W50S8C22Q0004-RFI02.pdf
PDF 222 KB Posted
- Attached to
- Bldg. 700 Air Compressor Replacement
- Solicitation number
- W50S8C-22-Q-0004
- Issued by
-
Department of the Army National Guard
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W50S8C22Q0004
RFI 02
29 March 2022
1. Was to verify that you wanted the refrigerated dryer to be included. The model of the old IR compressor has a built in air dryer. Answer: Yes, we want some form of dryer on the system, whether it be built-in or stand-alone as the long as the performance and standard is getting accomplished.
2. Is the power 460V? I am assuming it is because of the VFD. Answer: Like you found on the power specs that are within the solicitation on the PWS. But to clarify, existing air compressor is on a 480 volt, 3 phase, 4 wire, 60hz circuit with a 100 amp breaker. This would allow the voltage range to reach up to 480.
3. We will be providing Forklift and driver? Answer: Yes, this question and answer was already presented on SAM.gov within RFI01 with “We do not have a forklift that will fit through the doors to the mechanical room where the compressor is located. Contractor will be required to provide the forklift/means and operator to bring in/remove equipment.”
4. Site Visit? Answer: We do not have a site visit opportunity for this solicitation.
File details come from the government source that posted it. Updated .