RFI Questions and Answers W50S6T24QA024 (2) - 20Sep2024.pdf
PDF 25 KB Posted
- Attached to
- Automatic Transfer Switch Replacement
- Solicitation number
- W50S6T24QA024
- Issued by
-
Department of the Army National Guard
About this file
This document is a set of Questions and Answers related to a Request for Information (RFI) for solicitation W50S6T24QA024 to replace Automatic Transfer Switches (ATS) at two buildings, 130 and 125, for the 144th Fighter Wing (144 FW).
The key details are: The current ATS units do not have bypass switches, and bypass switches are not required for the new ATS units. The serial numbers of the existing ATS units are provided. The replacement ATS units for both buildings shall be closed transition switches, as updated in the Performance Work Statement (PWS). This is a Firm Fixed Price solicitation set aside for Service-Disabled Veteran-Owned Small Businesses, with a NAICS code of 238210 and a $19M size standard. Quotes are due via email, and the Government reserves the right to amend or cancel the solicitation. Funds are not presently available, but if they become available and prices are deemed fair and reasonable, the Government intends to make an award.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Request for Information, Questions and Answers for solicitation W50S6T24QA024:
19. We received feedback stating a bypass switch cannot be put into an existing switch board, do you know if bypass is needed?
Based on the drawings we do not have bypass switches on the existing ATSs, so it is not required.
20. Please provide serial numbers of ATS per building?
The serial numbers are on the existing ATSs per building are:
Building 130 (Medical): 60-60315-2 Building 125 (CE): 60-61358-1
21. Please confirm if the replacement B130 ATS will need to include a Bypass function at the existing ATS unit. Will B125 replacement ATS unit need to have a Bypass function also?
The current unit does not have a bypass function, and a bypass function is not required for the new ATS units.
22. Will the replacement ATS units for B125 & B130 need to be an Open Transition type or a Closed Transition type?
Switches are for critical facilities; closed transition switch is desirable equipment. Both switches shall be closed transition switches as updated in the PWS.