SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

R-11SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

O & M

HOUSING DIV.

REVIEWED BY

UNITED STATES ARMY GARRISON DAEGU

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

DIRECTORATE OF PUBLIC WORK

HGFEDCBA

D - 22 - 07

CHON, HYON TAE

DESIGN REVIEW SIGNATURE

ORGANIZATION

USING AGENCY

36TH SIGNAL

MASTER PLN.

ENVIRONMENTAL

NAME SIGNATURE

O&M DIV.

FIRE DEPT.

SAFETY OFFICE

DPTMS(AT/FP)

188TH MP COM.

IND. HYGENIST

HA-00529-3J

UNIT #15746, APO AP 96218-5746

DRAWING NO.

CHIEF,

DESIGN & TECH. REVIEW Br.

YI, TONG KI

AS SHOWN

1 1 OF 1R - 1

T I T L E S H E E T

TITLE SHEET

DATE: 07 MAR 22

M - 12

M - 23

M - 34

M - 67

M - 78

M - 45

M - 56

MECHANICAL

BLDG. NO. S-821

REPLACE A/C AND HEATING SYSTEM,

BLDG. NO. S-821

REPLACE A/C AND HEATING SYSTEM,

CAMP CARROLL

PROJECT NO. HA-00529-3J, CAMP CARROLL

M - 89

M - 910

M - 1011

M - 1112

M - 1314

M - 1213

E - 418

E - 317

E - 216

E - 115

MECHANICAL

LEGEND, NOTES AND SCOPE OF WORK

LEGEND AND ABBREVIATIONS

EQUIPMENT SCHEDULE

GENERAL NOTES AND SCOPE OF WORK

NEW HVAC DUCT PLAN

NEW HVAC AND PLUMBING PIPING PLAN

NEW MECH. ROOM PARTIAL PLAN

AHU SCHEMATIC CONTROL DIAGRAM

DETAIL DRAWINGS - 1

DETAIL DRAWINGS - 2

DETAIL DRAWINGS - 3

HVAC POWER PLAN

PANEL BOARD DIAGRAM

REMOVAL / EXISTING HVAC AND PLUMBING PLAN

NEW MECH. ROOM PIPING ISOMETRIC DIAGRAM

H & V SYSTEM AND HOT WATER HEATING SYSTEM SCHEMATIC AND CONTROL DIAGRAM

POWER SINGLE LINE DIAGRAM, MECH. ROOM POWER PARTIAL PLAN AND DETAIL OF ARC FLASH LABELS

SCH

SA

SAN

QTY

R12, R22

RA

RDTR

RPM

RT

PG

PH

POC

POL

PPM

PRV

QT

OA

OAIL

OD

OS&Y

Pa

NTS

BUTTERFLY

CUBIC METER PER HOUR

AIR CONDITION (-ING,-ED)

AIR CONDITION UNIT (S)

AIR COOLED CONDENSING UNIT

CHILLED/HOT WATER RETURN

CHILLED/HOT WATER SUPPLY

REFRIGERANT LIQUID

CAP CAPACITY

CUBIC METER

COMPRESSOR

CONTINUE

CONNECTION

CPRSR

CU M

CONT

CONN

COUNTER CLOCKWISE

COEFFICIENT

CIRCUIT

CAST IRON PIPE

CHILLED WATER

CKT

CMH

COEF

CHW

CCW

CIP

ALARM CHECK VALVEACV

AVG AVERAGE

BAROMETER(-TRIC)

CENTIGRADEC

BARO

AMPERE(AMP, AMPS)

ALUMINUM

APPROX

AMP

AIR COND

AHU

AL

AIR COOLED

ACU

ACLD

ACCU

CHWS

CHWR

CHR

CHS

D

RL

DRAIN

KILOCALORIE PER HOUR

KILOGRAM PER SQ. CENTIMETER

KILOGRAM

THERMAL CONDUCTIVITY

IRON PIPE SIZE

ISOMETRIC

DIAMETER, INSIDE

FACE AREA OR FRESH AIR

EXTERNAL STATIC PRESSURE

EVAPORAT (-E,-ING,-ED,-OR)

ENTERING WATER TEMP

FIRE HOSE CABINET

EXPLOSION PROOF

FHC

FA

ESP

EVAP

EWT

EFF

ENT

EQPT

EP

EFFICIENCY

ENTERING

EQUIPMENT

KG

K

IPS

ISO

ID

NIC

N.O.

NO

MPS

N.C.

N/A

MM

MPH

MIN

MAX

NOT IN CONTRACT

NORMALLY OPEN

NUMBER

NORMALLY CLOSED

METERS PER SECOND

METERS PER HOUR

MINIMUM OR MINUTE

NOT APPLICABLE

MILLIMETER

MAXIMUM

HERTZ

HOSE BIBB

HEAD

HORSEPOWER

HOUR(S)

HOT WATER

HOT WATER HEATER

HORIZONTAL

FIBERGLASS REINFORCED PLASTIC

FREQUENCY

FLUSH VALVE

FEED WATER PUMP

FIXTURE

GAGE OR GAUGE

GALVANIZED STEEL

FUEL OIL

FEMALE PIPE THREAD

CIRCULATING WATER PUMPCWP

FRP

DECIBEL OR DRY BULB

DRY BULB TEMPERATURE

ENTERING AIR TEMPERATURE

DRY PIPE VALVE

DIRECT EXPANSION

DO DIESEL OIL

EAT

DPV

DX

DIV

DIAG

DIFF

DB

DBT

DIVISION

DIAMETER

DIAGRAM

DIFFERENCE

DEGREE

HR

HZ

HW

HWH

HORIZ

HB

HD

HP

GA

GALVS

FV

FWP

FXTR

CLOCKWISE OR COLD WATERCW

PLUG VALVE

THREE WAY

FREQ

FO

FPT

GATE, GLOBE

GATE, ANGLE

GLOBE

CONTROL

GATE

M

LPS

LWT

LT

LPH

LPD

LL

LG

LBS

LAT

LAV

L

KWH

KW

LITERS PER SECOND

LITERS PER HOUR

LEAVING WATER TEMPERATURE

METERS

LAUNDRY TRAY

LITERS PER DAY

LIQUID LINE

LEAVING AIR TEMPERATURE

POUNDS

LAVATORY

LENGTH

KILOWATT HOUR

KILOWATT

LITERS

P

STRAINER, BLOW OFF

STRAINER

PUMP (INDICATE USE)

KG/ SM KILOGRAM PER SQ. METER

REFRIGERANT SUCTION

REFRIGERANT DISCHARGE

PIPE TO BE REMOVED

MEDIUM TEMPERATURE HOT WATER RETURN

MEDIUM TEMPERATURE HOT WATER SUPPLY

CONDENSER WATER RETURN

CONDENSER WATER SUPPLY

RS

RD

(NAME)

(NAME)E EXISTING PIPE

HWR

HWS

MTWR

MTWS

CR

CS

PIPING

SANITARY DRAIN

CHECK, SWING

PIPE SLEEVE WITH FIRE STOPPING

VENT THRU ROOF

BFP

PLAN

HOSE BIBB

BALL

ELEV.

PIPE SLEEVE

BACKFLOW PREVENTER

FLOOR DRAIN

FLOOR CLEANOUT

FD

FCO

FLEXIBLE CONNECTOR

ANCHOR, INTERMEDIATE

ANCHOR, MAIN

EXPANSION JOINT

EXPANSION LOOP

EJ

RELIEF

SAFETY

HOSE END DRAIN

LOCK SHIELD

NEEDLE

PRESSURE REDUCING

CONTROL, PNEUMATIC-ELECTRIC

CONTROL, ELECTRIC-PNEUMATIC

CHECK, NON-SLAM

S

R

EP

PE

COLD WATER

VENT

AD FD

QUANTITY

TEMPERATURE DIFFERENCE

TONS OF REFRIGERATION

SCHEDULE

SUPPLY AIR

SANITARY

REFRIGERANT (12, 22, ETC)

RETURN AIR

REVOLUTIONS PER MINUTE

REFRIGERATION TON

RADIATOR

TYP TYPICAL

UNIT HEATER

URINAL

UH

UR

SYMBOL

TEMPERATURE

THICKNESS

TONS

THK

TEMP

SYM

TD

OUTSIDE AIR INTAKE LOUVER

PRESSURE REDUCING VALVE

PHASE (ELECTRIC)

PETROLEUM, OIL AND LUBRICANTS

POINT OF CONNECTION

PARTS PER MILLION

PERCENT/

QUART

PRESSURE GAGE

DIAMETER, OUTSIDE

OUTSIDE SCREW & YOKE

PASCAL

POLE

SPR SPRINKLER

STAINLESS STEEL

SQUARE

STEAM

STANDARD

STEEL

ST

STD

STL

SQ

SST

SPECIFICATION

SQUARE METER

STATIC PRESSURE

SPEC

SP

SM

OUTSIDE AIR

NOT TO SCALE

SECONDSEC

VAV VARIABLE AIR VOLUME

WATER CLOSET

VENTILATION

W/

WT

WC

WD

WITH

WEIGHT

WIDTH

W

WB

VOL

VEL

VENT

VERT

WATT

WET BULB

VOLUME

VELOCITY

VERTICAL

SMOKE DAMPER (PROVIDE ACCESS DOOR)

MANUAL VOLUME DAMPER

VAC

V

VACUUM

VOLT

SPLITTER DAMPER

AD

SD

VD

TEE, SINGLE SWEEP

TEE, OUTLET DOWN

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

ELBOW, TURNED DOWN

UNION, FLANGED

UNION, SCREWED

TEE, OUTLET UP

TEE

LATERAL

ELBOW, TURNED UP

CONNECTION, TOP

CONNECTION, BOTTOM

BUSHING

CAP

FIRE DAMPER (PROVIDE ACCESS DOOR)

BDD

TURNING VANES

TRANSITION

FLEXIBLE CONNECTION

FLEXIBLE DUCT

FC

DUCT WORK

A B B R E V I A T I O N S

L E G E N D

PG

TM

AAV

FOS

3-WAY VALVE (MOTORIZED)

PRESSURE GAUGE

THERMOMETER

AUTOMATIC AIR VENT

GATE VALVE

CHECK VALVE

FUEL OIL SUPPLY

FLEXIBLE JOINTFJ

& STRAINER

M

CS

SD

SHOWER DRAIN

DEG

DIA or o

CEAT CONDENSER ENTERING AIR TEMP

LCWT LEAVING CHILLED WATER TEMP

FAIL FRESH AIR INTAKE LOUVER

EXPANSION JOINTEXPJT

EXST EXISTING

A / C AIR CONDITIONING

APPROXIMATELY

ARCH ARCHITECTURAL

BLDG BUILDING

CONC CONCRETE

DWG DRAWING

EA EACH

F.C.U. FAN COIL UNIT

MECH MECHANICAL

KCAL/ HR

KG/ SQ CM

HOT WATER SUPPLY

HOT WATER RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

V

DOMESTIC HOT WATER SUPPLY

DOMESTIC HOT WATER RETURN

AAV

ED EXHAUST DUCT

AUTOMATIC AIR VENT

AIR HANDLING UNIT

GROUND LEVELGL

REGISTER, SIDEWALL

SUPPLY AIR GRILLE OR

REGISTER, CEILING

SUPPLY AIR GRILLE OR

(200mm NECK DIAMETER)

CEILING DIFFUSER, ROUND TYPE

REGISTER, CEILING

EXHAUST AIR GRILLE OR

GRILLES, REGISTERS AND DIFFUSERS

SQUARE TYPE

CEILING DIFFUSER,

EG

ER

SG

SR

SG

SR

RG

RR

CD

200mm NCD

COWL, (GOOSENECK) AND FLASHING

(810mm WIDTH x 400mm DEPTH)

DUCT SIZES SHOWN810mm x 400mm

M

ELECTRIC MOTOR OPERATED DAMPER

S

MOTORIZED DAMPER

MD

SUPPLY AIR DUCT RISER

RETURN OR EXHAUST AIR DUCT RISER

SUPPLY AIR DUCT SECTION

RETURN AIR DUCT SECTION

GATE, GLOBE OR BALL VALVE

CHECK VALVE (FLOW)

ANGLE VALVE

STRAINER

DRIP CHECK VALVE

RESTRICTED ORIFICE

FILL CUP

PRESSURE GAUGE

SOLENOID VALVE

ECCENTRIC REDUCER

CONCENTRIC REDUCER

FLEXIBLE PIPE CONNECTION

RELAY

HOSE VALVE

TEST HEADER

SMOKE DAMPER

R

SD

S

: WATER MOTER ALARM GONG

SPRINKLER SYSTEM

: UP-RIGHT TYPE SPRINKLER

: PENDENT TYPE SPRINKLER

: SIDE WALL TYPE SPRINKLER

REMOVAL WORK

RELOCATED WORK

SUPPLY AIR DUCT

RETURN AIR DUCT

EXHAUST AIR DUCT

SA

RA

EA

VALVES, SPECIAL DUTY

HEATING

AIR CONDITIONING & REFRIGERATION

PLUMBING

VALVES : (for selective actuators)

BACK DRAFT DAMPER

CIRCUIT SETTER

POINT OF CONNECTIONPOC

POR POINT OF REMOVAL

TcH THERMOSTAT HEATING/COOLING

THERMOSTAT OF HEATING

REGISTER, CEILING

RETURN AIR GRILLE OR

Th

REDUCER, CONCENTRIC

M-1

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

1 17

DAMPERS

LEGEND AND ABBREVIATIONS

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

BLDG. NO. S-821

REPLACE A/C AND HEATING SYSTEM,

M-2

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

2 17

EQUIPMENT SCHEDULE

CAMP CARROLL

NAM, TAE CHIN

07 MAR 22

HA-00529-3J

(BTU/H)

CAPACITY

FILTER OUTSIDE AIRDX - HEATING COIL

CFM

PERCENT

20133,000

NECESSARY ACCESSORIES.

WITH DRAIN PAN, DIRECT EXPANSION REFRIGERANT COILS, PRE-FILTER AND

HORIZ. DISCHARGE, SINGLE ZONE, BELT DRIVEN, CENTRIFUGAL FAN EQUIPPED

FLOOR MOUNTED, DOUBLE WALLED CONSTRUCTION, HORIZONTAL TYPE, VERT. /

(BTU/H)

CAPACITY

166,510

SUPPLY FAN

CFM

MOTOR

HP POWER SUPPLY

DX - COOLING COIL

(SM)

FACE AREA

3,472

(mmAq)

T.S.P

50 3 460 V, 60 HZ, 3 PH

ROW

0.6356

MERV-8

PRE

DX - COOLING COIL

AIR HANDLING UNIT

HEATING & VENTILATING UNIT

CFM

MOTOR

KW POWER SUPPLY(mmAq)

T.S.P

16 460 V, 60 HZ, 3 PH

DEHUMIDIFIER

FAN CAPACITY

(BTU/H)

COOLING

(BTU/H)

HEATING

(KW)

REHEAT

214,289 81,906 241.5 x 2

CFM

MOTOR

KW POWER SUPPLY(mmAq)

T.S.P

16 460 V, 60 HZ, 3 PH

FAN CAPACITY

(BTU/H)

COOLING

(BTU/H)

HEATING

(KW)

REHEAT

160,717 68,255

1.1 x 2

5,650

7,416

SIMILAR TO "ACE R&A." MODEL NO. CRAC-150AU OR APPROVED EQUAL

SIMILAR TO "ACE R&A." MODEL NO. CRAC-200AU OR APPROVED EQUAL

SIMILAR TO "LG ELECTRONICS." MODEL NO. BAE0098HFA0 OR APPROVED EQUAL

(CFM)

FAN CAP.

(BTUH)

HEATING CAP.

(BTUH)

COOLING CAP.

(A)

MOP

(A)

MCA RATED AMPS (A)

COMP. BCOMP. A

POWER SUPPLY: 460V, 60HZ, 3PH

SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUM216DTE5 OR APPROVED EQUAL

13.915.5

38.35011,300243,000216,000

5.0

FAN

34.4

DISTRIBUTING OPERATION SYSTEM. AHRI CERTIFIED.

REFRIGERANT LIQUID, FOUR SEASONAL HERMETIC SAFETY COVER, MULTI

PROPELLER TYPE BLOW-THRU OUTDOOR FAN, ACCUMULATOR, R410A

BRIDGE CIRCUIT AIR-COOLED COIL WITH CORROSION RESISTANT COATING,

TYPE COMPRESSOR WITH MULTI POWER SYSTEM, SUB COOL INTERCHANGER

DIGITAL CONTROLLED INVERTER COMPRESSOR AND CONSTANT VELOCITY

CONDENSING UNIT SYSTEM FOR ABOVE-GROUND INSTALLATION. BUILT IN

OUTDOOR MOUNTED SEASONAL HEATING AND COOLING MULTI OUTDOOR

OUTDOOR HEAT PUMP UNIT

8 1

(CFM)

FAN CAP.

(BTUH)

HEATING CAP.

(BTUH)

COOLING CAP.

(A)

MOP

(A)

MCA RATED AMPS (A)

COMP. BCOMP. A

POWER SUPPLY: 460V, 60HZ, 3PH 9.211.4

28.53511,300189,000168,000

5.0

FAN

25.6

SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUM168DTE5 OR APPROVED EQUAL

7 1

(CFM)

FAN CAP.

(BTUH)

HEATING CAP.

(BTUH)

COOLING CAP.

(A)

MOP

(A)

MCA RATED AMPS (A)

COMP. BCOMP. A

POWER SUPPLY: 460V, 60HZ, 3PH

SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUM192DTE5 OR APPROVED EQUAL

12.214.8

35.75011,300216,000192,000

5.0

FAN

32.0

HOT WATER HEATING BOILER

(CMH)

INPUT

GAS

9 1

(CFM)

FAN CAP.

(BTUH)

HEATING CAP.

(BTUH)

COOLING CAP.

(A)

MOP

(A)

MCA RATED AMPS (A)

COMP. BCOMP. A

POWER SUPPLY: 208V, 60HZ, 1PH 19.5

403,885

1.0

FAN

20.5

SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUN038GSS4 OR APPROVED EQUAL

38,000 42,000 25

(CFM)

FAN CAP.

(BTUH)

HEATING CAP.

(BTUH)

COOLING CAP.

POWER SUPPLY

(W)

POWER INPUT

208V, 60HZ, 1PH

SIMILAR TO "LG ELECTRONICS." MODEL NO. ARNU183SKA4 OR APPROVED EQUAL

19,100 39.5

21,500 424

INDOOR HEAT PUMP UNIT (WALL MOUNTED TYPE)

SYSTEM.

INDOOR WALL MOUNTED TYPE UNIT FOR HEATING AND COOLING INVERTER

(CFM)

FAN CAP.

(BTUH)

HEATING CAP.

(BTUH)

COOLING CAP.

POWER SUPPLY

(W)

POWER INPUT

208V, 60HZ, 1PH15,400

17,100 318 21

12 1

HP VOLT/PH/HZ

460 V, 3 PH, 60 HZ

CAPACITY

MOTOR

RPM

1,750

SIMILAR TO "LG ELECTRONICS." MODEL NO. BAB0207HFA0 OR APPROVED EQUAL

260 GPM AT 66 FT THD

HOT WATER CIRCULATING PUMP

UNIT HEATER

THERMOSTAT, UL LISTED.

EXPLOSION PROOF FAN MOTOR, HOT WATER COIL FACE LOUVER AND

CEILING HUNG, HORIZONTAL DISCHARGE, HEAVY GAUGE STEEL ENCLOSURE,

1/20

(BTUH)

HEATING CAP.

(GPM)

WATER FLOW

( C)

EWT

( C)

EAT

( C)

LWT FAN CAP.

CFM RPM HP

115V, 60HZ, 1PH

82 32

(BTUH)

HEATING CAP.

(GPM)

WATER FLOW

( C)

EWT

( C)

EAT

( C)

LWT FAN CAP.

CFM RPM

115V, 60HZ, 1PH

82 32

27,397

14,297

2.7

1.45

1,550

1,550 1/20

HP

POWER SUPPLY

(CFM)

CAPACITY

(HP)

FAN MOTOR

460 V, 60 HZ, 3 PH

VIBRATION ISOLATORS AND STANDARD ACCESSORIES.

DUCT MOUNTED, IN-LINE CENTRIFUGAL FAN, CORROSION RESISTANT, EQUIPPED W/

IN-LINE DUCT FAN

POWER SUPPLY

(CFM)

CAPACITY

(HP)

FAN MOTOR

ROOF EXHAUST FAN

277 V, 60 HZ, 1 PH1,000 AT 0.26 SP (Inches wg) 1/ 4

17 1

115 V, 60 HZ, 1 PH1/ 22,100 AT 0.26 SP (Inches wg)

277 V, 60 HZ, 1 PH1/ 418 3

W/ DISCONNECT SWITCH, BIRD SCREEN, BACKDRAFT DAMPER.

ROOF CURB MOUNTED, CENTRIFUGAL TYPE WEATHER-PROOF ALUMINUM HOSING

D E S C R I P T I O NQ’ TY

NO.

ITEM

D E S C R I P T I O NQ’ TY

NO.

ITEM

D E S C R I P T I O NQ’ TY

NO.

ITEM

D E S C R I P T I O NQ’ TY

NO.

ITEM

E Q U I P M E N T S C H E D U L E

700 AT 0.26 SP (Inches wg)

PIPE TAPPING.

PRESSURE, EQUIPPED W/ HEAVY DUTY REMOVABLE BLADDER AND NECESSARY

AND PRESSURE VESSEL CODE (ASME BPVC SEC VIII D1), MAX. 125 PSI WORKING

CLOSED ROUND DIAPHRAGM TYPE, SHELL CONFORMING TO ASME CODE

(GAL)

TANK CAP. (ACCEPTANCE VOLUME)

(DIA x LG)

TANK SIZE

15" x 25"

HOT WATER EXPANSION TANK

AIR SEPARATOR

GALVANIZED STEEL STRAINER, BLOWDOWN AND COLD WATER CONNECTION.

CONNECTION CONSIST OF STAINLESS STEEL AIR COLLECTOR TUBE,

PIPE MOUNTED, ASME CODE AND STAMPED FOR 125 PSI @ 350 F, THREADED

(PSI)

WORKING PRESSUREPIPE SIZE (MM)

INLET OUTLET

80 125

ELEC. POWER

DOMESTIC HOT WATER HEATER

1729111.6

(LPH)

RECOVERY

HEAT

FLA: 2, 120 V, 1 PH, 60 HZ 60 C 16.7 C

(KW)

OUTPUT

GROSS

ELEC. POWER

TEMP.

SUPPLY

RISE

TEMP.

DOMESTIC WATER EXPANSION TANK

ACROSS-THE-LINE MAGNETIC CONTROLLER IN A NEMA 250 AND NEMA MG 1.

ALL BRONZE CONSTRUCTION. MOTORS SHALL BE EQUIPPED WITH AN

IN-LINE CLOSED COUPLED CENTRIFUGAL TYPE, FLANGE CONNECTION AND

(GAL)

TANK CAP. (ACCEPTANCE VOLUME)

(DIA x LG)

TANK SIZE

12" x 18"6

PROVIDE W/ ELECTRIC EXPANSION VALVE, REHEAT COIL

SPLIT SYSTEM DEHUMIDIFIER, AIR COOLED, FLOOR STANDING, UP FLOW TYPE.

(BTU/H)

CAPACITY

355,994

SUPPLY FAN

CFM

MOTOR

HP POWER SUPPLY

7,304

(mmAq)

T.S.P

5 460 V, 60 HZ, 3 PH 1.2614

HEATING COIL

HEATING COIL

2,530 AT 0.5" SP (Inches wg)

(C )

EWT

SIMILAR TO "LG ELECTRONICS." MODEL NO. ARNU153SJA4 OR APPROVED EQUAL

(MBH)

OUTPUT

GROSS

728 FLA: 16, 120 V, 1 PH, 60 HZ 80

( C)

TEMP.

SUPPLY

(PSI)

PRESS

MAX.

ACCESSORIES.

WITH DRAIN PAN, HOT WATER HEATING COIL, PRE-FILTER AND NECESSARY

HORIZ. DISCHARGE, SINGLE ZONE, BELT DRIVEN, CENTRIFUGAL FAN EQUIPPED

FLOOR MOUNTED, DOUBLE WALLED CONSTRUCTION, HORIZONTAL TYPE, VERT. /

(SM)

FACE AREA

ROW

82.2

MERV-8

PRE

FILTER

PERCENT

CFM

OUTSIDE AIR

7,304 100-9.5

(C )

EAT

15.6

(C )

LAT

ACCESSORIES. ASME, AHRI AND CSA CERTIFIED PRODUCT.

CASCADE SYSTEM, MODULE TYPE CONDENSING WATER HEATER WITH STANDARD

ACCESSORIES. ASME, AHRI AND CSA CERTIFIED PRODUCT.

CASCADE SYSTEM, MODULE TYPE CONDENSING WATER BOILER WITH STANDARD

GENERAL NOTES

DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR AREA.

4. ALL WALL / FLOOR / ROOF OPENINGS RESULTING FROM THE REMOVAL OF PIPING AND

AS DIRECTED BY THE CONTRACTING OFFICER.

EXISTING AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS

5. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO

CEILING, ROOF, EQUIPMENT, PIPE, DUCT AND ELECTRICAL ITEMS.

PREVENTION SYSTEM WITH NO ADDITIONAL COST TO THE GOVERNMENT SUCH AS WALLS,

ITEMS TO MAKE WAY FOR THE INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE

18. THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND REINSTALL THE OBSTRUCTED

SPECIFICATIONS.

CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE CONTRACT

OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH MAY DEVIATE FROM THAT SHOWN ON

SYSTEM TO SATISFY ALL FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS

17. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL

9. ANY PIPES THAT PENETRATE FIRE RATED WALLS (EXISTING/ NEW) SHALL BE SEALED PER SPEC.

TO ENSURE PROPER OPERATION, AS ORIGINALLY INTENDED.

EQUIPMENT. THE CONTRACTOR SHALL TEST, ADJUST AND BALANCE EQUIPMENT AS REQUIRED

14. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY START-UP AND TESTING OF THE NEW

AND SHALL BE VERIFIED AT THE JOB SITE.

2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC, ARE APPROXIMATE

PRIOR TO COMMENCING CONSTRUCTION FOR APPROVAL.

ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER

FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR

3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY TO THE

CONTRACTING OFFICER’S APPROVAL.

REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR

IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER’S

PRIOR TO COMMENCING ANY CONSTRUCTION OR REPAIR.

EQUIPMENT, DUCTWORK, PIPING, DIMENSIONS AND ETC. UNDER THE SUPERVISION OF C.O.R

1. THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION,

A SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.

10. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWING.

THE REQUIREMENTS OF SEAL CLASS C.

TO SMACNA STATIC PRESSURE CONSTRUCTION CLASS 500PA AND DUCTWORK SHALL MEET

7. THE SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING

START OF CONSTRUCTION.

PLAN SHALL BE SUBMITTED TO AND APPROVED BY DPW AND THE USER, PRIOR TO THE

USER TO FULLY UTILIZE THE FACILITY DURING THE CONSTRUCTION PERIOD. THIS PHASING

SHALL PROVIDE A PHASING PLAN FOR CONSTRUCTION COMPLETION ALLOWING FOR THE

FACILITY BE FULLY OPERATIONAL DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR

19. DUE TO THE CRITICAL NATURE OF THE FACILITY FUNCTION, IF IT IS REQUIRED THAT THE

CONTRACTOR.

THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY THIS

THE EXISTING EQUIPMENT, NEW EQUIPMENT, DUCT WORK, PIPING AND ETC. DAMAGES DUE TO

11. CONNECTIONS TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE

FOR APPROVAL.

DESIGN & TECHNICAL REVIEW BRANCH VIA C.O.R. PRIOR TO COMMENCING CONSTRUCTION

12. THE CONTRACTOR SHALL SUBMIT MANUFACTURER’S INSTALLATION SHOP DRAWINGS TO THE

SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)".

15. ALL EQUIPMENT AND MATERIALS SHALL MEET THE REQUIREMENTS OF "STANDARD TECHNICAL

ADDITIONAL COST TO THE PROJECT CONTRACT.

THE DETAILS WILL BE UTILIZED TO ACCOMPLISH THE MECHANICAL SCOPE OF WORK AT NO

O & MA PROJECTS, KOREA (NOVEMBER 30, 2015)" FORM AS A PART OF THIS PROJECT.

16. THE MECHANICAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL DRAWINGS FOR

REVIEW BRANCH FOR APPROVAL BEFORE COMMENCING THE WORK.

13. THE CONTRACTOR SHALL SUBMIT ALL MATERIAL INFORMATION TO THE DESIGN & TECHNICAL

SUCH AS ANCHORS, HANGERS, SUPPORTS, ETC.

8. ALL PIPES, DRAINS AND DUCTWORK TO BE REMOVED SHALL INCLUDE ALL ITS ACCESSORIES

AS ORIGINALLY INTENDED.

AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT CONNECTION TO FUNCTION

ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION, REMOVE THE EXISTING DUCTWORK

& LOCATION PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING. IF THE EXISTING DUCT

6. THE CONTRACTOR SHALL COORDINATE WITH THE EXISTING DUCTWORK AND PIPING ELEVATION

CONSTRUCTION.

20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF CORE DRILLING DURING

M-3

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

US ORIGIN MATERIALS:

AS INDICATED ON THE DRAWINGS.

INTERNET SITE HTTP:// WWW.CCKBID.COM). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE

DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT

REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS",

ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL

SCOPE OF WORK

WORK CLASS: "K" (REPAIR / MAINTENANCE WORK)

3 17

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

8. REPLACE EXISTING FIRE EXTINGUISHER CABINET AS INDICATED.

7. RESTORE EXISTING CEILING FINISHES AFTER HEAT PUMP UNIT INSTALLATION.

GENERAL NOTES AND SCOPE OF WORK

BLDG. NO. S-821

REPLACE A/C AND HEATING SYSTEM,

ACCESSORIES PARTS FOR THIS SYSTEM.

WIRE-MESH SCREENS, CONCRETE PADS, CONCRETE SPLASH BLOCKS AND ALL NECESSARY

PIPES, CONDENSATE PIPES, INSULATION, INSULATION JACKETING, THERMOSTATS, STAINLESS STEEL

2. PROVIDE NEW SPLIT SYSTEM DEHUMIDIFIERS COMPLETE WITH ASSOCIATED REFRIGERANT

5. PROVIDE COMPLETE CLEANING OF ALL EXISTING DUCTWORK TO THE ACCEPTANCE OF THE COR.

6. REMOVE AND REINSTALL EXISTING DDC SYSTEM IN MECHANICAL ROOM.

ACCESSORIES PARTS FOR THIS SYSTEM.

WIRE-MESH SCREENS, CONCRETE PADS, CONCRETE SPLASH BLOCKS AND ALL NECESSARY

PIPES, CONDENSATE PIPES, INSULATION, INSULATION JACKETING, THERMOSTATS, STAINLESS STEEL

3. PROVIDE NEW SPLIT SYSTEM HEAT PUMP UNITS COMPLETE WITH ASSOCIATED REFRIGERANT

A FULLY REPLACEMENT.

PREVENTION ASSEMBLY, SMOKE STACK, AND ASSOCIATED ACCESSORIES AND PARTS NECESSARY FOR

INSULATION, JACKETING, STAINLESS STEEL WIRE-MESH SCREENS, CONCRETE PADS, BACKFLOW

DAMPERS, THERMOSTATS, GAS LINE AND TRAIN ASSEMBLY, CHEMICAL FEEDER, EXHAUST FANS, OARC, PANELS, PUMP, EXPANSION TANK, AIR SEPARATOR, DUCTWORK, PIPES, UNIT HEATERS, GAUGES, VALVES, UNIT, HEATING AND VENTILATING UNIT, HOT WATER BOILER, HEAT PUMP OUTDOOR UNIT, CONTROL

1. REPLACE EXISTING DETERIORATED HVAC SYSTEM WITH NEW ONE INCLUDING, AIR HANDLING

ASSEMBLY AND ALL NECESSARY ACCESSORIES PARTS FOR THIS SYSTEM.

BACKFLOW PREVENTION ASSEMBLY, CONCRETE PADS, VALVES, GAUGES, GAS LINE AND TRAIN

HEATER, EXPANSION TANK, DOMESTIC WATER PIPING, SMOKE STACK, DAMPERS, INSULATION,

4. REPLACE EXISTING PLUMBING SYSTEM WITH NEW ONE INCLUDING DOMESTIC HOT WATER

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

FD

FD

FD

EXTINGUISHER CABINET

RE-LOCATE EXIST. FIRE EXTINGUISHER TO NEW FIRE

CABINET AND RECOVER EXIST. WALL

REMOVE EXIST. SEMI-RECESSED FIRE EXTINGUISHER

EXIST. FIRE DEPT. CONNECTION

EXIST. 2" MAIN WATER LINE

EXIST. 8" FIRE PROTECTION MAIN LINE

GAS METER ASSEMBLY CABINET TO REMAIN

EXIST. GAS FILTER & REGULATOR W/

TO REMAIN

EXIST. ROOF GOOSENECK

SHUT-OFF VALVE AND GAS ALARM GONG TO REMAIN

EXIST. GAS LEAK DETECTION CONTROL PANEL, AUTO EMERGENCY

TO WEAPON STORAGE

EXIST. DHW & DCW LINES

WEAPON STORAGE

EXIST. DCW LINE TO

TO REMAIN

EXIST. AIR COMPRESSOR

SYSTEM TO REMAIN

EXIST. DRY PIPE FIRE SPRINKLER

TO REMAIN

EXIST. GAS LEAK DETECTOR

CONC. PAD W/ ASSOCIATED PIPING AND PARTS

REMOVE EXIST. AIR CONDENSING UNIT AND

AND ASSOCIATED ACCESSORIES AND PARTS

INSULATION, BACKFLOW PREVENTION ASSEMBLY, SMOKE STACK,

& TRAIN ASSEMBLY, CHEMICAL FEEDER, EXHAUST FAN, OARC,

HEATER, GAUGES, VALVES, DAMPER, THERMOSTATS, GAS LINE

EXPANSION TANK, AIR SEPARATOR, DUCTWORK, PIPES, UNIT

VENTILATING UNIT, AIR HANDLING UNIT, CONC. PADS, PUMPS,

HOT WATER BOILER, DOMESTIC WATER HEATER, HEATING &

REMOVE EXIST. HVAC AND PLUMBING SYSTEMS INCLUDING

DCW LINES

EXIST. DHW &

VENT LINE

EXIST. SEWER

WATER LINE

EXIST. SPRINKLER

TO REMAIN

EXIST. 50 SEWER VENT LINE

TO REMAIN

EXIST. 150 SPRINKLER WATER LINE

1200x450 S.A.

600x500 R.A.

600x500 S.A.

Th

Th

Th

Th

Th

Th

TO REMAIN

EXIST. HOT WATER LINES

UNIT HEATERS AND THERMOSTATS

REMOVE EXIST. HOT WATER LINES,

(TYP. OF 4)

ABANDON EXIST. STEEL SECURITY BAR

REMOVE EXIST. ROOF EXHAUST FAN /

TO REMAIN

EXIST. ROOF EXHAUST FAN

TO REMAIN

EXIST. ROOF EXHAUST FAN

EXIST. MAIN GAS LINE TO REMAIN

- M-4

P-1

SCALE : 1 / 100

LEGEND

TO BE REMOVED

GRAPHIC SCALE

SCALE: 1 : 100

4000mm

KEY PLAN

BLDG.#821

REMOVAL / EXISTING HVAC AND PLUMBING PLAN

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

SPECIFIC NOTES

SHALL BE PATCHED AND FILLED OR RESTORED.

2. THE OPENING RESULTING FROM THE REMOVAL OF HVAC UNITS

EQUIPMENT, DUCTWORK AND PIPING SHALL BE VERIFIED IN FIELD.

3. EXACT SIZES, LOCATIONS AND DIRECTIONS OF EXISTING HVAC

M-44 17

PLUMBING PLAN

REMOVAL / EXISTING HVAC AND

(TYP. OF 4)

TO REMAIN

SECURITY BAR

EXIST. FD AND

& PIPING SHALL BE VERIFIED IN FIELD.

THEREFORE, EXACT SIZE, LOCATION AND DIRECTION OF HVAC DUCT

1. EXISTING HVAC PLANS MAY NOT EXACTLY MATCH THE FIELD AND

N

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

600x500 R.A.

500x250

1200x450 S.A.

600x500 S.A.

300x200

- M-7

SEE

AND RE-LOCATED EXIST. FIRE EXTINGUISHER

NEW WALL MOUNTED FIRE EXTINGUISHER CABINET

P-1

SCALE : 1 / 100M-5

NEW HVAC DUCT PLAN

GRAPHIC SCALE

SCALE: 1 : 100

4000mm

ROOF EXHAUST FAN

EXIST. ROOF EXHAUST FAN-2

EXIST. ROOF EXHAUST FAN-1

-1 ROOF EXHAUST FAN

-2 ROOF EXHAUST FAN

-3 ROOF EXHAUST FAN

CAMP CARROLL

NEW HVAC DUCT PLAN

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

SPECIFIC NOTES

SITE CONDITIONS. THE CONTRACTOR SHALL VERIFY THEM.

MAY CHANGE DEPENDING ON MANUFACTURER’S RECOMMENDATION AND

3. SIZES AND LAYOUTS OF DUCTWORK AND REFRIGERANT & DRAIN PIPING

INSTALLATION GUIDE.

CONFIGURATION. THE CONTRACTORS SHALL FOLLOW THE MANUFACTURER’S

2. THIS DRAWING SHOWS SUGGESTED EQUIPMENT, DUCTWORK AND PIPING

DRAWINGS OF HVAC SYSTEMS AND EQUIPMENT SHOWING LOCATIONS.

1. THE CONTRACTOR SHALL PROVIDE MANUFACTURER’S DETAILED SHOP

WITH SEALANT.

14. THE CONTRACTOR SHALL CAULK AT THE BASE OF ALL DUCT PENETRATION

FIELD CONDITIONS.

15. ALL HVAC UNITS, PIPES AND DUCTS SHALL BE INSTALLED ACCORDING TO

DEPENDING ON SITE CONDITIONS.

5. THE SIZES OF SUPPLY / RETURN AIR DUCTS AND CHAMBERS MAY CHANGE

PROOF PADS WHERE NECESSARY.

16. THE CONTRACTOR SHALL INSTALL DUCT SUPPORTS AND VIBRATION

MATERIALS.

17. THE VIBRATION PROOF PADS SHALL BE MADE OF CORROSION-RESISTANT

EQUIPMENT MAINTENANCE.

8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ARRANGING A SPACE FOR

BOXES.

12. ALL THERMOSTATS AND CONTROLLERS SHALL BE INSTALLED WITH LOCK

WHERE NECESSARY.

9. THE CONTRACTOR SHALL INSTALL VOLUME DAMPERS AND FIRE DAMPERS

10. FIRE DAMPERS SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 90A.

11. 600 x 600 ACCESS DOORS SHALL BE PROVIDED AT ALL DAMPER LOCATIONS.

IN ACCORDANCE WITH MANUFACTURER’S INSTALLATION INSTRUCTIONS.

4. CLEARANCE DISTANCE FOR ALL HVAC EQUIPMENT SHALL BE DETERMINED

6. ALL DUCTS FOR HVAC SYSTEM SHALL BE INSULATED.

AND SMOKE DETECTORS FOR HVAC SYSTEM WHERE NECESSARY.

7. THE CONTRACTOR SHALL INSTALL TEMPERATURE & HUMIDITY SENSORS

INSTALLING ROOF EXHAUST FANS AND SMOKE STACKS.

13. THE CONTRACTOR SHALL REUSE EXISTING OPENINGS IN THE ROOF WHEN

M-55 17

P-1

N

M-6

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

Tch

Tch

THERMOSTAT (TYP. OF 2)

HPU CONTROLLER W/

Th

Th

Th

Th

Th

Th

(TYP. OF 6)

THERMOSTAT FOR UNIT HEATER

- M-7

SEE

P-2

TO WEAPON STORAGE

EXIST. DHW & DCW LINES

WEAPON STORAGE

EXIST. DCW LINE TO

LINES TO TOILET

EXIST. DHW & DCW

EXIST. 40 STEEL PIPE

DIELECTRIC UNION

NEW 40 COPPER PIPE

20, 20

20, 20

4040, 20

32, 25

25, 32

25, 40

40, 20

RS=15.88

RL=9.52

RS=28.58

RL=15.88

RS=28.58

RL=15.88

RS=28.58

RL=15.88

RS=15.88

RL=9.52

RS=12.7

RL=6.35

HWR

HWS

HWR

HWS

HWR

HWS

H W

S

H W

R

H W

S

H W

R

P-1

SCALE : 1 / 100M-6

NEW HVAC AND PLUMBING PIPING PLAN

GRAPHIC SCALE

SCALE: 1 : 100

4000mm

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

SPECIFIC NOTES

INSTALLATION GUIDE.

CONFIGURATION. THE CONTRACTORS SHALL FOLLOW THE MANUFACTURER’S

2. THIS DRAWING SHOWS SUGGESTED EQUIPMENT, DUCTWORK AND PIPING

INSULATED.

6. ALL REFRIGERANT & DRAIN PIPING FOR HEAT PUMP UNITS SHALL BE

ON HEAT PUMP OUTDOOR UNITS.

10. THE CONTRACTOR SHALL INSTALL STAINLESS STEEL WIRE-MESH SCREENS

WITH SEALANT.

12. THE CONTRACTOR SHALL CAULK AT THE BASE OF ALL PIPE PENETRATION

HVAC SYSTEM IS FULLY OPERATIONAL AND FUNCTIONAL.

16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT NEW

THE MANUFACTURER’S INSTALLATION GUIDE.

11. CONCRETE PAD SIZES SHALL BE DETERMINED BY EQUIPMENT SIZES AND

4. ALL REFRIGERANT LINES SHALL BE VIBRATION ISOLATED.

CONNECTIONS THAT MEET ASME B31.5 REQUIREMENTS.

5. PIPING AND TUBING FOR VRF SYSTEMS SHALL HAVE ALL BRAZED

DRAWINGS OF HVAC SYSTEMS AND EQUIPMENT SHOWING LOCATIONS.

1. THE CONTRACTOR SHALL PROVIDE MANUFACTURER’S DETAILED SHOP

SITE CONDITIONS. THE CONTRACTOR SHALL VERIFY THEM.

MAY CHANGE DEPENDING ON MANUFACTURER’S RECOMMENDATION AND

3. SIZES AND LAYOUTS OF DUCTWORK AND REFRIGERANT & DRAIN PIPING

UP WITH PIPE JACKETS.

7. ALL EXPOSED REFRIGERANT & CONDENSATE PIPES SHALL BE COVERED

BOXES.

9. ALL THERMOSTATS AND CONTROLLERS SHALL BE INSTALLED WITH LOCK

DRAINAGE SYSTEM.

14. THE SLOPE OF DRAIN LINES SHALL BE SUFFICIENT TO PROVIDE A GRAVITY

FIELD CONDITIONS.

13. ALL HVAC UNITS, PIPES AND DUCTS SHALL BE INSTALLED ACCORDING TO

IN ACCORDANCE WITH MANUFACTURER’S INSTALLATION INSTRUCTIONS.

8. CLEARANCE DISTANCE FOR ALL HVAC EQUIPMENT SHALL BE DETERMINED

OF OUTDOOR HEAT PUMP UNIT COULD BE OBSTRUCTED.

15. THE CONTRACTOR SHALL RELOCATE EXISTING BULLET TRAP IF INSTALLATION

6 17

NEW HVAC AND PLUMBING PIPING PLAN

N

M-7

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

Th OARC

21 DOMESTIC HOT WATER HEATER

THERMOSTATIC MIXING VALVE

EXIST. AIR COMPRESSOR

EXIST. DRY PIPE FIRE SPRINKLER SYSTEM

TT

3/4" HOSE BIBB

EXIST. GAS ALARM GONG

PRESSURE RELIEF VALVE

EXIST. GAS LEAK DETECTION CONTROL PANEL

13 UNIT HEATER

THERMOSTAT FOR UNIT HEATER

W/ GAS METER ASSEMBLY CABINET

EXIST. GAS FILTER & REGULATOR

12 HOT WATER CIRCULATING PUMP

HEATING & VENTILATING UNIT2

PRESSURE RELIEF VALVE

5 HOT WATER HEATING BOILER

EXIST. DCW LINE TO WEAPON STORAGE

WEAPON STORAGE

EXIST. DHW & DCW LINES TO

EXIST. DHW & DCW LINES TO TOILET

MODULATING 3-WAY CONTROL VALVE

BACKFLOW PREVENTER

CHEMICAL FEEDER

PRESSURE REDUCING VALVE

20 AIR SEPARATOR

19 HOT WATER EXPANSION TANK

DOMESTIC EXPANSION TANK

WORKBENCH & PROCESSING AREA

EXIST. HOT WATER LINES FROM / TO

NEW GAS LINE

OUTDOOR AIR TEMP SENSOR

OUTDOOR AIR RESET CONTROLLER

REMOTE BULB FOR COOLING / HEATING

OUTDOOR AIR THERMOSTAT W/

EXIST. FIRE DEPT. CONNECTION

EXIST. 2" MAIN WATER LINE

EXIST. 8" FIRE PROTECTION MAIN LINEEXIST. AUTO EMERGENCY SHUT-OFF VALVE

EXIST. DRY PIPE FIRE SPRINKLER SYSTEM

EXIST. AIR COMPRESSOR

21 DOMESTIC HOT WATER HEATER

5 HOT WATER HEATING BOILER

600x500 S.A.

600x500 R.A.

FD

FD

FD

HEATING & VENTILATING UNIT2

EXIST. ROOF GOOSENECK

x5

O .A

PLENUM BOX

600x600 COMBUSTION AIR

AND CONNECT TO ROOF GOOSENECK

600x500 RELIEF AIR DUCT UP THRU ROOF

1200x450 S.A.

1000x350 R.A. DUCT DROP

1500x500 O.A. DUCT DROP

2000x1800

BIRD SCREEN AND PLENUM BOX BEHIND

3400x1800 O.A. & COMBUSTION AIR INTAKE LOUVER W/

AIR HANDLING UNIT

600x300 DROP

M

12 HOT WATER CIRCULATING PUMP

19 HOT WATER EXPANSION TANK

1600x900

16 ROOF EXHAUST FAN

OUTDOOR HPU

OUTDOOR HPU

OUTDOOR HPU

T

THERMOSTAT FOR ROOF EXHAUST FAN

TOP AND BOTTOM

OPENING W/ SCREEN AT

600x300 COMBUSTION AIR

EXIST. GAS LEAK DETECTOR

DIELECTRIC UNION

BRONZE GATE VALE

COPPER ADAPTER 40

20, 20

40, 40

RS=28.58

RL=15.88

32, 32

EXIST. MAIN GAS LINE

HWR

HWS

P-1

SCALE : 1 / 50M-7

NEW MECH. ROOM DUCT PARTIAL PLAN

P-2

SCALE : 1 / 50M-7

NEW MECH. ROOM PIPING PARTIAL PLAN

GRAPHIC SCALE

1000 2000mm

SCALE: 1 : 50

1 AIR HANDLING UNIT

IN-LINE DUCT FAN

SEQUENCE OF OPERATION FOR FAN

SET POINT. WHENEVER FAN IS ENERGIZED, DAMPAER-1 SHALL OPEN.

THERMOSTAT FOR ROOF EXHAUST FAN SHALL CONTROL FAN TO MAINTAIN ITS

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

SPECIFIC NOTES

FOLLOW THE MANUFACTURER’S INSTALLATION GUIDE.

1. THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION. CONTRACTORS SHALL

GAS PIPING AND ACCESSORIES.

3. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR THE INSTALLATIONS OF

4. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR GAS PIPE SIZING.

2. THE CONTRACTOR SHALL INSTALL GAUGES WHERE NECESSARY.

BETWEEN THE RPZ RELIEF VALVE OPENING AND ANY DISCHARGE PIPING.

AN AIR GAP NOT LESS THAN TWICE THE DIAMETER OF THE RELIEF PORT OPENING

5. THE REDUCED PRESSURE BACKFLOW PREVENTER SHALL BE PROVIDED WITH

6. CONCRETE PAD SIZES SHALL BE DETERMINED BY EQUIPMENT SIZES.

SO ALL INDIVIDUAL STACKS SHALL BE COMBINED INTO ONE SMOKESTACK.

7. THE CASCADE TYPE OF BOILER AND HEATER HAVE STACKS IN EACH UNITS.

8. CLEARANCE DISTANCE FOR EXISTING ELECTRIC PANEL SHALL BE 3 FEET MINIMUM.

EXIST. ELECTRIC PANEL (SEE SPECIFIC NOTES NO. 8)

80, 80

7 17

NEW MECH. ROOM PARTIAL PLAN

N

MOTORIZED DAMPER - 1

1000x600 O.A. INTAKE OPENING W/

M-8

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

M

I-1

M-8

NEW MECH. ROOM PIPING ISOMETRIC DIAGRAM

NOT TO SCALE

DOMES

TIC

E

XP

ANSIO

N

TA

NK

WEAPON STORAGE

EXIST. DHW & DCW LINES TO

EXIS

T.

DCW

LIN

E

TO

WEAP

ON

ST

ORAGE

PRESSURE RELIEF VALVE

AIR

S

EP

ARAT

OR

MI

XIN

G

VAL

VE

TH

ER

MOST

AT

IC

CONTROL VALVE

MODULATING 3-WAY

BACKFLOW PREVENTER VAL

VERE

DUCIN

G

PR

ES

SURE

DOMES

TIC

H

OT

WAT

ER

H

EAT

ER

HOT

WAT

ER

H

EAT

ING

BOI

LE

R

PR

ES

SURE

R

EL

IEF

V

AL

VE

WAT

ER

M

ET

ER

PR

ES

SURE

R

EDUCIN

G

VAL

VE

BACKF

LO

W

PR

EVE

NTE

R

UNIT HEATER

H

OSE

B

IBB

FE

EDER

CHEMI

CAL

HOT WATER CIRCULATING PUMP

HOT WATER EXPANSION TANK

HEAT

ING

VE

NTIL

AT

ING

UNIT

AIR

H

ANDLIN

G

UNIT

OUTDOOR HPU

EXIS

T.

DHW

DCW

LIN

ES

T

O

TO

ILE

T

WORKBE

NCH

PR

OCES

SIN

G

ARE

A

EXIS

T.

HOT

WAT

ER

L

INES

F

ROM

/ T

O

, 3

50,32

65, 65 20 , 2

RS

.58

RL

15.

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

50,32

40, 40

, 4

8 17

ISOMETRIC DIAGRAM

NEW MECH. ROOM PIPING

M-9

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

R.A.

M

N.C.

N.O.

FILTER

C

SDTS

TS 2

1TS

LT

DX

N.C.

SMOKE DETECTOR

S.A. SENSOR

TO SPACE

SUPPLY FANDX COILFREEZESTAT

LOW TEMP

GAUGE

MAGNEHELIC

RETURN FAN

SUPPLY FAN

INTERLOCK W/

SENSOR

R.A. TEMP.

COOLING (ADJ.)

SET AT 24 C FOR

HEATING (ADJ.)

SET AT 20 C FOR

MOTORS

OA / RA DAMPER

RELIEF AIR

O.A.

O.A. TEMP. SENSOR

MOTOR (TYP.)

E.A. DAMPER

R S

R L

D-1

M-9 NOT TO SCALE

AHU SCHEMATIC CONTROL DIAGRAM

6.

5.

4.

3.

2.

1.

7.

GENERAL:

SAFETY CONTROLS:

DUCT, AHU SHALL BE TURNED OFF. MANUAL RESET IS REQUIRED.

WHEN SUPPLY DUCT SMOKE DETECTOR SENSES SMOKE IN THE SUPPLY 2.1

2.2

OCCUPIED HEATING MODE:

3.1

3.2

UNOCCUPIED HEATING MODE:

4.1

CLOSED. FACE & BYPASS DAMPER SHALL BE IN THE FULL FACE POSITION.

SHALL BE FULLY OPEN AND O.A. & E.A. DAMPERS SHALL BE FULLY

DURING UNOCCUPIED MODE, AHU SHALL BE DE-ENERGIZED. R.A. DAMPER

4.2

OCCUPIED COOLING MODE:

5.1 SAME AS PARAGRAPH 3.1

5.2

5.3

UNOCCUPIED COOLING MODE:

SAME AS PARA. 4.1.6.1

SYSTEM INTERLOCKS:

6.1

RETURN FAN SHALL OPERATE ONLY WHEN AHU FAN IS OPERATING.

RETURN FAN SHALL BE INTERLOCKED WITH AHU CONTROL SO THAT

AHU (AIR HANDLING UNIT) SEQUENCE OF OPERATION

SPECIFIC NOTES

AND RECOMMENDATION.

IN ACCORDANCE WITH MANUFACTURER’S INSTALLATION GUIDE

1. THE CONTROL EQUIPMENT FOR AHU SHALL BE DETERMINED

M

FROM CONTROLLERTO CONTROLLER

EEV

TO CONTROLLER

TO CONTROLLER

TO CONTROLLER

FROM CONTROLLER

MINIMUM CFM OF O.A. AS SCHEDULED.

MANUAL POSITION POTENTIOMETER SHALL BE SET TO INTRODUCE

MINIMUM O.A. POSITION AND E.A. DAMPERS SHALL BE CLOSED. THE

WHEN AHU FAN MOTOR START O.A./R.A. DAMPERS SHALL BE AT

(ADJUSTABLE)

PROGRAMMABLE THERMOSTAT TO MAINTAIN R.A. TEMPERATURE AT 24.0 C.

AND S.A SENSOR (TS2, AS ANTICIPATOR) SHALL SEND A SIGNAL TO THE

O.A. TEMP. SENSOR (TS0) AND ASSOCIATED R.A. TEMP. SENSOR (TS1)

(ADJUSTABLE)

PROGRAMMABLE THERMOSTAT TO MAINTAIN R.A. TEMPERATURE AT 20 C.

AND S.A SENSOR (TS2, AS ANTICIPATOR) SHALL SEND A SIGNAL TO THE

O.A. TEMP. SENSOR (TS0) AND ASSOCIATED R.A. TEMP. SENSOR (TS1)

2.7 C. MANUAL RESET SHALL BE REQUIRED. (ADJUSTABLE)

FREEZESTAT STOPS OPERATION OF AHU UPON ITS SET POINT OF

DIAGRAM AND THE LADDER DIAGRAM.

3. THE CONTRACTOR SHALL SUBMIT THE AHU SCHEMATIC CONTROL

VALVE

EXPANSION

ELECTRIC

9 17

AHU SCHEMATIC CONTROL DIAGRAM

THE AHU FAN SHALL RUN CONTINUOUSLY BASED ON TIME CLOCK SCHEDULE.

WHEN THE SYSTEM SWITCH FOR THE AHU IS SET TO THE "ON" POSITION,

REQUIREMENTS, MECHANICAL EQUIPMENT SCHEDULE, AND DETAILS.

SYSTEM SPECIFICATIONS, MANUFACTURERS’ INSTALLATION

INSTALLATION REQUIREMENTS SHALL BE IN ACCORDANCE WITH

FOR CONTROL SYSTEM REQUIREMENTS ONLY, SYSTEMS EQUIPMENT

2. THE CONTROL DIAGRAMS IN THESE DRAWINGS ARE INTENDED

SPACE TEMPERATURE AT 12.8 C. (ADJUSTABLE)

SETPOINT, THE CONTROLLER. SHALL CYCLE THE AHU FAN MOTOR TO MAINTAIN

WHENEVER SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED T-STAT

BELOW 10 C. (ADJUSTABLE)

LOW-LIMIT AND MODULATE THE O.A. DAMPER CLOSED AS S.A. TEMP. FALLS

THE CONTROLLER SHALL USE THE S.A. TEMPERATURE SENSOR (TS2) AS A

SETPOINT. (ADJUSTABLE)

SHALL MODULATE THE C.W. COIL VALVE TO MAINTAIN THE R.A. TEMPERATURE

24 C (WHEN R.A. TEMP EXCEEDS 24 C WITH 100% O.A.), THE CONTROLLER

WHEN THE ECONOMIZER CAN NO LONGER MAINTAIN R.A. TEMPERATURE AT

THE R.A. AT 24 C. (ADJUSTABLE)

CONTROLLER SHALL MODULATE THE O.A., R.A., & E.A. DAMPERS TO MAINTAIN

100% O.A. AS R.A. TEMPERATURE FALLS BELOW THE 24 C SET POINT, THE

CONTROLLER SHALL CONTROL THE O.A., R.A., & E.A. DAMPERS TO PROVIDE

INITIALLY CONTROL THE C. W. COIL VALVE TO FULL BYPASS AND THE

SET BY THE O.A. CHANGE-OVER CONTROLLER, THE CONTROLLER SHALL

ECONOMIZER CYCLE: WHEN O.A. TEMPERATURE DROPS BELOW 15.6 C AS

M-1010 17

M

SH

C

M

H W

R H

W S

T

FR

T O

M

TS

EA

EA

H-O-A

EXIST. ROOF EXHAUST FAN-1

EA

EA

ROOF EXHAUST FAN -118

EA

EA

EA

EA

ROOF EXHAUST FAN -218

EA

EA

ROOF EXHAUST FAN -318

EA

EA

ROOF EXHAUST FAN EXIST. ROOF EXHAUST FAN-2

S.A.

O.A.

SENSOR

S.A. TEMP.

DETECTOR

SMOKE

MOTOR STARTER

H-O-A H-O-A H-O-A H-O-A H-O-A

H & V UNIT

FACE & BY-PASS DAMPER

FREEZESTAT

O.A.

W/ BIRD SCREEN

INTAKE LOUVER

OUTSIDE AIR

O.A. THERMOSTAT

TC

TEMPERATURE CONTROLLER

D-1

M-10 NOT TO SCALE

T O

T OARC

M

H W

R

HWS

HWR

HWS

SUNSHIELD

SENSOR

O.A. TEMP.

SUNSHIELD

W/ REMOTE BULB

OUTDOOR AIR THERMOSTAT

CONTROLLER

OUTDOOR AIR RESET

HEATING & VENTILATING SYSTEM SCHEMATIC DIAGRAM

5 HOT WATER HEATING BOILER

CONTROL VALVE

MODULATING 3-WAY

SENSOR BACKFLOW PREVENTER ASSEMBLY

PRESSURE REDUCING VALVE

E

REMOVABLE FUNNEL

CHEMICAL FEEDER W/

12 HOT WATER CIRCULATING PUMP

MOTOR STARTER

20 AIR SEPARATOR

TANK

EXPANSION

HOT WATER

MAKE UP COLD WATER

TO / FROM BLDG. HEATING SYSTEM

D-2

M-10 NOT TO SCALE

HOT WATER HEATING SYSTEM CONTROL DIAGRAM

SEQUENCE OF OPERATION

1.

CAMP CARROLL

07 MAR 22

NAM, TAE CHIN

HA-00529-3J

-1,1817 -2,18, 18

"HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION RUNS FAN-1, FAN-2,

-1,1817 -2,18, 18

"HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS FAN-1, FAN-2,

-3 UNTIL MANUALLY STOPPED.

2.

3. -1,1817 -2,18, 18

OPERATED CONTINUOUSLY DURING OPERATING HOURS. THESE 6 FANS SHALL

OPERATE CONTINUOUSLY TO PROVIDE GENERAL VENTILATION.

4.

TEMPERATURE CONTROLLER SHALL MODULATE H & V UNIT FACE / BY-PASS

-3 ONLY WHEN H & V UNIT IS RUNNING.

5. FREEZESTAT STOPS OPERATION OF H & V UNIT UPON ITS SET POINT OF 2.8

SMOKE DETECTOR STOPS H & V UNIT OPERATION WHEN SMOKE IS DETECTED.

DAMPER MOTOR TO MAINTAIN S.A. TEMPERATURE AT 15.6 DEG.C. (ADJUSTABLE)

DEG. C. (ADJUSTABLE)

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

SYSTEM SCHEMATIC AND CONTROL DIAGRAM

H & V SYSTEM AND HOT WATER HEATING

WHEN O.A. THERMOSTAT FALLS TO SET POINT OF 15.6 DEG C., PROPORTIONAL

FAN-1, FAN-2, -3 SHALL BE ENERGIZED BY TIMEC LOCK AND

OUTER TAPE

INSULATION

COVER

REFRIGERANT GAS PIPE

TO INDOOR UNIT

FROM HEAT PUMP

: POSSIBLE

(X) VERTICAL LEVEL

TO INDOOR UNIT

- NOT TO SCALE

REFRIGERANT PIPE BRANCH TAKE OFF

- NOT TO SCALE

REFRIGERANT PIPES PRIOR TO / AFTER

BRANCH TAKE OFF FITTINGS.

NOT TO SCALE

OUTDOOR HPU CONCRETE PAD

HEAT PUMP

PIPES FROM

REFRIGERANT PIPE SLEEVE

FROM HEAT PUMP

NOTES

PIPES TO INDOOR UNIT

: IMPOSSIBLE

MAINTAIN HORIZONTAL LEVEL BETWEEN

(EXTERIOR WALL ONLY)

OUTER SEALING PLATE

ARC WELDING

PIPE SLEEVE

PIPE

YARN OR INSULATION 64K

CAULKING COMPOUND

4.5THK. STEEL PLATE

INSULATION

PVC PIPE

ARC WELDING

INSULATION

PIPE

MIN 30MM

WALL & FLOOR

4.5THK. STEEL PLATE

YARN OR INSULATION 64K

PIPE SLEEVE

ELEC. CONDUIT

INSULATION REFRIGERANT GAS PIPE

REFRIGERANT LIQUID PIPE

TELECOM LINE

PIPE SLEEVE

COMPOUND

CAULKING

: POSSIBLE BRANCH TAKE OFF LEVEL

FIN GRADE

19 CHAMFER

150 MIN 150 MIN

E.W.T.B

D16 @200 OC

200 150

MECHANICAL EQUIPMENT

CONCRETE PAD

100% COMPACTED BASE COURSE

NOTE :

ABBREVIATION:

T.B: TOP AND BOTTOM

E.W: EACH WAY

MATERIAL PROPERTIES:

2. REINFORCING STEEL YIELD STRENGTHS, fy=300 Mpa.

1. CONCRETE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, f’c=24 Mpa.

"H" BEAM

(150MM HEIGHT)

RUBBER PAD

PAD 12T

CONCRETE PAD

RUBBER PAD

CONC. PAD

NOT TO SCALE-

2. CHAMFER ALL EXPOSED EDGES OF CAST-IN-PLACE CONCRETE 19mm UNLESS OTHERWISE NOTED.

1. PAD SIZE SHALL BE COORDINATED WITH THE EQUIPMENT UNIT MANUFACTURER.

OUTDOOR HPU RUBBER PAD

M-11

DETAIL DRAWINGS - 1

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

M-11

2 3

SEE ARCH. DWGS.

WOOD NAILER

ALL AROUND

GASKET SEAL

(SPECIFIED IN DIVISION 7)

ROOF CONSTR.

FLASHING

CURB HT.

12"(300) MIN.

DIVISION 7 WORK

ROOF CURB,

POWER ROOF VENTILATOR

MIN. 2 EACH SIDE

BY FAN MFR.,

RECOMMENDED

SEE ARCH. DWGS.

WOOD BLOCKING,

SEE ARCH. DWGS.

MANUAL

BACKDRAFT DAMPER REQ’D

EXHAUST DUCT WORK

AS PER EQUIPMENT SCHEDULE

- NOT TO SCALE

POWER ROOF VENTILATOR

LAG BOLTS AS

11 17

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

M-11

M-11M-11M-11

NOT TO SCALE-

CHEMICAL FEEDER

- NOT TO SCALE

EXPANSION TANK AND AIR SEPARATOR 2

"D 1"

"D

PIPE

PIPE

o

WELDED (TYP)

.8

8100 100

MAX.300

"D2" IS NOMINAL PIPE SIZE FOR 63mm AND LARGER.

"D1" IS NOMINAL PIPE SIZE FOR 50mm AND SMALLER.

2.

1.

NOT TO SCALE-

PIPE ANCHOR

STEEL ANGLE

38 x 38 x 7 THK

(TYP. OF 6)

10 BOLT & NUT

STEEL PLATE

5 THK

(TYP)

MAX.45°

STEEL ANGLE

50 x 50 x 6 THK

STEEL PLATE

100 x 300 x 10 THK

(TYP)

MAX. 45°

NOTES :

NOT TO SCALE-

FD ECA BG HF

HOT PIPE LINE

HGD FECBG H A

CG

MF

EXPOSED

CLINCHING STAPLE @ 100 O.C.

CG OR

MF

EXPOSED

WEATHER

A

C

D

B

CLASS II ADHESIVE

OVERLAP (40)

VAPOR-BARRIER JACKET

2. HOT WATER HEATING

3. HEATED OIL PIPE LINE

1. STEAM & CONDENSATE

5. REFRIGERATION SUCTION

4. A/C CONDENSATE DRAIN

LONGITUDINAL JOINTS

COLD WATER PIPE LINE

3. DUAL TEMP. WATER

2. CHILLED WATER

1. MAKE-UP WATER

DOWN TO SHED WATER

SHALL BE OVERLAPPED

ALUMINUM JACKET

H

G

NOTE :

BAPIPING

COLD PIPE LINE

HOT PIPE LINE

D EC

INSULATION

PIPE

AREA

ITEM

80 JACKET STRIPE

F

CONCEALED

VAPOR-BARRIER JACKET

(MIN. 40 JACKET OVERLAP)

VAPOR-BARRIER COATING

10 W x 0.5 THK @300 O.C.

ALUMINUM LOCK-TYPE BANDS

80 JACKET STRIP OR

MF - MINERAL FIBER SHALL BE USED FOR HOT PIPES

CG - CELLULAR GLASS SHALL BE USED FOR COLD PIPES

SEE SPECIFICATION FOR INSULATION THICKNESS

PIPE SADDLE

PIPE SADDLE

65 THRU 80

UP TO 50

PIPE SIZE

15 DIA

100 THRU 12510 DIA

PIPE SIZEROD SIZE

CLEVIS HANGER

(NOT VAPOR BARRIER)

3,600

ROLLER

STAND

PIPE

LENGTH AS REQ’D

LOCKING

CONC BEAM

TRAPEZE HANGER

PL 15 X 200 X 200

BOLT PIPE ROLLERS TO ANGLE (TYP)

ANCH BOLT.

HANGER ROD (TYP)

NO INSULATION

16 GAGE STEEL

654032 5025

HANGER ROD SPACING

PIPE SIZE

3,3002,7002,400 3,0002,100

OF SMALLEST PIPE ON TRAPEZE.

MAX. ALLOWABLE

SPACING

NOTE : FOR TRAPEZE HANGER TAKE SPACING

ANGLE

SUPPORT NUT

PIPE SADDLE AT

LEAST 300 LONG

WELD

10080

3,900

(TYP)

INSULATION (TYP)

CONNECTION TO CONCRETE FLOOR W/CONCRETE ANCHORS OR TO

ROOF STRUCTURE MEMBER FOR TOP FLOOR

MIN. 600VAPOR BARRIER

INSULATION

NOTE

ANCHOR

ANGLE

CROSS BRACING

SLAB OR BEAM

NOT TO SCALE-

4 5

AT LEAST 300 LONG

100 THRU 125

HANGER ROD SCHEDULE

15 DIA.65 THRU 80

10 DIA.UP TO 50

PIPE SIZEROD SIZEPIPE SIZE

16 DIA

ROD SIZE

CROSS BRACE : REFER TO SMACNA’S SEISMIC RESTRAINT MANUAL CHAPTER 5.

AT LEAST 300 LONG

LOCKING NUT

SUPPORT NUT

INSULATION

VAPOR BARRIER

16 DIA

ROD SIZE

HANGER ROD

HANGER ROD SCHEDULE

PIPE

HEAVY DUTY

CLEVIS HANGER

16 GAGE SHEET METAL

16 GAGE SHEET METAL

PIPE HANGER PIPE INSULATION

M-1212 17

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

DETAIL DRAWINGS - 2

M-12

SHEET COPPER FUNNEL

20mm VALVE

SHUT-OFF COCK

18mm GAUGE GLASS

CARBON STL. PIPE

SCH. 80 SEAMLESS

200mmx600mm LG.

WITH GASKET

COMPANION FLANGES

20mm DRAIN VALVE

CHILLER

TO BOILER OR

GLOBE VALVE

VALVE

20mm GATE

FROM SYSTEM

10mm AIR COCK

125mm

SHEET COPPER FUNNEL

TANK

EXPANSION

INSULATION

PUMP

CONNECT TO

AIR SEPARATOR

PAD

CONCRETE

DRAIN

25mm NPT

VERTICAL

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

M-12

M-12M-12M-12

SP

FL

O

W

GA

SPR

SINGLE VANE SCHEDULE

USED. OTHER VANE

OTHER RUNNERS MAY BE

SEE NOTES ON FIG.2-4

SIZES OR SPACINGS

LARGE

SMALL

FLAT

R SP

RUNNER TYPE 2

20mm TRAILING EDGE

SINGLE VANE WITH

SP

50 40

81113

SP=40

R=50

112.5

OR

APPROVAL.

R

ACCEPTABLE ON DESIGNER

22 GA

INLET AREA.

APPROXIMATES ELBOW

FREE AREA BETWEEN

DOUBLE WALL VANES

RUNNER TYPE 1

OR RUN A TIE ROD THROUGH THE CENTER VANE.

WELD EVERY 6TH VANE TO RUNNER(OVER 5 MPS)

BOLT, SCREW, OR

WELD RUNNER TO DUCT

32 MIN

NOT TO SCALE-

45 45

45 45

DUCT TURNING VANE 3

ALL TRANSVERSE EDGES

DIMENSIONS

TO BE COATED WITH ADHESIVE

CB

E

FOLDED CORNER

PIN AND WASHER

ALTERNATE

(FASTENER)

12.71 TO 30.5 MPS

DUCT SECTION

UP TO 12.7 MPS

VELOCITY

(TYPICAL 1,200 OR 1,500mm)

A

E

B

LINING

C

B

C

B

C

A

E

2.

1.NOTE :

ATTACHED BY SCREWS, RIVETS OR WELDS.)

BE FORMED ON DUCT OR BE CHANNEL OR ZEE

NOSING ON EVERY LEADING EDGE. (NOSING MAY

WHEN VELOCITY ABOVE 20.3 MPS USE METAL

MAXIMUM SPACING FOR FASTENERS ACTUAL

INTERVALS ARE APPROXIMATE.

LAPPED AND BUTTED CORNER

NOT TO SCALE

DUCT LINING DETAIL

REMARKS

2,400

2,400

3,000

2,400

3,000

3,000

3,000

SPACING

MAXIMUM

SPACING

MAXIMUM

HANGER SIZES FOR ROUND DUCT

25 x 22 GA

HANGERS

STARP

6 DIA OR

8 GA WIRE

HANGER

RODS

3,000

25 x 18 GA

40 x 16 GA

25 x 16 GA

25 x 16 GA

25 x 18 GA

10 DIA

15 DIA

10 DIA

10 DIA

10 DIA

25 x 22 GA

HANGERS

STARP

25 x 22 GA

HANGER

RODS

HANGERS

50 x 50 x 6

50 x 50 x 5

40 x 40 x 3

50 x 50 x 3

40 x 40 x 3

ANGLES

25 x 25 x 3

25 x 25 x 3

CROSS BRASSING

ANGLE (TYP)

HANGER

NUTS

ROD

DIAMETER

DUCT

ANGLES

DIMENSION

LONGEST

OF DUCT

775 THRU 1,050

2,125 THRU 2,400

1,525 THRU 2,100

1,075 THRU 1,500

UP THRU 450

OVER 2425

475 THRU 750

UP THRU 450

1.

PLACED UNDER A BOTTOM REINFORCEMENT.

2.

FOR BOTH DUTIES.

25 x 16 GA

25 x 20 GA10 DIA

10 DIA

3,000

3,000

1,250 DIA MAX.

NOTES :

925 THRU 1,250

1275 THRU 2,100

475 THRU 900 25 x 20 GA10 DIA 3,000 1

OMITTED IF

HANGER LOOPS

SCREWS MAY BE

SCREWS

FOR LOAD

SIZE BOLT(S)

INSULATION

LOAD RATED

SEE NOTE 2

OR ANGLE

STRAP

ANCHOR TO CEILING SLAB

OR STEEL PLATE (TYP)

TRAPEZE HANGERS

STRAPS

HANGER SEE NOTE 1

25MIN.

STRAP HANGERS

600 DIA MAX.250 DIA MAX.

STRAP

AS HANGER

SAME SIZE

WIRE

BAND OF

SECURE FASTENERS

(VERIFY UPPER TRAPEZE

LOAD CAPACITY)

ALTERNATIVE LOCATION

DISTANCE IS NOT EXCEED 1,500 UNLESS FOOT OF STRAP IS

REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT QUALIFIES

HANGER SIZES FOR RECTANGULAR DUCT

NUMBER OF

TRAPEZE SHELF

DO NOT EXCEED ALLOWABLE LOAD LIMITS.

NOT TO SCALE-

4 DUCT HANGER

M-13

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

SHEET OF

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

E

AS SHOWN

DATE:

MECHANICAL

D - 22 - 07

A B C D F G H

DETAIL DRAWINGS - 3

C cmhx Y=X

SD

A cmh B cmh

NOTE; ABOVE APPLY TO SUPPLY AND RETURN

W

SD

YX

W

Y

D

FOR D OF 300 OR MORE

USE VANED ELBOW

D LESS THAN 300

R=D YR1=(X+Y)/2

R2=X+Y

X OR W LESS THAN 300

Y

R

D

R2=X+Y R1=(X+Y)/2

SD

X

R

TURNING VANES (TYP.)

RETURN ONLY

Y

BRANCH TAKEOFFS

C 300 OR MORE

MANUAL DAMPER

X OR Y LESS THAN 300

R1=(W1+W2)/2

SPLITTER DAMPER(TYP.)

PROVIDE VE WHEN COIL OR DIFFUSER IS

1,500 OR LESS FROM BRANCH TAKEOFF.

A cmh x Y=XC cmh

SD

A cmhB cmh

W

W

X

W

R=W

W

NOTE; SEE SMACNA DUCT MANUAL

C LESS THAN 300

(1985) FIGS. 2-7

C c m h

A cmh

PREFERRED OFFSET

FULL RADIUS WHERE POSSIBLE

OFFSETS

FROM RECTANGULAR MAIN

ROUND DUCT TAKEOFF

NOT TO SCALE

DUCT WORK DETAIL

C c h m

R1 W2

R2=W1+W2

Y

X

20 max.

90 TEES

20 max.

90 RADIUS ELBOWS

M-13

13 17

CAMP CARROLL

HA-00529-3J

07 MAR 22

NAM, TAE CHIN

M-13M-13M-13

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

ELECTRICAL

KIM, CK

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :SAFETY REP

SIGNAL REP

FES

FORCE PROTECTION

CHIEF,

DESIGN & TECH. REVIEW Br.

O & M

HOUSING DIV.

REVIEWED BY

SYMBOL BY CHK.ZONE DATE APVD.

R E V I S I O N S

DESCRIPTION

UNITED STATES ARMY GARRISION DAEGU

DIRECTORATE OF PUBLIC WORK

UNIT #15746, APO AP 96218-5746

DATE:

N O T E S

3.

2.

4. MOUNTING HEIGHTS ARE AS BELOW. MEASUREMENT IS TO CENTER OF OUTLET.

WIRES IS INDICATED AS FOLLOW;

AND ONE (1)-#12AWG GROUND WIRE IN 16mm CONDUIT. A GREATER NUMBER OF

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES TWO (2)-#12AWG WIRES

3-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.

4-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.

PANELBOARD, CIRCUIT BREAKER------------------------SEE SPECIFICATION

CAULKING MATERIAL SHALL BE VERIFIED BY F&ES OFFICE PRIOR TO CONSTRUCTION.

BOTH SIDE OF FIRE WALLS, FIRE-PARTITIONS AND FIRE-RATED PIPE CHASE WALLS.

ALL PIPE PENETRATIONS SHALL BE SEALED WITH FIRE RATED CAULKING MATERIAL ON

1.

SPECIFICATIONS FOR O&MA PROJECTS, AND SPECIFICATIONS.

ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, FIRE CODE, TECHNICAL STANDARD

ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL

CONDUIT WHICH IS TO BE BONDED TO THE MAIN GROUNDING SYSTEM AT BOTH ENDS.

GROUNDING WIRE SHALL BE GREEN INSULATED COPPER WIRE IN RIGID GALVANIZED STEEL

ALL WIRING SHALL BE CONCEALED ABOVE THE CEILING WHEN THE ROOM HAS A CEILING.

MAGNETIC MOTOR STARTER

L E G E N D

NEWEXSTREMOVE

PANELBOARD OR LOAD CENTER

J

JUNCTION BOX

+ WIRING CONCEALED IN UNDERGROUND

HOMERUN CIRCUIT TO PANELBOARD OR ENCLOSURE

WIRING CONCEALED IN CEILINGS AND WALL

WIRING EXPOSED ON CEILINGS AND WALL

1.6

J

1.6

J

1.6

1.6M ABOVE FLOOR

///// C C CONTROL CIRCUITC

SCOPE OF WORK

5.

6.

7.

AND THE COLOR OF TOGGLE SWITCHES AND RECEPTACLE SHALL BE GRAY.

ALL COVER PLATES OF RECEPTACLES AND SWITCHES SHALL BE STAINLESS STEEL METALLIC ONES

LEGEND, NOTES AND SCOPE OF WORK

US ORIGIN MATERIAL:

CHANGES SHALL BE APPROVED BY THE CONTRACTING OFFICE.

BE RESPONSIBLE TO RESIZE AND PROVIDE THE REQUIRED WIRING AND OVER CURRENT DEVICES. THE

IF EQUIPMENT OTHER THAN INDICATED ON THE PLANS ARE PROVIDED, THEN THE CONTRACTOR SHALL

INDICATED ON THE DRAWINGS.

INTERNET SITE (http//www.cckbid.com). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE AS

DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT

REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS

ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL

SIN, YS

HA-00529-3J

CAMP CARROLL

RECEPTACLE, SINGLE, 2P-3W-20A-250V, GRD’G TYPE

D - 22 - 07

WIRING CONCEALED IN CEILINGS AND WALL/////

1.

SHEET OF14 17

A. REPAIR / MAINTENANCE

E-01

8.

BREAKERS, SAFETY SWITCHES, MAGNETIC MOTOR STARTERS, POWER LINE AND NECESSARY ACCESSORIES.

REPLACE DETERIORATED EXISTING POWER SYSTEM WITH NEW DRY TYPE TRANSFORMER, PANEL BOARD, CIRCUIT

BLDG. NO. S-821

REPLACE A/C AND HEATING SYSTEM,

07 MAR 22

SAFETY SWITCH

M-7

E-1

1/4HP, 277V, 1PH, 60Hz

ROOF EXHAUST FAN

"2A"

"4A"

Tch

Tch

"2D""4E"

3REHEAT: 24KW, 460V, 3PH, 60Hz

FAN MOTOR(2EA): 1.5KW, 460V, 3PH, 60Hz, DEHUMIDIFIER

"4B"

"2B"

"4MDP" "2MDP"

REHEAT: 20KW, 460V, 3PH, 60Hz

FAN MOTOR(2EA): 1.1KW, 460V, 3PH, 60Hz, DEHUMIDIFIER

N

W/50A FUSES, NEMA 3R ENCL.

SAFETY SWITCH 3PH, 600V, 60A

W/40A FUSES, NEMA 1 ENCL.

SAFETY SWITCH 3PH, 600V, 60A

3-#8 "THWN" & 1-#10(G) IN 22mmC

3-#6 "THWN" & 1-#10(G) IN 28mmC

460V, 3PH, 60Hz, MCA:38.3

HEAT PUMP OUTDOOR UNIT

3/4HP, 460V, 3PH, 60Hz

EXIST. ROOF EXHAUST FAN-1

F

F

F

F

F

F

J

J

J

J

J

J

4A-2

4A-7

4A-5

4A-3

4A-4

4A-1

ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br

ELECTRICAL

KIM, CK

AS SHOWN

HGFEDCBA

DESIGNED BY

CHECKED BY

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJE…