W50S8C22Q0004

RFI 02

29 March 2022

1. Was to verify that you wanted the refrigerated dryer to be included. The model of the old IR compressor has a built in air dryer. Answer: Yes, we want some form of dryer on the system, whether it be built-in or stand-alone as the long as the performance and standard is getting accomplished.

2. Is the power 460V? I am assuming it is because of the VFD. Answer: Like you found on the power specs that are within the solicitation on the PWS. But to clarify, existing air compressor is on a 480 volt, 3 phase, 4 wire, 60hz circuit with a 100 amp breaker. This would allow the voltage range to reach up to 480.

3. We will be providing Forklift and driver? Answer: Yes, this question and answer was already presented on SAM.gov within RFI01 with “We do not have a forklift that will fit through the doors to the mechanical room where the compressor is located. Contractor will be required to provide the forklift/means and operator to bring in/remove equipment.”

4. Site Visit? Answer: We do not have a site visit opportunity for this solicitation.