W90WL521Q0010 Pre-Award Q&A G-32 Weather Cover
1. Provide type, gauge, size of steel girder, beam and post:
Government Response: The structure is to be designed by the building manufacture. That includes all member sizes and connections. Building must meet UFC 3-301-01, local and national building codes.
2. Provide color of roof (different colors have different cost and availability), type of SSMR?
Government Response: Color of the roof shall be white or galvalume.
3. Provide type of connection (welding and type or nuts/bolts and size) location connection:
Government Response: The structure is to be designed by the building manufacture. That includes all member sizes and connections. Connections can be welded or bolted. Building must meet UFC 3-301-01, local and national building codes.
4. Provide type, size, gauge of base/connection plates:
Government Response: The structure is to be designed by the building manufacture. That includes all member sizes and connections. Building must meet UFC 3-301-01, local and national building codes.
5. Provide type of epoxy:
Government Response: The structure is to be designed by the building manufacture. That includes all member sizes and connections. Building must meet UFC 3-301-01, local and national building codes.
6. Hot work permit required?
Government Response: Hot work permits are a requirement on TEAD. Hot work permits can be issued if needed.
7. How tall is the Lightning protection system:
Government Response: The height measured is approximately 60 feet.