Sheet1
| 108 Wing |
| Pre-Bid Questions & Clarifications |
| Solicitation #: | W50S8B-21-B-0004 |
| Project Name & Number: | PTFL212 |
| Updated: | Friday, September 03, 2021 |
| RFI # | Submitted | Answered | Question | Response | Response By |
| 1 | 31-Aug-21 | 03-Sep-21 | Please confirm if a new steel lintel is required within the new brick wall infill above the new 6'x7' STC45 double doors. If so, please specify detail and size of steel lintel. | See attached file for BOSS header detail. Use concrete lintel "U" blocks, with 2 #5 rebar, filled with concrete. Steel lintel 6'x3-1/2"x5/16" used to support exterior face brick. | 108 CES |
| 2 | 31-Aug-21 | 03-Sep-21 | Please confirm if it is required and if so who will be responsible to relocate the air sampling and FA devices at the existing ceiling in location of new vestibule. This area will have new GWB ceiling and batt insulation installed. Will these devices be abandoned in place or removed prior to ceiling installation? See attached picture. | Relocate location of proposed wall and vestibule door a few feet toward building main haillway to avoid air sampling and FA devices, and fire sprinkler head. | 108 CES |