SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
R-11SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
O & M
HOUSING DIV.
REVIEWED BY
UNITED STATES ARMY GARRISON DAEGU
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
DIRECTORATE OF PUBLIC WORK
HGFEDCBA
D - 22 - 07
CHON, HYON TAE
DESIGN REVIEW SIGNATURE
ORGANIZATION
USING AGENCY
36TH SIGNAL
MASTER PLN.
ENVIRONMENTAL
NAME SIGNATURE
O&M DIV.
FIRE DEPT.
SAFETY OFFICE
DPTMS(AT/FP)
188TH MP COM.
IND. HYGENIST
HA-00529-3J
UNIT #15746, APO AP 96218-5746
DRAWING NO.
CHIEF,
DESIGN & TECH. REVIEW Br.
YI, TONG KI
AS SHOWN
1 1 OF 1R - 1
T I T L E S H E E T
TITLE SHEET
DATE: 07 MAR 22
M - 12
M - 23
M - 34
M - 67
M - 78
M - 45
M - 56
MECHANICAL
BLDG. NO. S-821
REPLACE A/C AND HEATING SYSTEM,
BLDG. NO. S-821
REPLACE A/C AND HEATING SYSTEM,
CAMP CARROLL
PROJECT NO. HA-00529-3J, CAMP CARROLL
M - 89
M - 910
M - 1011
M - 1112
M - 1314
M - 1213
E - 418
E - 317
E - 216
E - 115
MECHANICAL
LEGEND, NOTES AND SCOPE OF WORK
LEGEND AND ABBREVIATIONS
EQUIPMENT SCHEDULE
GENERAL NOTES AND SCOPE OF WORK
NEW HVAC DUCT PLAN
NEW HVAC AND PLUMBING PIPING PLAN
NEW MECH. ROOM PARTIAL PLAN
AHU SCHEMATIC CONTROL DIAGRAM
DETAIL DRAWINGS - 1
DETAIL DRAWINGS - 2
DETAIL DRAWINGS - 3
HVAC POWER PLAN
PANEL BOARD DIAGRAM
REMOVAL / EXISTING HVAC AND PLUMBING PLAN
NEW MECH. ROOM PIPING ISOMETRIC DIAGRAM
H & V SYSTEM AND HOT WATER HEATING SYSTEM SCHEMATIC AND CONTROL DIAGRAM
POWER SINGLE LINE DIAGRAM, MECH. ROOM POWER PARTIAL PLAN AND DETAIL OF ARC FLASH LABELS
SCH
SA
SAN
QTY
R12, R22
RA
RDTR
RPM
RT
PG
PH
POC
POL
PPM
PRV
QT
OA
OAIL
OD
OS&Y
Pa
NTS
BUTTERFLY
CUBIC METER PER HOUR
AIR CONDITION (-ING,-ED)
AIR CONDITION UNIT (S)
AIR COOLED CONDENSING UNIT
CHILLED/HOT WATER RETURN
CHILLED/HOT WATER SUPPLY
REFRIGERANT LIQUID
CAP CAPACITY
CUBIC METER
COMPRESSOR
CONTINUE
CONNECTION
CPRSR
CU M
CONT
CONN
COUNTER CLOCKWISE
COEFFICIENT
CIRCUIT
CAST IRON PIPE
CHILLED WATER
CKT
CMH
COEF
CHW
CCW
CIP
ALARM CHECK VALVEACV
AVG AVERAGE
BAROMETER(-TRIC)
CENTIGRADEC
BARO
AMPERE(AMP, AMPS)
ALUMINUM
APPROX
AMP
AIR COND
AHU
AL
AIR COOLED
ACU
ACLD
ACCU
CHWS
CHWR
CHR
CHS
D
RL
DRAIN
KILOCALORIE PER HOUR
KILOGRAM PER SQ. CENTIMETER
KILOGRAM
THERMAL CONDUCTIVITY
IRON PIPE SIZE
ISOMETRIC
DIAMETER, INSIDE
FACE AREA OR FRESH AIR
EXTERNAL STATIC PRESSURE
EVAPORAT (-E,-ING,-ED,-OR)
ENTERING WATER TEMP
FIRE HOSE CABINET
EXPLOSION PROOF
FHC
FA
ESP
EVAP
EWT
EFF
ENT
EQPT
EP
EFFICIENCY
ENTERING
EQUIPMENT
KG
K
IPS
ISO
ID
NIC
N.O.
NO
MPS
N.C.
N/A
MM
MPH
MIN
MAX
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NORMALLY CLOSED
METERS PER SECOND
METERS PER HOUR
MINIMUM OR MINUTE
NOT APPLICABLE
MILLIMETER
MAXIMUM
HERTZ
HOSE BIBB
HEAD
HORSEPOWER
HOUR(S)
HOT WATER
HOT WATER HEATER
HORIZONTAL
FIBERGLASS REINFORCED PLASTIC
FREQUENCY
FLUSH VALVE
FEED WATER PUMP
FIXTURE
GAGE OR GAUGE
GALVANIZED STEEL
FUEL OIL
FEMALE PIPE THREAD
CIRCULATING WATER PUMPCWP
FRP
DECIBEL OR DRY BULB
DRY BULB TEMPERATURE
ENTERING AIR TEMPERATURE
DRY PIPE VALVE
DIRECT EXPANSION
DO DIESEL OIL
EAT
DPV
DX
DIV
DIAG
DIFF
DB
DBT
DIVISION
DIAMETER
DIAGRAM
DIFFERENCE
DEGREE
HR
HZ
HW
HWH
HORIZ
HB
HD
HP
GA
GALVS
FV
FWP
FXTR
CLOCKWISE OR COLD WATERCW
PLUG VALVE
THREE WAY
FREQ
FO
FPT
GATE, GLOBE
GATE, ANGLE
GLOBE
CONTROL
GATE
M
LPS
LWT
LT
LPH
LPD
LL
LG
LBS
LAT
LAV
L
KWH
KW
LITERS PER SECOND
LITERS PER HOUR
LEAVING WATER TEMPERATURE
METERS
LAUNDRY TRAY
LITERS PER DAY
LIQUID LINE
LEAVING AIR TEMPERATURE
POUNDS
LAVATORY
LENGTH
KILOWATT HOUR
KILOWATT
LITERS
P
STRAINER, BLOW OFF
STRAINER
PUMP (INDICATE USE)
KG/ SM KILOGRAM PER SQ. METER
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
PIPE TO BE REMOVED
MEDIUM TEMPERATURE HOT WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
RS
RD
(NAME)
(NAME)E EXISTING PIPE
HWR
HWS
MTWR
MTWS
CR
CS
PIPING
SANITARY DRAIN
CHECK, SWING
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
PLAN
HOSE BIBB
BALL
ELEV.
PIPE SLEEVE
BACKFLOW PREVENTER
FLOOR DRAIN
FLOOR CLEANOUT
FD
FCO
FLEXIBLE CONNECTOR
ANCHOR, INTERMEDIATE
ANCHOR, MAIN
EXPANSION JOINT
EXPANSION LOOP
EJ
RELIEF
SAFETY
HOSE END DRAIN
LOCK SHIELD
NEEDLE
PRESSURE REDUCING
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
CHECK, NON-SLAM
S
R
EP
PE
COLD WATER
VENT
AD FD
QUANTITY
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
SCHEDULE
SUPPLY AIR
SANITARY
REFRIGERANT (12, 22, ETC)
RETURN AIR
REVOLUTIONS PER MINUTE
REFRIGERATION TON
RADIATOR
TYP TYPICAL
UNIT HEATER
URINAL
UH
UR
SYMBOL
TEMPERATURE
THICKNESS
TONS
THK
TEMP
SYM
TD
OUTSIDE AIR INTAKE LOUVER
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PETROLEUM, OIL AND LUBRICANTS
POINT OF CONNECTION
PARTS PER MILLION
PERCENT/
QUART
PRESSURE GAGE
DIAMETER, OUTSIDE
OUTSIDE SCREW & YOKE
PASCAL
POLE
SPR SPRINKLER
STAINLESS STEEL
SQUARE
STEAM
STANDARD
STEEL
ST
STD
STL
SQ
SST
SPECIFICATION
SQUARE METER
STATIC PRESSURE
SPEC
SP
SM
OUTSIDE AIR
NOT TO SCALE
SECONDSEC
VAV VARIABLE AIR VOLUME
WATER CLOSET
VENTILATION
W/
WT
WC
WD
WITH
WEIGHT
WIDTH
W
WB
VOL
VEL
VENT
VERT
WATT
WET BULB
VOLUME
VELOCITY
VERTICAL
SMOKE DAMPER (PROVIDE ACCESS DOOR)
MANUAL VOLUME DAMPER
VAC
V
VACUUM
VOLT
SPLITTER DAMPER
AD
SD
VD
TEE, SINGLE SWEEP
TEE, OUTLET DOWN
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
ELBOW, TURNED DOWN
UNION, FLANGED
UNION, SCREWED
TEE, OUTLET UP
TEE
LATERAL
ELBOW, TURNED UP
CONNECTION, TOP
CONNECTION, BOTTOM
BUSHING
CAP
FIRE DAMPER (PROVIDE ACCESS DOOR)
BDD
TURNING VANES
TRANSITION
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FC
DUCT WORK
A B B R E V I A T I O N S
L E G E N D
PG
TM
AAV
FOS
3-WAY VALVE (MOTORIZED)
PRESSURE GAUGE
THERMOMETER
AUTOMATIC AIR VENT
GATE VALVE
CHECK VALVE
FUEL OIL SUPPLY
FLEXIBLE JOINTFJ
& STRAINER
M
CS
SD
SHOWER DRAIN
DEG
DIA or o
CEAT CONDENSER ENTERING AIR TEMP
LCWT LEAVING CHILLED WATER TEMP
FAIL FRESH AIR INTAKE LOUVER
EXPANSION JOINTEXPJT
EXST EXISTING
A / C AIR CONDITIONING
APPROXIMATELY
ARCH ARCHITECTURAL
BLDG BUILDING
CONC CONCRETE
DWG DRAWING
EA EACH
F.C.U. FAN COIL UNIT
MECH MECHANICAL
KCAL/ HR
KG/ SQ CM
HOT WATER SUPPLY
HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
V
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
AAV
ED EXHAUST DUCT
AUTOMATIC AIR VENT
AIR HANDLING UNIT
GROUND LEVELGL
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
SUPPLY AIR GRILLE OR
(200mm NECK DIAMETER)
CEILING DIFFUSER, ROUND TYPE
REGISTER, CEILING
EXHAUST AIR GRILLE OR
GRILLES, REGISTERS AND DIFFUSERS
SQUARE TYPE
CEILING DIFFUSER,
EG
ER
SG
SR
SG
SR
RG
RR
CD
200mm NCD
COWL, (GOOSENECK) AND FLASHING
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN810mm x 400mm
M
ELECTRIC MOTOR OPERATED DAMPER
S
MOTORIZED DAMPER
MD
SUPPLY AIR DUCT RISER
RETURN OR EXHAUST AIR DUCT RISER
SUPPLY AIR DUCT SECTION
RETURN AIR DUCT SECTION
GATE, GLOBE OR BALL VALVE
CHECK VALVE (FLOW)
ANGLE VALVE
STRAINER
DRIP CHECK VALVE
RESTRICTED ORIFICE
FILL CUP
PRESSURE GAUGE
SOLENOID VALVE
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLEXIBLE PIPE CONNECTION
RELAY
HOSE VALVE
TEST HEADER
SMOKE DAMPER
R
SD
S
: WATER MOTER ALARM GONG
SPRINKLER SYSTEM
: UP-RIGHT TYPE SPRINKLER
: PENDENT TYPE SPRINKLER
: SIDE WALL TYPE SPRINKLER
REMOVAL WORK
RELOCATED WORK
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
SA
RA
EA
VALVES, SPECIAL DUTY
HEATING
AIR CONDITIONING & REFRIGERATION
PLUMBING
VALVES : (for selective actuators)
BACK DRAFT DAMPER
CIRCUIT SETTER
POINT OF CONNECTIONPOC
POR POINT OF REMOVAL
TcH THERMOSTAT HEATING/COOLING
THERMOSTAT OF HEATING
REGISTER, CEILING
RETURN AIR GRILLE OR
Th
REDUCER, CONCENTRIC
M-1
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
1 17
DAMPERS
LEGEND AND ABBREVIATIONS
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
BLDG. NO. S-821
REPLACE A/C AND HEATING SYSTEM,
M-2
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
2 17
EQUIPMENT SCHEDULE
CAMP CARROLL
NAM, TAE CHIN
07 MAR 22
HA-00529-3J
(BTU/H)
CAPACITY
FILTER OUTSIDE AIRDX - HEATING COIL
CFM
PERCENT
20133,000
NECESSARY ACCESSORIES.
WITH DRAIN PAN, DIRECT EXPANSION REFRIGERANT COILS, PRE-FILTER AND
HORIZ. DISCHARGE, SINGLE ZONE, BELT DRIVEN, CENTRIFUGAL FAN EQUIPPED
FLOOR MOUNTED, DOUBLE WALLED CONSTRUCTION, HORIZONTAL TYPE, VERT. /
(BTU/H)
CAPACITY
166,510
SUPPLY FAN
CFM
MOTOR
HP POWER SUPPLY
DX - COOLING COIL
(SM)
FACE AREA
3,472
(mmAq)
T.S.P
50 3 460 V, 60 HZ, 3 PH
ROW
0.6356
MERV-8
PRE
DX - COOLING COIL
AIR HANDLING UNIT
HEATING & VENTILATING UNIT
CFM
MOTOR
KW POWER SUPPLY(mmAq)
T.S.P
16 460 V, 60 HZ, 3 PH
DEHUMIDIFIER
FAN CAPACITY
(BTU/H)
COOLING
(BTU/H)
HEATING
(KW)
REHEAT
214,289 81,906 241.5 x 2
CFM
MOTOR
KW POWER SUPPLY(mmAq)
T.S.P
16 460 V, 60 HZ, 3 PH
FAN CAPACITY
(BTU/H)
COOLING
(BTU/H)
HEATING
(KW)
REHEAT
160,717 68,255
1.1 x 2
5,650
7,416
SIMILAR TO "ACE R&A." MODEL NO. CRAC-150AU OR APPROVED EQUAL
SIMILAR TO "ACE R&A." MODEL NO. CRAC-200AU OR APPROVED EQUAL
SIMILAR TO "LG ELECTRONICS." MODEL NO. BAE0098HFA0 OR APPROVED EQUAL
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
(A)
MOP
(A)
MCA RATED AMPS (A)
COMP. BCOMP. A
POWER SUPPLY: 460V, 60HZ, 3PH
SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUM216DTE5 OR APPROVED EQUAL
13.915.5
38.35011,300243,000216,000
5.0
FAN
34.4
DISTRIBUTING OPERATION SYSTEM. AHRI CERTIFIED.
REFRIGERANT LIQUID, FOUR SEASONAL HERMETIC SAFETY COVER, MULTI
PROPELLER TYPE BLOW-THRU OUTDOOR FAN, ACCUMULATOR, R410A
BRIDGE CIRCUIT AIR-COOLED COIL WITH CORROSION RESISTANT COATING,
TYPE COMPRESSOR WITH MULTI POWER SYSTEM, SUB COOL INTERCHANGER
DIGITAL CONTROLLED INVERTER COMPRESSOR AND CONSTANT VELOCITY
CONDENSING UNIT SYSTEM FOR ABOVE-GROUND INSTALLATION. BUILT IN
OUTDOOR MOUNTED SEASONAL HEATING AND COOLING MULTI OUTDOOR
OUTDOOR HEAT PUMP UNIT
8 1
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
(A)
MOP
(A)
MCA RATED AMPS (A)
COMP. BCOMP. A
POWER SUPPLY: 460V, 60HZ, 3PH 9.211.4
28.53511,300189,000168,000
5.0
FAN
25.6
SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUM168DTE5 OR APPROVED EQUAL
7 1
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
(A)
MOP
(A)
MCA RATED AMPS (A)
COMP. BCOMP. A
POWER SUPPLY: 460V, 60HZ, 3PH
SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUM192DTE5 OR APPROVED EQUAL
12.214.8
35.75011,300216,000192,000
5.0
FAN
32.0
HOT WATER HEATING BOILER
(CMH)
INPUT
GAS
9 1
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
(A)
MOP
(A)
MCA RATED AMPS (A)
COMP. BCOMP. A
POWER SUPPLY: 208V, 60HZ, 1PH 19.5
403,885
1.0
FAN
20.5
SIMILAR TO "LG ELECTRONICS." MODEL NO. ARUN038GSS4 OR APPROVED EQUAL
38,000 42,000 25
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
POWER SUPPLY
(W)
POWER INPUT
208V, 60HZ, 1PH
SIMILAR TO "LG ELECTRONICS." MODEL NO. ARNU183SKA4 OR APPROVED EQUAL
19,100 39.5
21,500 424
INDOOR HEAT PUMP UNIT (WALL MOUNTED TYPE)
SYSTEM.
INDOOR WALL MOUNTED TYPE UNIT FOR HEATING AND COOLING INVERTER
(CFM)
FAN CAP.
(BTUH)
HEATING CAP.
(BTUH)
COOLING CAP.
POWER SUPPLY
(W)
POWER INPUT
208V, 60HZ, 1PH15,400
17,100 318 21
12 1
HP VOLT/PH/HZ
460 V, 3 PH, 60 HZ
CAPACITY
MOTOR
RPM
1,750
SIMILAR TO "LG ELECTRONICS." MODEL NO. BAB0207HFA0 OR APPROVED EQUAL
260 GPM AT 66 FT THD
HOT WATER CIRCULATING PUMP
UNIT HEATER
THERMOSTAT, UL LISTED.
EXPLOSION PROOF FAN MOTOR, HOT WATER COIL FACE LOUVER AND
CEILING HUNG, HORIZONTAL DISCHARGE, HEAVY GAUGE STEEL ENCLOSURE,
1/20
(BTUH)
HEATING CAP.
(GPM)
WATER FLOW
( C)
EWT
( C)
EAT
( C)
LWT FAN CAP.
CFM RPM HP
115V, 60HZ, 1PH
82 32
(BTUH)
HEATING CAP.
(GPM)
WATER FLOW
( C)
EWT
( C)
EAT
( C)
LWT FAN CAP.
CFM RPM
115V, 60HZ, 1PH
82 32
27,397
14,297
2.7
1.45
1,550
1,550 1/20
HP
POWER SUPPLY
(CFM)
CAPACITY
(HP)
FAN MOTOR
460 V, 60 HZ, 3 PH
VIBRATION ISOLATORS AND STANDARD ACCESSORIES.
DUCT MOUNTED, IN-LINE CENTRIFUGAL FAN, CORROSION RESISTANT, EQUIPPED W/
IN-LINE DUCT FAN
POWER SUPPLY
(CFM)
CAPACITY
(HP)
FAN MOTOR
ROOF EXHAUST FAN
277 V, 60 HZ, 1 PH1,000 AT 0.26 SP (Inches wg) 1/ 4
17 1
115 V, 60 HZ, 1 PH1/ 22,100 AT 0.26 SP (Inches wg)
277 V, 60 HZ, 1 PH1/ 418 3
W/ DISCONNECT SWITCH, BIRD SCREEN, BACKDRAFT DAMPER.
ROOF CURB MOUNTED, CENTRIFUGAL TYPE WEATHER-PROOF ALUMINUM HOSING
D E S C R I P T I O NQ’ TY
NO.
ITEM
D E S C R I P T I O NQ’ TY
NO.
ITEM
D E S C R I P T I O NQ’ TY
NO.
ITEM
D E S C R I P T I O NQ’ TY
NO.
ITEM
E Q U I P M E N T S C H E D U L E
700 AT 0.26 SP (Inches wg)
PIPE TAPPING.
PRESSURE, EQUIPPED W/ HEAVY DUTY REMOVABLE BLADDER AND NECESSARY
AND PRESSURE VESSEL CODE (ASME BPVC SEC VIII D1), MAX. 125 PSI WORKING
CLOSED ROUND DIAPHRAGM TYPE, SHELL CONFORMING TO ASME CODE
(GAL)
TANK CAP. (ACCEPTANCE VOLUME)
(DIA x LG)
TANK SIZE
15" x 25"
HOT WATER EXPANSION TANK
AIR SEPARATOR
GALVANIZED STEEL STRAINER, BLOWDOWN AND COLD WATER CONNECTION.
CONNECTION CONSIST OF STAINLESS STEEL AIR COLLECTOR TUBE,
PIPE MOUNTED, ASME CODE AND STAMPED FOR 125 PSI @ 350 F, THREADED
(PSI)
WORKING PRESSUREPIPE SIZE (MM)
INLET OUTLET
80 125
ELEC. POWER
DOMESTIC HOT WATER HEATER
1729111.6
(LPH)
RECOVERY
HEAT
FLA: 2, 120 V, 1 PH, 60 HZ 60 C 16.7 C
(KW)
OUTPUT
GROSS
ELEC. POWER
TEMP.
SUPPLY
RISE
TEMP.
DOMESTIC WATER EXPANSION TANK
ACROSS-THE-LINE MAGNETIC CONTROLLER IN A NEMA 250 AND NEMA MG 1.
ALL BRONZE CONSTRUCTION. MOTORS SHALL BE EQUIPPED WITH AN
IN-LINE CLOSED COUPLED CENTRIFUGAL TYPE, FLANGE CONNECTION AND
(GAL)
TANK CAP. (ACCEPTANCE VOLUME)
(DIA x LG)
TANK SIZE
12" x 18"6
PROVIDE W/ ELECTRIC EXPANSION VALVE, REHEAT COIL
SPLIT SYSTEM DEHUMIDIFIER, AIR COOLED, FLOOR STANDING, UP FLOW TYPE.
(BTU/H)
CAPACITY
355,994
SUPPLY FAN
CFM
MOTOR
HP POWER SUPPLY
7,304
(mmAq)
T.S.P
5 460 V, 60 HZ, 3 PH 1.2614
HEATING COIL
HEATING COIL
2,530 AT 0.5" SP (Inches wg)
(C )
EWT
SIMILAR TO "LG ELECTRONICS." MODEL NO. ARNU153SJA4 OR APPROVED EQUAL
(MBH)
OUTPUT
GROSS
728 FLA: 16, 120 V, 1 PH, 60 HZ 80
( C)
TEMP.
SUPPLY
(PSI)
PRESS
MAX.
ACCESSORIES.
WITH DRAIN PAN, HOT WATER HEATING COIL, PRE-FILTER AND NECESSARY
HORIZ. DISCHARGE, SINGLE ZONE, BELT DRIVEN, CENTRIFUGAL FAN EQUIPPED
FLOOR MOUNTED, DOUBLE WALLED CONSTRUCTION, HORIZONTAL TYPE, VERT. /
(SM)
FACE AREA
ROW
82.2
MERV-8
PRE
FILTER
PERCENT
CFM
OUTSIDE AIR
7,304 100-9.5
(C )
EAT
15.6
(C )
LAT
ACCESSORIES. ASME, AHRI AND CSA CERTIFIED PRODUCT.
CASCADE SYSTEM, MODULE TYPE CONDENSING WATER HEATER WITH STANDARD
ACCESSORIES. ASME, AHRI AND CSA CERTIFIED PRODUCT.
CASCADE SYSTEM, MODULE TYPE CONDENSING WATER BOILER WITH STANDARD
GENERAL NOTES
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR AREA.
4. ALL WALL / FLOOR / ROOF OPENINGS RESULTING FROM THE REMOVAL OF PIPING AND
AS DIRECTED BY THE CONTRACTING OFFICER.
EXISTING AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS
5. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO
CEILING, ROOF, EQUIPMENT, PIPE, DUCT AND ELECTRICAL ITEMS.
PREVENTION SYSTEM WITH NO ADDITIONAL COST TO THE GOVERNMENT SUCH AS WALLS,
ITEMS TO MAKE WAY FOR THE INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE
18. THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND REINSTALL THE OBSTRUCTED
SPECIFICATIONS.
CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE CONTRACT
OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH MAY DEVIATE FROM THAT SHOWN ON
SYSTEM TO SATISFY ALL FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS
17. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL
9. ANY PIPES THAT PENETRATE FIRE RATED WALLS (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
TO ENSURE PROPER OPERATION, AS ORIGINALLY INTENDED.
EQUIPMENT. THE CONTRACTOR SHALL TEST, ADJUST AND BALANCE EQUIPMENT AS REQUIRED
14. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY START-UP AND TESTING OF THE NEW
AND SHALL BE VERIFIED AT THE JOB SITE.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC, ARE APPROXIMATE
PRIOR TO COMMENCING CONSTRUCTION FOR APPROVAL.
ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR
3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY TO THE
CONTRACTING OFFICER’S APPROVAL.
REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER’S
PRIOR TO COMMENCING ANY CONSTRUCTION OR REPAIR.
EQUIPMENT, DUCTWORK, PIPING, DIMENSIONS AND ETC. UNDER THE SUPERVISION OF C.O.R
1. THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION,
A SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
10. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWING.
THE REQUIREMENTS OF SEAL CLASS C.
TO SMACNA STATIC PRESSURE CONSTRUCTION CLASS 500PA AND DUCTWORK SHALL MEET
7. THE SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING
START OF CONSTRUCTION.
PLAN SHALL BE SUBMITTED TO AND APPROVED BY DPW AND THE USER, PRIOR TO THE
USER TO FULLY UTILIZE THE FACILITY DURING THE CONSTRUCTION PERIOD. THIS PHASING
SHALL PROVIDE A PHASING PLAN FOR CONSTRUCTION COMPLETION ALLOWING FOR THE
FACILITY BE FULLY OPERATIONAL DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR
19. DUE TO THE CRITICAL NATURE OF THE FACILITY FUNCTION, IF IT IS REQUIRED THAT THE
CONTRACTOR.
THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY THIS
THE EXISTING EQUIPMENT, NEW EQUIPMENT, DUCT WORK, PIPING AND ETC. DAMAGES DUE TO
11. CONNECTIONS TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE
FOR APPROVAL.
DESIGN & TECHNICAL REVIEW BRANCH VIA C.O.R. PRIOR TO COMMENCING CONSTRUCTION
12. THE CONTRACTOR SHALL SUBMIT MANUFACTURER’S INSTALLATION SHOP DRAWINGS TO THE
SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)".
15. ALL EQUIPMENT AND MATERIALS SHALL MEET THE REQUIREMENTS OF "STANDARD TECHNICAL
ADDITIONAL COST TO THE PROJECT CONTRACT.
THE DETAILS WILL BE UTILIZED TO ACCOMPLISH THE MECHANICAL SCOPE OF WORK AT NO
O & MA PROJECTS, KOREA (NOVEMBER 30, 2015)" FORM AS A PART OF THIS PROJECT.
16. THE MECHANICAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL DRAWINGS FOR
REVIEW BRANCH FOR APPROVAL BEFORE COMMENCING THE WORK.
13. THE CONTRACTOR SHALL SUBMIT ALL MATERIAL INFORMATION TO THE DESIGN & TECHNICAL
SUCH AS ANCHORS, HANGERS, SUPPORTS, ETC.
8. ALL PIPES, DRAINS AND DUCTWORK TO BE REMOVED SHALL INCLUDE ALL ITS ACCESSORIES
AS ORIGINALLY INTENDED.
AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT CONNECTION TO FUNCTION
ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION, REMOVE THE EXISTING DUCTWORK
& LOCATION PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING. IF THE EXISTING DUCT
6. THE CONTRACTOR SHALL COORDINATE WITH THE EXISTING DUCTWORK AND PIPING ELEVATION
CONSTRUCTION.
20. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF CORE DRILLING DURING
M-3
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
US ORIGIN MATERIALS:
AS INDICATED ON THE DRAWINGS.
INTERNET SITE HTTP:// WWW.CCKBID.COM). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE
DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS",
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL
SCOPE OF WORK
WORK CLASS: "K" (REPAIR / MAINTENANCE WORK)
3 17
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
8. REPLACE EXISTING FIRE EXTINGUISHER CABINET AS INDICATED.
7. RESTORE EXISTING CEILING FINISHES AFTER HEAT PUMP UNIT INSTALLATION.
GENERAL NOTES AND SCOPE OF WORK
BLDG. NO. S-821
REPLACE A/C AND HEATING SYSTEM,
ACCESSORIES PARTS FOR THIS SYSTEM.
WIRE-MESH SCREENS, CONCRETE PADS, CONCRETE SPLASH BLOCKS AND ALL NECESSARY
PIPES, CONDENSATE PIPES, INSULATION, INSULATION JACKETING, THERMOSTATS, STAINLESS STEEL
2. PROVIDE NEW SPLIT SYSTEM DEHUMIDIFIERS COMPLETE WITH ASSOCIATED REFRIGERANT
5. PROVIDE COMPLETE CLEANING OF ALL EXISTING DUCTWORK TO THE ACCEPTANCE OF THE COR.
6. REMOVE AND REINSTALL EXISTING DDC SYSTEM IN MECHANICAL ROOM.
ACCESSORIES PARTS FOR THIS SYSTEM.
WIRE-MESH SCREENS, CONCRETE PADS, CONCRETE SPLASH BLOCKS AND ALL NECESSARY
PIPES, CONDENSATE PIPES, INSULATION, INSULATION JACKETING, THERMOSTATS, STAINLESS STEEL
3. PROVIDE NEW SPLIT SYSTEM HEAT PUMP UNITS COMPLETE WITH ASSOCIATED REFRIGERANT
A FULLY REPLACEMENT.
PREVENTION ASSEMBLY, SMOKE STACK, AND ASSOCIATED ACCESSORIES AND PARTS NECESSARY FOR
INSULATION, JACKETING, STAINLESS STEEL WIRE-MESH SCREENS, CONCRETE PADS, BACKFLOW
DAMPERS, THERMOSTATS, GAS LINE AND TRAIN ASSEMBLY, CHEMICAL FEEDER, EXHAUST FANS, OARC, PANELS, PUMP, EXPANSION TANK, AIR SEPARATOR, DUCTWORK, PIPES, UNIT HEATERS, GAUGES, VALVES, UNIT, HEATING AND VENTILATING UNIT, HOT WATER BOILER, HEAT PUMP OUTDOOR UNIT, CONTROL
1. REPLACE EXISTING DETERIORATED HVAC SYSTEM WITH NEW ONE INCLUDING, AIR HANDLING
ASSEMBLY AND ALL NECESSARY ACCESSORIES PARTS FOR THIS SYSTEM.
BACKFLOW PREVENTION ASSEMBLY, CONCRETE PADS, VALVES, GAUGES, GAS LINE AND TRAIN
HEATER, EXPANSION TANK, DOMESTIC WATER PIPING, SMOKE STACK, DAMPERS, INSULATION,
4. REPLACE EXISTING PLUMBING SYSTEM WITH NEW ONE INCLUDING DOMESTIC HOT WATER
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
FD
FD
FD
EXTINGUISHER CABINET
RE-LOCATE EXIST. FIRE EXTINGUISHER TO NEW FIRE
CABINET AND RECOVER EXIST. WALL
REMOVE EXIST. SEMI-RECESSED FIRE EXTINGUISHER
EXIST. FIRE DEPT. CONNECTION
EXIST. 2" MAIN WATER LINE
EXIST. 8" FIRE PROTECTION MAIN LINE
GAS METER ASSEMBLY CABINET TO REMAIN
EXIST. GAS FILTER & REGULATOR W/
TO REMAIN
EXIST. ROOF GOOSENECK
SHUT-OFF VALVE AND GAS ALARM GONG TO REMAIN
EXIST. GAS LEAK DETECTION CONTROL PANEL, AUTO EMERGENCY
TO WEAPON STORAGE
EXIST. DHW & DCW LINES
WEAPON STORAGE
EXIST. DCW LINE TO
TO REMAIN
EXIST. AIR COMPRESSOR
SYSTEM TO REMAIN
EXIST. DRY PIPE FIRE SPRINKLER
TO REMAIN
EXIST. GAS LEAK DETECTOR
CONC. PAD W/ ASSOCIATED PIPING AND PARTS
REMOVE EXIST. AIR CONDENSING UNIT AND
AND ASSOCIATED ACCESSORIES AND PARTS
INSULATION, BACKFLOW PREVENTION ASSEMBLY, SMOKE STACK,
& TRAIN ASSEMBLY, CHEMICAL FEEDER, EXHAUST FAN, OARC,
HEATER, GAUGES, VALVES, DAMPER, THERMOSTATS, GAS LINE
EXPANSION TANK, AIR SEPARATOR, DUCTWORK, PIPES, UNIT
VENTILATING UNIT, AIR HANDLING UNIT, CONC. PADS, PUMPS,
HOT WATER BOILER, DOMESTIC WATER HEATER, HEATING &
REMOVE EXIST. HVAC AND PLUMBING SYSTEMS INCLUDING
DCW LINES
EXIST. DHW &
VENT LINE
EXIST. SEWER
WATER LINE
EXIST. SPRINKLER
TO REMAIN
EXIST. 50 SEWER VENT LINE
TO REMAIN
EXIST. 150 SPRINKLER WATER LINE
1200x450 S.A.
600x500 R.A.
600x500 S.A.
Th
Th
Th
Th
Th
Th
TO REMAIN
EXIST. HOT WATER LINES
UNIT HEATERS AND THERMOSTATS
REMOVE EXIST. HOT WATER LINES,
(TYP. OF 4)
ABANDON EXIST. STEEL SECURITY BAR
REMOVE EXIST. ROOF EXHAUST FAN /
TO REMAIN
EXIST. ROOF EXHAUST FAN
TO REMAIN
EXIST. ROOF EXHAUST FAN
EXIST. MAIN GAS LINE TO REMAIN
- M-4
P-1
SCALE : 1 / 100
LEGEND
TO BE REMOVED
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
KEY PLAN
BLDG.#821
REMOVAL / EXISTING HVAC AND PLUMBING PLAN
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
SPECIFIC NOTES
SHALL BE PATCHED AND FILLED OR RESTORED.
2. THE OPENING RESULTING FROM THE REMOVAL OF HVAC UNITS
EQUIPMENT, DUCTWORK AND PIPING SHALL BE VERIFIED IN FIELD.
3. EXACT SIZES, LOCATIONS AND DIRECTIONS OF EXISTING HVAC
M-44 17
PLUMBING PLAN
REMOVAL / EXISTING HVAC AND
(TYP. OF 4)
TO REMAIN
SECURITY BAR
EXIST. FD AND
& PIPING SHALL BE VERIFIED IN FIELD.
THEREFORE, EXACT SIZE, LOCATION AND DIRECTION OF HVAC DUCT
1. EXISTING HVAC PLANS MAY NOT EXACTLY MATCH THE FIELD AND
N
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
600x500 R.A.
500x250
1200x450 S.A.
600x500 S.A.
300x200
- M-7
SEE
AND RE-LOCATED EXIST. FIRE EXTINGUISHER
NEW WALL MOUNTED FIRE EXTINGUISHER CABINET
P-1
SCALE : 1 / 100M-5
NEW HVAC DUCT PLAN
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
ROOF EXHAUST FAN
EXIST. ROOF EXHAUST FAN-2
EXIST. ROOF EXHAUST FAN-1
-1 ROOF EXHAUST FAN
-2 ROOF EXHAUST FAN
-3 ROOF EXHAUST FAN
CAMP CARROLL
NEW HVAC DUCT PLAN
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
SPECIFIC NOTES
SITE CONDITIONS. THE CONTRACTOR SHALL VERIFY THEM.
MAY CHANGE DEPENDING ON MANUFACTURER’S RECOMMENDATION AND
3. SIZES AND LAYOUTS OF DUCTWORK AND REFRIGERANT & DRAIN PIPING
INSTALLATION GUIDE.
CONFIGURATION. THE CONTRACTORS SHALL FOLLOW THE MANUFACTURER’S
2. THIS DRAWING SHOWS SUGGESTED EQUIPMENT, DUCTWORK AND PIPING
DRAWINGS OF HVAC SYSTEMS AND EQUIPMENT SHOWING LOCATIONS.
1. THE CONTRACTOR SHALL PROVIDE MANUFACTURER’S DETAILED SHOP
WITH SEALANT.
14. THE CONTRACTOR SHALL CAULK AT THE BASE OF ALL DUCT PENETRATION
FIELD CONDITIONS.
15. ALL HVAC UNITS, PIPES AND DUCTS SHALL BE INSTALLED ACCORDING TO
DEPENDING ON SITE CONDITIONS.
5. THE SIZES OF SUPPLY / RETURN AIR DUCTS AND CHAMBERS MAY CHANGE
PROOF PADS WHERE NECESSARY.
16. THE CONTRACTOR SHALL INSTALL DUCT SUPPORTS AND VIBRATION
MATERIALS.
17. THE VIBRATION PROOF PADS SHALL BE MADE OF CORROSION-RESISTANT
EQUIPMENT MAINTENANCE.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ARRANGING A SPACE FOR
BOXES.
12. ALL THERMOSTATS AND CONTROLLERS SHALL BE INSTALLED WITH LOCK
WHERE NECESSARY.
9. THE CONTRACTOR SHALL INSTALL VOLUME DAMPERS AND FIRE DAMPERS
10. FIRE DAMPERS SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 90A.
11. 600 x 600 ACCESS DOORS SHALL BE PROVIDED AT ALL DAMPER LOCATIONS.
IN ACCORDANCE WITH MANUFACTURER’S INSTALLATION INSTRUCTIONS.
4. CLEARANCE DISTANCE FOR ALL HVAC EQUIPMENT SHALL BE DETERMINED
6. ALL DUCTS FOR HVAC SYSTEM SHALL BE INSULATED.
AND SMOKE DETECTORS FOR HVAC SYSTEM WHERE NECESSARY.
7. THE CONTRACTOR SHALL INSTALL TEMPERATURE & HUMIDITY SENSORS
INSTALLING ROOF EXHAUST FANS AND SMOKE STACKS.
13. THE CONTRACTOR SHALL REUSE EXISTING OPENINGS IN THE ROOF WHEN
M-55 17
P-1
N
M-6
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
Tch
Tch
THERMOSTAT (TYP. OF 2)
HPU CONTROLLER W/
Th
Th
Th
Th
Th
Th
(TYP. OF 6)
THERMOSTAT FOR UNIT HEATER
- M-7
SEE
P-2
TO WEAPON STORAGE
EXIST. DHW & DCW LINES
WEAPON STORAGE
EXIST. DCW LINE TO
LINES TO TOILET
EXIST. DHW & DCW
EXIST. 40 STEEL PIPE
DIELECTRIC UNION
NEW 40 COPPER PIPE
20, 20
20, 20
4040, 20
32, 25
25, 32
25, 40
40, 20
RS=15.88
RL=9.52
RS=28.58
RL=15.88
RS=28.58
RL=15.88
RS=28.58
RL=15.88
RS=15.88
RL=9.52
RS=12.7
RL=6.35
HWR
HWS
HWR
HWS
HWR
HWS
H W
S
H W
R
H W
S
H W
R
P-1
SCALE : 1 / 100M-6
NEW HVAC AND PLUMBING PIPING PLAN
GRAPHIC SCALE
SCALE: 1 : 100
4000mm
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
SPECIFIC NOTES
INSTALLATION GUIDE.
CONFIGURATION. THE CONTRACTORS SHALL FOLLOW THE MANUFACTURER’S
2. THIS DRAWING SHOWS SUGGESTED EQUIPMENT, DUCTWORK AND PIPING
INSULATED.
6. ALL REFRIGERANT & DRAIN PIPING FOR HEAT PUMP UNITS SHALL BE
ON HEAT PUMP OUTDOOR UNITS.
10. THE CONTRACTOR SHALL INSTALL STAINLESS STEEL WIRE-MESH SCREENS
WITH SEALANT.
12. THE CONTRACTOR SHALL CAULK AT THE BASE OF ALL PIPE PENETRATION
HVAC SYSTEM IS FULLY OPERATIONAL AND FUNCTIONAL.
16. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT NEW
THE MANUFACTURER’S INSTALLATION GUIDE.
11. CONCRETE PAD SIZES SHALL BE DETERMINED BY EQUIPMENT SIZES AND
4. ALL REFRIGERANT LINES SHALL BE VIBRATION ISOLATED.
CONNECTIONS THAT MEET ASME B31.5 REQUIREMENTS.
5. PIPING AND TUBING FOR VRF SYSTEMS SHALL HAVE ALL BRAZED
DRAWINGS OF HVAC SYSTEMS AND EQUIPMENT SHOWING LOCATIONS.
1. THE CONTRACTOR SHALL PROVIDE MANUFACTURER’S DETAILED SHOP
SITE CONDITIONS. THE CONTRACTOR SHALL VERIFY THEM.
MAY CHANGE DEPENDING ON MANUFACTURER’S RECOMMENDATION AND
3. SIZES AND LAYOUTS OF DUCTWORK AND REFRIGERANT & DRAIN PIPING
UP WITH PIPE JACKETS.
7. ALL EXPOSED REFRIGERANT & CONDENSATE PIPES SHALL BE COVERED
BOXES.
9. ALL THERMOSTATS AND CONTROLLERS SHALL BE INSTALLED WITH LOCK
DRAINAGE SYSTEM.
14. THE SLOPE OF DRAIN LINES SHALL BE SUFFICIENT TO PROVIDE A GRAVITY
FIELD CONDITIONS.
13. ALL HVAC UNITS, PIPES AND DUCTS SHALL BE INSTALLED ACCORDING TO
IN ACCORDANCE WITH MANUFACTURER’S INSTALLATION INSTRUCTIONS.
8. CLEARANCE DISTANCE FOR ALL HVAC EQUIPMENT SHALL BE DETERMINED
OF OUTDOOR HEAT PUMP UNIT COULD BE OBSTRUCTED.
15. THE CONTRACTOR SHALL RELOCATE EXISTING BULLET TRAP IF INSTALLATION
6 17
NEW HVAC AND PLUMBING PIPING PLAN
N
M-7
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
Th OARC
21 DOMESTIC HOT WATER HEATER
THERMOSTATIC MIXING VALVE
EXIST. AIR COMPRESSOR
EXIST. DRY PIPE FIRE SPRINKLER SYSTEM
TT
3/4" HOSE BIBB
EXIST. GAS ALARM GONG
PRESSURE RELIEF VALVE
EXIST. GAS LEAK DETECTION CONTROL PANEL
13 UNIT HEATER
THERMOSTAT FOR UNIT HEATER
W/ GAS METER ASSEMBLY CABINET
EXIST. GAS FILTER & REGULATOR
12 HOT WATER CIRCULATING PUMP
HEATING & VENTILATING UNIT2
PRESSURE RELIEF VALVE
5 HOT WATER HEATING BOILER
EXIST. DCW LINE TO WEAPON STORAGE
WEAPON STORAGE
EXIST. DHW & DCW LINES TO
EXIST. DHW & DCW LINES TO TOILET
MODULATING 3-WAY CONTROL VALVE
BACKFLOW PREVENTER
CHEMICAL FEEDER
PRESSURE REDUCING VALVE
20 AIR SEPARATOR
19 HOT WATER EXPANSION TANK
DOMESTIC EXPANSION TANK
WORKBENCH & PROCESSING AREA
EXIST. HOT WATER LINES FROM / TO
NEW GAS LINE
OUTDOOR AIR TEMP SENSOR
OUTDOOR AIR RESET CONTROLLER
REMOTE BULB FOR COOLING / HEATING
OUTDOOR AIR THERMOSTAT W/
EXIST. FIRE DEPT. CONNECTION
EXIST. 2" MAIN WATER LINE
EXIST. 8" FIRE PROTECTION MAIN LINEEXIST. AUTO EMERGENCY SHUT-OFF VALVE
EXIST. DRY PIPE FIRE SPRINKLER SYSTEM
EXIST. AIR COMPRESSOR
21 DOMESTIC HOT WATER HEATER
5 HOT WATER HEATING BOILER
600x500 S.A.
600x500 R.A.
FD
FD
FD
HEATING & VENTILATING UNIT2
EXIST. ROOF GOOSENECK
x5
O .A
PLENUM BOX
600x600 COMBUSTION AIR
AND CONNECT TO ROOF GOOSENECK
600x500 RELIEF AIR DUCT UP THRU ROOF
1200x450 S.A.
1000x350 R.A. DUCT DROP
1500x500 O.A. DUCT DROP
2000x1800
BIRD SCREEN AND PLENUM BOX BEHIND
3400x1800 O.A. & COMBUSTION AIR INTAKE LOUVER W/
AIR HANDLING UNIT
600x300 DROP
M
12 HOT WATER CIRCULATING PUMP
19 HOT WATER EXPANSION TANK
1600x900
16 ROOF EXHAUST FAN
OUTDOOR HPU
OUTDOOR HPU
OUTDOOR HPU
T
THERMOSTAT FOR ROOF EXHAUST FAN
TOP AND BOTTOM
OPENING W/ SCREEN AT
600x300 COMBUSTION AIR
EXIST. GAS LEAK DETECTOR
DIELECTRIC UNION
BRONZE GATE VALE
COPPER ADAPTER 40
20, 20
40, 40
RS=28.58
RL=15.88
32, 32
EXIST. MAIN GAS LINE
HWR
HWS
P-1
SCALE : 1 / 50M-7
NEW MECH. ROOM DUCT PARTIAL PLAN
P-2
SCALE : 1 / 50M-7
NEW MECH. ROOM PIPING PARTIAL PLAN
GRAPHIC SCALE
1000 2000mm
SCALE: 1 : 50
1 AIR HANDLING UNIT
IN-LINE DUCT FAN
SEQUENCE OF OPERATION FOR FAN
SET POINT. WHENEVER FAN IS ENERGIZED, DAMPAER-1 SHALL OPEN.
THERMOSTAT FOR ROOF EXHAUST FAN SHALL CONTROL FAN TO MAINTAIN ITS
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
SPECIFIC NOTES
FOLLOW THE MANUFACTURER’S INSTALLATION GUIDE.
1. THIS DRAWING SHOWS SUGGESTED PIPING CONFIGURATION. CONTRACTORS SHALL
GAS PIPING AND ACCESSORIES.
3. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR THE INSTALLATIONS OF
4. THE CONTRACTOR SHALL CONSULT GAS SUPPLIER FOR GAS PIPE SIZING.
2. THE CONTRACTOR SHALL INSTALL GAUGES WHERE NECESSARY.
BETWEEN THE RPZ RELIEF VALVE OPENING AND ANY DISCHARGE PIPING.
AN AIR GAP NOT LESS THAN TWICE THE DIAMETER OF THE RELIEF PORT OPENING
5. THE REDUCED PRESSURE BACKFLOW PREVENTER SHALL BE PROVIDED WITH
6. CONCRETE PAD SIZES SHALL BE DETERMINED BY EQUIPMENT SIZES.
SO ALL INDIVIDUAL STACKS SHALL BE COMBINED INTO ONE SMOKESTACK.
7. THE CASCADE TYPE OF BOILER AND HEATER HAVE STACKS IN EACH UNITS.
8. CLEARANCE DISTANCE FOR EXISTING ELECTRIC PANEL SHALL BE 3 FEET MINIMUM.
EXIST. ELECTRIC PANEL (SEE SPECIFIC NOTES NO. 8)
80, 80
7 17
NEW MECH. ROOM PARTIAL PLAN
N
MOTORIZED DAMPER - 1
1000x600 O.A. INTAKE OPENING W/
M-8
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
M
I-1
M-8
NEW MECH. ROOM PIPING ISOMETRIC DIAGRAM
NOT TO SCALE
DOMES
TIC
E
XP
ANSIO
N
TA
NK
WEAPON STORAGE
EXIST. DHW & DCW LINES TO
EXIS
T.
DCW
LIN
E
TO
WEAP
ON
ST
ORAGE
PRESSURE RELIEF VALVE
AIR
S
EP
ARAT
OR
MI
XIN
G
VAL
VE
TH
ER
MOST
AT
IC
CONTROL VALVE
MODULATING 3-WAY
BACKFLOW PREVENTER VAL
VERE
DUCIN
G
PR
ES
SURE
DOMES
TIC
H
OT
WAT
ER
H
EAT
ER
HOT
WAT
ER
H
EAT
ING
BOI
LE
R
PR
ES
SURE
R
EL
IEF
V
AL
VE
WAT
ER
M
ET
ER
PR
ES
SURE
R
EDUCIN
G
VAL
VE
BACKF
LO
W
PR
EVE
NTE
R
UNIT HEATER
H
OSE
B
IBB
FE
EDER
CHEMI
CAL
HOT WATER CIRCULATING PUMP
HOT WATER EXPANSION TANK
HEAT
ING
VE
NTIL
AT
ING
UNIT
AIR
H
ANDLIN
G
UNIT
OUTDOOR HPU
EXIS
T.
DHW
DCW
LIN
ES
T
O
TO
ILE
T
WORKBE
NCH
PR
OCES
SIN
G
ARE
A
EXIS
T.
HOT
WAT
ER
L
INES
F
ROM
/ T
O
, 3
50,32
65, 65 20 , 2
RS
.58
RL
15.
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
50,32
40, 40
, 4
8 17
ISOMETRIC DIAGRAM
NEW MECH. ROOM PIPING
M-9
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
R.A.
M
N.C.
N.O.
FILTER
C
SDTS
TS 2
1TS
LT
DX
N.C.
SMOKE DETECTOR
S.A. SENSOR
TO SPACE
SUPPLY FANDX COILFREEZESTAT
LOW TEMP
GAUGE
MAGNEHELIC
RETURN FAN
SUPPLY FAN
INTERLOCK W/
SENSOR
R.A. TEMP.
COOLING (ADJ.)
SET AT 24 C FOR
HEATING (ADJ.)
SET AT 20 C FOR
MOTORS
OA / RA DAMPER
RELIEF AIR
O.A.
O.A. TEMP. SENSOR
MOTOR (TYP.)
E.A. DAMPER
R S
R L
D-1
M-9 NOT TO SCALE
AHU SCHEMATIC CONTROL DIAGRAM
6.
5.
4.
3.
2.
1.
7.
GENERAL:
SAFETY CONTROLS:
DUCT, AHU SHALL BE TURNED OFF. MANUAL RESET IS REQUIRED.
WHEN SUPPLY DUCT SMOKE DETECTOR SENSES SMOKE IN THE SUPPLY 2.1
2.2
OCCUPIED HEATING MODE:
3.1
3.2
UNOCCUPIED HEATING MODE:
4.1
CLOSED. FACE & BYPASS DAMPER SHALL BE IN THE FULL FACE POSITION.
SHALL BE FULLY OPEN AND O.A. & E.A. DAMPERS SHALL BE FULLY
DURING UNOCCUPIED MODE, AHU SHALL BE DE-ENERGIZED. R.A. DAMPER
4.2
OCCUPIED COOLING MODE:
5.1 SAME AS PARAGRAPH 3.1
5.2
5.3
UNOCCUPIED COOLING MODE:
SAME AS PARA. 4.1.6.1
SYSTEM INTERLOCKS:
6.1
RETURN FAN SHALL OPERATE ONLY WHEN AHU FAN IS OPERATING.
RETURN FAN SHALL BE INTERLOCKED WITH AHU CONTROL SO THAT
AHU (AIR HANDLING UNIT) SEQUENCE OF OPERATION
SPECIFIC NOTES
AND RECOMMENDATION.
IN ACCORDANCE WITH MANUFACTURER’S INSTALLATION GUIDE
1. THE CONTROL EQUIPMENT FOR AHU SHALL BE DETERMINED
M
FROM CONTROLLERTO CONTROLLER
EEV
TO CONTROLLER
TO CONTROLLER
TO CONTROLLER
FROM CONTROLLER
MINIMUM CFM OF O.A. AS SCHEDULED.
MANUAL POSITION POTENTIOMETER SHALL BE SET TO INTRODUCE
MINIMUM O.A. POSITION AND E.A. DAMPERS SHALL BE CLOSED. THE
WHEN AHU FAN MOTOR START O.A./R.A. DAMPERS SHALL BE AT
(ADJUSTABLE)
PROGRAMMABLE THERMOSTAT TO MAINTAIN R.A. TEMPERATURE AT 24.0 C.
AND S.A SENSOR (TS2, AS ANTICIPATOR) SHALL SEND A SIGNAL TO THE
O.A. TEMP. SENSOR (TS0) AND ASSOCIATED R.A. TEMP. SENSOR (TS1)
(ADJUSTABLE)
PROGRAMMABLE THERMOSTAT TO MAINTAIN R.A. TEMPERATURE AT 20 C.
AND S.A SENSOR (TS2, AS ANTICIPATOR) SHALL SEND A SIGNAL TO THE
O.A. TEMP. SENSOR (TS0) AND ASSOCIATED R.A. TEMP. SENSOR (TS1)
2.7 C. MANUAL RESET SHALL BE REQUIRED. (ADJUSTABLE)
FREEZESTAT STOPS OPERATION OF AHU UPON ITS SET POINT OF
DIAGRAM AND THE LADDER DIAGRAM.
3. THE CONTRACTOR SHALL SUBMIT THE AHU SCHEMATIC CONTROL
VALVE
EXPANSION
ELECTRIC
9 17
AHU SCHEMATIC CONTROL DIAGRAM
THE AHU FAN SHALL RUN CONTINUOUSLY BASED ON TIME CLOCK SCHEDULE.
WHEN THE SYSTEM SWITCH FOR THE AHU IS SET TO THE "ON" POSITION,
REQUIREMENTS, MECHANICAL EQUIPMENT SCHEDULE, AND DETAILS.
SYSTEM SPECIFICATIONS, MANUFACTURERS’ INSTALLATION
INSTALLATION REQUIREMENTS SHALL BE IN ACCORDANCE WITH
FOR CONTROL SYSTEM REQUIREMENTS ONLY, SYSTEMS EQUIPMENT
2. THE CONTROL DIAGRAMS IN THESE DRAWINGS ARE INTENDED
SPACE TEMPERATURE AT 12.8 C. (ADJUSTABLE)
SETPOINT, THE CONTROLLER. SHALL CYCLE THE AHU FAN MOTOR TO MAINTAIN
WHENEVER SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED T-STAT
BELOW 10 C. (ADJUSTABLE)
LOW-LIMIT AND MODULATE THE O.A. DAMPER CLOSED AS S.A. TEMP. FALLS
THE CONTROLLER SHALL USE THE S.A. TEMPERATURE SENSOR (TS2) AS A
SETPOINT. (ADJUSTABLE)
SHALL MODULATE THE C.W. COIL VALVE TO MAINTAIN THE R.A. TEMPERATURE
24 C (WHEN R.A. TEMP EXCEEDS 24 C WITH 100% O.A.), THE CONTROLLER
WHEN THE ECONOMIZER CAN NO LONGER MAINTAIN R.A. TEMPERATURE AT
THE R.A. AT 24 C. (ADJUSTABLE)
CONTROLLER SHALL MODULATE THE O.A., R.A., & E.A. DAMPERS TO MAINTAIN
100% O.A. AS R.A. TEMPERATURE FALLS BELOW THE 24 C SET POINT, THE
CONTROLLER SHALL CONTROL THE O.A., R.A., & E.A. DAMPERS TO PROVIDE
INITIALLY CONTROL THE C. W. COIL VALVE TO FULL BYPASS AND THE
SET BY THE O.A. CHANGE-OVER CONTROLLER, THE CONTROLLER SHALL
ECONOMIZER CYCLE: WHEN O.A. TEMPERATURE DROPS BELOW 15.6 C AS
M-1010 17
M
SH
C
M
H W
R H
W S
T
FR
T O
M
TS
EA
EA
H-O-A
EXIST. ROOF EXHAUST FAN-1
EA
EA
ROOF EXHAUST FAN -118
EA
EA
EA
EA
ROOF EXHAUST FAN -218
EA
EA
ROOF EXHAUST FAN -318
EA
EA
ROOF EXHAUST FAN EXIST. ROOF EXHAUST FAN-2
S.A.
O.A.
SENSOR
S.A. TEMP.
DETECTOR
SMOKE
MOTOR STARTER
H-O-A H-O-A H-O-A H-O-A H-O-A
H & V UNIT
FACE & BY-PASS DAMPER
FREEZESTAT
O.A.
W/ BIRD SCREEN
INTAKE LOUVER
OUTSIDE AIR
O.A. THERMOSTAT
TC
TEMPERATURE CONTROLLER
D-1
M-10 NOT TO SCALE
T O
T OARC
M
H W
R
HWS
HWR
HWS
SUNSHIELD
SENSOR
O.A. TEMP.
SUNSHIELD
W/ REMOTE BULB
OUTDOOR AIR THERMOSTAT
CONTROLLER
OUTDOOR AIR RESET
HEATING & VENTILATING SYSTEM SCHEMATIC DIAGRAM
5 HOT WATER HEATING BOILER
CONTROL VALVE
MODULATING 3-WAY
SENSOR BACKFLOW PREVENTER ASSEMBLY
PRESSURE REDUCING VALVE
E
REMOVABLE FUNNEL
CHEMICAL FEEDER W/
12 HOT WATER CIRCULATING PUMP
MOTOR STARTER
20 AIR SEPARATOR
TANK
EXPANSION
HOT WATER
MAKE UP COLD WATER
TO / FROM BLDG. HEATING SYSTEM
D-2
M-10 NOT TO SCALE
HOT WATER HEATING SYSTEM CONTROL DIAGRAM
SEQUENCE OF OPERATION
1.
CAMP CARROLL
07 MAR 22
NAM, TAE CHIN
HA-00529-3J
-1,1817 -2,18, 18
"HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION RUNS FAN-1, FAN-2,
-1,1817 -2,18, 18
"HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS FAN-1, FAN-2,
-3 UNTIL MANUALLY STOPPED.
2.
3. -1,1817 -2,18, 18
OPERATED CONTINUOUSLY DURING OPERATING HOURS. THESE 6 FANS SHALL
OPERATE CONTINUOUSLY TO PROVIDE GENERAL VENTILATION.
4.
TEMPERATURE CONTROLLER SHALL MODULATE H & V UNIT FACE / BY-PASS
-3 ONLY WHEN H & V UNIT IS RUNNING.
5. FREEZESTAT STOPS OPERATION OF H & V UNIT UPON ITS SET POINT OF 2.8
SMOKE DETECTOR STOPS H & V UNIT OPERATION WHEN SMOKE IS DETECTED.
DAMPER MOTOR TO MAINTAIN S.A. TEMPERATURE AT 15.6 DEG.C. (ADJUSTABLE)
DEG. C. (ADJUSTABLE)
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
SYSTEM SCHEMATIC AND CONTROL DIAGRAM
H & V SYSTEM AND HOT WATER HEATING
WHEN O.A. THERMOSTAT FALLS TO SET POINT OF 15.6 DEG C., PROPORTIONAL
FAN-1, FAN-2, -3 SHALL BE ENERGIZED BY TIMEC LOCK AND
OUTER TAPE
INSULATION
COVER
REFRIGERANT GAS PIPE
TO INDOOR UNIT
FROM HEAT PUMP
: POSSIBLE
(X) VERTICAL LEVEL
TO INDOOR UNIT
- NOT TO SCALE
REFRIGERANT PIPE BRANCH TAKE OFF
- NOT TO SCALE
REFRIGERANT PIPES PRIOR TO / AFTER
BRANCH TAKE OFF FITTINGS.
NOT TO SCALE
OUTDOOR HPU CONCRETE PAD
HEAT PUMP
PIPES FROM
REFRIGERANT PIPE SLEEVE
FROM HEAT PUMP
NOTES
PIPES TO INDOOR UNIT
: IMPOSSIBLE
MAINTAIN HORIZONTAL LEVEL BETWEEN
(EXTERIOR WALL ONLY)
OUTER SEALING PLATE
ARC WELDING
PIPE SLEEVE
PIPE
YARN OR INSULATION 64K
CAULKING COMPOUND
4.5THK. STEEL PLATE
INSULATION
PVC PIPE
ARC WELDING
INSULATION
PIPE
MIN 30MM
WALL & FLOOR
4.5THK. STEEL PLATE
YARN OR INSULATION 64K
PIPE SLEEVE
ELEC. CONDUIT
INSULATION REFRIGERANT GAS PIPE
REFRIGERANT LIQUID PIPE
TELECOM LINE
PIPE SLEEVE
COMPOUND
CAULKING
: POSSIBLE BRANCH TAKE OFF LEVEL
FIN GRADE
19 CHAMFER
150 MIN 150 MIN
E.W.T.B
D16 @200 OC
200 150
MECHANICAL EQUIPMENT
CONCRETE PAD
100% COMPACTED BASE COURSE
NOTE :
ABBREVIATION:
T.B: TOP AND BOTTOM
E.W: EACH WAY
MATERIAL PROPERTIES:
2. REINFORCING STEEL YIELD STRENGTHS, fy=300 Mpa.
1. CONCRETE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, f’c=24 Mpa.
"H" BEAM
(150MM HEIGHT)
RUBBER PAD
PAD 12T
CONCRETE PAD
RUBBER PAD
CONC. PAD
NOT TO SCALE-
2. CHAMFER ALL EXPOSED EDGES OF CAST-IN-PLACE CONCRETE 19mm UNLESS OTHERWISE NOTED.
1. PAD SIZE SHALL BE COORDINATED WITH THE EQUIPMENT UNIT MANUFACTURER.
OUTDOOR HPU RUBBER PAD
M-11
DETAIL DRAWINGS - 1
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
M-11
2 3
SEE ARCH. DWGS.
WOOD NAILER
ALL AROUND
GASKET SEAL
(SPECIFIED IN DIVISION 7)
ROOF CONSTR.
FLASHING
CURB HT.
12"(300) MIN.
DIVISION 7 WORK
ROOF CURB,
POWER ROOF VENTILATOR
MIN. 2 EACH SIDE
BY FAN MFR.,
RECOMMENDED
SEE ARCH. DWGS.
WOOD BLOCKING,
SEE ARCH. DWGS.
MANUAL
BACKDRAFT DAMPER REQ’D
EXHAUST DUCT WORK
AS PER EQUIPMENT SCHEDULE
- NOT TO SCALE
POWER ROOF VENTILATOR
LAG BOLTS AS
11 17
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
M-11
M-11M-11M-11
NOT TO SCALE-
CHEMICAL FEEDER
- NOT TO SCALE
EXPANSION TANK AND AIR SEPARATOR 2
"D 1"
"D
PIPE
PIPE
o
WELDED (TYP)
.8
8100 100
MAX.300
"D2" IS NOMINAL PIPE SIZE FOR 63mm AND LARGER.
"D1" IS NOMINAL PIPE SIZE FOR 50mm AND SMALLER.
2.
1.
NOT TO SCALE-
PIPE ANCHOR
STEEL ANGLE
38 x 38 x 7 THK
(TYP. OF 6)
10 BOLT & NUT
STEEL PLATE
5 THK
(TYP)
MAX.45°
STEEL ANGLE
50 x 50 x 6 THK
STEEL PLATE
100 x 300 x 10 THK
(TYP)
MAX. 45°
NOTES :
NOT TO SCALE-
FD ECA BG HF
HOT PIPE LINE
HGD FECBG H A
CG
MF
EXPOSED
CLINCHING STAPLE @ 100 O.C.
CG OR
MF
EXPOSED
WEATHER
A
C
D
B
CLASS II ADHESIVE
OVERLAP (40)
VAPOR-BARRIER JACKET
2. HOT WATER HEATING
3. HEATED OIL PIPE LINE
1. STEAM & CONDENSATE
5. REFRIGERATION SUCTION
4. A/C CONDENSATE DRAIN
LONGITUDINAL JOINTS
COLD WATER PIPE LINE
3. DUAL TEMP. WATER
2. CHILLED WATER
1. MAKE-UP WATER
DOWN TO SHED WATER
SHALL BE OVERLAPPED
ALUMINUM JACKET
H
G
NOTE :
BAPIPING
COLD PIPE LINE
HOT PIPE LINE
D EC
INSULATION
PIPE
AREA
ITEM
80 JACKET STRIPE
F
CONCEALED
VAPOR-BARRIER JACKET
(MIN. 40 JACKET OVERLAP)
VAPOR-BARRIER COATING
10 W x 0.5 THK @300 O.C.
ALUMINUM LOCK-TYPE BANDS
80 JACKET STRIP OR
MF - MINERAL FIBER SHALL BE USED FOR HOT PIPES
CG - CELLULAR GLASS SHALL BE USED FOR COLD PIPES
SEE SPECIFICATION FOR INSULATION THICKNESS
PIPE SADDLE
PIPE SADDLE
65 THRU 80
UP TO 50
PIPE SIZE
15 DIA
100 THRU 12510 DIA
PIPE SIZEROD SIZE
CLEVIS HANGER
(NOT VAPOR BARRIER)
3,600
ROLLER
STAND
PIPE
LENGTH AS REQ’D
LOCKING
CONC BEAM
TRAPEZE HANGER
PL 15 X 200 X 200
BOLT PIPE ROLLERS TO ANGLE (TYP)
ANCH BOLT.
HANGER ROD (TYP)
NO INSULATION
16 GAGE STEEL
654032 5025
HANGER ROD SPACING
PIPE SIZE
3,3002,7002,400 3,0002,100
OF SMALLEST PIPE ON TRAPEZE.
MAX. ALLOWABLE
SPACING
NOTE : FOR TRAPEZE HANGER TAKE SPACING
ANGLE
SUPPORT NUT
PIPE SADDLE AT
LEAST 300 LONG
WELD
10080
3,900
(TYP)
INSULATION (TYP)
CONNECTION TO CONCRETE FLOOR W/CONCRETE ANCHORS OR TO
ROOF STRUCTURE MEMBER FOR TOP FLOOR
MIN. 600VAPOR BARRIER
INSULATION
NOTE
ANCHOR
ANGLE
CROSS BRACING
SLAB OR BEAM
NOT TO SCALE-
4 5
AT LEAST 300 LONG
100 THRU 125
HANGER ROD SCHEDULE
15 DIA.65 THRU 80
10 DIA.UP TO 50
PIPE SIZEROD SIZEPIPE SIZE
16 DIA
ROD SIZE
CROSS BRACE : REFER TO SMACNA’S SEISMIC RESTRAINT MANUAL CHAPTER 5.
AT LEAST 300 LONG
LOCKING NUT
SUPPORT NUT
INSULATION
VAPOR BARRIER
16 DIA
ROD SIZE
HANGER ROD
HANGER ROD SCHEDULE
PIPE
HEAVY DUTY
CLEVIS HANGER
16 GAGE SHEET METAL
16 GAGE SHEET METAL
PIPE HANGER PIPE INSULATION
M-1212 17
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
DETAIL DRAWINGS - 2
M-12
SHEET COPPER FUNNEL
20mm VALVE
SHUT-OFF COCK
18mm GAUGE GLASS
CARBON STL. PIPE
SCH. 80 SEAMLESS
200mmx600mm LG.
WITH GASKET
COMPANION FLANGES
20mm DRAIN VALVE
CHILLER
TO BOILER OR
GLOBE VALVE
VALVE
20mm GATE
FROM SYSTEM
10mm AIR COCK
125mm
SHEET COPPER FUNNEL
TANK
EXPANSION
INSULATION
PUMP
CONNECT TO
AIR SEPARATOR
PAD
CONCRETE
DRAIN
25mm NPT
VERTICAL
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
M-12
M-12M-12M-12
SP
FL
O
W
GA
SPR
SINGLE VANE SCHEDULE
USED. OTHER VANE
OTHER RUNNERS MAY BE
SEE NOTES ON FIG.2-4
SIZES OR SPACINGS
LARGE
SMALL
FLAT
R SP
RUNNER TYPE 2
20mm TRAILING EDGE
SINGLE VANE WITH
SP
50 40
81113
SP=40
R=50
112.5
OR
APPROVAL.
R
ACCEPTABLE ON DESIGNER
22 GA
INLET AREA.
APPROXIMATES ELBOW
FREE AREA BETWEEN
DOUBLE WALL VANES
RUNNER TYPE 1
OR RUN A TIE ROD THROUGH THE CENTER VANE.
WELD EVERY 6TH VANE TO RUNNER(OVER 5 MPS)
BOLT, SCREW, OR
WELD RUNNER TO DUCT
32 MIN
NOT TO SCALE-
45 45
45 45
DUCT TURNING VANE 3
ALL TRANSVERSE EDGES
DIMENSIONS
TO BE COATED WITH ADHESIVE
CB
E
FOLDED CORNER
PIN AND WASHER
ALTERNATE
(FASTENER)
12.71 TO 30.5 MPS
DUCT SECTION
UP TO 12.7 MPS
VELOCITY
(TYPICAL 1,200 OR 1,500mm)
A
E
B
LINING
C
B
C
B
C
A
E
2.
1.NOTE :
ATTACHED BY SCREWS, RIVETS OR WELDS.)
BE FORMED ON DUCT OR BE CHANNEL OR ZEE
NOSING ON EVERY LEADING EDGE. (NOSING MAY
WHEN VELOCITY ABOVE 20.3 MPS USE METAL
MAXIMUM SPACING FOR FASTENERS ACTUAL
INTERVALS ARE APPROXIMATE.
LAPPED AND BUTTED CORNER
NOT TO SCALE
DUCT LINING DETAIL
REMARKS
2,400
2,400
3,000
2,400
3,000
3,000
3,000
SPACING
MAXIMUM
SPACING
MAXIMUM
HANGER SIZES FOR ROUND DUCT
25 x 22 GA
HANGERS
STARP
6 DIA OR
8 GA WIRE
HANGER
RODS
3,000
25 x 18 GA
40 x 16 GA
25 x 16 GA
25 x 16 GA
25 x 18 GA
10 DIA
15 DIA
10 DIA
10 DIA
10 DIA
25 x 22 GA
HANGERS
STARP
25 x 22 GA
HANGER
RODS
HANGERS
50 x 50 x 6
50 x 50 x 5
40 x 40 x 3
50 x 50 x 3
40 x 40 x 3
ANGLES
25 x 25 x 3
25 x 25 x 3
CROSS BRASSING
ANGLE (TYP)
HANGER
NUTS
ROD
DIAMETER
DUCT
ANGLES
DIMENSION
LONGEST
OF DUCT
775 THRU 1,050
2,125 THRU 2,400
1,525 THRU 2,100
1,075 THRU 1,500
UP THRU 450
OVER 2425
475 THRU 750
UP THRU 450
1.
PLACED UNDER A BOTTOM REINFORCEMENT.
2.
FOR BOTH DUTIES.
25 x 16 GA
25 x 20 GA10 DIA
10 DIA
3,000
3,000
1,250 DIA MAX.
NOTES :
925 THRU 1,250
1275 THRU 2,100
475 THRU 900 25 x 20 GA10 DIA 3,000 1
OMITTED IF
HANGER LOOPS
SCREWS MAY BE
SCREWS
FOR LOAD
SIZE BOLT(S)
INSULATION
LOAD RATED
SEE NOTE 2
OR ANGLE
STRAP
ANCHOR TO CEILING SLAB
OR STEEL PLATE (TYP)
TRAPEZE HANGERS
STRAPS
HANGER SEE NOTE 1
25MIN.
STRAP HANGERS
600 DIA MAX.250 DIA MAX.
STRAP
AS HANGER
SAME SIZE
WIRE
BAND OF
SECURE FASTENERS
(VERIFY UPPER TRAPEZE
LOAD CAPACITY)
ALTERNATIVE LOCATION
DISTANCE IS NOT EXCEED 1,500 UNLESS FOOT OF STRAP IS
REINFORCEMENT MAY BE USED FOR ATTACHMENT IF IT QUALIFIES
HANGER SIZES FOR RECTANGULAR DUCT
NUMBER OF
TRAPEZE SHELF
DO NOT EXCEED ALLOWABLE LOAD LIMITS.
NOT TO SCALE-
4 DUCT HANGER
M-13
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
E
AS SHOWN
DATE:
MECHANICAL
D - 22 - 07
A B C D F G H
DETAIL DRAWINGS - 3
C cmhx Y=X
SD
A cmh B cmh
NOTE; ABOVE APPLY TO SUPPLY AND RETURN
W
SD
YX
W
Y
D
FOR D OF 300 OR MORE
USE VANED ELBOW
D LESS THAN 300
R=D YR1=(X+Y)/2
R2=X+Y
X OR W LESS THAN 300
Y
R
D
R2=X+Y R1=(X+Y)/2
SD
X
R
TURNING VANES (TYP.)
RETURN ONLY
Y
BRANCH TAKEOFFS
C 300 OR MORE
MANUAL DAMPER
X OR Y LESS THAN 300
R1=(W1+W2)/2
SPLITTER DAMPER(TYP.)
PROVIDE VE WHEN COIL OR DIFFUSER IS
1,500 OR LESS FROM BRANCH TAKEOFF.
A cmh x Y=XC cmh
SD
A cmhB cmh
W
W
X
W
R=W
W
NOTE; SEE SMACNA DUCT MANUAL
C LESS THAN 300
(1985) FIGS. 2-7
C c m h
A cmh
PREFERRED OFFSET
FULL RADIUS WHERE POSSIBLE
OFFSETS
FROM RECTANGULAR MAIN
ROUND DUCT TAKEOFF
NOT TO SCALE
DUCT WORK DETAIL
C c h m
R1 W2
R2=W1+W2
Y
X
20 max.
90 TEES
20 max.
90 RADIUS ELBOWS
M-13
13 17
CAMP CARROLL
HA-00529-3J
07 MAR 22
NAM, TAE CHIN
M-13M-13M-13
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
ELECTRICAL
KIM, CK
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
N O T E S
3.
2.
4. MOUNTING HEIGHTS ARE AS BELOW. MEASUREMENT IS TO CENTER OF OUTLET.
WIRES IS INDICATED AS FOLLOW;
AND ONE (1)-#12AWG GROUND WIRE IN 16mm CONDUIT. A GREATER NUMBER OF
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES TWO (2)-#12AWG WIRES
3-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.
4-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.
PANELBOARD, CIRCUIT BREAKER------------------------SEE SPECIFICATION
CAULKING MATERIAL SHALL BE VERIFIED BY F&ES OFFICE PRIOR TO CONSTRUCTION.
BOTH SIDE OF FIRE WALLS, FIRE-PARTITIONS AND FIRE-RATED PIPE CHASE WALLS.
ALL PIPE PENETRATIONS SHALL BE SEALED WITH FIRE RATED CAULKING MATERIAL ON
1.
SPECIFICATIONS FOR O&MA PROJECTS, AND SPECIFICATIONS.
ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, FIRE CODE, TECHNICAL STANDARD
ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL
CONDUIT WHICH IS TO BE BONDED TO THE MAIN GROUNDING SYSTEM AT BOTH ENDS.
GROUNDING WIRE SHALL BE GREEN INSULATED COPPER WIRE IN RIGID GALVANIZED STEEL
ALL WIRING SHALL BE CONCEALED ABOVE THE CEILING WHEN THE ROOM HAS A CEILING.
MAGNETIC MOTOR STARTER
L E G E N D
NEWEXSTREMOVE
PANELBOARD OR LOAD CENTER
J
JUNCTION BOX
+ WIRING CONCEALED IN UNDERGROUND
HOMERUN CIRCUIT TO PANELBOARD OR ENCLOSURE
WIRING CONCEALED IN CEILINGS AND WALL
WIRING EXPOSED ON CEILINGS AND WALL
1.6
J
1.6
J
1.6
1.6M ABOVE FLOOR
///// C C CONTROL CIRCUITC
SCOPE OF WORK
5.
6.
7.
AND THE COLOR OF TOGGLE SWITCHES AND RECEPTACLE SHALL BE GRAY.
ALL COVER PLATES OF RECEPTACLES AND SWITCHES SHALL BE STAINLESS STEEL METALLIC ONES
LEGEND, NOTES AND SCOPE OF WORK
US ORIGIN MATERIAL:
CHANGES SHALL BE APPROVED BY THE CONTRACTING OFFICE.
BE RESPONSIBLE TO RESIZE AND PROVIDE THE REQUIRED WIRING AND OVER CURRENT DEVICES. THE
IF EQUIPMENT OTHER THAN INDICATED ON THE PLANS ARE PROVIDED, THEN THE CONTRACTOR SHALL
INDICATED ON THE DRAWINGS.
INTERNET SITE (http//www.cckbid.com). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE AS
DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL
SIN, YS
HA-00529-3J
CAMP CARROLL
RECEPTACLE, SINGLE, 2P-3W-20A-250V, GRD’G TYPE
D - 22 - 07
WIRING CONCEALED IN CEILINGS AND WALL/////
1.
SHEET OF14 17
A. REPAIR / MAINTENANCE
E-01
8.
BREAKERS, SAFETY SWITCHES, MAGNETIC MOTOR STARTERS, POWER LINE AND NECESSARY ACCESSORIES.
REPLACE DETERIORATED EXISTING POWER SYSTEM WITH NEW DRY TYPE TRANSFORMER, PANEL BOARD, CIRCUIT
BLDG. NO. S-821
REPLACE A/C AND HEATING SYSTEM,
07 MAR 22
SAFETY SWITCH
M-7
E-1
1/4HP, 277V, 1PH, 60Hz
ROOF EXHAUST FAN
"2A"
"4A"
Tch
Tch
"2D""4E"
3REHEAT: 24KW, 460V, 3PH, 60Hz
FAN MOTOR(2EA): 1.5KW, 460V, 3PH, 60Hz, DEHUMIDIFIER
"4B"
"2B"
"4MDP" "2MDP"
REHEAT: 20KW, 460V, 3PH, 60Hz
FAN MOTOR(2EA): 1.1KW, 460V, 3PH, 60Hz, DEHUMIDIFIER
N
W/50A FUSES, NEMA 3R ENCL.
SAFETY SWITCH 3PH, 600V, 60A
W/40A FUSES, NEMA 1 ENCL.
SAFETY SWITCH 3PH, 600V, 60A
3-#8 "THWN" & 1-#10(G) IN 22mmC
3-#6 "THWN" & 1-#10(G) IN 28mmC
460V, 3PH, 60Hz, MCA:38.3
HEAT PUMP OUTDOOR UNIT
3/4HP, 460V, 3PH, 60Hz
EXIST. ROOF EXHAUST FAN-1
F
F
F
F
F
F
J
J
J
J
J
J
4A-2
4A-7
4A-5
4A-3
4A-4
4A-1
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
ELECTRICAL
KIM, CK
AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJE…