EEW1
-EMERGENCY SHOWER/EYEWASH - FLOOR MOUNTED, COLUMN TYPE1 1/4"
-EMERGENCY EYEWASH - HAND HELD WAND TYPE, MOUNTED ON HOSE REEL RACK1/2"
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
T M
G
T M
G
S T
V
/2
/1
/1
/2
V A
N C
A S
H E
N P
.E
P-001
P L U
M B
IN
G
L E
G E
N D
S
C H
E D
U L E
S A
N D
G E
N E
R A
L N
O T
E S
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
.E .M
.F
R E
N O
V A
T
IO
N B
L D
G
M A
R K
D E
S C
R
IP
T I O
N D
A
GENERAL NOTES
1. REFER TO P-001 FOR GENERAL NOTES,
ABBREVIATIONS AND LEGEND.
NOTES BY SYMBOL " "
1. ALL FIXTURES AND ASSOCIATED PIPING TO BE
DEMOLISHED.
2. ALL EXISTING NATURAL GAS PIPING TO BE
DEMOLISHED.
3. ALL EXISTING DOMESTIC WATER PIPING AND
ASSOCIATED FIXTURES TO BE DEMOLISHED.
4. ALL EXISTING SANITARY PIPING AND ASSOCIATED
FIXTURES TO BE DEMOLISHED. SAW-CUT
FOUNDATION AND REMOVE SANITARY PIPING.
5. ALL COMPRESSED AIR PIPING TO BE
DEMOLISHED.
C W
A A
AAA
A A
AA
A A
C W
C W
SS SS
A
1.1
4.4
B C D E F
G H J
3.5
2.5
A.8A.2
F.5F.7 G.7G.9F.9
4.7
4.3
1.2
2.3
3.7
4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø
1 1/4"ø 1 1/4"ø1 1/4"ø
1 1/4"ø
1 1/4"ø 4"ø
3"ø
3"ø
1 1/4"ø
1"ø
1"ø
1 1/4"ø
1"ø1"ø
1 1/4"ø
3/4"ø
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S T
R U
C T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
T M
G
T M
G
S T
V
/2
/1
/1
/2
V A
N C
A S
H E
N P
.E
PD-101
D E
M O
L
IT
IO
N
P L A
N
F
IR
S T
F L O
O R
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
.E .M
.F
R E
N O
V A
T
IO
N B
L D
G
3/32" = 1'-0"
1 DEMOLITION PLAN - FIRST FLOOR
M A
R K
D E
S C
R
IP
T I O
N D
A T
E
PLAN
NORTH
0 8' 16'
3/32"=1'-0"
4'
1.1
4.4
B C D E F
G H J
3.5
2.5
A.8A.2
F.5F.7 G.7G.9F.9
4.7
4.3
1.2
2.3
3.7
MAINTENANCE
AREA
COMBAT SPARES
ARMS VAULT
119 CONSOLIDATED
BENCH REPAIR
COMSEC VAULT
FLUID DISTR
BREAK /
TRAINING
MENS
WOMENS
NON-SENS
SECURE STOR
OFFICE 1
OFFICE 2
ADMIN SHOP
CONTROL
TOOL ROOM
ELEC
T
GR
GO
A
G
A
GO
GR
T
G
T G
R G
O A
G
A G
O G
R T
G
G
C W
AF
O
AF
A F
O
O
A F
O
WOSWOUAF
4" VTR
4" VTR
FCOFCO
GCO
FCOFCOFCO GCO
DGCO
GCO
GCO
GCO
4" VTR 4" VTR
GCO
FCO
FCO
FCO
FCO
GCO
P-401
6"
6"
6"
6"
4"
4" 4"
4"
4"
OW
OW
O W
O W
O W
OW
GCO
G
OW
OW
4"
4"
PCO AT 2'-0" AFF PCO AT 2'-0" AFF
4" 4"
OW
PCO AT 2'-0" AFF
PCO AT 2'-0" AFF
GENERAL NOTES
NOTES BY SYMBOL " "
1. FOR PLUMBING LEGEND, SCHEDULES AND
GENERAL NOTES, REFER TO SHEET P-001.
2. PROVIDE FIRE RATED SLEEVES AND INTUMESCENT
CAULK (ASTM E 814 UL 1479) FOR EVERY
PENETRATION THROUGH A FIRE RATED
ENCLOSURE EQUAL TO THE RATING OF THE
ENCLOSURE, IN ACCORDANCE WITH THE
MANUFACTURERS WRITTEN INSTRUCTIONS.
1. PROVIDE NEW PLUMBING FIXTURES, PIPING,
SUPPLIES, HANGERS AND SUPPORTS, FAUCETS,
FLUSH VALVES, FITTINGS, AND APPURTENANCES.
2. 2" FLOOR DRAIN WITH TRAP GUARD INSERT.
3. 2" SHOWER DRAIN WITH TRAP GUARD INSERT IN
PRECAST SHOWER BASIN (INTEGRAL WITH BASIN BY
BASIN MFG.).
4. NATURAL GAS FIRED INSTANTANEOUS TANKLESS
WATER HEATER (GWH-1).
5. POL FLUIDS EQUIPMENT. RE: 3/P-601.
6. DUPLEX AIR COMPRESSOR. 25 HP 208V, 3PH & AIR
DRYER 1/3 HP, 208V, 1PH.
7. GAS METER AND REGULATOR. PROVIDE NEW GAS
REGULATOR CAPABLE OF HANDLING XXX CFH AT 14"
W.C. DOWNSTREAM.
8. MAINTENANCE PIT. RE: 2/P-601.
9. 500 GALLON ABOVE GROUND DOUBLE WALL USED
OIL STORAGE TANK.
10.500 GALLON DOUBLE WALL OUT OF SPEC OIL
STORAGE TANK.
11.500 GALLON DOUBLE WALL USED ENGINE
COOLANT (ANTIFREEZE) STORAGE TANK.
12.POL DISPENSING HOSE REELS FOR REASE, ENGINE
OIL, GEAR OIL, TRANSMISSION FLUID, AND
ANTIFREEZE MOUNTED ON SUPPORT RACK.
RE: P-601.
13.POL DISPENSING HOSE REELS MOUNTED IN A
RECESSED AREA IN THE MAINTENANCE PIT WALL,
GREASE, GEAR OIL AND TRANSMISSION FLUID.
14.SUMP PUMP IN SUMP IN MAINTENANCE PIT FLOOR;
20 GPM @ 20' HD., 1750 RPM, 1HP, 208V, 1PH.
15.COMPRESSED AIR OUTLET IN MAINTENANCE PIT.
16.USED ENGINE COOLANT (ANTIFREEZE)
RECEPTACLE/PUMP. RE: 2/P-601.
17.WASTE (OUT OF SPEC) OIL RECEPTACLE/PUMP.
RE: 2/P-601.
18.WASTE (USED) OIL RECEPTACLE/PUMP. RE: 2/P-601.
19.CONNECT EACH TRENCH DRAIN TO 4" OW DRAIN
BELOW FLOOR. PROVIDE P-TRAP AT CONNECTION.
20.1/2" GAS TO UNIT HEATER, PROVIDE DIRT LEG, FULL
PORT PLUG VALVE AND UNION WITH 12" U.L. FLEX
CONNECTOR.
21.BRIDGE CRANE ABOVE. RE: STRUCTURAL DRAWINGS.
22.2000 GALLON OIL WATER SEPARATOR.
23.1/2" CW DOWN TO EMERGENCY EYEWASH EEW1 WITH
HAND HELD SHOWER HOSE AND SPRAY MOUNTED ON
SUPPORT RACK.
24.1-1/4" CW DOWN ON WALL TO EMERGENCY
SHOWER/EYEWASH ESE1.
25.3/4" COMPRESSED AIR DOWN TO HOSE REEL, 3/4" CW
DOWN TO WATER HOSE REEL, HOSE BIBB AND EEW1.
COORDINATE PIPE DROPS AND HOSE REELS WITH
VEHICLE EXHAUST SYSTEM, ELECTRICAL SYSTEM,
SUPPORT RACK AND BRIDGE CRANE. RE: 1/P-601.
26.6" WIDE X 28' LONG TRENCH DRAIN WITH 6" DRAIN
TO OIL WATER SEPARATOR.
27.FLOOR DRAIN FOR ICE MAKER DRAIN.
28.2" W & V, 1/2" CW & HW TO SINK.
29.REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER
(RPZ).
30.DROP T, G, GO, A INTO 6" PVC PIPE TO MAINTENANCE
PIT.
31.UAF, WO, WOS RISE OUT OF 6" PVC PIPE - ALL ALONG
WALL, RISE TO JOIST SPACE.
32.PROVIDE HOT WATER TEMPERATURE MAINTENANCE
TAPE (HWTM) ON ALL EXPOSED HW PIPING (208V, 1PH,
30A GFCI) J-BOX PROVIDED BY ELECTRICAL
CONTRACTOR. RE: ELECTRICAL DRAWINGS.
33. REFER TO CIVIL DRAWINGS FOR CONTINUATION.
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
T M
G
T M
G
S T
V
/2
/1
/1
/2
V A
N C
A S
H E
N P
.E
P-102
F L O
O R
P L A
N
F
IR
S T
F L O
O R
O V
E R
A L L
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
.E .M
.F
R E
N O
V A
T
IO
N B
L D
G
3/32" = 1'-0"
1 FLOOR PLAN - FIRST FLOOR OVERALL
9 10 11
TYP @
EACH BAY
M A
R K
D E
S C
R
IP
T I O
N D
A T
E
PLAN
NORTH
0 8' 16'
3/32"=1'-0"
4'
31 30
18 13
TYP @
EACH BAY
TYP @
EACH BAY
12 25
TYP @
EACH BAY
(TYP)
(TYP)
TYP @
EACH BAY
TYP @
EACH BAY
23 23
TYP @
EACH BAY
TYP @
EACH BAY
23 23
1"
1" 1"
3/8"
1" 1-1/2"
3/8"
1/2"
1"
3/8"
1/2"
1-1/2"
3/8"
1/2"
1"
3/8"
1/2"
1-1/2"
2"
2"
1"
3/8"
3/8"
1/2"
1/2" 2-1/2"
2"
3"
3"
A
T G
R G
O
3/8"1/2" 1"
3"
2"
2-1/2" 2" 1-1/2"
1"
1"1-1/2"
3/8" 1/2" 1" 3/8" 1/2"
3/8" 1/2" 1" 3/8" 1/2"
A F
O
4.4
B C
WC2WC2
UR1 WC1
L1
L1L1
L1
SSK1
SH1
SH1
FD1FD1FD1
FD1
FCO
GWH1
WC1
UR1
WC2
WC2
L1
L1
L1
L1
SH1
SH1
SSK1
FCO
FCO
FCO
FD1
4" VTR
2"
3/4"
3/4"
3/4"
1/2"
1/2"
FD1
FD1
FD1
GWH1
FD1
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S T
R U
C T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
T M
G
T M
G
S T
V
/2
/1
/1
/2
V A
N C
A S
H E
N P
.E
P-401
P L U
M B
IN
G
E N
L A
R G
E D
P L A
N
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
.E .M
.F
R E
N O
V A
T
IO
N B
L D
G
M A
R K
D E
S C
R
IP
T I O
N D
A T
E
1/4" = 1'-0"
1 PLUMBING ENLARGED PLAN
2 RISER DIAGRAM
PLAN
NORTH
0 2' 4' 8'
1/4"=1'-0"
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S T
R U
C T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
T M
G
T M
G
S T
V
/2
/1
/1
/2
V A
N C
A S
H E
N P
.E
P-601
P L U
M B
IN
G
I S
O M
E T
R
IC
D E
T A
IL
S
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
.E .M
.F
R E
N O
V A
T
IO
N B
L D
G
M A
R K
D E
S C
R
IP
T I O
N D
A T
E
USED ANTI-FREEZE
PUMP TO STORAGE
TANK OUTSIDE
SLEEVDED
UNDERGROUND
PIPING TO WASTE
TANKS
WASTE OIL PUMP
TO STORAGE TANK
OUTSIDE
OUT OF SPEC OIL
PUMP TO STORAGE
TANK OUTSIDE
(MOUNTED IN RECESS
IN PIT WALL. TYPICAL)
RE: STRUCTURAL
HOSE REELS
MOUNTED IN
RECESS IN PIT WALL.
RE: STRUCTURAL
POL HOSE REELS MOUNTED
14' AFF. TYPICAL EACH BAY.
RE: STRUCTURAL FOR
MOUNTING FRAME
FLEXIBLE HOSE TO POL
HOSE REELS. (TYPICAL )
ROUTE TO AVOID BRIDGE
CRANE AND OTHER
UTILITIES
NATURAL GAS LOOP
THROUHOUT BUILDING.
ROUTE TO AVOID
OTHER UTILITIES AND
BRIDGE CRANE
SLEEVED
UNDERGROUND
PIPING TO POL
HOSE REELS IN PIT
COMPRESSED AIR
DRIVEN FLUID
PUMP MOUNTED
ON WALL. TYPICAL
ENGINE OIL OUT TO
HOSE REELS AT
EACH BAY
COMPRESSED AIR
FROM COMPRESSOR
IN MECH ROOM
ANTI-FREEZE OUT
TO HOSE REELS AT
EACH BAY
GEAR OIL OUT TO
HOSE REELS AT
EACH BAY
GREASE OUT
TO HOSE REELS
AT EACH BAY
TRANSMISSION
FLUID OUT TO
HOSE REELS AT
EACH BAY
1 HOSE REEL ISOMETRIC
2 MAINTENANCE PIT ISOMETRIC
FLUIDS DISTRIBUTION ROOM
ISOMETRIC
55 GALLON DRUM
FOR ENGINE OIL
DISTRIBUTION
55 GALLON DRUM
FOR ANTI-FREEZE
DISTRIBUTION
55 GALLON DRUM
FOR GEAR OIL
DISTRIBUTION
55 GALLON DRUM FOR
TRANSMISSION FLUID
DISTRIBUTION
55 GALLON DRUM FOR
GREASE DISTRIBUTION
CW
T
GR
GO
AAF
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S T
R U
C T
IO
N
US Army Corps of
Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
T M
G
T M
G
S T
V
/2
/1
/1
/2
V A
N C
A S
H E
N P
.E
P-602
O V
E R
A L L I S
O M
E T
R
IC
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
.E .M
.F
R E
N O
V A
T
IO
N B
L D
G
M A
R K
D E
S C
R
IP
T I O
N D
A T
1 OVERALL ISOMETRIC
MC1-XXX
NOTE:
THIS IS A STANDARD LEGEND. THEREFORE, NOT ALL OF
THIS INFORMATION MAY BE USED ON THIS PROJECT.
X
X
TR. TRIAD
PHOTOCELLPC
AIC
C/C CENTER TO CENTER
DP
FT
EXIST.
EUC
HP
HTP
GA.
GFS
DIFFERENTIAL PRESSURE
HORSEPOWER
HEATER
ELECTRIC UTILITY CO.
GAUGE
FEET
EXISTING
GROUND FAULT SENSING
ID
JB
LED
KW
KVA
IRP
MFR'S
MCB
MANUFACTURER'S
KILOWATT
MAIN CIRCUIT BREAKER
LIGHT EMITTING DIODE
KILOVOLT-AMPERE
INTERPOSING RELAY PANEL
JUNCTION BOX
INTERNAL DIAMETER
AMPERES INTERRUPTING CAPACITY
OD
NF
MPR
PL.
PH
PLC
P POLE
OUTSIDE DIAMETER
NON-FUSED
MOTOR PROTECTION RELAY
PHASE
PLATE
REC.
RTU
RTD
REQD.
SHLD. OR SH
SN OR S/N
STC
STA.
CIRCUIT RECLOSURE
REMOTE TERMINAL UNIT
SOLID NEUTRAL
REQUIRED
SHIELD OR SHIELDED
STATION
SIGNAL TERMINATION CABINET
REMOTE CONTROLRC
UTP
UPS
VAR.
W
XMTR
VARIABLE
TRANSMITTER
WITH, WIRE OR WATT
UNSHIELDED TWISTED PAIR CABLE
UNINTERRUPTIBLE POWER SUPPLY
RESISTANCE TEMPERATURE DETECTOR
PROGRAMMABLE LOGIC CONTROLLER
SSRVS SOLID-STATE REDUCED VOLTAGE STARTER
MBFV MOTOR OPERATED BUTTERFLY VALVE
WR WEATHER RESISTANT
OHE OVERHEAD ELECTRIC
SPD SURGE PROTECTION DEVICES
SV SOLENOID VALVE
WP WEATHERPROOF
XFMR
XP EXPLOSION PROOF
TRANSFORMER
SS STAINLESS STEEL
VO
TC
TEL
SW
SWGR
TYP
TS
TW
TO
VFD
UG
V
TWISTED
VALVE OPERATOR
UNDERGROUND
VARIABLE FREQUENCY DRIVE
TYPICAL
VOLTS
TEMPERATURE SWITCH
TERMINATION CABINET OR TRAY CABLE
TIME DELAY ON OPENING
TELEPHONE
SWITCHGEAR
SWITCH
RCP
PT
PVC
SC
QTY
SEC
OL
PB
PR.
PCC
OLX
RELAY CONTROL PANEL
SURGE CAPACITOR
POLYVINYL CHLORIDE
SECONDS OR SECONDARY
QUANTITY
PULL BOX OR PUSH BUTTON
PUMP CONTROL CONSOLE
OVERLOAD CONTROL RELAY
POTENTIAL TRANSFORMER
PAIR OR PAIR CABLE
OVERLOAD
EM EMERGENCY
LP
LA
MFR
MCC
MCP
INST
LGTS ON LTG
MTS
MTD
MTG
MH
MANUFACTURER
NORMALLY CLOSED
NORMALLY OPEN OR NUMBER
MANUAL TRANSFER SWITCH
MOUNTING
MOUNTED
MANHOLE
LIGHTING PANEL
MOTOR CIRCUIT PROTECTOR
MOTOR CONTROL CENTER
LIGHTNING ARRESTER
LIGHTS/LIGHTING
INSTRUMENT
EHH
FU
FRP
GCP
GFI
GEN
GRS
HT
HH
HZ
FBO
FO
G. OR GRD
GENERATOR CONTROL PANEL
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL
HANDHOLE
HERTZ
HEIGHT
GROUND
GENERATOR
ELECTRICAL MANHOLE
FIBERGLASS REINFORCED POLYESTER
FURNISHED BY OTHERS
FUSE
FIBER OPTIC
ELEC
EC
ELEV
EMPTY CONDUIT
ELEVATION
ELECTRICAL
CONDUIT
CIRCUIT BREAKER
AMPERE
ABOVE GRADE
AMERICAN WIRE GAUGE
AUTOMATIC TRANSFER SWITCH
ABOVE FINISHED FLOOR OR GRADE
ALTERNATING CURRENT
ABBREVIATIONS
AUTOMATIC
AUXILIARY
ALUMINUM
CB
C.
AFF
AUTO
AUX
AWG
ATS
AMP OR A
AG
AL OR ALUM
AC
CKT
CLF
CPT
CR
CS
CT
CU
DC
DI
DN
EMH
CONTROL POWER TRANSFORMER
DIRECT CURRENT
DOOR INTERLOCK
DOWN
CURRENT TRANSFORMER
CURRENT LIMITING FUSE
CONTROL SWITCH OR COMBINATION STARTER
CONTROL RELAY
COPPER
CIRCUIT
SHEETSHT
LIGHTNING CONTACTORLC
IMH INSTRUMENT MANHOLE
DWG DRAWING
SCH SCHEMATIC
PFR PHASE FAILURE RELAY
PUSH TO TEST TYPEPTT
ADJUSTABLE FREQUENCY DRIVEAFD
EO ELECTRICALLY OPERATED
HTR
HEAT TRACE PANEL
MOV MOTOR OPERATED VALVE
PPR PHASE PROTECTIVE RELAY
RECP RECEPTACLES
CONT. CONTINUATION
GO GATE OPERATOR
ST STARTER
CP CONTROL PANEL
ABBREVIATIONS
ML MULTILIN
SCTB SHORT CIRCUIT TERMINAL BLOCK
MR MULTIRATIO
AGSB ABOVE GROUND SPLICE BOX
NC or N.C.
NO or N.O.
ELECTRICAL MANHOLE/HANDHOLE
CHH COMMUNICATION MANHOLE/HANDHOLE
VFI VACUUM FAULT INTERUPTER
ETM ELAPSED TIME METER
LSIG LONG, SHORT, INSTANTANEOUS, GROUND
SHEET NUMBER
WHERE DRAWN
NUMBER
MLO MAIN LUGS ONLY
NUMBERNO.
AMP FRAMEAF
AMP TRIPAT
RE: X/X-XX
SHEET
NUMBER
IDENTIFIER
REFERENCE
PB
nBRG 8 KIT
BRIDGE-8 PORT WITH 150mA POWER SUPPLY nPODM 2P DX
2 CHANNEL ON/OFF TOGGLE WITH DIMMING
nPODM 4P DX
4 CHANNEL ON/OFF TOGGLE WITH DIMMING
nWSX PDT LV DX [COLOR]
WALL SWITCH DECORATOR SENSOR-DUAL TECHNOLOGY
NWV PDT 16 KIT
WIDE VIEW SENSOR-CORNER MOUNT, LOW VOLTAGE, DUAL TECHNOLOGY
BR
OS
D2
D4
LV
nCM ADCX
AUTOMATIC DIMMING CONTROL PHOTOCELL
P nAR40
AUXILIARY RELAY
R nPODM DX
1 CHANNEL ON/OFF TOGGLE WITH DIMMING
D
E
OS
O
OS
P nCM PDT 10 ADCX
EXTENDED RANGE 360° SENSOR-CEILING MOUNT, DUAL TECHNOLOGY:
PHOTOCELL w/DIMMING nCM PDT 10
EXTENDED RANGE 360° SENSOR-CEILING MOUNT, DUAL TECHNOLOGY
THREE 4-INCH CONDUITS
DENOTES A QUANTITY OF TWO INSTRUMENT CABLES.
EACH CONSISTS OF TWO NO.16 AWG CONDUCTORS
CABLE TAG FOUR #14 CONTROL OR POWER CONDUCTORS, ONE #14
GROUND CONDUCTOR. ALL CONDUCTORS IN A 3/4" CONDUIT. TWO OF
THE FOUR #14 CONTROL OR POWER CONDUCTORS ARE SPARE.
PREWIRED
UTILITY METER
MANHOLE
"b" - SWITCH NUMBER
LIGHTING FIXTURE
"A" - FIXTURE TYPE
CONDUIT STUBBED OUT AND CAPPED
3-4"C
2-2/C#16
JUNCTION BOX - CEILING MOUNTED
DESCRIPTION
"X" - FIXTURE TYPE
CEILING MOUNTED EXIT SIGN
PLAN SYMBOL
TIME SWITCH
3 WAY SWITCH
DIMMER LIGHTING SWITCH (REVERSE PHASE DIMMING)
"c" - INDICATES SWITCH SHALL CONTROL LIGHT
MULTI POLE SWITCH
"X" - INDICATES NUMBER OF POLE
CONDUIT, EXPOSED/SURFACE MOUNTED
CONDUIT, EXPOSED/SURFACE MOUNTED, TURNING UP
CONDUIT, EXPOSED/SURFACE MOUNTED, TURNING DOWN
MANUAL MOTOR STARTER /DISCONNECT
FIXTURES WITH "c" DESIGNATION
EMERGENCY BATTERY PACK LIGHT FIXTURE
"A" - FIXTURE TYPE
"X" - FIXTURE TYPE
WALL MOUNTED EXIT SIGN
ARROW INDICATES DIRECTION OF EGRESS
CONDUIT OR DUCTBANK, CONCEALED
FLEXIBLE METAL CONDUIT
LA-1,3
4 WAY SWITCH
DUPLEX RECEPTACLE, 20A, 120V, 2P, 3W
"C" - MOUNTED 6" ABOVE COUNTERTOP
"WP" - WEATHERPROOF
FLOOR MOUNTED RECEPTACLE
SIMPLEX RECEPTACLE, GROUNDED TYPE
QUADPLEX RECEPTACLE
PULL BOX
PHOTOCELL
DENOTES A QUANTITY OF TWO (2) 3-INCH CONDUITS
AND ONE NO.2 AWG GROUND CONDUCTOR
EACH CONTAINING THREE NO. 3/0 AWG CONDUCTORS(2) 3 #3/0,
#2G., 3"C.
"GFI" OR "GF" - GROUND FAULT INTERRUPTER TYPE
HEAT TRACE
HOMERUN, CIRCUITS 1 AND 3 RUN TO PANEL LA
2 #12, #12G., 3/4"C. UNLESS NOTED OTHERWISE
X
A
NON FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
POWER POLE
CEILING MOUNTED DUPLEX RECEPTACLE
CEILING MOUNTED QUADPLEX RECEPTACLE
4 #14, #14G., 3/4"C.
(2 #14 SPARE)
J
DESCRIPTIONPLAN SYMBOL
SINGLE POLE SWITCH
PP
b A
PW
M
MH
PC
PB
X
Xc
M
DIM
TM
OVERHEAD SECONDARY LINE
UNDERGROUND PRIMARY LINE
OVERHEAD PRIMARY LINE
UNDERGROUND ELECTRIC LINE
OVERHEAD ELECTRIC LINE
UNDERGROUND SECONDARY LINE
UNDERGROUND COMMUNICATION LINE
OVERHEAD COMMUNICATION LINE
OVERHEAD FIBER OPTIC LINE
UNDERGROUND FIBER OPTIC LINEUGFO
OHFO
UGC
OHC
UGS
OHS
UGP
OHP
UGE
OHE
COMBINATION TELEPHONE/DATA
TELEPHONE
DATA
FLOOR MOUNTED DATA OUTLET
FLOOR MOUNTED TELEPHONE OUTLET
POKE-THRU DEVICE - COMBINATION POWER/DATA/VOICE OUTLET
FLOOR COMBINATION POWER/DATA/VOICE OUTLET
SECURITY CAMERA
JUNCTION BOX - WALL MOUNTEDJ
GROUND ROD TEST WELL
GROUND RODG
SPECIAL RECEPTACLE
nPP16 D SA
POWER/RELAY PACK: 16A DIMMING
PR
T H
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
EG-001
L E
G E
N D
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
M A
R K
D E
S C
R
IP
T
IO
N D
A
IS
D
O C
U M
E N
T I
S R
E
LE
A S
E D
F O
R T
R P
O S
E O
F I
N T
E R
IM
R
E V
IE
W
U N
D E
R T
T H
O R
IT
Y
O F
T E
X A
S N
D
A T
E
IT
I
S N
O T
T O
B E
U S
E D
F O
R C
O N
S T
R U
C T
IO
N
B
ID
D
IN
G O
R P
E R
M
IT
P U
R P
O S
E S
N O
T F
O R
C O
N S
T R
U C
T
IO
N
US Army Corps of Engineers ®
SHEET ID
U .S
A
R M
Y E
N G
IN
E
E R
D
IS
T R
IC
T
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I 'D
F
IL
E
N A
M E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
F
IL
E N
U M
B E
R
1 2 3 4 5
D
C
B
A
S a v o y D ri v e S u it e
H o u s to n T e x a s
-2
-8
F re e se a n d N ic h o ls
In c.
T e xa s
R e g is te re d E n g in e e ri n g
F ir m F
-2
C J R
C J R
V R
B
/5
/2
V
IS
H A
L R
B
H A
N P
.E
C O
R P
S O
F E
N G
IN
E
E R
S F
O R
T W
O R
T H
T
E X
A S
EG-002
G E
N E
R A
L N
O T
E S
/5
/2
95% DESIGN SUBMITTAL
F O
R T
H O
O D
T
E X
A S
D E
S
IG
N O
F T
E M
F R
E N
O V
A T
IO
N
S B
L D
G
GENERAL NOTES - LIGHTING PLANS:
1. CONTRACTOR SHALL PROVIDE ALL CONDUITS, CABLE, JUNCTION BOXES,
AND ASSOCIATED HARDWARE FOR A COMPLETE AND OPERATIONAL
SYSTEM.
2. ALL LIGHTING CIRCUITRY SHALL BE 2 #12, #12G., 3/4"C. UNLESS NOTED
OTHERWISE, FOR LIGHTING CIRCUITS GREATER THAN 100'-0" PROVIDE 2
#10, #10G., 3/4"C. FOR LIGHTING CIRCUITS GREATER THAN 250'-0"
PROVIDE 2 #8, #8G., 3/4"C. PROVIDE ALL CONDUCTORS AND CONDUIT AS
REQUIRED FOR A COMPLETE AND OPERATIONAL SYSTEM.
3. CONDUIT SHALL NOT BE ROUTED ON THE OUTSIDE OF THE BUILDING FOR
EXTERIOR LIGHTS.
4. ALL EXPOSED CONDUIT AND ASSOCIATED MOUNTING HARDWARE SHALL
BE PAINTED TO MATCH THE SURFACE IT IS ATTACHED TO. FIELD VERIFY
ALL REQUIREMENTS.
5. PROVIDE CONCEALED INSTALLATION OF CONDUIT IN SLAB AND WALL.
6. PROVIDE IDENTIFICATION LABELS FOR ANY REMOTE SWITCHES,
DISCONNECTS, JUNCTION BOXES MOUNTED ON THE CEILING.
7. ALL WORK SHALL COMPLY WITH APPLICABLE NATIONAL, STATE AND
LOCAL CODES, RULES AND REGULATIONS.
8. ALL WORK SHALL COMPLY WITH THE BUILDING OWNER’S
CONSTRUCTION GUIDELINES.
9. THE CONTRACTOR SHALL PROVIDE AND ADJUST OCCUPANCY SENSORS IN
ALL AREAS TO COORDINATE WITH ROOM CIRCULATION PATTERNS AND
COVERAGE OF THE OCCUPANCY SENSOR. ADJUST ALL TIMED EVENTS
(FOR EXAMPLE, 'OFF' DELAY) WHEN ROOM IS UNOCCUPIED TO
COORDINATE WITH OWNERS' REQUIREMENTS.
10. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL OCCUPANCY
SENSORS/POWER PACKS AND ASSOCIATED POWER AND CONTROLS
CABLING FOR A COMPLETE AND OPERATIONAL SYSTEM. INSTALL ALL
DEVICES, BACKBOXES, CONDUIT, AND ACCESSORIES IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS.
11. THE OCCUPANCY SENSORS SHOWN ON THE PLANS IS CONCEPTUAL AND
IS NOT INTENDED TO INDICATE THE NUMBER OF OCCUPANCY SENSORS
REQUIRED FOR COMPLETE COVERAGE IN AN AREA. THE CONTRACTOR
SHALL SUBMIT A PLAN SHOWING OCCUPANCY SENSOR LOCATIONS AND
COVERAGE, POWER PACKS, ETC. AS AN OFFICIAL SUBMITTAL TO THE
ENGINEER FOR APPROVAL.
12. ALL CONTROL DEVICES SUCH AS BRIDGE PORT, POWER PACK, WALLPOD,
RELAY PANEL, ETC. SHALL BE POWERED FROM THE NEAREST LIGHTING
CIRCUIT FOR 120V AND FROM THE NEAREST RECEPTACLE CIRCUIT FOR
120V INPUT SERVICE. PROVIDE NECESSARY 2 #12, 12G., 3/4"C .FOR A
COMPLETE AND OPERATIONAL SYSTEM.
13. ALL CAT5E RUNNING BELOW THE CEILING FOR LIGHT SWITCHING SHALL
BE IN 3/4"C. AND SHALL NOT BE RUN EXPOSED.
14. ALL LIGHTING CONTROLS ARE ACUITY CONTROLS OR APPROVED EQUAL.
15. AT LOCATIONS WHERE ROOM LIGHT FIXTURES ARE CONTROLLED
THROUGH THE USE OF OCCUPANCY SENSORS, PROVIDE THE NUMBER OF
SENSORS AND LOCATE THE UNITS AS REQUIRED FOR COMPLETE ROOM
COVERAGE. WHERE MORE THAN ONE SENSOR IS LOCATED IN A
COMMON SPACE, CONNECT THE UNITS SUCH THAT DETECTION OF
OCCUPANCY FROM EITHER UNIT…