GENERATOR_-_Spec.docx
DOCX document 18 KB Posted
- Attached to
- Generator
- Solicitation number
- w56hzv19q0027
About this file
Generator Specification
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W56HZV19Q0027_FBO.pdf | ||
| GENERATOR_-_TIQ.DOCX | DOCX document | |
| W56HZV19Q0027.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Generic Specification
GENERATOR
1. Generator, 3-phase, minimum 500 kVA prime power rating, 220/380 V, 50 Hz
1.1. Permanent Magnet Generator (PMG)
1.2. Equipped with anti-condensation heater
2. Generator mounted with anti-vibration pads on a movable metal skid and enclosed with sheet-metal housing
2.1. Enclosure:
2.1.1. Weather protective
2.1.2. Sound deadening
2.1.3. IP23 enclosure protection
3. Diesel engine powered:
3.1. Capable of operating long-term on 5,000 ppm sulfur diesel fuel
3.2. Liquid cooled with water-jacketed engine and radiator
3.3. Fuel/water separator
4. Starting/charging system with:
4.1. 24 V starting motor with batteries
4.2. Charging alternator
5. Miscellaneous:
5.1. Circuit breakers for overload protection and power termination
5.2. UL-142 base mounted fuel tank sized to operate for at least 8 hours at peak power
5.3. Electric hours meter
5.4. Generator Control Unit that displays faults, operation, and has ports for engine CAN Bus (J1939), Ethernet, and USB
5.5. White exterior color
5.6. Manual(s), maintenance schedule, equipment markings, and warning labels all written in English, or universal symbols where appropriate
6. Radio frequency identification (RFID) tags:
6.1. Each generator and associated lot of spares tagged with a removable active RFID data rich tracking tag, specifically designated as either:
6.1.1. Savi ST-654-031, Savi ST-654-041, Identec I-Q310 DRT, or Evigia EV3-DRT
6.2. At least 128 Kbytes of memory
6.3. Compliant with ISO 18000/7
6.4. Tag located on exterior of generator in easily observable spot; tag for spares located in easily observable spot on exterior of the pallet or container
6.5. RFID tag securely affixed to the generator or item with two or more plastic cable ties, or in such a way that it cannot fall off
6.6. Tag data and electronic data field format in accordance with specifications established by Joint Total Asset Visibility (JTAV) version 2.0, section 3.4.1 “Commodity Item Database Format” with the following clarifications:
6.6.1. The “document field” titled “DOCUMENT” the document number (e.g. “milstrip”) as specified by the Government procuring agency
6.6.2. The “MISC1” field: The item serial number, if available
6.6.3. The “MISC2” field: Used for user comments (e.g. contract number)
File details come from the government source that posted it.